WFD Vane-type Waterflow Detectors Specifications Contact Ratings: Triggering Threshold Bandwidth (Flow Rate): Static Pressure Rating: Dimensions, Installed: Operating Temperature Range: Compatible Pipe: Shipping Weight: Enclosure Rating: U. S. Patent Numbers: 3825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 www.systemsensor.com 10 A @ 125/250 VAC ; 2.5 A @ 24 VDC 4 to 10 gpm See models listed below 3.5 in H x 3.0 in W x 6.7 in D 32°F to 120°F (0°C to 49°C) Steel water pipe, schedule 10 through 40 4 to 7 lb (according to size) NEMA Type 4, as tested by Underwriters Laboratories, Inc. (IP56) 5,213,205 Important Please Read Carefully And Save Installation Guidelines Before installing any waterflow alarm device, be thoroughly familiar with: This instruction manual contains important information about the installation and operation of waterflow detectors. Purchasers who install waterflow detectors for use by others must leave this manual or a copy of it with the user. NFPA 72: National Fire Alarm Code NFPA 13: Installation of Sprinkler Systems, Sect. 3.17 NFPA 25: Inspection, Testing and Maintenance of Sprinkler Systems, Sect. 5.3.3.2 Read all instructions carefully before beginning. Follow only those instructions that apply to the model you are installing. Other applicable NFPA standards, local codes, and the requirements of the authority having jurisdiction CAUTION NOTE: Installation methods other than those listed in this installation manual may prevent the device from reporting the flow of water in the event the associated sprinkler system is activated by a fire. System Sensor is not responsible for devices that have been improperly installed, tested, or maintained. Use vane-type waterflow detectors in wet-pipe systems only. Do NOT use them in dry pipe, deluge, or preaction systems. The sudden inrush of water in such systems may break the vane or damage the mechanism. 1.Mount the detector where there is adequate clearance for installation and removal and a clear view of it for inspections. See Figure 1 for mounting dimensions. 2.Locate the detector 6 to 7 feet above the floor to protect from accidental damage. 3.On horizontal runs, position the detector on the top or side of the pipe. Do not mount it upside down because condensation may collect in the housing and impair the operation of the detector. For vertical flow applications, mount the detector on pipe through which water flows upward. Otherwise, the unit may not operate properly. 4.Mount the detector at least 6 inches from a fitting that changes the direction of water flow and no less than 24 inches from a valve or drain. 5.Be sure the direction-of-flow arrow matches the direction of flow in the pipe. Mounting Instructions 1. Drain the pipe. 2.Cut a hole at the desired location. Center the hole in the pipe, as shown in Figure 2, and be sure the hole is perpendicular to the center of the pipe. Before drilling, use a punch or scribe to mark the drill site to prevent the bit from slipping. If the hole is off center, the vane will bind against the inside wall of the pipe. Use a drill or hole saw to cut a hole of the proper diameter. See Table 1 for hole size. Do not use in potentially explosive atmospheres. Do not allow unused wires to remain exposed. Principles Of Operation Vane-type waterflow detectors mount to water-filled pipes in sprinkler systems. Waterflow in the pipe deflects a vane, which produces a switched output– usually after a specified delay. All waterflow detectors have a pneumatically controlled mechanical delay mechanism. Delays do NOT accumulate; they reset if the flow of water stops before the entire delay has elapsed. All switches actuate when the water flow rate is 10 gallons per minute or greater, but will not actuate if the flow rate is less than 4 gallons per minute. This System Sensor installation manual covers the following waterflow detectors for sprinkler/ fire alarm applications. Pipe Size (inches) Pipe Schedule Max. Pressure Rating (psig) WFD20 2 10 thru 40 450 WFD25 2.5 10 thru 40 450 WFD30-2 3 10 thru 40 450 WFD35 3.5 10 thru 40 450 WFD40 4 10 thru 40 450 WFD50 5 10 thru 40 450 WFD60 6 10 thru 40 450* WFD80 8 10 thru 40 450* Model CAUTION When drilling the hole with a hole saw, make certain that the center of the cut does not remain in the pipe. 3.Remove burrs and sharp edges from the hole. Clean and remove all scale and foreign matter from the inside of the pipe for one diameter on each side of the hole to ensure free movement of the vane. Clean the outside of the pipe to remove dirt, metal chips, and cutting lubricant. 4.Seat the gasket against the saddle and mount the detector directly to the pipe. Carefully roll the vane opposite the direction of flow and insert it through the hole. Seat the saddle firmly against the pipe so that the locating boss goes into the hole. *Maximum Pressure Rating 400 psig as approved by Factory Mutual Research. CAUTION Do NOT use any of the WFD models on copper pipe. The clamping forces of the mounting bolts may collapse the pipe sufficiently to prevent the detector from functioning properly. Do NOT install steel or iron pipe sections in copper piping for mounting a waterflow detector. Incompatibility between the dissimilar metals causes bimetallic corrosion. D770-01-00 1 I56-0459-018R I56-0459-018R INSTALLATION AND MAINTENANCE INSTRUCTIONS Pre-Operation Testing 1.Fill the sprinkler system and check for leaks around the waterflow detector. If it leaks, first check for the proper torque on the U-bolt nuts. If the leak persists, drain the system and remove the detector (refer to Maintenance). Check for dirt or foreign objects under the gasket, and make sure that the pipe surface is not dented. Reinstall the detector and check again for leaks. Do not proceed until all leaks have been stopped. 2.Connect an ohmmeter or continuity tester across the COM and B-NO switch terminals. The ohmmeter should indicate an open circuit. 3.Deflect the actuator lever and hold it until the pneumatic delay shaft releases the switch buttons. The ohmmeter or continuity tester should show a short circuit after the delay has elapsed. If there is no delay, check the setting of the delay adjustment dial. Figure 3. Assembly diagram: 5.Install the U-bolt, tightening the nuts alternately to ensure a uniform seal (see Table 1 for torque values). 6. Remove the metal cover with the tamper-proof wrench provided. Move the actuator lever back and forth to check for binding. If the vane binds, remove the detector and correct the cause before proceeding. CAUTION Be sure the direction-of-flow arrow points in the right direction or else water flow will go unreported. See Figure 3. Figure 1. Mounting dimensions: 9.5 CM (33/4˝) TAMPER PROOF WRENCH (P/N WFDW) 7.6 CM (3˝) COVER PIPE DIAMETER PLUS 13.3 CM (51/4˝) U-BOLT NUT PIPE SADDLE DELAY MECHANISM (REPLACEMENT (P/N A3008-00) PIPE MOUNTING PLATE PIPE VANE PIPE SADDLE TERMINAL BLOCK (REPLACEMENT P/N A77-01-02) ELECTRICAL CONDUIT ENTRANCE U-BOLT NUT PLASTIC VANE U-BOLT ROLL PADDLE OPPOSITE OF FLOW ARROW WHILE INSERTING OVERALL WIDTH = PIPE DIAMETER + 7.6 CM (3˝) W0105-00 Figure 2. Mounting hole location: SADDLE GASKET WRONG PIPE W LO F ER T WA RIGHT REFER TO TABLE 1 U-BOLT W101-01 Wiring REMOVE BURRS FROM EDGE OF HOLE. CLEAN OUT SCALE AND FOREIGN MATTER FROM INSIDE WALL OF PIPE. 1. All models have two SPDT switches. Switch contacts COM and B-NO are closed when water is flowing and open when it is not. Connect the switches, as shown in Figure 4, depending on the application. 2. When connected to a listed sprinkler/fire alarm control panel, the initiating circuit must be nonsilenceable. 3. A ground screw is provided with all waterflow detectors. When grounding is required, clamp wire with screw in hole located between conduit entrance holes. See Figure 5A, page 4. 4.If a second conduit entry is required, remove the knockout plug using a flat blade screwdriver as shown on Figure 5B, page 4. Strike sharply with a hammer to pierce the wall of the knockout plug. Move to an adjacent wall section and repeat until the plug falls out. Make sure that the waterflow detector is supported adequately during this operation to avoid injury. W0106-00 Table 1: Wfd model Hole size (in) Torque 20, 25, 35 11/4 30–35 ft.-lb. 30-2, 40, 50, 60, 80 2 55–60 ft.-lb. D770-01-00 2 I56-0459-018R To remove a detector: WARNING 1. Drain the pipe. 2. Turn off electrical power to the detector and disconnect the wiring. 3. Loosen the nuts and remove the U-bolts. 4.Gently lift the saddle far enough to get your fingers under it. Then, roll the vane so it will fit through the hole while continuing to lift the waterflow detector saddle. 5. Lift the detector clear of the pipe. High Voltage. Electrocution Hazard. Do not handle live AC wiring or work on a device to which AC power is applied. Doing so may result in injury or death. When utilizing switches at voltages greater than 74VDC or 49VAC means to provide all–pole disconnection must be incorporated in the fixed wiring, such as a circuit breaker. Figure 4. WFD wiring: UL-LISTED COMPATIBLE CONTROL PANEL SSM24-X SSV120-X POWER + 24VDC OR 120VAC – INITIATING LOOP + – SUGGESTED EOL RESISTOR NOTE: COMMON AND B-NO CONNECTIONS WILL CLOSE WHEN VANE IS DEFLECTED, I.E., WHEN WATER IS FLOWING. DUAL SWITCHES PERMIT APPLICATIONS TO BE COMBINED ON A SINGLE DETECTOR. CAUTION If a vane breaks in a pipe, find and remove it. If it is not removed, the vane may restrict the flow of water to all or part of the sprinkler system. Figure 5A. Ground screw location: CONTACT RATINGS 125/250 VAC 10 AMPS 24 VDC 2.5 AMPS SCHEMATIC OF INDIVIDUAL SWITCH IN “NO WATERFLOW” CONDITION BREAK WIRE AS SHOWN FOR SUPERVISION OF CONNECTION. DO NOT ALLOW STRIPPED WIRE LEADS TO EXTEND BEYOND SWITCH HOUSING. DO NOT LOOP WIRES. GROUND SCREW (GREEN) A-NC COM MOUNTING PLATE B-NO W103-00 Figure 5B. Knockout plug removal: W0356-01 Mechanical Delay Adjustment The pneumatic delay is preset at the factory to 30 seconds. To adjust the setting, turn the adjustment dial clockwise to increase the delay, counterclockwise to decrease it. The delay is adjustable from 0 to 90 seconds. See Figure 6, page 4. NOTE: Set the delay to the minimum required to prevent false alarms from flow surges. Periodically test time delay as required by Authority Having Jurisdiction or code authority. Operational Testing Always notify a central station monitoring waterflow alarms before repairing, maintaining, or testing waterflow alarm devices. 1.Replace the cover and tighten the tamper proof screws with the tamper proof wrench. Store the wrench in a secure place. 2.Open the inspector’s test valve and time how long it takes for the detector to indicate a flow condition. The detector should remain activated until the inspector’s test valve is closed. Air pockets in the sprinkler system may increase the apparent delay. Maintenance To prevent accidental water damage, control valves should be shut tight and the system completely drained before waterflow detectors are removed or replaced. W0148-01 Figure 6. Delay adjustment dial: 0 70 15 55 30 Inspect detectors in accordance with applicable NFPA codes and standards and/or the authority having jurisdiction for leaks and replace if a leak occurs. Test detectors at least quarterly, as described under Operational Testing, to ensure proper operation. Test more often if required by the authority having jurisdiction. 45 Under normal conditions, System Sensor waterflow detectors should provide years of trouble-free service. However, if the delay mechanism or switch enclosure needs to be replaced, follow these directions. To replace the delay mechanism or switch enclosure, use a 3/16˝ socket head screwdriver to remove the three screws that hold it in place. Either mechanism can be easily replaced without removing the detector from the pipe or draining the pipe. To replace the delay mechanism, request Part No. A3008-00. For switch enclosure, request Part No. A77-01-02. Do not repair or replace any other waterflow detector components. If any other part of the detector does not perform properly, replace the entire detector. Installation methods other than those listed in this installation manual may prevent the device from reporting the flow of water in the event the associated sprinkler system is activated by a fire. System Sensor is not responsible for devices that have been improperly installed, tested, or maintained. D770-01-00 DIAL IS AP ON LAY IN SE PRO R E CO XIM D ND A BE M IME S T TE NU DELAY ADJUSTMENT DIAL NOTE: RETARD TIME MAY EXCEED 90 SECONDS. ADJUST AND VERIFY THAT TIME DOES NOT EXCEED 90 SECONDS. NUMBER ON DIAL IS APPROXIMATE TIME DELAY IN SECONDS WITH AN ACCURACY OF +/− 50%. W0112-02 3 I56-0459-018R Please refer to insert for the Limitations of Fire Alarm Systems WARNING The Limitations of Waterflow Alarm Devices 1. Waterflow detectors may not work or operate properly if sprinkler piping being 3. Vane-type waterflow detectors have a normal service life of 10-15 years. Hard water monitored is plugged with pipe scale, mud, stones or other foreign material. Sprinkler systems, however, may substantially reduce waterflow detector service life. systems should be checked regularly for such blocking material, following the instruc4. Waterflow detectors are not a substitute for insurance. Building owners should always tions in Chapter 5 of NFPA Standard 13A. insure property and lives being protected by sprinkler systems. 2. Alarms generated by the activation of waterflow detectors may not be received by a 5. If valves controlling the water supply to a sprinkler system are closed, vane-type wacentral station if telephone or other communication lines to the detector are out of terflow detectors will not work. All valves controlling a sprinkler water supply should service, disabled, or open. be sealed or locked in the normally open position. The normally open position should be monitored by a sprinkler supervisory switch. Three-Year Limited Warranty System Sensor warrants its enclosed waterflow detector to be free from defects in materiDepartment, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a als and workmanship under normal use and service for a period of three years from date note describing the malfunction and suspected cause of failure. The Company shall not of manufacture. System Sensor makes no other express warranty for this waterflow detecbe obligated to repair or replace units which are found to be defective because of damage, tor. No agent, representative, dealer, or employee of the Company has the authority to unreasonable use, modifications, or alterations occurring after the date of manufacture. increase or alter the obligations or limitations of this Warranty. The Company’s obligation In no case shall the Company be liable for any consequential or incidental damages for of this Warranty shall be limited to the repair or replacement of any part of the waterflow breach of this or any other Warranty, expressed or implied whatsoever, even if the loss detector which is found to be defective in materials or workmanship under normal use or damage is caused by the Company’s negligence or fault. Some states do not allow the and service during the three year period commencing with the date of manufacture. exclusion or limitation of incidental or consequential damages, so the above limitation After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return or exclusion may not apply to you. This Warranty gives you specific legal rights, and you Authorization number, send defective units postage prepaid to: System Sensor, Returns may also have other rights which vary from state to state. D770-01-00 4 I56-0459-018R ©2012 System Sensor