InnovairFlex™ Series DNR/DNRW Duct Smoke Housing

InnovairFlex™ Series
DNR/DNRW Duct
Smoke Housing
Description
Intelligent Non-Relay
Photoelectric Duct Smoke Housing
The InnovairFlex™ Series, DNR intelligent, non-relay photoelectric duct smoke detector, and the DNRW watertight,
non-relay photoelectric duct smoke detector feature a pivoting housing that fits both square and rectangular footprints. These detectors are capable of mounting to a round
or rectangular duct. The DNR/DNRW detectors can be
used with the E3 Series® and 7100 Series Systems.
Note: The InnovairFlex™ Series, DNR requires the Velociti® Series, ASD-PL2FR Sensor and AOM-2RF, if relays
are required for the fan control.
InnovairFlex-DNR/DNRW
The DNRW duct smoke detector, with its NEMA 4 rating, is
Listed as a watertight enclosure providing protection
against falling dirt, rain, and windblown dust, splashing and
hose directed water. These features allow operators to use
the detector in the most extreme environments.
The units sense smoke in the most challenging conditions,
operating in airflow speeds of 100 to 4,000 feet per minute,
temperatures of -4°F to 158°F, and a humidity range of 0 to
95 percent (non-condensing).
An improved cover design isolates the sensor head from
the low-flow feature for simple maintenance. A cover tamper feature was added to indicate a trouble signal for a
removed or improperly installed sensor cover. The
InnovairFlex housing provides a 3/4-inch conduit knockout
and ample space to facilitate easy wiring and mounting of
the relay module.
The InnovairFlex duct smoke detector can be customized
to meet local codes and specifications without additional
wiring. The new InnovairFlex product line is compatible
with all previous Innovair models, including remote test
accessories.
WARNING:Duct smoke detectors have specific limitations.
DUCT SMOKE DETECTORS ARE:
NOT a substitute for an open area smoke detector,
NOT a substitute for early warning detection, and NOT a
replacement for a building’s regular fire detection system.
Refer to NFPA 72 and 90A for additional duct smoke
detector 2911 application information.
Features
• Photoelectric, integrated low-flow technology
• Air velocity rating from 100 ft/min to 4,000ft/min
(0.5m/s to 20.32m/sec)
• Versatile mounting options: square or rectangular
configuration
• Broad ranges for operating temperature (-4°F to 158°F)
and humidity (0% to 95% non-condensing)
• Patented sampling tube installs from front or back of the
detector with no tools required
• New Cover tamper signal
• Increased wiring space with a newly added 3/4-inch
conduit knockout
• Available space within housing to accommodate the
mounting of the relay module
• Easily accessible code wheels on sensor head (sold
separately)
• Clear cover for convenient visual inspection
•
•
•
•
UL® 268A Listed
Remote testing capability
Requires SLC line power only
NEMA Type 4 UL Listed for non-hazardous indoor and
outdoor applications (DNRW only)
• UV Resistant, UL® Listed housing and cover material
(DNRW only)
®
®
E3 Series and Velociti are registered trademarks and InnovairFlex™ is a
trademark of Honeywell International, Inc.
®
UL is a registered trademark of Underwriters Laboratories Inc.
SIGNALING
FM
MSFM
APPROVED
S911
2202
3029700 2207 7272-1703:0121 S911
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9021-60475 Rev. E page 1 of 4
©2013 by Honeywell International Inc. All rights reserved.
Architectural/Engineering Specifications
The air duct smoke detector shall be a System Sensor InnovairFlex™ DNR Intelligent Non-Relay Photoelectric Duct
Smoke Detector and DNRW Watertight NEMA4 Duct Smoke Detector. The detector housing shall be UL Listed per UL
268A specifically for use in air handling systems. The flexible housing of the duct smoke detector fits both square and
rectangular footprints. The detector shall operate at air velocities of 100 ft/min to 4,000 ft/min (0.5 m/sec to 20.32 m/
sec). The unit shall be capable of providing a trouble signal in the event that the sensor cover is removed or improperly
installed. It shall be capable of local testing via magnetic switch or remote testing using the RTS151KEY remote test
station. Terminal connections shall be of the strip and clamp method suitable for 12–18 AWG wiring.
Physical Specifications
Size:
Rectangular Dimensions:
Square Dimensions:
Weight:
Environmental Rating:
Operating Temperature
Range:
Storage Temperature
Range:
Operating Humidity
Range:
Air Duct Velocity:
DCOIL - (if included)
14.38 in (37 cm) Length; 5 in (12.7 cm) Width; 2.5 in (6.6 cm) Depth
7.75 in (19.7 cm) Length; 9 in (22.9 cm) Width; 2.5 in (6.35 cm) Depth
1.6 lb (0.73 kg)
NEMA4 (DNRW only)
–4° to 158°F (–20° to 70°C)
–22° to 158°F (–30° to 70°C)
0% to 95% relative humidity non-condensing
100 to 4000 ft/min (0.5 to 20.32 m/sec)
17.5 - 26.4 VDC .95mA max.
Electrical Ratings
For information on the electrical specifications, refer to the InnovairFlex DNR Duct Smoke Detector Installation
Instructions, P/N I56-3051-001R.
Accessory Current Loads at 24 VDC
Device
RA100Z
RTS151/RTS151KEY
Standby
0 mA
0 mA
Trouble
12 mA Max.
12 mA Max.
Installing the InnovairFlex Sampling Tube
The InnovairFlex sampling tube may be installed from the front or back of the detector. The tube locks securely into
place and can be removed by releasing the front or rear locking tab. (Figure 3 illustrates the front locking tab).
Figure 1
Figure 2
Figure 3
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9021-60475 Rev. E page 2 of 4
www.gamewell-fci.com
Wiring for Intelligent Non-Relay Duct Smoke Detector
Figure 4 System Wiring Diagram for DNR
RA100Z
Figure 5 DNR to RA100Z
DNR TO RTS451/RTS451KEY/RTS151/
RTS151KEY WITH “R” REMOTE TEST
CAPABLE DETECTOR HEAD OPTION:
TEST COIL +
TEST COIL COMM +
OUT (CONV ONLY) +
RTS451/RTS451KEY
RTS151/RTS151KEY
1
COMM -
2
RA/RTS -
3
RA +
RTS +
4
JUMPER
TEST COIL +
TEST COIL COMM +
OUT (CONV ONLY) +
COMM –
RA/RTS –
RA +
RTS +
EXTERNAL
(-) POWER (+)
SUPPLY
RT151/RTS151KEY
REMOTE TEST STATION
LED OPTION
1 PER UNIT
TEST COIL OPTION
1 PER UNIT
95mA CURRENT DRAW
5
Figure 6 DNR to RTS151/RTS151 Key
Important Notes:
• The use of either RTS151 or RTS151KEY requires the installation of an accessory coil, DCOIL, sold separately.
For additional information, refer to the DNR or DNRW Duct Smoke Detector Installation Instructions,
P/N I56-3051-001R and the Duct Application Smoke Detectors Application Guide.
• The RTS151/RTS151KEY test coil circuit requires an external 24 VDC power supply which must be UL Listed.
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
www.gamewell-fci.com
9021-60475 Rev. E page 3 of 4
Accessories
System Sensor provides system flexibility with a variety of accessories, including two remote test stations and different
means of visible and audible system annunciation. As with our duct smoke detectors, all duct smoke detector accessories are UL Listed.
Figure 7 RTS151 UL S2522
Figure 8 RTS151KEY UL
S2522
Figure 9 RA100Z UL S2522
Figure 10 ASD-PL2FR
Ordering Information
Part Number
DNR
DNRW
ASD-PL2FR
Description
Intelligent non-relay photoelectric low-flow duct smoke detector
Watertight intelligent non-relay photoelectric low-flow duct smoke detector
Intelligent photoelectric smoke sensor with remote test capability in duct applications
Accessories
Part Number
Description
DCOIL
Remove test coil required with RTS151/RTS151151KEY
DST1
Metal sampling tube duct width up to 1 ft (0.3m)
DST1.5
Metal sampling tube duct widths 1 ft to 2 ft (0.3 to 0.6 m)
DST1.5
Metal sampling tube duct widths 1 ft to 2 ft (0.3 to 0.6 m)
DST3
Metal sampling tube duct widths 2 ft to 4 ft (0.6 to 1.2 m)
DST5
Metal sampling tube duct widths 4 ft to 8 ft (1.2 to 2.4 m)
DST10
Metal sampling tube duct widths 8 ft to 12 ft (2.4 to 3.7 m)
DH400OE-1
Weatherproof enclosure
ETX
Metal exhaust tube duct width 1ft (0.3m)
M02-04-00
Test magnet
P48-21-00
End cap for metal sampling tubes
RA100Z/RA100ZA Remote annunciator alarm LED
RTS151
Remote test station
RTS151KEY
Remote test station with key lock
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9021-60475 Rev. E page 4 of 4