FUJI EDS6-141D

ULTRASONIC FLOWMETER
(2-Path System type)
DATA SHEET
FSH, FSG, FSD
This flowmeter is a fixed type ultrasonic flowmeter based
on transit-time measuring method.
The flowmeter is a compact and light-weight instrument
incorporating the latest electronics and high speed digital
signal processing technologies, realizing high performance
and easy operation. This high performance flowmeter is
used for 2-path system only.
FEATURES
1.Compact and light-weight
Thanks to the adoption of the latest electronics the
flow transmitter size and mass are 1/2 of our traditional
instrument.
2.Full variety of sensors
The flowmeter can be used with various types of sensors
applicable for wide range of pipe size (ø13 to ø6000mm)
and fluid temperature (-40 to +200°C).
3.High accuracy
The flowmeter is designed for high accuracy (± 1.0%).
The adoption of new sound velocity measurement
system permits measurements of fluids of unknown
sound velocity, and also slightly affection from fluid
temperature and pressure.
4.Excellent resistance against aerated flow
Fuji's unique ABM feature improves measurement reliability for different flow like slurries, sludge, raw sewage
and bubble-contained flow (acceptable up to air bubble
of 12% volume at 1m/s velocity).
5.Quick response
With the use of high-speed micro-processor suited for digital signal processing, the fast response time is realized.
6.Multi-lingual
The following languages are supported for display:
Japanese (Katakana), English, German French, and
Spanish.
7.Excellent performance and easy operation
LCD and function keys are allowing easy configuration
and trouble shooting.
− LCD with back light
− Easy mounting of sensor
− Trouble shooting
SPECIFICATIONS
Operational specifications
System configuration:
The system is composed of two detectors
(Model: FSG, FSD) and one Flow transmitter
(Model: FSH), realizing two-path measurement.
Flow transmitter
(FSH)
Detector
(FSD)
Detector
(FSG)
Applicable fluid:Homogenous liquid where the ultrasonic
signal can be transmitted
Bubble quantity: 0 to 12vol% (for pipe size
50A, water, velocity 1m/s)
Fluid turbidity: 10000mg/L max.
Type of flow: Fully-developed turbulent or
laminar flow in a full-filled pipe
Applicable flow pipe:
Material:
Plastics (PVC, FRP, etc.) or
Metals (carbon steel, SS, copper, aluminum, etc.)
50 to 6000 mm
Pipe size: (inside
diameter)
Liner: Tar epoxy, mortar, etc.
Straight pipe length: Typically 10D for upstream
and 5D for downstream. Refer
to JEMIS-032 in detail.
Velocity:
0 to ±0.3·········±32 m/s
Power supply:
100 to 240 Vac+10%/-15%, 50/60Hz or 20 to
30 Vdc
EDS6-141d
Date
Apr. 1, 2011
FSH, FSG, FSD
Signal cable: High-frequency coaxial cable and 3-wire
shielded cable.
Maximum cable length: 150m
Allowable temperature limit: 80ºC
Coaxial cable (4 pcs)
Environment: Non-explosive environment without direct
sunlight, corrosive gas and heat radiation
Ambient temperature:
-10 to +50ºC for flow transmitter,
-20 to +80ºC for detector
Ambient humidity:
95%RH or less for flow transmitter, 100%RH
or less for detector
Grounding: Class D (less than 100 ohm)
Arrester:
Surge absorbers for outputs and power supply incorporated as standard
Display device:
Graphic LCD (number of pixels: 240x64) with
back light
Display language:
Japanese, English, French, German or Spanish selectable
Velocity/Flow rate display:
Display of velocity and/or flow rate with flow
direction
Data: up to 10 digits (decimal point to be
counted as 1 digit)
Unit: Metric/English system selectable
Metric system
Velocity
m/s
ft/s
Flow rate
L/s, L/min, L/h, L/d, kL/h,
ML/d, m3/s, m3/min, m3/h,
m3/d, km3/d, Mm3/d,
BBL/s, BBL/min, BBL/h,
kBBL/d, MBBL/d
ft3/s, ft3/min, ft3/h, Mft3/d,
Performance specifications
Accuracy :
Common type
Detector
Pipe size
(diameter)
Applicable pipe
material
Flow velocity Accuracy
2 to 32m/s
0 to 2m/s
0.75 to 32m/s
0 to 0.75m/s
Plastic, metal pipe
2 to 32m/s
ø50 to below ø300
0 to 2m/s
FSGS31
FSGS50
0.75 to 32m/s
ø300 to ø6000 mm
0 to 0.75m/s
FSGS32 ø50 to below ø300
FSD32
FSGS51 ø300 to ø6000 mm
±1.0% of rate
±0.02m/s
±1.0% of rate
±0.0075m/s
±1.5% of rate
±0.03m/s
±1.5% of rate
±0.0113m/s
0.5sec
Functional specifications
Analog output:4 to 20 mAdc (1 point)
Max. load resistance: 1k ohm
Digital output:+total, -total, alarm, acting range, flow
switch or total switch -- arbitrarily selectable
Mechanical relay contact:
1 point with socket (replaceable)
Normally closed/open selectable
Capacity:240 Vac/30 Vdc, 1 A
Total pulse: less than 1 p/s
(Pulse width: 50, 100 or 200 ms
selectable)
Transistor open collector: 2 points
Capacity: 30 Vdc, 0.1 A
Normally off/on selectable
Total pulse: less than 1000 p/s
(Pulse width: 0.5, 1, 2, 5, 10, 20,
50, 100 or 200 ms selectable)
Communication interface:
RS-232C equivalent / RS-485 (selectable)
Number of connectable units: one (RS-232C)/
up to 31 (RS-485)
Baud rate: 9600/19200/38400 bps selectable
Parity: none/odd/even selectable
Stop bit: 1 or 2 bits selectable
Distance: up to 15 m (RS-232C)/up to 1k m
(RS-485)
Data: velocity, flow rate, +total, -total, status
(standard), velocity profile (option)
2
gal/s, gal/min, gal/h, Mgal/d,
BBL/s, BBL/min, BBL/h,
BBL/d, kBBL/d, MBBL/d
Note: ˝gal˝ means US gal.
Total display: Display of forward or reverse total
Data:up to 10 digits (decimal point to be
counted as 1 digit)
Unit: Metric/English system selectable
Total
Metric system
English system
mL, L, m3, km3, Mm3,
mBBL, BBL, kBBL
ft3, kft3, Mft3, gal, kgal,
mBBL, BBL, kBBL, ACRf
Configuration:
Response time:
Transit time method:
Power consumption:
20W or less
English system
Fully configurable on keyboard by menudriven software
Zero adjustment:
Set zero/Clear available.
Damping:
0 to 100s (every 0.1s) configurable for analog
output and display
Low flow cut off:
0 to 5 m/s configurable
Alarm:
Hardware fault/process fault can be tied to
digital output
Burnout:
Analog output: Hold/Upper limit/Lower limit/
Zero/Not-used selectable
Total: Hold/Count selectable
Timer: 0 to 900s (every 1s) configurable
Bi-directional range:
Forward and reverse ranges configurable independently
Hysteresis: 0 to 20% of working range configurable
Working range applicable to digital output
Auto-2 ranges:
Forward 2 ranges configurable independently
Hysteresis: 0 to 20% of working range configurable
Working range applicable to digital output
Flow switch: Lower and upper switching points configurable independently
Acting point applicable to digital output
Total switch: +total switching point configurable
Acting point applicable to digital output
Signal cable:
Physical specifications
Enclosure protection:
Flow Transmitter: IP67,
Detector:
FSG (common type):
IP67 (Silicon compound is filled on the
terminal part when wiring)
FSG (submersible type):
IP68 (submersible in water for 5 days)
FSD (high temperature type): IP52
Flow Transmitter: wall mount
Mounting:
Detector: clamped on pipe surface
Acoustic coupler: Silicon compound (RTV)
Flow Transmitter: aluminum alloy
Material:
Detector:
Detector Sensor housing Sensor cover Guide rail
FSGS3
FSGS5
FSD32
PBT
PBT
SUS304
SUS304
SUS304
–
SUS304 + plastic
–
SUS304 + aluminum alloy
FLY8, FLY9 (applicable detector: FSG,
FSD)
•Structure: High frequency coaxial cable
(double shield)
•Sheath: Black flame-resisting PVC
•Outer diameter: ø7.5mm
•Termination: M3.5 amp terminal (flow
transmitter side) and M4 amp terminal
(FLY8).Note, however, that the detecter
side of FSD32 is provided with BNC
connector (FLY9).
•Mass: Approx. 90g/m
Dimensions:
Flow transmitter FSH:
H240×W247×D134mm
Detector: H46×W410×D50mm (FSGS3)
H67×W78×D84mm (FSGS5)
H205×W530×D52mm (FSD32)
Mass:
Flow transmitter
Detector: 0.6kg
1.2kg
1.6kg
Conditions on straight pipe
( D : Inside diameter of pipe)
Upstream side
L
5D
10D
Detector
L
10D
or
more
90 bend
Downstream side
L
10D or more
Classification
: 5kg
(FSGS3)
(FSGS5)
(FSD32)
L
10D
50D
Tee
L
30D
L
10D
L
30D
L
5D
D
Diffuser
0.5D
or
more
10D or more
1.5D
L
5D
Reducer
L
10D
Various Valve
In case that flow control valve exists on
upstream side.
Stop valve
Check valve
Pump
In case that flow control valve exists on
downstream side.
L
50D
P
(Note) The source : JEMIS-032
3
FSH, FSG, FSD
MEASUREMENT PRINCIPLE
MOUNTING OF DETECTOR
Ultrasonic pulses are propagated aslant between the upstream and downstream sensors, detecting the time difference due to flow for measurement.
Ultrasonic oscillator
Plastic wedge
Pipe
Upstream sensor
t1
Lining
Output signal
Flow
transmitter
D
t2
Velocity V
Downstream sensor
CONFIGURATION DIAGRAM
(1) 2-path system (V method) (2) 2-path system (Z method)
Cable
Cable
Flow
transmitter
Detector
Detector
4-20mA DC
Contact (up to 3 points)
Flow
transmitter
4-20mA DC
Contact (up to 3 points)
DETECTOR SELECTION GUIDE
Type
Fluid
Mounting
temperature [°C] method
FSGS32 Note)
FSGS31
V
–40 to 80
FSGS51 Note)
FSGS50
FSD32
–40 to 200
50
50
100
200
250
300
Px, P, M
400
200
Px, P, M
Z
200
Px, P, M
V
50
Px, P, M
150
1000
3000
6000
300
V
Z
Classification of
piping materials
Inner diameter of piping ø (mm)
13 25
3000
250
Px, P, M
400
Px : PP, PVDF
P : Plastic (PVC, etc.)
M : Msetallic piping (steel pipe, copper pipe, aluminum, etc.)
Note: The ultrasonic signal cannot be transmitted easily when the classification of piping material is Px or the turbidity is high.
In such a case, a preliminary check by a portable ultrasonic flowmeter is recommended.
4
6000
CODE SYMBOLS
<Detector, submersible type>
1 2 3 4 5 6 7 8
<Flow transmitter>
1 2 3 4 5 6 7 8
9 10 11 12
F SH
SYY
YA
1
F SGS
Description
Type (4th digit)
Standard
E
Use (6th digit)
Transit time measurement (two path)
A
Power supply (7th digit)
100 to 240 Vac, 50/60 Hz
20 to 30 Vdc
1
4
Conduit connection (10th digit)
G1/2 and G3/8 (female screw) with
water-proof connection
Y
Parameter setting, Tag Plate (12th digit)
None
With setting
With setting and Tag Plate
With Tag Plate
Y
A
B
C
<Detector, high temperature type>
1 2 3 4 5 6 7 8
1
F SD
Description
Type (4th, 5th and 6th digits)
High-temperature sensor *1
(ø50 to ø400), V or Z method
3 2 0
Belt, acoustic coupler (7th digit) *3
For fixed type
Y
<Detector, common type>
1 2 3 4 5 6 7 8
9 10 11 12 13
F SGS
Y
Y1
3
3
5
5
1
Acoustic coupler (10th digit)
None*4
Silicon rubber (KE348W)
Silicone-free grease (HIGH-Z) *5
Silicone grease (G40M)*5
Additional specification (11th digit)
None
Tag plate
Y
A
B
C
Y
A
Y
A
B
C
D
E
3
3
5
5
1
Description
Type (5th and 6th digits)
Small sensor 2MHz (ø50 to ø300)
V method
Small sensor 1MHz (ø50 to ø300)*2
Large sensor 1MHz (ø200 to ø6000)
V or Z
Large sensor 0.5KHz (ø200 to ø6000)*2 method
2
1
1
0
Dedicated signal cable (9th digit)
10m
20m
30m
40m
50m
60m
70m
80m
90m
100m
110m
120m
130m
140m
150m
Specified length
(Contact us if length is more than 150m.
Max. length is 300m.)
Acoustic coupler (10th digit)
Silicon rubber (KE348)
Silicone grease (G40M) *5
Additional specification (11th digit)
None
Tag plate
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
R
Z
A
C
Y
A
Y
A
B
C
D
E
Wire rope for mounting (12th digit)
Specify it in the case of FSGS41 or FSGS5.
None
Nominal diameter: up to ø500mm
Nominal diameter: up to ø1000mm
Nominal diameter: up to ø1500mm
Nominal diameter: up to ø3000mm Can be specified
Nominal diameter: up to ø6000mm only for FSGS5
Description
Type (5th and 6th digits)
Small sensor 2MHz (ø50 to ø300)
V method
Small sensor 1MHz (ø50 to ø300)*2
V or Z
Large sensor 1MHz (ø200 to ø6000)
Large sensor 0.5KHz (ø200 to ø6000)*2 method
2
1
1
0
9 10 11 12 13
A1
Wire rope for mounting (12th digit)
Specify it in the case of FSGS41 or FSGS5.
None
Nominal diameter: up to ø500mm
Nominal diameter: up to ø1000mm
Nominal diameter: up to ø1500mm
Nominal diameter: up to ø3000mm Can be specified
Nominal diameter: up to ø6000mm only for FSGS5
*1: For turbid fluid or old pipe, cast iron pipe, mortar lining pipe
or others through which the ultrasonic signal could not be
transmitted easily, use an optional guide rail (TK4C6164C1),
and carry out mounting by Z method.
Applicable diameter range
V method: ø50 to ø250 Z method: ø150 to ø400
*2: For aging pipes, cast iron pipes or mortar-lined pipes that
interrupts the propagation of ultrasonic signals, select
FSGS31 or FSGS50.
*3: As for the acoustic coupler, grease (KS62M) for high
temperatures is attached.
*4: Silicone rubber (KE-348W) is provided as a standard
accessory to fill the wiring mold. (It can also be used as an
acoustic coupler.)
If an additional acoustic coupler is required, select one
among A, B and C.
*5: Normally select silicone rubber as acoustic coupler.
Siliconerubber in tube (100g) is furnished. If you place an
order for several units, 1 tube may suffice for every 2 units.
Select silicone-free grease for semiconductor anufacturing
equipment or the like that is vulnerable to silicone.
The silicone-free grease is water-soluble and, therefore,
cannot be used in environment exposed to water or on
piping subjected to a condensation. Since the grease does
not set, a periodic maintenance (cleaning, refilling every
about 6 months at normal temperature) is necessary.
5
FSH, FSG, FSD
<Signal cable>
Note: Must be procured unless the sensor is a submersible type.
• For detector FSG and FSD
1 2 3 4 5 6 7 8
1
F L Y
Description
Type of sensor (4th digit)
Small and large sensor (for FSG)
Hight temp sensor (for FSD)
8
9
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
Z
0
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
0
1
2
3
4
5
Z
5
0
5
0
5
0
5
0
5
0
5
0
5
0
5
0
5
0
5
0
0
0
0
0
0
Z
Cable length (5,6 and 7th digit)
5m
10 m
15 m
20 m
25 m
30 m
35 m
40 m
45 m
50 m
55 m
60 m
65 m
70 m
75 m
80 m
85 m
90 m
95 m
100 m
110 m
120 m
130 m
140 m
150 m
Others (contact us)
Note: Preapare a detector and dedicated signal cable (2 set).
Loader software for PCs
Equipped as standard
• Works on PC/AT compatible machines.
• Operation on PC98-series machines (NEC) cannot be
guaranteed.
• Operation on self-made PCs or shop-brand PCs cannot
be guaranteed.
• Major functions: Setting/changing of various parameters
for the main unit
• O/S: Windows2000/XP
• Memory requirement: 128MB or more
• Disk unit: Windows2000/XP-compatible CD-ROM drive
• Hard disk drive capacity: Free space of 52MB or more
Note: PC loader communication cable (type ZZP*TK4H6253,
Specifications: D-sub 9 pin receptacle, cable length
3m) is separately required.
6
SCOPE OF DELIVERY
ITEMS DESIGNATED ORDERING
•Flow transmitter (Type: FSH): F
low transmitter
CD-ROM (Instruction manual,
Loader software)
•Detector (Type: FSG, FSD): S ensor unit, Mounting belt,
Silicon compound
•Signal cable (Type: FLY): Cable (2 wires)
1.Detector code symbols
2.Flow transmitter code symbols
3.Signal cable code symbols
4.For large sensor: Mounting pipe size
5.Tag No. as necessary
6.If parameter setting is specified, send back the attached
parameter specification table duly filled.
OUTLINE DIAGRAM (Unit:mm)
<Flow transmitter (type: FSH)>
4-Ø
9
(273)
240
332
352
30
Mtg. plate
Duosonics
72
134
14
233
33 33
3
5-G3/8
Female screw
30 30 30
48
48
4-G1/2
Female screw
24
48
CONNECTION DIAGRAM
Power supply terminals (AC)
1
2
3
4
L
N
1
B
2
B
3
A
4
100 to 240V AC
50/60Hz
–
2
GND
UP STR
3
HF
4
GND
DOWN STR
LINE1
7
5
HF
8
+
–
9
Iout
SERIAL
20 to 30V DC
1
HF
6
SERIAL
Power supply terminals (DC)
4
1
2
3
+
5
6
GND
UP STR
7
HF
8
GND
DOWN STR
LINE2
1
2
+
–
DO1
No.
RS485
RS232C
4
5
6
TRX2 (–)
TRX1 (+)
SHILD
TXD
RXD
COM
3
+
DO2
Open collector
4
–
5
+
6
–
Communication cable
(option)
Cap (red)
Cap (yellow)
Cap (black)
7
DO3
Relay contact
7
FSH, FSG, FSD
OUTLINE DIAGRAM (Unit:mm)
Connector
Scale(inch)
Saddle
Scale(mm)
530±2
Distance between
two sensors 0 to 330
Name plate
Lock nut
Element holder
Cursor
φ26
33±0.5
90max.
205max.
44±1
Detector FSD32 (High-temperature sensor)
5
Frame
Sensor
410±2
400
5
Sensor
410±2
400
5
5
P
P
Name plate
Name plate
47
Spacing : 0 to 270mm
47
Spacing : 0 to 270mm
50±1
33
Chain
50±1
33
46±1
Mounting spring
Chain
46±1
Mounting spring
(10)
(10)
Frame guide
VIEW FROM P
(Common type)
VIEW FROM P
Frame guide
(Submersible type)
Detector FSGS3 (Small sensor)
Name plate
84±1
84±1
Name plate
114
114
78±1
Sensor
Wire rope
78±1
Sensor
Mounting spring
L(cable length (m) : specified by order)
Wire rope
ø19
Ø19
67±1
67±1
Mounting spring
(Common type)
(Submersible type)
Detector FSGS5 (Large sensor)
8
L(cable length (m) : specified by order)
Frame
Signal cable : FLY8 (For FSG)
8
3-ø4.3
L(cable length (m) : specified by order)
ø11
30
To Detector
ø7.3
To Flow transmitter
3-ø3.7
L : By specification
when ordered.
5.5
Signal cable : FLY9 (For FSD)
Loader cable : ZZP*TK4H6253
34
Connector
ø14.5
46
BNC connector
67
30
To Personal
computer
ø7.3
To Detector
3.2±0.2 (m)
L(cable length (m) : specified by order)
ø11
To Flow transmitter
3-ø3.7
5.5
L : By specification
when ordered.
ø6.9
To Flow transmitter
Terminal cap
(Red)
3ø3
.7
Terminal cap (Yellow)
Terminal cap (Black)
6.6
Red
Yellow
Black
TXD
RXD
COM
RS-232C
9
FSH, FSG, FSD
<Parameter specification table>
No.
Setting item
Settable range
Initial value
1
Outer diameter
10.00 to 6200.00mm
(0.393 to 244.100 inch)
60.00mm
(2.362 inch)
2
Pipe material
12 menus
PVC
3
4
5
6
PiPing specification
Pipe S.V. : 1000 to 3700m/s
(3280 to 12140 ft/s)
Wall thickness
0.10 to 100.00mm
(0.003 to 3.940 inch)
4.00mm
(0.157 inch)
Lining material
8 menus
No lining
Lining S.V. : 1000 to 3700m/s
(3280 to 12140 ft/s)
Lining thickness
0.01 to 100.00mm
(0.000 to 3.940 inch)
Kind of Fluid
17 menus
[mm, inch]
Carbon steel, Stainless steel, PVC, Copper,
Castiron, Aluminum, FRP, Ductileiron, PEEK,
PVDF, Acrylic
Others (Sound velocity :
[m/s, ft/s])
[mm, inch]
No lining, Tar epoxy, Mortar, Rubber,
Teflon, Pyrex glass, PVC,
Others (Sound velocity :
[m/s, ft/s])
[mm, inch]
Water
Water, Seawater, DIST. water, Ammonia,
Alcohol, Benzene, Bromide, Ethanol, Glycol,
Kerosene, Milk, Methanol, Toluol,
Lube oil,
Fuel oil, Petrol,
Others (Sound velocity :
[m/s, ft/s])
(Kinematic viscosity
[x10-6m2/s, ft2/s])
Fluid S.V. : 500 to 2500m/s
(1641 to 8203 ft/s)
Kinematic viscosity :
0.001 to 999.9999 x 10-6m2/s
(0.0107 to 10763.9088 x 10-6ft2/s)
Range unit
19 menus
m/s
(ft/s)
m/s, L/s, L/min, L/h, L/d, kL/d, ML/d, m3/s,
m3/min, m3/h, m3/d, km3/d, Mm3/d, BBL/s,
BBL/min, BBL/h, BBL/d, KBBL/d, MBBL/d,
(ft/s, ft3/s, ft3/min, ft3/h, ft3/d, kft3/d, Mft3/d,
gal/s, gal/min, gal/h, gal/d, kgal/d, Mgal/d,
BBL/s, BBL/min, BBL/h, BBL/d, kBBL/d,
MBBL/d)
8
Range type
4 menus
Single
Single, Auto 2, Bi-dir, Bi-dir Auto 2
9
Full scale or
Full scale 1
In terms of flow velocity 0.00 ···
0.30 to 32.00m/s
(0.98 to 104.98 ft/s)
2.00m/s
(6.56 ft/s)
[
]
Full scale 2
In terms of flow velocity 0.00 ···
0.30 to 32.00m/s
(0.98 to 104.98 ft/s)
4.00m/s
(13.12 ft/s)
[
]
Range HYS.
0.00 to 20.0%
10.00%
%
12
Output limit LO.
-20 to 0%
-20%
%
13
Output limit HI.
100 to 120%
120%
%
14
Output burnout
5 menus
Hold
15
Burnout timer
0 to 900sec
10sec
16
Rate limit
0.00 to 5.00m/s
(0.00 to 16.40 ft/s)
in terms of flow velocity
0.00m/s
(0.00 ft/s)
17
Rate limit timer
0 to 900sec
0sec
sec
0.0 to 100.0sec
5.0sec
sec
1 : Display kind
7 menus
Flowrate (m3/s)
2 : Display kind
7 menus
Flow velocity (m/s) Flow velocity, Flowrate, Total forward,
Total reverse,
F : Total pulse, R : Total pulse, Flow rate (%)
0.00 to 5.00m/s
(0.00 to 16.40 ft/s)
in terms of flow velocity
0.01m/s
(0.03 ft/s)
18
19
20
21
Damping
Display setting
11
Output setting
7
10
10
Settable value
Low flow cut
Not use, Hold, Upper, Lower, Zero
sec
[
]
Flow velocity, Flowrate, Total forward,
Total reverse,
F : Total pulse, R : Total pulse, Flow rate (%)
[
]
No.
Setting item
Settable range
Initial value
Settable value
Total mode
3 menus
Total stop
Total stop, Total run, Total reset
23
Total unit
8 menus
mL
mL, L, m3, km3, Mm3, mBBL, BBL, kBBL,
ft3, kft3, Mft3, kgal, gal, mBBL, BBL, kBBL,
ACRF
24
Total rate
0.000 to 999999.999
0.000
[
]
25
F : Total preset
0.000 to 9999999999.999
0.000
[
]
26
F : Total SW
0.000 to 9999999999.999
0.000
[
]
R : Total preset
0.000 to 9999999999.999
0.000
[
]
28
R : Total SW
0.000 to 9999999999.999
0.000
[
]
29
Output burnout
2 menus
Hold
30
Burnout timer
0 to 900sec
10sec
31
Pulse width 1
3 menus
50ms
50, 100, 200
32
Pulse width 2
9 menus
50ms
0.5, 1.0, 2.0, 5.0, 10.0, 20.0, 50.0, 100.0,
200.0
33
Flow sw high
In terms of flow velocity
0.00 to 32.00m/s
(0.00 to 104.98 ft/s)
0.00m/s
[
]
Flow sw low
In terms of flow velocity
0.00 to 32.00m/s
(0.00 to 104.98 ft/s)
4.00m/s
[
]
35
Flow sw HYS.
0 to 20%
10%
36
Output DO1
15 menus
Not use
Not use, Signal error, F : Total pulse,
R : Total pulse, F : Total alarm,
R : Total alarm, F : Total overflow,
R : Total overflow, Flow SW high,
Flow SW Low, Full scale2, AO range over,
Pulse range over, R : Flow direction,
Device error
37
Mode DO1
2 menus
Normal
Normal, Reverse
38
Output DO2
15 menus
Not use
Not use, Signal error, F : Total pulse,
R : Total pulse, F : Total alarm,
R : Total alarm, F : Total overflow,
R : Total overflow, Flow SW high,
Flow SW Low, Full scale2, AO range over,
Pulse range over, R : Flow direction,
Device error
39
Mode DO2
2 menus
Normal
Normal, Reverse
40
Output DO3
15 menus
Not use
Not use, Signal error, F : Total pulse,
R : Total pulse, F : Total alarm,
R : Total alarm, F : Total overflow,
R : Total overflow, Flow SW high,
Flow SW Low, Full scale2, AO range over,
Pulse range over, R : Flow direction,
Device error
41
Mode DO3
2 menus
Normal
Normal, Reverse
Status output
34
Flow switch
27
Total
22
Not use, Hold
sec
%
11
FSH, FSG, FSD
No.
Setting item
Settable range
Initial value
Settable value
42
System unit
2 menus
Metric
Metric, English
43
Language
5 menus
English
Japanese, English, German, French,
spanish
COM. speed
3 menus
38400BPS
9600BPS, 19200BPS, 38400BPS
COM. parity
3 menus
None
None, Even, Odd
COM. stop bit
2 menus
1 bit
1 bit, 2bits
Serial method
2 menus
RS232C
RS232C, RS485
Station No.
31 menus
1
1 to 31
Measurement
mode
2 menus
1 Path
(2 path)
AO Definition
3 menus
Line 1
(Average) Note2
Average, Line 1, Line 2
4 menus
FSW12
(FLW51/FSG51)
Note2
FSW12, FSW21, FSW40, FSW50,
FLW11/FSG31, FLW41/FSG41, FLW12/FSG32,
FLD12/FSD12, FLD22/FSD22, FLW32/FSD32,
FLS50/FSG50, FLW51/FSG51
46
47
System
45
Serial com.
44
49
50
51
Measuremant
mode
48
Sensor Type
2 Path
Note2
Note1: When total pulse output has been selected for DO1, DO2 or DO3 specify total pulse value and total pulse width so that conditions 1
and 2 shown below are satisfies.
Condition 1 :
Condition 2 :
Flow span-1*[m3/s]
total pulse value*[m3]
1000 [In the case of DO1 and DO2]
1 [In the case of DO3]
Flow span-1*[m3/s]
1000
total pulse value*[m3]
2 × total pulse width [ms]
* In the case of 2 ranges, perform calculations using either flow span-1 or flow span-2, whichever is greater.
Note2: Settable value at the time of shipment.
Caution on Safety
*Before using this product, be sure to read its instruction manual in advance.
International Sales Div
Sales Group
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome,
Shinagawa-ku, Tokyo 141-0032, Japan
http://www.fujielectric.com
Phone: 81-3-5435-7280, 7281 Fax: 81-3-5435-7425
http://www.fjielectric.com/products/instruments/
Information in this catalog is subject to change without notice.
Printed in Japan