Data Sheet - System Sensor

WFDTH
Waterflow Detector
The System Sensor WFDTH Retard T-Tap Waterflow
Detector is designed for primary signaling in
residential systems and fits within 2×4 stud wall
construction.
Features
The WFDTH fits any tee that has a 1˝ NPT branch, including: 1˝, 1¼˝,
1½˝, and 2˝ NPT threaded ferrous and brass tees; 1˝, 1¼˝, 1½˝ and 2˝
copper sweat tees; Central, Spears®, and Victaulic® brand 1˝ CPVC tees;
and 1½˝ polybutylene tees.
•Residential sprinkler systems
•Sealed retard mechanism
•Visual switch activation
•Rugged, dual SPDT switches enclosed in a durable terminal block
• Easy to install and maintain design
•Vertical or horizontal mount
•Field replaceable retard mechanism and switch assembly
•Twelve different flexible paddles
Design. The design of the WFDTH makes it easy to install and
simple to maintain. It can be mounted in the vertical or horizontal
position. Two conduit openings permit easy attachment to the local
alarm system. The retard mechanism and switch assembly are fieldreplaceable.
Features. Twelve different flexible paddles fit 1˝, 1¼˝, 1½˝, and 2˝
tees. Sizes are marked clearly on the paddle for ease of installation.
Plastic paddles slip over the actuating lever and are securely
fastened with one screw. The handy depth gauge insures the proper
installation depth and clearance of the detector to the tee.
•Durable, tamper resistant enclosure
•Two conduit openings
•Handy depth gauge
•Accommodates up to 12 AWG wire
Construction. The WFDTH includes a durable and tamper resistant
enclosure. Its sealed retard assures that the delay mechanism is
not contaminated by dust and dirt when the cover is removed. The
long lasting cover completely encloses the electrical components
to further keep out dust and dirt. Improved self-guiding security
screws and removal tools make detectors resistant to tampering and
simplify field maintenance. •100% synchronization fires alarm panel and local bell
simultaneously
Agency Listings
S739
CS169
7770-1653:114
167-93-E
3033305
WFDTH Specifications
Architectural/Engineering Specifications
Model shall be a WFDTH as manufactured by System Sensor. T-tap waterflow detectors shall be installed on a tee that has a 1˝ NPT branch including: 1˝, 1¼˝,
1½˝, or 2˝ threaded ferrous or brass tee; 1–2˝ copper sweat tees; Central, Spears®, and Victaulic® brand 1˝ CPVC tees; or 1½˝ polybutylene tee as designated on the
drawings and/or as specified herein. Detectors shall mount on any clear pipe span of the appropriate size, either a vertical or horizontal run at least 6˝ from any
fittings or valves which may change water direction, flow rate, or pipe diameter or no closer than 24˝ from a valve or drain. Detectors shall have a sensitivity in
the range of 4 to 10 gallons per minute and a static pressure rating of 250 psi. The retard t-tap detector shall be a sealed mechanical pneumatic unit with visual
indication of actuation. The actuation mechanism shall include a polyethylene vane inserted through the tee fitting and connected by a mechanical linkage
to the delay mechanism. Outputs shall consist of dual SPDT switches (Form C contacts). Two conduit entrances (one of which is a knockout type) for standard
fittings of commonly used electrical conduit shall be provided on the detectors. A grounding provision is provided. WFDTH is listed by Underwriters Laboratories
for indoor use.
Physical/Operating Specifications
Static Pressure Rating
250 PSI (max.)
Maximum Surge
18 FPS
Triggering Threshold
4–10 GPM
Bandwidth (Flow Rate)
Overall Dimensions,
4.5˝ H × 3.55˝ W × 6.7˝ L
Installed
(11.4cm H × 9cm W × 17cm L)
Service Use
Two sets of SPDT (Form C)
Shipping Weight
10.0 A @ 125/250 VAC
2.5 A @ 24 VDC
Threaded ferrous and brass tees, copper
Warranty
sweat tees, CPVC tees, and polybutylene tees
Two openings for ½˝ conduit.
U.S. Patent Numbers
Delay Adjustment Dial
POWER +
24VDC OR
120VAC
–
+
CONTACT RATINGS
125/250 VAC 10 AMPS
24 VDC
2.5 AMPS
SUGGESTED EOL
RESISTOR
–
SCHEMATIC OF
INDIVIDUAL
SWITCH IN
“NO WATERFLOW”
CONDITION
DIAL IS APP
R
ON
R DELAY IN SECO OXI
ND MA
BE
M IME
S
T
30
INITIATING
LOOP
Delay
adjustment
dial
55
SSM24-X
SSV120-X
15
NOTE: COMMON AND B-NO
CONNECTIONS WILL CLOSE
WHEN VANE IS DEFLECTED, I.E.,
WHEN WATER IS FLOWING. DUAL
SWITCHES PERMIT
APPLICATIONS TO BE COMBINED
ON A SINGLE DETECTOR.
TE
UL-LISTED
COMPATIBLE
CONTROL PANEL
3,845,259; 4,782,333; 5,213,205
70
Electrical Connections
3 years
NU
Compatible Tee
Fittings
Conduit Entrances
Automatic Sprinkler: NFPA 13
One or Two Family Dwelling: NFPA 13D
Residential Occupancies up to 4 Stories: NFPA 13R
National Fire Alarm Code: NFPA 72
2.6 lbs. (1.2 kg.)
0
Contact Ratings
Operating Temperature Range 32°F to 120°F (0°C to 49°C)
Enclosure Rating
UL listed for indoor use
Cover Tamper Switch
Canadian models only, factory installed
45
A-NC
COM
NOTE: Retard time may exceed 90 seconds.
Adjust and verify that time does not exceed 90 seconds.
B-NO
BREAK WIRE AS
SHOWN FOR
SUPERVISION OF
CONNECTION. DO
NOT ALLOW
STRIPPED WIRE
LEADS TO EXTEND
BEYOND SWITCH
HOUSING. DO NOT
LOOP WIRES.
Ordering Information
UL Model No.
WFDTH
Accessories
A77-01-02
PRK9
A3008-00
ULC/Canadian Model No.
WFDTHA
Description
Waterflow Detector, Fits 1˝, 1¼˝, 1½˝, 2˝ ferrous and brass threaded tees; 1˝, 1¼˝, 1½˝, 2˝ copper
sweat tees; 1˝ CPVC tees; and 1½˝ polybutylene tees
Replacement terminal block for WFDTH
Replacement paddle kit – 12 paddles for WFDTH (see
WFDTH for sizes included)
Replacement retard mechanism
S07-66002
WFDW
C58-0009-000
Replacement tamper screws for covers of WFDTH
Replacement tamper proof wrench for cover of
WFDTH
Replacement metal cover
Spears® is a registered trademark of the Spears Manufacturing Company. Victaulic® is a registered trademark of the Victaulic Company of America.
3825 Ohio Avenue • St. Charles, IL 60174
Phone: 800-SENSOR2 • Fax: 630-377-6495
©2010 System Sensor.
Product specifications subject to change without notice. Visit systemsensor.com for
current product information, including the latest version of this data sheet.
A05-0941-008 • 7/10 • #2451