WFDE Series Water Flow Detectors

WFDE Series
Waterflow Detector
The System Sensor WFDE series is compatible with pipe
diameters ranging from 50mm through 200mm and
can be mounted in a vertical or horizontal position.
Robust Construction. The WFDE series consists of a rugged,
IP54-rated enclosure. Designed for both indoor and outdoor use,
the WFDE series operates across a wide temperature range, from
0°C to 68°C (32°F to 155°F).
Features
•Compliant with Construction Products Directive
•EC Certificate Number 0786‑CPD‑40151
•WFD30-2E models install in 50.8mm (2”) hole sizes
•IP54-rated enclosure
•Sealed retard mechanism assures that the retard is not
contaminated by dust and dirt when the cover is removed
•Visual switch activation permits installer to accurately set the retard,
even under extremely noisy conditions
•Rugged, dual SPDT switches are enclosed in a durable terminal
block for added strength
•100% synchronization activates both alarm panel and local bell
simultaneously
Agency Listings
TE83724
VdS
G4940006
Scientific Services
Laboratory
1Z0A7.AH
afp-836
0786
Reliable Performance. WFDE models are equipped with tamperresistant cover screws to prevent unauthorized entry. Inside, two sets
of SPDT (Form C) synchronized switches are enclosed in a durable
terminal block to ensure reliable performance.
False Alarm Immunity. The WFDE series incorporates a
mechanical retard feature, which minimizes the risk of false alarm
due to pressure surges or air trapped in the sprinkler system. In
addition, the mechanical retard’s unique sealed design is immune
to dust and other contaminants.
Simplified Operation. The WFDE series is designed to simplify
installation. Two conduit openings permit easy attachment to the
local alarm system. The retard mechanism and dual SPDT switches
are field-replaceable.
Waterflow Detector Specifications
Engineering Specifications
Vane-type System Sensor WFDE series waterflow detectors shall be installed on system piping as designated on the drawings and/or as specified herein.
Detectors shall mount on any clear pipe span of the appropriate nominal size, either a vertical upflow or horizontal run, at least 15 cm (6 in.) from any
fittings, which may change water direction, flow rate or pipe diameter, or no closer than 61 cm (24 in.) from a valve or drain. The detector shall respond
to waterflow in the specified direction after a preset time delay, which is field adjustable. The delay mechanism shall be a sealed mechanical pneumatic
unit with visual indication of actuation. The actuation mechanism shall include a polyethylene vane inserted through a hole in the pipe and connected
by a mechanical linkage to the delay mechanism. Outputs shall consist of dual SPDT switches (Form C contacts). Two conduit entrances (one of which is
a knockout type) for standard fittings of commonly used electrical conduit shall be provided on the detectors. A grounding provision is provided. WFDE
waterflow detectors shall be approved by Factory Mutual, LPC, VdS and SSL.
Standard Specifications
Static Pressure Rating
LPC: 17.25 BAR (250 PSI)
VdS: PN16 (16 BAR, 232 PSI)
30–57 liters/minute
10.0 A @ 125/250 VAC
2.5 A @ 24 VDC
Triggering Threshold Bandwidth (Flow Rate)
Contact Ratings; Two sets of SPDT (Form C)
Conduit Entrances
Operating Temperature Range
Enclosure Rating
U.S. Patent Numbers
Warranty
Two openings 22.2mm (.875 in.) diameter. One open, one knock-out type
0°C to 68°C (32°F to 155°F)
IP54
5,213,205
3 Years
WFDE Field Wiring Diagram
Compatible Pipe
Model
Ref. Pipe
Size mm
(in.)
WFD20E
50 (2)
WFD25E
65 (2½)
WFD30-2E 80 (3)
WFD40E
100 (4)
WFD60E
150 (6)
WFD80E
200 (8)
Shipping Weight
WFD20E
Model
WFD25E
1.85 kg
(4.08 lbs.)
Nominal Pipe O.D.
(mm)
LPC
VdS
60.3
60.3
76.0
76.1
88.8
88.9
114.1
114.3
165.1
168.3
219.1
219.1
Wall Thickness
(mm)
LPC
VdS
3.6
2.3/2.9
3.6
2.6/2.9
4.0
2.9/3.2
4.5
3.2/3.6
5.0
4.0/4.5
6.3
4.5/5.9
WFD30-2E WFD40E
WFD60E
WFD80E
2.05 kg
(4.53 lbs.)
3.03 kg
(6.68 lbs.)
3.45 kg
(7.70 lbs.)
2.36 kg
(5.20 lbs.)
UL-LISTED
COMPATIBLE
CONTROL PANEL
SSM24-X
SSV120-X
POWER +
24VDC OR
120VDC –
INITIATING
LOOP
+
SUGGESTED EOL
RESISTOR
–
20
10
25
5
0
15
Dial setting
0
5
10
15
20
25
CONTACT RATINGS
125/250 VAC 10 AMPS
24 VDC
2.5 AMPS
SCHEMATIC OF
INDIVIDUAL
SWITCH IN
“NO WATERFLOW”
CONDITION
A-NC
COM
B-NO
BREAK WIRE AS
SHOWN FOR
SUPERVISION OF
CONNECTION. DO
NOT ALLOW
STRIPPED WIRE
LEADS TO EXTEND
BEYOND SWITCH
HOUSING. DO NOT
LOOP WIRES.
Delay Adjustment Dial
Delay
adjustment
dial
NOTE: COMMON AND B-NO
CONNECTIONS WILL CLOSE
WHEN VANE IS DEFLECTED, I.E.,
WHEN WATER IS FLOWING. DUAL
SWITCHES PERMIT
APPLICATIONS TO BE COMBINED
ON A SINGLE DETECTOR.
Ordering Information
Model
Pipe Size
WFD20E
50mm (2”)
WFD25E
65mm (2½”)
WFD30-2E
80mm (3”)
WFD40E
100mm (4”)
WFD60E
150mm (6”)
WFD80E
200mm (8”)
Hole Size
31.8mm (1¼”)
31.8mm (1¼”)
50.8mm (2”)
50.8mm (2”)
50.8mm (2”)
50.8mm (2”)
Dial setting equals delay in seconds. Reference only.
3825 Ohio Avenue • St. Charles, IL 60174
Phone: 800-SENSOR2 • Fax: 630-377-6495
©2009 System Sensor.
Product specifications subject to change without notice. Visit systemsensor.com for
current product information, including the latest version of this data sheet.
A05-0243-008 • 2/09 • #1924