(light and motion sensor) Operating instructions Description

Description
Purpose and application
The DUO sensor detects the presence of persons and measures the intensity of ambient light.
DUO
The sensor is designed for installation on ceilings or in luminaires using a T5/T8 holding clip and is ideal for the expansion
of existing electrical installations.
The following application types are available, depending on
how the sensor is connected (see the connection diagram in the
fitting instructions):
• Alternative 1: One sensor switches a load area by means of
light and/or motion detection.
• Alternative 2: One sensor switches a load area by means
of light and/or motion detection. Additional motion detection
sensors are used to expand the detection area (slave mode).
Function
The sensor operates fully automatically and the values detected
by the sensor (motion, light value) control the switching
behaviour on the basis of the parameters set by the user. The
measured light value depends on the incidence of daylight, the
artificial lighting and the properties of the surface (light/dark).
The following parameters can be set:
Presence sensor
(light and motion sensor)
Operating instructions
• Switch-off delay time (if no motion is detected)
• Light value
• Function mode
Design
The G
sensor is made up of the following components:
A
Upper section of housing:
• Motion sensor (A)
B
1
5
B
• Light sensor (C)
DUO
• Adjusting screws:
C
6 mm
0,34 - 1,5mm2
1
D
B
• LED (B)
1 2 3 4
E
F
ON
5
–– Setpoint for brightness (D)
0V N L
–0V– NSwitch-off
delay time (E)
L
DUO
• DIP switch on the back (F)
G
A
Lower section of housing:
G
• Connections (G):
–– L, N: Supply lines
–– Switch contact
B
5
1 2 3 4
C
1
DUO
–– Parallel circuit for joint motion detection
DUO
6 mm
0,34 - 1,5mm2
D
B
1
F
ON
E
5
B
0V N
0V N L
L
G
LED display
The LED (B) indicates the operating state of the sensor.
LED
Operating state
Green
Switch contact OFF
(sufficient daylight)
Orange
Switch contact ON
(artificial lighting required)
Flashes slowly
(green/orange)
Motion detected
(orange = normal mode;
green = slave mode)
Flashes rapidly
(orange)
Setpoint for brightness was exceeded.
Reduce the setpoint and check the light
conditions at the installation location.
Off
Slave mode (see the connection diagram in
the fitting instructions)
IX 2009
DUO_ba0909en_we1.01.indd
OSRAM GmbH
Kunden Service Center
Customer-Service-Center (CSC)
Steinerne Furt 62
86167 Augsburg
Germany
Tel : +49 (0) 1803 677 - 200
(kostenpflichtig / charges apply)
Fax.: +49 (0) 1803 677 - 202
www.osram.com
www.osram.de
40083214963550
4008321496355
Page 1 of 4
Operation
Symbols
Luminaire on
Luminaire off
Automatic control principle
Precondition: Motion detection and brightness control are
activated. Luminaire
OFF
Luminaire
OFF
Motion?
no
yes
Motion?
no
Artificial light required?
no
yes
yes
Artificial light required?
Luminaire
ON
no
yes
Luminaire
ON
Luminaire
ON
Luminaire
ON
Motion?
1 - 60 min
Luminaire
OFF
no
yes
1 - 60 min
Motion?
no
Artificial light required?
Luminaire
OFF
5 min
Luminaire
OFF
no
yes
yes
5 min
Artificial light required?
Luminaire
OFF
no
After the mains voltage is applied and the mains voltage
returns, the lighting
is switched on.
yes
Function of the DIP switches
Function
Motion detection
Brightness control
Switch-off­signaling
DIP switch (F)
Activated
1
ON
Deactivated
1
OFF
Activated
2
ON
Deactivated
2
OFF
Activated
3
ON
Deactivated
3
OFF
DIP switch 4 has no function (only used for production purposes)
Default setting (state at delivery):
DIP switches 1+2 are activated, DIP switch 3 is deactivated
Page 2 of 4
Activating motion detection and brightness
control
Operation (cont.)
Motion detection and brightness control can be activated
individually or jointly.
Motion detection
To activate: DIP switch 1 = ON
To deactivate: DIP switch 1 = OFF
Brightness control
To activate: DIP switch 2 = ON
To deactivate: DIP switch 2 = OFF
Note:
When DIP switches 1 and 2 are set to OFF, the sensor is in
slave mode (expansion of the motion detection area); see the
connection diagram in the fitting instructions.
Activating switch-off signaling
Precondition: Motion detection is activated
(DIP switch 1 = ON).
The switch-off is signaled by a brief flash of the lighting 30 s
before the switch-off delay time expires if no motion is detected.
To activate: DIP switch 3 = ON
To deactivate: DIP switch 3 = OFF
Specifying set value for brightness control
Note:
• Make the setting while there is a low incidence of daylight.
• Do not cover the sensor while making the setting.
• When checking the function, keep an adequate distance to
the sensor to avoid altering the luminance measurement.
• While the setpoint is being changed, the switch-off delay
time is set to 10 seconds for one minute if there is too much
light.
5
Turn the adjusting screw (D) on the sensor to the required
setting:
5
• Default setting: Position 10 = automatic mode
1
• Position 1 – 9:
30, 60, 100, 150, 200, 250, 300, 400, 500 lux
1
• Position 10 (all the way to the right):
Automatic mode. The sensor independently defines the
switch-on and switch-off thresholds based on the measured
values.
Adjusting the switch-off delay time
Switch-off delay time if no motion is detected.
Turn the adjusting screw (E) on the sensor to the required
setting:
• Default setting: Position 5 = 10 minutes delay time
5
5
1
1
• Position 1 (all the way to the left): Test mode for checking
the function. Switch-off delay times (no motion or sufficient
daylight) are reduced to 10 s.
• Position 2 – 9:
1, 3, 5, 10, 15, 20, 30, 45, 60 minutes
Page 3 of 4
Appendix
Technical data
Operating voltage
220-240 V/50-60 Hz
(no DC operation)
Fuse
External 6 A (10 A)
Power consumption
Switched on: Approx. 1 W
Switched off: Approx. 0.7 W
Maximum total line length
100 m
Switch output
Floating contact (internal relay,
make contact)
Switch output load capacity
Resistive load: 10 A/250 V AC,
6 A/30 V DC
Ohmic lamp load: 5 A
Inductive load: 5 A
30 x single-lamp ECG 18 W
20 x two-lamp ECG 18 W
30 x single-lamp ECG 36 W
20 x two-lamp ECG 36 W
20 x single-lamp ECG 58 W
10 x two-lamp ECG 58 W
Detection area
Max. Ø 12 m
Installation height
Max. 5 m (ideal: 2.5 - 3 m)
Switching hysteresis
Approx. 15%
Operating temperature
0 °C ... +50 °C
Protection class
II
Protection type
IP 20
Weight
Approx. 150 g
Dimensions (L x W x H)
58.5 x 70.5 x 47 mm
Dimensioned drawing
Conformity with the relevant EU directives is
confirmed by the CE symbol.