Product Manual - System Sensor

I56-3050-004R
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
D2 Duct Smoke Detector
Specifications
Operating Temperature:
–4° to 158° F (–20° to 70° C)
Storage Temperature:
–22° to 158° F (–30° to 70° C)
Humidity:
0% to 93% Relative Humidity Non-condensing
Air Velocity:
100 to 4000 ft./min. (0.5 to 20.3 m/sec.)
Rectangular Footprint Dimensions:
14.38 in L x 5 in W x 2.5 in D (37 cm L x 12.7 cm W x 6.36 cm D)
Square Footprint Dimensions:
7.75 in L x 9 in W x 2.5 in D (19.7 cm L x 22.9 cm W x 6.35 cm D)
Weight:
1.8 pounds; 0.82 kg
Electrical
Power supply voltage:
8.5-35 VDC
Input capacitance:
0.1 µF max.
Reset Voltage:
2.5 VDC min.
Reset Time (with RTS451/RTS151):
.03 to 0.3 sec.
ACCESSORY CURRENT LOADS AT 24 VDC
Reset Time (by power down):
0.3 sec. max.
DEVICE
STANDBY
ALARM
Power Up Time:
35 sec. max.
RA400Z/RA100Z
0mA
12mA Max.
Alarm response time:
15 sec.
Sensitivity Test:
See detector label
RTS451/RTS151
0mA
12mA Max.
Current Requirements (Using No Accessories)
RTS451KEY/RTS151KEY
0mA
12mA Max.
Peak standby current
120µA
Average standby current
60µA
Max. alarm current
130 mA
Table of Contents
Page
[1] Limitations of Duct Smoke Detectors. . . . . . . . . . . . . . . . . . . . . . . . . 1
[2] General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
[3] Contents of the Duct Smoke Detector Kit. . . . . . . . . . . . . . . . . . . . . . 1
[4] Exploded View of Duct Smoke Detector Components. . . . . . . . . . . . . 2
[5] Detector Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
[6] Sampling Tube Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
[7] Measurement Tests. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
[8] Field Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
[9] Detector Status Indicator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
[10] Verification of Operator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
[11] Dectector Cleaning Procedures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
[12] Sensor Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
[13] Optional Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Wiring Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4,6
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
The D2 model is a photoelectric detector approved for an extended air speed
range of 100 to 4000 feet per minute (0.5 m/s to 20.3 m/s) and an operational
temperature range of −4°F to 158°F (−20°C to 70°C).
This device will not operate without electrical power. Fire situations may
cause an interruption of power. The system safeguards should be discussed
with your local fire protection specialist.
This device will not sense smoke unless the ventilation system is operating
and the cover is installed.
For this detector to function properly, it MUST be installed according to the instructions in this manual. Furthermore, the detector MUST be operated within
ALL electrical and environmental specifications listed in this manual. Failure
to comply with these requirements may prevent the detector from activating
when smoke is present in the air duct.
[2] General Description
Smoke introduced into the air duct system will be distributed throughout the
entire building. Smoke detectors designed for use in air duct systems are used
to sense the presence of smoke in the duct.
Model D2 Duct Smoke Detector utilizes photoelectric technology for the detection of smoke. This detection method, when combined with an efficient
housing design, samples air passing through the duct allowing detection of a
developing hazardous condition. When sufficient smoke is sensed, an alarm
signal is initiated and appropriate action can be taken to shut off fans,
blowers, change over air handling systems, etc. These actions can facilitate
the management of toxic smoke and fire gases throughout the areas served
by the duct system.
Before Installing
Read the System Sensor Guide for Proper Use of Smoke Detectors in Duct Applications (A05-1004), which provides detailed information on detector spacing,
placement, zoning, wiring, and special applications. Copies of this manual
are available online at www.systemsensor.com. NFPA Standards 72 and 90A
should also be referenced for detailed information.
[2.1] DETECTOR FEATURE SET
- Utilizes 2151 plug-in head
- Sampling tubes installed from front or rear
- Compatible with existing accessories
NOTICE: This manual shall be left with the owner/user of this equipment.
IMPORTANT: This detector must be tested and maintained regularly following
NFPA 72 requirements. The detector should be cleaned at least once a year.
[3] Contents Of The Duct Smoke Detector Kit
1. Sensor/power board assembly and covers
2. Three #10 sheet metal screws for mounting
3. Drilling template
4. One sampling tube end cap
5. One plastic exhaust tube
NOTE: A sampling tube must be ordered to complete the installation. It must
be the correct length for the width of the duct where it will be installed. See Table 1 on page 3 to determine the inlet tube required for different duct widths.
[1] Limitations Of Duct Smoke Detectors
WARNING
The National Fire Protection Association has established that DUCT DETECTORS MUST NOT BE USED AS A SUBSTITUTE FOR OPEN AREA DETECTOR
PROTECTION as a means of providing life safety. Nor are they a substitute for
early warning in a building’s regular fire detection system.
System Sensor supports this position and strongly recommends that the user
read NFPA Standards 90A, 72, and 101. The D2 Air Duct Smoke Detectors are
listed per UL 268A.
SS-300-014
1
I56-3050-004R
[4] Figure 1. Exploded View of Duct Smoke Detector Components:
SAMPLING TUBE
(sold seperately)
EXHAUST TUBE
WIRING TERMINALS
TERMINAL HOUSING
MODULE COVER
SENSOR HEAD
SENSOR MODULE COVER
MAGNET TEST LOCATION
H0574-05
[5.3] Drill the Mounting Holes
Remove the paper backing from the mounting template supplied. Affix the template to the duct at the desired mounting location. Make sure the template lies
flat and smooth on the duct.
[5] Detector Installation
[5.1] Verify Duct Air Flow Direction And Velocity
Model D2 detectors are designed to be used in air handling systems having air
velocities of 100 to 4000 feet per minute. Duct widths from 6 inches to 12 feet
can be accommodated. Be sure to check engineering specifications to ensure
that the air velocity in the duct falls within these parameters. If necessary, use
a velocity meter (anemometer) to check the air velocity in the duct.
[5.3.1] For rectangular side-by-side mounting configuration:
Center punch at (4) target centers: (2) “A” for sampling tubes and (2) “B” for
the rectangular configuration mounting tabs as shown on mounting template.
Drill pilot holes at target “A” centers and cut two 1.375 inch diameter holes using a 13/8 inch hole saw or punch. Drill .156 inch diameter holes using a 5/32”
inch drill at target “B” centers.
[5.2] Determine Mounting location
and Configuration
On ducts wider than 18 inches it is recommended that the detector be
mounted downstream of a bend, obstruction in the duct, or the supply or
return air inlet.
[5.3.2] For square top-over-bottom mounting configuration:
Center punch at (4) target centers: (2) “A” for sampling tubes and (2) “C” for
the square configuration mounting tabs as shown on mounting template. Drill
pilot holes at target “A” centers and cut two 1.375 inch diameter holes using a
13/8” inch hole saw or punch. Drill .156 inch diameter holes using a 5/32 inch
drill at target “C” centers. If desired, drill an additional .156 inch hole at the
location of one of the mounting tabs on the lower housing.
Exception: Installation of duct detectors can be on or within a commercial
packaged rooftop heating and air-conditioning system, fire/smoke dampers
and economizers. They may be mounted in either the supply and/or return air
section as determined by local code.
Once a suitable location is selected, determine if the detector is to be mounted
in a side-by-side “rectangular” configuration or a top-over-bottom “square”
configuration as shown in Figure 2. If mounting in the square configuration,
remove the rear attachment screw, rotate the unit at hinge, and replace the
screw into the new attachment hole as shown in Figure 2. Do NOT remove
the hinge screw during this process. Final installation approval shall be based
upon passing section 10.4.2 and 10.4.4 tests.
[5.4] Secure the Duct Detector to the Duct
Use two (rectangular configuration) or three (square configuration) of the provided sheet metal screws to screw the duct detector to the duct.
CAUTION: Do not overtighten the screws.
Figure 2:
REMOVE SCREW AND PIVOT
DETECTOR AS SHOWN BELOW.
REPLACE SCREW
TO SECURE DETECTOR
IN PLACE.
H0550-00
SS-300-014
2
I56-3050-004R
[6] Sampling Tube Installation
[6.1] Sampling Tube Selection
The sampling tube must be purchased separately. Order the correct length,
as specified in Table 1, for width of the duct where it will be installed. It is
recommended that the sampling tube length extend at least 2/3 across the duct
width for optimal performance.
width of the duct. If there are more than 2 holes in the section of the
tube extending out of the duct, select a shorter tube using Table 1. Otherwise, trim the tube to leave approximately 1-2 inches extending outside the duct. Plug the end with the end cap and tape closed any holes
in the protruding section of the tube. Be sure to seal the duct where the
tube protrudes.
Table 1. Sampling tubes recommended for
different duct widths:
Figure 4:
Sampling Tube
Recommended*
Outside Duct Width
Up to 1 ft.
/˝
1 4
DST1
1 to 2 ft.
DST1.5
2 to 4 ft.
2˝
DST3
4 to 8 ft.
12˝
DST5
8 to 12 ft.
DST10 (2-piece)
3 4
/˝
HOLE
*Must extend a minimum of /3 the duct width
2
DETECTOR
H0215-00
The sampling tube is always installed with the air inlet holes facing into the
air flow. To assist proper installation, the tube’s connector is marked with an
arrow. Make sure the sampling tube is mounted so that the arrow points into
the airflow as shown in Figure 3. Mounting the detector housing in a vertical
orientation is acceptable provided that the air flows directly into the sampling
tube holes as indicated in Figure 3. The sampling tube and exhaust tube
can be mounted in either housing connection as long as the exhaust tube is
mounted downstream from the sampling tube.
NOTE: Air currents inside the duct may cause excessive vibration, especially
when the longer sampling tubes are used. In these cases, a 3 inch floor flange
(available at most plumbing supply stores) may be used to fasten the sampling
tube to the other side of the duct. When using the flange/connector mounting
technique, drill a 1 to 11⁄4 inch hole where the flange will be used.
[6.3] Modifications of Sampling Tubes
There may be applications where duct widths are not what is specified for the
installation. In such cases, it is permissible to modify a sampling tube that is
longer than necessary to span the duct width.
Figure 3. Air duct detector sampling tube:
SAMPLING TUBE ENDCAP
Use a 0.193 inch diameter (#10) drill and add the appropriate number of holes
so that the total number of holes exposed to the air flow in the duct is 10 to 12.
Space the additional holes as evenly as possible over the length of the tube.
ARROW MUST FACE
INTO AIR FLOW
NOTE: This procedure should only be used as a temporary fix. It is not intended as a permanent substitute for ordering the correct length tubes.
[6.4] Remote Sampling Tube Installation
The detector arrangement can also incorporate the remote mounting of the
sampling tube and/or exhaust tube. In this case both the detector, sampling
tube and exhaust tube (if included) should be rigidly mounted to withstand
the pressure and vibrations caused by the air velocity. The location of the
detector’s sampling tube should be such that there is uniform airflow in the
cross section area.
AIR FLOW
DIRECTION
H0551-00
CAUTION: The sampling tube end cap, included with the detector, is critical to proper operation of the duct smoke detector. The end cap is needed to
create the proper air flow to the sensor of the duct smoke detector. Once any
sampling tube length adjustments are made, plug the end of the sampling tube
with the provided end cap.
The pressure differential across the sampling and exhaust ports in the detector housing shall be verified to be between .01 and 1.11 inches of water. Do
so by measuring the pressure difference between the inlet and outlet ports
on the detector housing using a manometer as described in Section 10.4.4 of
this manual.
A plastic exhaust tube is included with the unit to be installed if needed. Install into the housing connection that is downstream from the sampling tube
connection. The exhaust tube can be installed from the front of the detector
or the back. A longer 1 foot exhaust tube, model ETX is available as an accessory in cases where the molded exhaust tube does not extend at least 2 inches
into the duct.
[7] Measurement Tests
[7.1] Air Flow
The D2 is designed to operate over an extended air speed range of 100 to
4000 FPM. To verify sufficient sampling of ducted air, turn the air handler on
and use a manometer to measure the differential pressure between the two
sampling tubes. The differential pressure should measure at least 0.01 inches
of water and no more than 1.11 inches of water. Because most commercially
available manometers cannot accurately measure very low pressure differentials, applications with less than 500 FPM of duct air speed may require one
of the following: 1) the use of a current-sourcing pressure transmitter (Dwyer
Series 607) per Section 7.2; or 2) the use of aerosol smoke per section 10.4.4.
[6.2] Sampling Tube Installation
1.For tubes shorter than the width of the duct, slide the sampling tube,
with installed end cap, into the housing connection that meets the airflow first. Position the tube so that the arrow points into the airflow as
shown in Figure 3. Per NFPA sampling tubes over 3 feet long should be
supported at the end opposite of the duct detector. In ducts wider than 8
feet, work must be performed inside the duct to couple the other section
of the sampling tube to the section already installed using the 1/2 inch
conduit fitting supplied. Make sure that the holes on both sections of the
air inlet sampling tube are lined up and facing into the airflow.
2.For tubes longer than the width of the air duct, the tube should extend
out of the opposite side of the duct. Drill a 3/4 inch hole in the duct opposite the hole already cut for the sampling tube. Ensure that the sampling tube is angled downward from the duct smoke detector to allow for
moisture drainage away from the detector. The sampling tube should be
angled at least 1/4” downward for every 12” of duct width per Figure 4.
There should be 10 to 12 holes spaced as evenly as possible across the
SS-300-014
[7.2] Low Flow Air Flow Test using Dwyer Series 607 Differential Pressure Transmitter
Verify the air speed of the duct using an anemometer. Air speed must be at
least 100 FPM. Wire the Dwyer transmitter as shown in Figure 5. Connect the
leads of the meter to either side of the 1000Ω resistor. Allow unit to warm up
for 15 seconds. With both HIGH and LOW pressure ports open to ambient air,
measure and record the voltage drop across the 1000Ω resistor (measurement
1), 4.00 volts is typical. Using flexible tubing and rubber stoppers, connect the
HIGH side of the transmitter to the sampling tube of the duct smoke detec3
I56-3050-004R
tor housing, and the LOW side of the transmitter to the exhaust tube of the
duct smoke detector housing. Measure and record the voltage drop across the
1000Ω resistor (measurement 2). Subtract the voltage recorded in measurement 1 from the voltage recorded in measurement 2. If the difference is greater
than 0.15 volts, there is enough air flow through the duct smoke detector for
proper operation.
[8] Field Wiring; Installation Guidelines
All wiring must be installed in compliance with the National Electrical Code
and the local codes having jurisdiction. Proper wire gauges should be used.
The conductors used to connect smoke detectors to control panels and accessory devices should be color-coded to prevent wiring mistakes. Improper connections can prevent a system from responding properly in the event of a fire.
Figure 5. Procedure for verifying air flow:
For signal wiring, (the wiring between interconnected detectors or from detectors to auxiliary devices), it is recommended that single conductor wire be no
smaller than 18 gauge. The duct smoke detector terminals accommodate wire
sizes up to 12 gauge.
TO SAMPLING TUBE
TO EXHAUST TUBE
HIGH
Smoke detectors and alarm system control panels have specifications for allowable loop resistance. Consult the control panel manufacturer’s specifications for the total loop resistance allowed for the particular model control
panel being used before wiring the detector loop.
LOW
DIFFERENTIAL
PRESSURE
TRANSMITTER
MODEL #607-01
15 TO 36
VDC SUPPLY
1000 OHM 5%
1 WATT RESISTOR
9 VOLT
BATTERY
[8.1] Wiring Instructions
The D2 detectors are designed for easy wiring. The housing provides a terminal strip with clamping plates. Wiring connections are made by sliding the
bare end of the wire under the plate, and tightening the clamping plate screw.
See Figure 6 below for system wiring.
9 VOLT
BATTERY
9 VOLT
BATTERY
[9] DETECTOR STATUS INDICATION
Detector status is indicated by the LED’s on the sensor. Refer to table below
for more details.
VOLT METER FLUKE
MODEL 87 OR
EQUIVALENT
+
–
H0163-01
Figure 6. System wiring diagram for D2 2-wire duct smoke detectors
(detectors powered from initiating circuit):
UL/FM LISTED
COMPATIBLE 2-WIRE
CONTROL PANEL
(+) OUT
(+) RA
ALARM
INITIATION
LOOP
(–) RA
(+)
RA400Z (OPTIONAL)
REMOTE ALARM LED
(–)
4.4 VDC NOM.
IN ALARM
(+) IN
(+) OUT
(+) RA
(–) RA
(+)
RA400Z (OPTIONAL)
REMOTE ALARM LED
(–)
4.4 VDC NOM.
IN ALARM
(+) IN
EOL RESISTOR
SPECIFIED
BY PANEL
MANUFACTURER
(+) OUT
(+) RA
(–) RA
(+)
(–)
RA400Z (OPTIONAL) E
REMOTE ALARM LED O
L
R
4.4 VDC NOM.
IN ALARM
(–)
(–)
(–)
~
~
~
~
(–)
LAST DETECTOR
IN LOOP D2
~
~
(+) IN
~
~
(+)
2ND DETECTOR
IN LOOP D2
1ST DETECTOR
IN LOOP D2
STYLE D OPTIONAL WIRING
H0564-01
CAUTION
Do not loop wire under terminals when wiring detectors. Break wire runs to provide system supervision of connections.
TABLE 2. Detector Status Indications
Status
Sensor
Initialization
Standby
Sensor LEDs Designation
Alternating red blink every
5 seconds
Simultaneous red blink every
5 seconds
Maintenance
Not illuminated
Alarm
Solid Red
SS-300-014
Description/Trouble Shooting
At power up the sensor will take approximately 30 seconds to inialize. Also occurs when
sensor is removed during a seven minute delay.
The LED on the sensor should flash approximately every 5 seconds. If the sensor LEDs
are not illuminated, then the detector lacks power (check wiring, panel or power supply).
The sensor is outside of its sensitivity limits and shall be cleaned or replaced.
See Section 10.3 for details.
The unit is in alarm.
4
I56-3050-004R
[10] VERIFICATION OF OPERATION
[10.1] POWER THE UNIT
Apply 12VDC or 24 VDC to terminals marked as + in and -, see Figure 1, and
electrical specs for details.
CAUTION
Canned aerosol simulated smoke (canned smoke agent) formulas will vary
by manufacturer. Misuse or overuse to these products may have long term
adverse effects on the smoke detector. Consult the canned smoke agent manufacturer’s published instructions for any further warnings or caution statements.
[10.2] PERFORM DETECTOR CHECK
VERIFY STANDBY per Table 2 on page 4. The use of a remote accessory is
recommended.
[10.3] Sensitivity Verification
The sensitivity of the sensor is confirmed to be operating within its allowable
range each time the sensor LEDs blink red every 5 seconds. Note in a maintenance condition the sensor LEDs will not be illuminated as depicted in Table
2. The maintenance condition indicates that the sensor is operating outside its
original factory preset sensitivity and shall be cleaned or replaced. See Section
9 for reference. This is a valid UL test.
[10.5] Install The Cover
Install the covers making sure that the cover fits into the base groove. Tighten
the seven screws that are captured in the covers.
[11] Detector Cleaning Procedures
Notify the proper authorities that the smoke detector system is undergoing
maintenance, and that the system will temporarily be out of service. Disable
the zone or system undergoing maintenance to prevent unwanted alarms and
possible dispatch of the fire department.
The SENS-RDR sensitivity reader can also be used to measure the sensitivity
of the sensor. Sensitivity testing shall not be used as a substitute for alarm
testing.
Figure 7. Detector sensor exploded view:
SENSOR
COVER
[10.4] Duct Smoke Detector Test and
Maintenance Procedures
Test and maintain duct smoke detectors as recommended in NFPA 72. The
tests contained in this manual were devised to assist maintenance personnel
in verification of proper detector operation.
Before conducting these tests, notify the proper authorities that the smoke
detection system will be temporarily out of service. Disable the zone or system
under test to prevent unwanted alarms.
[10.4.1] Alarm Tests
1a.M02-04-00 Magnet Test (Sold Separately) – Place the painted surface of
the magnet onto the MAGNET TEST location on the sensor cover of unit
(Figure 1).
OR
1b.Remote Test Accessory - See list on page 1.
The red LEDs on the sensor should latch on, as should any accessories (i.e. RA400Z/RA100Z, RTS451/RTS151). Verify system control panel
alarm status and control panel execution of all intended auxiliary functions (i.e. fan shutdown, damper control, etc.)
2.The detector must be reset by the system control panel, or remote test
accessory
[10.4.2] Verify airflow test per Section 7 has been performed.
COVER
REMOVAL
TABS
SENSING
CHAMBER
COVER AND
SCREEN
SENSOR
CHAMBER
C1009-00
[11.1] Detector Sensor
1. Remove the sensor to be cleaned from the system.
2.Remove the sensor cover by pressing firmly on each of the four removal
tabs that hold the cover in place. See Figure 7.
3.Vacuum the screen carefully without removing it. If further cleaning is
required continue with Step 4, otherwise skip to Step 7.
4.Remove the chamber cover/screen assembly by pulling it straight out.
5.Use a vacuum cleaner or compressed air to remove dust and debris from
the sensing chamber.
6.Reinstall the chamber cover/screen assembly by sliding the edge over the
sensing chamber. Turn until it is firmly in place.
7.Replace the cover using the LEDs to align the cover and then gently
pushing it until it locks into place.
8. Reinstall the detector.
[11.2] Reinstallation
1. Reinstall the detector in its housing.
2. Restore system power.
3. Perform Detector Check, Section [10.2].
4.Notify the proper authorities testing has been completed and the smoke
detector system is back in operation.
[12] Sensor Replacement (part no. 2151)
1. Remove the sensor head by rotating counterclockwise.
2. Pull gently to remove it.
3.To replace the sensor head, align the mounting features and rotate clockwise into place.
[10.4.3] Smoke Response Tests
To determine if smoke is capable of entering the sensing chamber, visually
identify any obstructions. Close cover tamper terminals on sensor side of
housing to ensure communication to panel. Plug the exhaust and sampling
tube holes to prevent ducted air from carrying smoke away from the detector
head, then blow smoke such as cigarette, cotton wick, or punk directly at the
head to cause an alarm. REMEMBER TO REMOVE THE PLUGS AFTER THIS
TEST, OR THE DETECTOR WILL NOT FUNCTION PROPERLY.
[10.4.4] Smoke Entry using Aerosol Smoke
This test is intended for low-flow systems (100-500 FPM). If the air speed is
greater than 500 FPM, use a conventional manometer to measure differential
pressure between the sampling tubes, as described in 7.1.
Drill a 1⁄4 inch hole 3 feet upstream from the duct smoke detector. With the air
handler on, measure the air velocity with an anemometer. Air speed must be
at least 100 FPM. Spray aerosol smoke* into the duct through the 1⁄4 inch hole
for five seconds. Wait two minutes for the duct smoke detector to alarm. If the
duct smoke detector alarms, air is flowing through the detector. Remove the
duct smoke detector cover and blow out the residual aerosol smoke from the
chamber and reset the duct smoke detector. Use duct tape to seal the aerosol
smoke entry hole.
*Aerosol smoke can be purchased from Home Safeguard Industries at homesafeguard.com, model 25S Smoke Detector Tester, and Chekkit Smoke Detector
Tester model CHEK02 and CHEK06 available from SDi. When used properly,
the canned smoke agent will cause the smoke detector to go into alarm. Refer to the manufacturer’s published instructions for proper use of the canned
smoke agent.
SS-300-014
5
I56-3050-004R
[13] OPTIONAL ACCESSORIES
The D2 duct smoke detector can be used with the RA400Z/RA100Z, RTS451/
RTS151, or RTS451KEY/RTS151KEY remote test station.
Figure 9. D2 with Optional Test Coil:
Figure 8. Wiring diagrams for optional accessories:
(+)
ALARM +
AUX OUT –
RED
(–)
D2
DUCT DETECTOR
RA400Z/RA100Z
(OPTIONAL)
REMOTE (LED)
ANNUNCIATOR
H0611-05
TEST COIL
TEST COIL SCREW
TEST COIL TERMINALS
[13.1] RTS451/RTS151/RTS451KEY/RTS151KEY Remote Test
Station
The RTS451/RTS151/RTS451KEY/RTS151KEY Remote Test Station facilitates
test of the alarm capability of the duct smoke detector as indicated in the
RTS451/RTS151/RTS451KEY/RTS151KEY manual. The D2 duct smoke detector
must be reset by the system control panel. If a system control panel is used,
the panel itself may also require testing.
H0561-00
To install the RTS451/RTS151/RTS451KEY/RTS151KEY, connect the device as
shown in Figure 10 on page 6; wire runs must be limited to 25 ohms or less
per interconnecting wire.
NOTE: The use of a remote test station requires the installation of an accessory coil, part number DCOIL, sold separately. See Figure for reference.
1) Install DCOIL in housing pocket insuring that arrow is pointing toward detector
2) Install DCOIL mounting screw
3) Connect each DCOIL lead to a Test Coil Terminal
Figure 10. Wiring diagram for RTS451/RTS151/RTS451KEY/RTS151KEY Remote Test Station to
2-wire D2 duct detector:
MAGNET
TEST
SWITCH
4
– TEST COIL
5
2
ALARM
LED (RED)
+ TEST COIL
1
(–)
(+)
RTS451/RTS451KEY
(OPTIONAL) REMOTE
TEST STATION
+ IN
+ OUT
–
(–)
(+)
24 VDC
AUX POWER
SUPPLIED
BY USER
(100mA
SUPPLY)
24 VDC
AUX POWER
SUPPLIED
BY USER
(100mA
SUPPLY)
24 VAC (+10%, –15%)
FULL WAVE RECTIFIED,
UNFILTERED POWER
MAY BE USED
MAGNET
TEST
SWITCH
24 VAC (+10%, –15%)
FULL WAVE RECTIFIED,
UNFILTERED POWER
MAY BE USED
– RA
– TEST COIL
5
2
ALARM
LED (RED)
+ TEST COIL
4
1
+ IN
+ OUT
(–)
–
(+)
– RA
RTS451/RTS451KEY
(OPTIONAL) REMOTE
TEST STATION
+ RA
+ RTS
D2
METHOD #1 - AUX POWER LOCATED
AT DUCT DETECTOR
+ RA
+ RTS
METHOD #2 - AUX POWER LOCATED
AT TEST STATION
D2
NOTE: THE USE OF EITHER THE RTS451 OR RTS451KEY REQUIRES THE INSTALLATION OF AN ACCESSORY COIL, DCOIL, SOLD
SEPARATELY. SEE FIGURE 9 ABOVE FOR REFERENCE.
H0612-02
Please refer to insert for the Limitations of Fire Alarm Systems
Three-Year Limited Warranty
System Sensor warrants its enclosed product to be free from defects in materials and
workmanship under normal use and service for a period of three years from date of
manufacture. System Sensor makes no other express warranty for the enclosed product.
No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation
of this Warranty shall be limited to the replacement of any part of the product which
is found to be defective in materials or workmanship under normal use and service
during the three year period commencing with the date of manufacture. After phoning
System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization
number, send defective units postage prepaid to: System Sensor, Returns Department, RA
SS-300-014
#__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing
the malfunction and suspected cause of failure. The Company shall not be obligated to
replace units which are found to be defective because of damage, unreasonable use,
modifications, or alterations occurring after the date of manufacture. In no case shall the
Company be liable for any consequential or incidental damages for breach of this or any
other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by
the Company’s negligence or fault. Some states do not allow the exclusion or limitation of
incidental or consequential damages, so the above limitation or exclusion may not apply
to you. This Warranty gives you specific legal rights, and you may also have other rights
which vary from state to state.
6
I56-3050-004R
©2012 System Sensor