Mounting instructions OSRAM VISION sensor

Description
Purpose and application
The VISION motion detector detects the movements of people.
The sensor is attached to ceilings and is ideal for mounting at
great heights and for wide detection areas. The unit is mounted
directly in a dry lining box or using the „Mounting Adapter“,
optionally available from OSRAM, to ensure that the installation
conforms to the CE guidelines.
VISION
The VISION motion detector can be connected to any control
component with a floating input that is designed for permanent
contact (switch).
Function
The motion detector detects motion within a detection area of
360° and switches on the connected luminaires when motion is
registered. When motion is no longer registered, the luminaires
switch off after an adjustable delay period.
Design
The sensor is made up of the following components:
• Housing (A)
A
• Connection cable (B):
B
–– L: phase (black)
–– N: neutral conductor (blue)
Motion detector
Fitting instructions
–– Floating switch contact (2x white)
• Motion sensor (C)
• Button for setting the delay (D)
C
E
Installation
• LED (E)
D
Safety instructions
The motion detector must only be installed and put into operation by a qualified electrician. The applicable safety regulations
and accident prevention regulations must be observed.
WARNING!
Exposed, live cables or damaged housing.
Danger of electric shock!
• Only work on the motion detector when it is
de-energised.
CAUTION!
Destruction of the motion detector and other
devices through incorrect
mounting!
• Adhere to the connection diagram.
• Do not exceed the maximum line length.
• Do not route sensor lines together with power
supply or lamp lines.
IX 2009
VISION_ma0911en_we1.01.indd
OSRAM GmbH
Kunden Service Center
Customer-Service-Center (CSC)
Steinerne Furt 62
86167 Augsburg
Germany
Tel : +49 (0) 1803 677 - 200
(kostenpflichtig / charges apply)
Fax.: +49 (0) 1803 677 - 202
www.osram.com
www.osram.de
40083219570470
4008321957047
Page 1 of 3
Selecting the installation location
Fitting (cont.)
FMaximum mounting height: 4,5 m
(à detection area Ø 21 m)
F
0m
1,5 m
3m
4,5 m
10 m
8m
6m
4m
2m
0
2m
4m
6m
8m
10 m
max. 4,5 m
max. Ø 21 m
GPlace devices that radiate heat outside of the monitoring
cone.
H Avoid drafts (e.g. from ventilators)
G
H
Attaching the motion detector to the ceiling
Note: The mounting adapter, available as an accessory, can be
used for attachment. Follow the separate fitting instructions.
Unlock and remove the plastic cover by turning it anticlockwise.
‚Screw on the motion detector, using the mounting adapter
as an aid, if necessary.
ƒConnect the sensor; see the connection diagram.
„Adjust the delay, if necessary; see the separate operating
instructions.
…Replace the plastic cover and lock it by turning it clockwise.
Page 2 of 3
J
Fitting (cont.)
L
N
PE
Connection diagram
16A
J
J Variant 1: switching of mains voltage
L
N
PE
K Switch contact
L Load (ECG, lamps, etc.)
K
N
L 16A
L
N
PE
L
K
N
L
L
N
PE
L
M
MVariant 2: floating switching (example with EASY PB Coupler)
L
N
PE
K Switch contact
N EASY PB Coupler
N
O EASY control line
P EASY control unit
T1…8
M
L
N
PE
GND
K
N
L
O
N
T1…8
GND
P
O
K
N
L
P
Appendix
Technical data
Operating voltage
120 V … 277 V AC / 50-60 Hz
Fuse
External 16 A
Switch output
Floating switch contact
Switch output load
capacity
Max. 5 A – 230 V
Inductive load: 250 VA
Ohmic lamp: 1200 W
Max. number of ECGs:
QTP5:
10 pcs. 1x14-35
8 pcs. 1x54 / 2x14-35
6 pcs. 2x80 / 2x54
QTP8:
10 pcs. 1x58
6 pcs. 2x58
QT-FIT8:10 pcs. 1x58 / 1x36
6 pcs. 2x58 / 2x36
QTi:
15 pcs. 1x28/54
10 pcs. 2x28/54
6 pcs. 2x35/49/80
Operating temperature
-10 °C … +70 °C
Protection type
IP 20
Dimensions
(Ø x H)
115.6 x 39.9 mm
Dimensioned drawing
Ø 115,6 mm
39,9 mm
The EMC requirements to EN 55015 are fulfilled.
Conformity with the relevant EU directives is
confirmed by the CE symbol.