WFD Models - System Sensor

WFD Vane-type Waterflow Detectors
Specifications
Contact Ratings:
Triggering Threshold Bandwidth (Flow Rate):
Static Pressure Rating:
Dimensions, Installed:
Operating Temperature Range:
Compatible Pipe:
Shipping Weight:
Enclosure Rating:
U. S. Patent Numbers:
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
10 A @ 125/250 VAC
; 2.5 A @ 24 VDC
4 to 10 gpm
See models listed below
3.5 in H x 3.0 in W x 6.7 in D
32°F to 120°F (0°C to 49°C)
Steel water pipe, schedule 10 through 40
4 to 7 lb (according to size)
NEMA Type 4, as tested by Underwriters Laboratories, Inc. (IP56)
5,213,205
Important
Please Read Carefully And Save
Installation Guidelines
Before installing any waterflow alarm device, be thoroughly familiar with:
This instruction manual contains important information about the installation
and operation of waterflow detectors. Purchasers who install waterflow detectors for use by others must leave this manual or a copy of it with the user.
NFPA 72: National Fire Alarm Code
NFPA 13: Installation of Sprinkler Systems, Sect. 3.17
NFPA 25: Inspection, Testing and Maintenance of Sprinkler Systems, Sect. 5.3.3.2
Read all instructions carefully before beginning. Follow only those instructions that apply to the model you are installing.
Other applicable NFPA standards, local codes, and the requirements of the
authority having jurisdiction
CAUTION
NOTE: Installation methods other than those listed in this installation manual
may prevent the device from reporting the flow of water in the event the associated sprinkler system is activated by a fire. System Sensor is not responsible
for devices that have been improperly installed, tested, or maintained.
Use vane-type waterflow detectors in wet-pipe systems only. Do NOT use
them in dry pipe, deluge, or preaction systems. The sudden inrush of water in
such systems may break the vane or damage the mechanism.
1.Mount the detector where there is adequate clearance for installation and
removal and a clear view of it for inspections. See Figure 1 for mounting
dimensions.
2.Locate the detector 6 to 7 feet above the floor to protect from accidental damage.
3.On horizontal runs, position the detector on the top or side of the pipe.
Do not mount it upside down because condensation may collect in the
housing and impair the operation of the detector. For vertical flow applications, mount the detector on pipe through which water flows upward.
Otherwise, the unit may not operate properly.
4.Mount the detector at least 6 inches from a fitting that changes the direction of water flow and no less than 24 inches from a valve or drain.
5.Be sure the direction-of-flow arrow matches the direction of flow in the pipe.
Mounting Instructions
1. Drain the pipe.
2.Cut a hole at the desired location. Center the hole in the pipe, as shown
in Figure 2, and be sure the hole is perpendicular to the center of the
pipe. Before drilling, use a punch or scribe to mark the drill site to prevent the bit from slipping. If the hole is off center, the vane will bind
against the inside wall of the pipe. Use a drill or hole saw to cut a hole of
the proper diameter. See Table 1 for hole size.
Do not use in potentially explosive atmospheres. Do not allow unused wires
to remain exposed.
Principles Of Operation
Vane-type waterflow detectors mount to water-filled pipes in sprinkler systems.
Waterflow in the pipe deflects a vane, which produces a switched output–
usually after a specified delay. All waterflow detectors have a pneumatically
controlled mechanical delay mechanism. Delays do NOT accumulate; they reset if the flow of water stops before the entire delay has elapsed. All switches
actuate when the water flow rate is 10 gallons per minute or greater, but will
not actuate if the flow rate is less than 4 gallons per minute. This System Sensor installation manual covers the following waterflow detectors for sprinkler/
fire alarm applications.
Pipe Size
(inches)
Pipe
Schedule
Max. Pressure
Rating (psig)
WFD20
2
10 thru 40
450
WFD25
2.5
10 thru 40
450
WFD30-2
3
10 thru 40
450
WFD35
3.5
10 thru 40
450
WFD40
4
10 thru 40
450
WFD50
5
10 thru 40
450
WFD60
6
10 thru 40
450*
WFD80
8
10 thru 40
450*
Model
CAUTION
When drilling the hole with a hole saw, make certain that the center of the cut
does not remain in the pipe.
3.Remove burrs and sharp edges from the hole. Clean and remove all scale
and foreign matter from the inside of the pipe for one diameter on each
side of the hole to ensure free movement of the vane. Clean the outside
of the pipe to remove dirt, metal chips, and cutting lubricant.
4.Seat the gasket against the saddle and mount the detector directly to the
pipe. Carefully roll the vane opposite the direction of flow and insert it
through the hole. Seat the saddle firmly against the pipe so that the locating boss goes into the hole.
*Maximum Pressure Rating 400 psig as approved by Factory Mutual Research.
CAUTION
Do NOT use any of the WFD models on copper pipe. The clamping forces of
the mounting bolts may collapse the pipe sufficiently to prevent the detector
from functioning properly.
Do NOT install steel or iron pipe sections in copper piping for mounting a
waterflow detector. Incompatibility between the dissimilar metals causes bimetallic corrosion.
D770-01-00
1
I56-0459-018R
I56-0459-018R
INSTALLATION AND MAINTENANCE INSTRUCTIONS
Pre-Operation Testing
1.Fill the sprinkler system and check for leaks around the waterflow detector. If it leaks, first check for the proper torque on the U-bolt nuts. If the
leak persists, drain the system and remove the detector (refer to Maintenance). Check for dirt or foreign objects under the gasket, and make sure
that the pipe surface is not dented. Reinstall the detector and check again
for leaks. Do not proceed until all leaks have been stopped.
2.Connect an ohmmeter or continuity tester across the COM and B-NO
switch terminals. The ohmmeter should indicate an open circuit.
3.Deflect the actuator lever and hold it until the pneumatic delay shaft
releases the switch buttons. The ohmmeter or continuity tester should
show a short circuit after the delay has elapsed. If there is no delay,
check the setting of the delay adjustment dial.
Figure 3. Assembly diagram:
5.Install the U-bolt, tightening the nuts alternately to ensure a uniform seal
(see Table 1 for torque values).
6. Remove the metal cover with the tamper-proof wrench provided. Move
the actuator lever back and forth to check for binding. If the vane binds, remove the detector and correct the cause before proceeding.
CAUTION
Be sure the direction-of-flow arrow points in the right direction or else water
flow will go unreported. See Figure 3.
Figure 1. Mounting dimensions:
9.5 CM
(33/4˝)
TAMPER PROOF
WRENCH
(P/N WFDW)
7.6 CM
(3˝)
COVER
PIPE DIAMETER
PLUS 13.3 CM
(51/4˝)
U-BOLT
NUT
PIPE
SADDLE
DELAY
MECHANISM
(REPLACEMENT
(P/N A3008-00)
PIPE
MOUNTING PLATE
PIPE
VANE
PIPE SADDLE
TERMINAL
BLOCK
(REPLACEMENT
P/N A77-01-02)
ELECTRICAL
CONDUIT
ENTRANCE
U-BOLT
NUT
PLASTIC VANE
U-BOLT
ROLL PADDLE
OPPOSITE OF
FLOW ARROW
WHILE INSERTING
OVERALL WIDTH = PIPE DIAMETER + 7.6 CM (3˝)
W0105-00
Figure 2. Mounting hole location:
SADDLE GASKET
WRONG
PIPE
W
LO
F
ER
T
WA
RIGHT
REFER TO
TABLE 1
U-BOLT
W101-01
Wiring
REMOVE BURRS FROM EDGE OF HOLE. CLEAN OUT SCALE
AND FOREIGN MATTER FROM INSIDE WALL OF PIPE.
1. All models have two SPDT switches. Switch contacts COM and B-NO
are closed when water is flowing and open when it is not. Connect the
switches, as shown in Figure 4, depending on the application.
2. When connected to a listed sprinkler/fire alarm control panel, the initiating circuit must be nonsilenceable.
3. A ground screw is provided with all waterflow detectors. When grounding is required, clamp wire with screw in hole located between conduit
entrance holes. See Figure 5A, page 4.
4.If a second conduit entry is required, remove the knockout plug using a
flat blade screwdriver as shown on Figure 5B, page 4. Strike sharply with a
hammer to pierce the wall of the knockout plug. Move to an adjacent wall
section and repeat until the plug falls out. Make sure that the waterflow
detector is supported adequately during this operation to avoid injury.
W0106-00
Table 1:
Wfd model
Hole size (in)
Torque
20, 25, 35
11/4
30–35 ft.-lb.
30-2, 40, 50, 60, 80
2
55–60 ft.-lb.
D770-01-00
2
I56-0459-018R
To remove a detector:
WARNING
1. Drain the pipe.
2. Turn off electrical power to the detector and disconnect the wiring.
3. Loosen the nuts and remove the U-bolts.
4.Gently lift the saddle far enough to get your fingers under it. Then, roll
the vane so it will fit through the hole while continuing to lift the waterflow detector saddle.
5. Lift the detector clear of the pipe.
High Voltage. Electrocution Hazard. Do not handle live AC wiring or work on a
device to which AC power is applied. Doing so may result in injury or death.
When utilizing switches at voltages greater than 74VDC
or 49VAC
means to provide all–pole disconnection must be incorporated in the fixed
wiring, such as a circuit breaker.
Figure 4. WFD wiring:
UL-LISTED
COMPATIBLE
CONTROL PANEL
SSM24-X
SSV120-X
POWER +
24VDC OR
120VAC
–
INITIATING
LOOP
+
–
SUGGESTED EOL
RESISTOR
NOTE: COMMON AND B-NO
CONNECTIONS WILL CLOSE
WHEN VANE IS DEFLECTED, I.E.,
WHEN WATER IS FLOWING. DUAL
SWITCHES PERMIT
APPLICATIONS TO BE COMBINED
ON A SINGLE DETECTOR.
CAUTION
If a vane breaks in a pipe, find and remove it. If it is not removed, the vane
may restrict the flow of water to all or part of the sprinkler system.
Figure 5A. Ground screw location:
CONTACT RATINGS
125/250 VAC 10 AMPS
24 VDC
2.5 AMPS
SCHEMATIC OF
INDIVIDUAL
SWITCH IN
“NO WATERFLOW”
CONDITION
BREAK WIRE AS
SHOWN FOR
SUPERVISION OF
CONNECTION. DO
NOT ALLOW
STRIPPED WIRE
LEADS TO EXTEND
BEYOND SWITCH
HOUSING. DO NOT
LOOP WIRES.
GROUND
SCREW
(GREEN)
A-NC
COM
MOUNTING
PLATE
B-NO
W103-00
Figure 5B. Knockout plug removal:
W0356-01
Mechanical Delay Adjustment
The pneumatic delay is preset at the factory to 30 seconds. To adjust the setting, turn the adjustment dial clockwise to increase the delay, counterclockwise to decrease it. The delay is adjustable from 0 to 90 seconds. See Figure
6, page 4.
NOTE: Set the delay to the minimum required to prevent false alarms from
flow surges.
Periodically test time delay as required by Authority Having Jurisdiction or
code authority.
Operational Testing
Always notify a central station monitoring waterflow alarms before repairing,
maintaining, or testing waterflow alarm devices.
1.Replace the cover and tighten the tamper proof screws with the tamper
proof wrench. Store the wrench in a secure place.
2.Open the inspector’s test valve and time how long it takes for the detector to indicate a flow condition. The detector should remain activated until the inspector’s test valve is closed. Air pockets in the sprinkler system
may increase the apparent delay.
Maintenance
To prevent accidental water damage, control valves should be shut tight and
the system completely drained before waterflow detectors are removed or replaced.
W0148-01
Figure 6. Delay adjustment dial:
0
70
15
55
30
Inspect detectors in accordance with applicable NFPA codes and standards
and/or the authority having jurisdiction for leaks and replace if a leak occurs.
Test detectors at least quarterly, as described under Operational Testing, to
ensure proper operation. Test more often if required by the authority having
jurisdiction.
45
Under normal conditions, System Sensor waterflow detectors should provide
years of trouble-free service. However, if the delay mechanism or switch enclosure needs to be replaced, follow these directions. To replace the delay
mechanism or switch enclosure, use a 3/16˝ socket head screwdriver to remove
the three screws that hold it in place. Either mechanism can be easily replaced
without removing the detector from the pipe or draining the pipe. To replace
the delay mechanism, request Part No. A3008-00. For switch enclosure, request Part No. A77-01-02. Do not repair or replace any other waterflow detector components. If any other part of the detector does not perform properly,
replace the entire detector. Installation methods other than those listed in this
installation manual may prevent the device from reporting the flow of water in
the event the associated sprinkler system is activated by a fire. System Sensor
is not responsible for devices that have been improperly installed, tested, or
maintained.
D770-01-00
DIAL IS AP
ON LAY IN SE PRO
R
E
CO XIM
D
ND A
BE
M IME
S
T
TE
NU
DELAY
ADJUSTMENT
DIAL
NOTE: RETARD TIME MAY EXCEED 90 SECONDS. ADJUST
AND VERIFY THAT TIME DOES NOT EXCEED 90 SECONDS.
NUMBER ON DIAL IS APPROXIMATE TIME DELAY IN
SECONDS WITH AN ACCURACY OF +/− 50%.
W0112-02
3
I56-0459-018R
Please refer to insert for the Limitations of Fire Alarm Systems
WARNING
The Limitations of Waterflow Alarm Devices
1. Waterflow detectors may not work or operate properly if sprinkler piping being
3. Vane-type waterflow detectors have a normal service life of 10-15 years. Hard water
monitored is plugged with pipe scale, mud, stones or other foreign material. Sprinkler
systems, however, may substantially reduce waterflow detector service life.
systems should be checked regularly for such blocking material, following the instruc4. Waterflow detectors are not a substitute for insurance. Building owners should always
tions in Chapter 5 of NFPA Standard 13A.
insure property and lives being protected by sprinkler systems.
2. Alarms generated by the activation of waterflow detectors may not be received by a
5. If valves controlling the water supply to a sprinkler system are closed, vane-type wacentral station if telephone or other communication lines to the detector are out of
terflow detectors will not work. All valves controlling a sprinkler water supply should
service, disabled, or open.
be sealed or locked in the normally open position. The normally open position should
be monitored by a sprinkler supervisory switch.
Three-Year Limited Warranty
System Sensor warrants its enclosed waterflow detector to be free from defects in materiDepartment, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a
als and workmanship under normal use and service for a period of three years from date
note describing the malfunction and suspected cause of failure. The Company shall not
of manufacture. System Sensor makes no other express warranty for this waterflow detecbe obligated to repair or replace units which are found to be defective because of damage,
tor. No agent, representative, dealer, or employee of the Company has the authority to
unreasonable use, modifications, or alterations occurring after the date of manufacture.
increase or alter the obligations or limitations of this Warranty. The Company’s obligation
In no case shall the Company be liable for any consequential or incidental damages for
of this Warranty shall be limited to the repair or replacement of any part of the waterflow
breach of this or any other Warranty, expressed or implied whatsoever, even if the loss
detector which is found to be defective in materials or workmanship under normal use
or damage is caused by the Company’s negligence or fault. Some states do not allow the
and service during the three year period commencing with the date of manufacture.
exclusion or limitation of incidental or consequential damages, so the above limitation
After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return
or exclusion may not apply to you. This Warranty gives you specific legal rights, and you
Authorization number, send defective units postage prepaid to: System Sensor, Returns
may also have other rights which vary from state to state.
D770-01-00
4
I56-0459-018R
©2012 System Sensor