8 Channel Discrete Input Modules Select these input modules when

8 Channel Discrete Input Modules
Select these input modules when…
…modularity and the convenience of pre-wired
field terminals will reduce your panel wiring.
 Optical isolation on each channel for best reliability
 Autopolarity for DC sinking or sourcing wiring
 Counting to 6000 pulses per minute
Performance Specifications
For each type:
Number of channels
Nominal input voltage (AC or DC)
(AC only)
Guaranteed ON voltage (AC or DC)
Maximum AC voltage
Maximum DC voltage
Guaranteed OFF current
Guaranteed OFF voltage
Input resistance
Nominal input current
Fast DC mode ON/OFF delay
Filtered mode On/OFF delay (Note 1)
Maximum count frequency (Note 2)
Channel to channel isolation w/U base
Maximum ST-Bus power
Isolation (input to ST-Bus)
Operating temperature range
Storage temperature range
Humidity (non-condensing)
-005
8
5
–
4
10
10
1.0
1.5
510
7.5
4
25
100
500
250 mW
1200 V
-30 to 70°C
-40 to 85°C
5 to 95%
-024
8
12/24
–
10
32
32
1.0
3.5
2.2K
5/10
4
25
100
500
-048
8
48
–
32
60
60
1.0
6.0
7.5K
6.5
4
25
100
500
-120
8
120
(Note 3)
60
140
140
1.0
25
18K
6.5
4
50
100
500
-240
8
–
240
140
265
–
1.0
50
36K
6.5
–
50
10
500
VAC/DC
VAC
VAC/DC
VAC
VDC
mA DC
VDC
Ohms
mA
mS
mS
Hz
Volts
Notes: 1. Configurable smart logic filtering ignores transients,
power line dropouts and switch contact bounce.
2. A count of OFF to ON transitions for each input is
reported in a 16 bit register.
3. ST-DI-120-08F: specified for AC or DC sourcing
wiring; not for grounded switch closures.
Ordering Information
Input Range
4-10 VDC
10-32 VAC/DC
32-60 VAC/DC
60-140 VAC/DC
140-265 VAC
Field Wiring Base
ST-DI-005-08F
ST-DI-024-08F
ST-DI-048-08F
ST-DI-120-08F
ST-DI-240-08F
Universal Wiring Base
ST-DI-005-08U
ST-DI-024-08U
ST-DI-048-08U
ST-DI-120-08U
ST-DI-240-08U
Replacement Module
ST-DI-005-08M
ST-DI-024-08M
ST-DI-048-08M
ST-DI-120-08M
ST-DI-240-08M
Sixnet, 331 Ushers Rd., Ballston Lake, NY 12019 www.sixnet.com
8 Channel Discrete Input Modules
Select a Field Wiring Ready Base when…
Select a Universal Base when…
…pre-wired field terminals will save you design,
panel wiring and installation time.
…special requirements call for individually
isolated input circuits with independent (floating)
wiring.
For most DC applications:
For special DC applications:
For special inputs from grounded switch closures:
For special AC applications:
For AC applications with inputs on a single AC service:
Note: In AC applications, each input may be wired to
independent AC sources or line phases.
Visit our web site for
the latest details!
www.sixnet.com
SIXNET
•
331 Ushers Rd
•
Ballston Lake, NY 12019 USA
•
+1 (518) 877-5173
•
FAX +1 (518) 877-8346
•
[email protected]