WFD Series Waterflow Detector

WFD Series
Waterflow Detector
The System Sensor WFD series is compatible
with schedule 10 through 40 steel pipe, sizes
2˝ through 8˝, and can be mounted in a vertical
or horizontal position.
Features
•Two-inch mounting hole provided in new WFD30-2 models
•UL-listed models are NEMA 4 rated
•Sealed retard mechanism immune to dust and other contaminants
•Visual switch activation
•Field-replaceable retard mechanism and SPDT switches
•Rugged, dual SPDT switches enclosed in a durable terminal block
•Accommodates up to 12 AWG wire
•Designed for both indoor and outdoor use
•100 percent synchronization activates both alarm panel and
local bell
Agency Listings
CS169
7770-1653:114
Reliable Performance. UL-listed models are equipped with
tamper-resistant cover screws to prevent unauthorized entry. Inside,
two sets of SPDT (Form C) synchronized switches are enclosed in a
durable terminal block to assure reliable performance.
False Alarm Immunity. The WFD series incorporates a mechanical
retard feature, which minimizes the risk of false alarm due to
pressure surges or air trapped in the sprinkler system. In addition,
the mechanical retard’s unique sealed design is immune to dust and
other contaminants.
Simplified Operation. The WFD series is designed to simplify
installation. Two conduit openings permit easy attachment to the
local alarm system. The retard mechanism and dual SPDT switches
are field-replaceable.
•Tamper-resistant cover screws
S739
Robust Construction. The WFD series consists of a rugged,
NEMA 4-rated enclosure. Designed for both indoor and outdoor
use, the WFD series operates across a wide temperature range, from
32°F to 120°F.
167-93-E
3006195
Waterflow Detector Specifications
Engineering Specifications
Vane-type waterflow detectors shall be installed on system piping as designated on the drawing and/or as specified herein. Detectors shall mount on any
clear pipe span of the appropriate nominal size, either a vertical upflow or horizontal run, at least 6˝ from any fittings that may change water direction,
flow rate, or pipe diameter or no closer than 24˝ from a valve or drain. Detectors shall have a sensitivity in the range of 4 to 10 gallons per minute and a
static pressure rating of 450 psi* for 2˝ – 8˝ pipes. The detector shall respond to waterflow in the specified direction after a preset time delay that is field
adjustable. The delay mechanism shall be a sealed mechanical pneumatic unit with visual indication of actuation. The actuation mechanism shall include
a polyethylene vane inserted through a hole in the pipe and connected by a mechanical linkage to the delay mechanism. Outputs shall consist of dual
SPDT switches (Form C contacts). Two conduit entrances for standard fittings of commonly used electrical conduit shall be provided on the detectors.
A grounding provision is provided. Unless noted, enclosures shall be NEMA 4 listed by Underwriters Laboratories Inc. All detectors shall be listed by
Underwriters Laboratories Inc. for indoor or outdoor use.
Two openings for ½˝ conduit.
One open, one knock-out type
Two sets of SPDT (Form C)
10.0 A, ½ HP @ 125/250 VAC
2.5 A @ 6/12/24 VDC
Steel water pipe, schedule 10 through 40
UL-LISTED
COMPATIBLE
CONTROL PANEL
SSM24-X
SSV120-X
SUGGESTED EOL
RESISTOR
CONTACT RATINGS
125/250 VAC 10 AMPS
24 VDC
2.5 AMPS
SCHEMATIC OF
INDIVIDUAL
SWITCH IN
“NO WATERFLOW”
CONDITION
Overall Dimensions, Installed
3.75″
DELAY
ADJUSTMENT
DIAL
DIAL IS APP
R
ON
R DELAY IN SECO OXI
ND MA
BE
M IME
S
T
Model Width Model Width
WFD20 4.6″ WFD40 6.8″
WFD25 4.6″ WFD50 7.8″
WFD30-2 5.2″ WFD60 9.0″
WFD35 5.7″ WFD80 10.8″
3.0″
30
–
Delay Adjustment Dial
NOTE: COMMON AND B-NO
CONNECTIONS WILL CLOSE
WHEN VANE IS DEFLECTED, I.E.,
WHEN WATER IS FLOWING. DUAL
SWITCHES PERMIT
APPLICATIONS TO BE COMBINED
ON A SINGLE DETECTOR.
15
INITIATING
LOOP
+
3 Years
TE
POWER +
24VDC OR
120VDC –
Warranty
70
WFD Field Wiring Diagram
NU
Compatible Pipe
55
Contact Ratings
Operating Temperature Range 32°F to 120°F (0°C to 49°C)
Enclosure Rating*
NEMA 4 – suitable for indoor/outdoor use
Cover Tamper Switch
Standard with ULC models, optional for UL
models, part no. 546-7000
Service Use
Automatic Sprinkler: NFPA-13
One or Two Family Dwelling: NFPA 13D
Residential Occupancies up to 4 Stories: NFPA 13R
National Fire Alarm Code: NFPA-72
U.S. Patent Numbers
5,213,205
450 PSI*
18 Feet Per Second (FPS)
4–10 GPM
0
Standard Specifications
Static Pressure Rating
Maximum Surge
Triggering Threshold
Bandwidth (Flow Rate)
Conduit Entrances
U bolt nut
A-NC
COM
B-NO
1.6″
Pipe saddle
45
BREAK WIRE AS
SHOWN FOR
SUPERVISION OF
CONNECTION. DO
NOT ALLOW
STRIPPED WIRE
LEADS TO EXTEND
BEYOND SWITCH
HOUSING. DO NOT
LOOP WIRES.
Pipe
Plastic vane
NOTE: RETARD TIME MAY EXCEED 90 SECONDS. ADJUST
AND VERIFY THAT TIME DOES NOT EXCEED 90 SECONDS.
NUMBER ON DIAL IS APPROXIMATE TIME DELAY IN
SECONDS WITH AN ACCURACY OF +/− 50%.
U bolt
Width: See Table
Ordering Information
UL Model
ULC Model
WFD20
WFD20A
WFD25
WFD25A
WFD30-2
WFD30-2A
WFD35
WFD35A
WFD40
WFD40A
WFD50
WFD50A
WFD60*
WFD60A
WFD80*
WFD80A
Accessories
A3008-00
Retard mechanism
A77-01-02
Terminal block
546-7000
Tamper-proof switch kit
WFDW
Tamper-proof wrench for cover
WFDN4
Gasket kit
Pipe Size
2˝
2½˝
3˝
3½˝
4˝
5˝
6˝
8˝
Hole Size
1¼˝
1¼˝
2˝
1¼˝
2˝
2˝
2˝
2˝
Shipping Weight
4.2 lbs.
4.3 lbs.
4.5 lbs.
4.7 lbs.
5.2 lbs.
6.3 lbs.
6.8 lbs.
7.5 lbs.
*Maximum pressure rating 400 psi as approved by Factory Mutual.