SPH Ni-Cd battery

SPH Ni-Cd battery
Instant power
April 2007
Immediate performance
in critical applications
Saft SPH battery’s reliability in
critical situations makes it the
perfect choice for UPS, engine
starting and many other high
rate discharge duties.
2
Your critical hospital, traffic control, power generation plant or offshore
application can be seriously endangered without the guarantee of reliable
back-up power. Saft batteries offer powerful protection with designed-in
durability, low maintenance and low life-cost.
The low life cycle cost,
low maintenance battery
The cost-efficient all round
solution
Engineers and manufacturers
around the world fit SPH as
original equipment and to replace
old lead acid products. Saft
experts will match battery weight,
size and performance to perfectly
meet your requirement.
Due to the long life and low
maintenance of the SPH battery
you can benefit significantly from
savings over regular replacement,
maintenance and down-time costs
that attend lead acid batteries.
Uninterruptible power supply
SPH delivers the high power within
a narrow voltage window that is
essential for UPS. Sintered/pbe is
well-proven technology giving
excellent performance and
durability, without the risk of
sudden electrical failure.
Starting engines, every time
In conditions off-shore, on-shore,
on industrial production lines and
in hospitals committed to meet
demanding schedules, SPH Ni-Cd
high power and reliability can make
a life and death difference.
Reliable in all conditions:
a worldwide language
Some of the world’s most critical
installations rely on Saft SPH for
top performance and total peace
of mind: Buenos Aires Hospital,
Rome ATC, Finnish Defence
Ministry, AT&T, Amoco, Elf
Serepca, Qatar Gas Extraction
Plant, Mitsui Engineering and
Shipbuilding, Thai Oil Company,
Bahamas Cititrust Bank, together
with industrial and marine
applications.
Generally operating between
temperatures of –20°C to +50°C
(–4°F to +122°F), SPH batteries
can tolerate extremes of –50°C to
+70°C (–58°F to +158°F) for short
periods. They can also remain in
storage for many years before
commissioning without affecting
subsequent performance.
Saft SPH
Valve Regulated
Lead Acid
3
Saft SPH is your key to safety and
productivity, efficiently operating
wherever and whenever needed.
SPH Ni-Cd
a proven design
Saft nickel-cadmium SPH
batteries are perfectly suited
for UPS and engine starting.
Optimum size and weight
SPH batteries are generally interchangeable with
other batteries used in UPS systems and engine
starting applications.
Small voltage window
4
Saft’s advanced nickel-cadmium technology and
well-proven sintered/plastic bonded electrode
design together provide optimum performance.
This high power in a constrained voltage window is
particularly geared to UPS and often allows a
smaller battery capacity to be installed.
Exceptional
all round performance
High resistance to electrical
abuse
The SPH range tolerates high
ripple current and remains
unaffected by deep or complete
discharge, high charge currents or
voltage reversal.
No temperature constraints
Long lifetime
SPH batteries maintain their high
performance levels even in the
most punishing climates and
temperatures, in hot and remote
desert locations or freezing arctic
temperatures. At –20°C (–4°F)
SPH still provides more than 90%
of its rated capacity where lead
acid is virtually unusable below
freezing.
The SPH has an exceptionally long
lifetime of over 20 years – three to
five times the life-expectancy of a
VRLA battery.
SPH’s alkaline electrolyte produces
no corrosive fumes, thereby giving
no risk of corrosion to sensitive
electrical or electronic equipment.
Faster recharging
SPH will recharge faster than a
VRLA battery, minimizing the
period when your power supply is
not protected, or more rapidly
being available for your next engine
start.
Trouble-free storage
SPH batteries do not need
refreshed charging and will
operate with complete reliability,
even after years in storage.
Trouble-free in service too
The SPH’s structure makes it
resistant to internal corrosion.
As a result there is no risk of
sudden death, the serious problem
that unpredictably affects lead acid
batteries.
SPH can provide very high
currents of up to 20 times the
battery’s nominal capacity. This
high cranking current allows for a
battery with a lower capacity and a
lower cost, distinct advantages
over VRLA. Additionally, SPH’s
sintered positive and compact
plastic-bonded negative electrode
enable it to maintain high
performance levels throughout its
life, even when it is partially
discharged.
Electrolyte
SPH holds a large electrolyte
reservoir that, together with
sintered/plastic-bonded
electrodes and robust steel
construction, gives the cell its
capability to function even in
harsh conditions.
The alkaline solution does not alter
during electro-chemical reactions
and does not react with steel
components. As a result the cell
will not prematurely age and will
continue in faithful service for
up to 20 years or more.
5
No corrosive fumes
High performance engine
starting
SPH advanced technology
with proven reliability
Bayonet flame
arresting vent plug
Virtually maintenance-free
Under normal conditions SPH
batteries will require no
maintenance within 10 years other
than routine checks. This electrochemistry makes sudden death
impossible and keeps performance
high whilst maintenance remains
very low.
Large
electrolyte
reserve with
visible level
Sintered
positive
electrode
The battery may be safely stored
for many years without affecting
performance. Predictable life-costs
now make long-term budgeting
simple.
Plastic bonded
negative electrode
Separator
6
Container
The technology to rely on
Saft’s sintered/pbe technology has
a proven track-record of reliability
and a rapid recharge capability at
either single or dual rate.
These are the essential battery
characteristics where uninterrupted
power or quick engine starting
must be guaranteed.
Worldwide
expertise for industry
Sizing calculation made easy
Calculations can be quickly made
with WinSize, Saft’s easy-to-use
battery sizing software. After
inputting performance criteria,
WinSize establishes the cranking
current/battery size for your
engine starting application, or the
ideal battery for your UPS stand-by
requirement. With SPH’s very high
currents, you may find a lower
capacity battery is suitable,
giving a lower total cost.
SPH versus Valve Regulated Lead Acid: variation of lifetime according to
temperature
Life time in years
20
15
SPH Battery
10
5
10 years-plus VRLA battery
On our website
www.saftbatteries.com
you will find details on Saft’s Ni-Cd
battery ranges and applications.
Alternatively, ask for assistance
on battery specification via the
Saft Worldwide Network.
0
+30°C
+86°F
+25°C
+77°F
+35°C
+95°F
+40°C
+104°F
+45°C
+113°F
+50°C
+122°F
+55 °C
+131°F
Temperature
SPH versus Valve Regulated Lead Acid: variation of cranking performance
according to temperature
% of cranking performance
110
100
SPH Battery
90
Lead Acid Valve Regulated battery
80
70
Limit of VRLA
capacity
60
50
-20°C
-4°F
-10°C
+14°F
0°C
+32°F
+10°C
+50°F
+20°C
+68°F
+30°C
+86°F
+40°C
+104°F
+50 °C
+122 °F
Temperature
7
Visit Saft on the web
Cell capacity
and dimensions
Cells are normally supplied as single cells, taped together into blocks or assembled in steel crates
SPH
type
Capacity
at the
5hr rate
Length per cell
Width per cell
Overall height
L
W
H
Approx.
weight per cell
Volume of
liquid
electrolyte
above
plates
cc
Ah
mm
in
mm
in
mm
SPH 11
11
46.5
1.8
86
3.4
196
7.2
1.0
2.2
66
SPH 16
16
46.5
1.8
86
3.4
276
10.9
1.5
3.5
160
SPH 21
21
46.5
1.8
86
3.4
276
10.9
1.6
3.5
160
SPH 24
24
46.5
1.8
86
3.4
276
10.9
1.7
3.8
160
SPH 28
28
61
2.4
86
3.4
276
10.9
2.0
4.4
215
SPH 36
36
86
3.4
86
3.4
276
10.9
2.7
6.0
325
SPH 45
45
86
3.4
86
3.4
276
10.9
2.9
6.4
315
SPH 52
52
86
3.4
86
3.4
276
10.9
2.9
6.4
315
SPH 60
60
86
3.4
86
3.4
306
12.1
3.4
7.5
405
SPH 70
70
86
3.4
86
3.4
306
12.1
3.5
7.5
405
SPH 80
80
86
3.4
86
3.4
306
12.1
3.5
7.5
390
SPH 90
90
78
3.1
166
6.5
339
13.4
5.8
12.8
750
SPH 100
100
78
3.1
166
6.5
339
13.4
6.1
13.5
735
SPH 115
115
78
3.1
166
6.5
339
13.4
6.3
13.9
720
SPH 130
130
87
3.4
166
6.5
339
13.4
7.0
15.4
815
SPH 150
150
103
4.1
166
6.5
339
13.4
8.2
18.1
990
SPH 170
170
117
4.6
166
6.5
339
13.4
9.7
21.6
1135
SPH 190
190
117
4.6
166
6.5
339
13.4
10.0
22.3
1115
SPH 220
220
198
8.0
166
6.5
339
13.4
14.7
32.4
2155
SPH 250
250
198
8.0
166
6.5
339
13.4
15.3
33.7
2120
SPH 280
280
198
8.0
166
6.5
339
13.4
15.8
34.6
2080
SPH 300
300
198
8.0
166
6.5
339
13.4
16.1
35.5
2060
SPH 320
320
198
8.0
166
6.5
339
13.4
16.5
36.2
2030
in
kg
lb
SPH batteries fulfil all requirements specified by IEC publication 60623.
Flame retardant (F) option available. Please add 1.5 % to dimensions.
Mounting
Charging
Saft recommend that Ni-Cd
batteries are mounted onto
suitable racking or into cabinets
for safety during operation.
Strong, purpose-built racks in
plastic-coated steel can be
supplied unassembled for easy
installation on site.
Normal charging is made at
constant voltage. The charge can
use either single or dual rate
charging (charging voltage at
+20°C/+68°F).
8
A variety of rack dimensions is
available. For rack information and
advice on the battery configuration
that best suits your installation,
contact Saft.
Single rate:
Terminals
1.41 ± 0.01 V/cell
at +20°C/+68°F
Dual rate:
High rate charge 1.45 ± 0.01 V/cell
at +20°C/+68°F
Float charge
1.40 ± 0.01 V/cell
at +20°C/+68°F
At +20°C/+68°F, the above values
ensure 10 topping-up free years
with a single rate charge.
It is not necessary to limit the
current during charge at constant
voltage.
SPH 11 - SPH 80
M10
SPH 90 - SPH 150
M12
SPH 170 - SPH 320
2 x M12
Setting standards
At Saft, our world standing
enables us to meet, and regularly
exceed current international
specifications (IEC, UL, IEEE, etc.)
and we will maintain a leading
position in the market for future
generations.
Performance data
for engine starting applications
Performance for fully charged cells by a constant current charge according to IEC 60623 standard
Available amperes at +20°C ± 5°C (+68°F ± 9°F)
Capacity
(C5Ah)
Minutes
Seconds
1.5
1
30
15
5
1
SPH 11
11
149
161
177
185
202
225
SPH 16
16
217
234
257
270
294
328
SPH 21
21
285
307
338
354
385
430
SPH 24
24
325
351
386
404
440
492
SPH 28
28
380
410
450
472
514
574
SPH 36
36
488
527
579
607
660
738
SPH 45
45
610
658
724
758
826
922
SPH 52
52
705
761
837
876
954
1070
SPH 60
60
813
878
966
1011
1101
1235
SPH 70
70
949
1024
1127
1179
1284
1440
SPH 80
80
1085
1171
1288
1348
1468
1646
SPH 90
90
1120
1230
1400
1500
1650
1790
SPH 100
100
1240
1370
1560
1660
1830
1990
SPH 115
115
1400
1540
1760
1860
2080
2230
SPH 130
130
1570
1720
1950
2080
2290
2470
SPH 150
150
1820
1990
2250
2400
2640
2850
SPH 170
170
2110
2320
2650
2830
3120
3380
SPH 190
190
2360
2590
2960
3160
3490
3780
SPH 220
220
2680
2950
3360
3560
3990
4270
SPH 250
250
3050
3360
3820
4050
4530
4850
SPH 280
280
3390
3710
4200
4480
4930
5330
SPH 300
300
3630
3970
4500
4800
5290
5710
SPH 320
320
3760
4160
4710
4970
5480
5930
Available amperes at +20°C ± 5°C (+68°F ± 9°F)
SPH
type
Capacity
(C5Ah)
Final voltage: 0.85 V/cell
Minutes
3
Seconds
1.5
1
30
15
5
1
SPH 11
11
95.5
107
115
124
133
148
162
SPH 16
16
139
156
167
181
194
215
235
SPH 21
21
182
205
219
237
254
282
309
SPH 24
24
208
234
250
271
291
323
353
SPH 28
28
243
273
292
316
339
376
412
SPH 36
36
313
351
375
407
436
484
530
SPH 45
45
391
439
469
509
545
605
662
SPH 52
52
451
508
541
588
630
699
765
SPH 60
60
520
586
624
678
727
807
883
SPH 70
70
607
684
728
792
848
941
1030
SPH 80
80
694
782
832
905
969
1075
1177
SPH 90
90
709
826
895
997
1090
1210
1290
SPH 100
100
787
917
994
1110
1210
1340
1430
SPH 115
115
885
1040
1120
1250
1370
1510
1600
SPH 130
130
997
1150
1250
1390
1510
1670
1780
SPH 150
150
1150
1330
1440
1600
1740
1930
2050
SPH 170
170
1340
1560
1690
1880
2050
2280
2430
SPH 190
190
1500
1740
1890
2100
2300
2550
2710
SPH 220
220
1690
1980
2140
2390
2620
2890
3060
SPH 250
250
1920
2250
2430
2720
2980
3290
3470
SPH 280
280
2150
2480
2680
3000
3250
3600
3820
SPH 300
300
2300
2660
2870
3210
3480
3857
4100
SPH 320
320
2390
2760
2990
3330
3640
4000
4270
9
SPH
type
Final voltage: 0.65 V/cell
Performance data
for stationary applications
Performance after prolonged float charge of fully charged cells
Available amperes at +20°C ± 5°C (+68°F ± 9°F)
SPH
type
1
30
Seconds
5
1
52.8
66.2
73.1
90.1
99.8
76.8
96.4
107
132
145
101
127
140
173
191
98.8
115
145
160
197
218
91.4
115
135
169
187
230
254
96.8
118
148
173
216
240
295
328
84.4
121
147
185
217
271
300
369
410
50.1
97.5
140
170
214
250
313
346
426
473
39.2
57.9
112
159
190
225
250
308
337
402
443
34.5
45.7
67.5
130
186
221
263
292
360
394
469
517
26.5
39.4
52.2
77.1
149
212
253
300
334
411
449
536
591
18.0
29.8
44.4
58.7
86.8
165
230
268
317
375
511
574
701
754
12.7
20.0
33.1
49.3
65.3
96.4
183
255
297
352
417
568
638
779
838
115
14.6
23.0
38.1
56.7
75.1
111
210
293
342
405
479
653
733
896
964
130
16.5
26.0
43.1
64.1
84.9
125
238
332
386
458
542
738
829
1010
1090
SPH 150
150
19.0
30.0
49.7
74.0
97.9
145
274
383
446
528
625
852
957
1170
1260
SPH 170
170
21.6
34.0
56.3
83.8
111
164
311
434
505
599
708
965
1080
1320
1420
SPH 190
190
24.1
38.0
63.0
93.7
124
183
347
485
565
669
791
1080
1210
1480
1590
SPH 220
220
27.9
44.0
72.9
108
143
212
402
561
654
775
916
1250
1400
1710
1840
SPH 250
250
31.7
50.0
82.8
123
163
241
457
638
743
881
1040
1420
1590
1950
2100
SPH 280
280
35.5
56.0
92.8
138
182
270
512
714
832
986
1170
1590
1790
2180
2350
SPH 300
300
38.1
60.0
99.4
147
195
289
548
765
892
1060
1250
1700
1910
2340
2510
SPH 320
320
40.6
64.0
106
157
208
309
585
816
951
1130
1330
1820
2040
2490
2680
Capacity
Hours
5
3
Final voltage: 1.00 V/cell
2
90
60
30
Minutes
20
15
(C5Ah)
8
10
SPH 11
11
1.4
2.2
3.6
5.4
7.2
10.6
20.6
29.6
35.9
45.3
SPH 16
16
2.0
3.2
5.3
7.9
10.4
15.4
30.0
43.0
52.3
65.8
SPH 21
21
2.7
4.2
7.0
10.4
13.7
20.3
39.4
56.5
68.6
86.4
SPH 24
24
3.0
4.8
8.0
11.8
15.7
23.1
45.0
64.6
78.4
SPH 28
28
3.6
5.6
9.3
13.8
18.3
27.0
52.5
75.3
SPH 36
36
4.6
7.2
11.9
17.8
23.5
34.7
67.5
SPH 45
45
5.7
9.0
14.9
22.2
29.4
43.4
SPH 52
52
6.6
10.4
17.2
25.6
33.9
SPH 60
60
7.5
12.0
19.9
29.6
SPH 70
70
8.8
14.0
23.2
SPH 80
80
10.2
16.0
SPH 90
90
11.4
SPH 100
100
SPH 115
SPH 130
5
Available amperes at +20°C ± 5°C (+68°F ± 9°F)
10
SPH
type
30
Seconds
5
1
55.3
62.3
76.9
85.6
80.4
90.5
112
125
106
119
147
164
95.9
121
136
168
187
97.5
112
141
159
196
218
107
125
144
181
204
252
280
113
134
157
180
226
255
315
350
95.4
130
154
181
208
261
294
364
405
57.1
109
145
168
187
206
257
285
342
373
66.7
127
169
196
218
240
300
333
399
436
51.6
76.2
145
193
223
249
274
343
380
456
498
44.1
58.1
85.7
157
202
230
262
307
435
490
600
650
32.9
49.0
64.5
95.2
175
225
256
291
341
483
544
667
723
22.8
37.8
56.4
74.2
110
201
259
294
335
393
556
626
767
831
16.4
25.8
42.8
63.7
83.9
124
227
292
332
379
444
628
708
867
940
18.9
29.8
49.3
73.5
96.8
143
262
337
383
437
512
725
817
1000
1080
170
21.4
33.7
55.9
83.3
110
162
297
382
434
495
580
821
925
1130
1230
190
23.9
37.7
62.5
93.1
123
181
332
427
485
553
648
918
1030
1270
1370
SPH 220
220
27.7
43.7
72.4
108
142
210
384
495
562
641
751
1060
1200
1470
1590
SPH 250
250
31.4
49.6
82.2
123
161
238
436
562
639
728
853
1200
1360
1670
1810
SPH 280
280
35.2
55.6
92.1
137
181
267
489
630
715
816
956
1350
1520
1870
2020
SPH 300
300
37.7
59.5
98.7
147
194
286
524
675
767
874
1020
1450
1630
2000
2170
SPH 320
320
40.3
63.5
105
157
207
305
559
719
818
932
1090
1550
1740
2130
2310
Capacity
Hours
5
3
Final voltage: 1.05 V/cell
2
90
60
30
Minutes
20
15
(C5Ah)
8
10
5
SPH 11
11
1.4
2.2
3.6
5.4
7.1
10.5
20.2
27.5
32.7
38.3
43.9
SPH 16
16
2.0
3.2
5.3
7.8
10.3
15.2
29.4
40.0
47.5
55.7
63.9
SPH 21
21
2.6
4.2
6.9
10.3
13.5
20.0
38.5
52.5
62.4
73.1
83.9
SPH 24
24
3.0
4.8
7.9
11.8
15.5
22.9
44.0
60.0
71.3
83.6
SPH 28
28
3.5
5.6
9.2
13.7
18.1
26.7
51.4
70.0
83.2
SPH 36
36
4.5
7.1
11.8
17.6
23.2
34.3
66.1
90.0
SPH 45
45
5.7
8.9
14.8
22.1
29.0
42.9
82.6
SPH 52
52
6.5
10.3
17.1
25.5
33.5
49.5
SPH 60
60
7.5
11.9
19.7
29.4
38.7
SPH 70
70
8.8
13.9
23.0
34.3
45.2
SPH 80
80
10.1
15.9
26.3
39.2
SPH 90
90
11.3
17.9
29.6
SPH 100
100
12.6
19.8
SPH 115
115
14.5
SPH 130
130
SPH 150
150
SPH 170
SPH 190
1
Performance data
for stationary applications
Performance after prolonged float charge of fully charged cells
Available amperes at +20°C ± 5°C (+68°F ± 9°F)
10
5
1
30
Seconds
5
1
25.8
29.8
34.9
45.1
51.6
64.0
71.3
37.5
43.3
50.7
65.6
75.1
93.1
104
43.0
49.2
56.8
66.6
86.0
98.6
122
136
38.3
49.1
56.2
65.0
76.1
98.3
113
140
156
25.2
44.7
57.3
65.6
75.8
88.7
115
131
163
182
32.4
57.4
73.7
84.3
97.4
114
148
169
210
233
28.2
40.5
71.8
92.1
105
122
143
184
211
262
292
24.8
32.6
46.8
83.0
107
122
141
165
213
244
303
337
19.3
28.6
37.6
54.0
92.6
115
128
142
162
209
234
283
310
13.7
22.5
33.4
43.9
63.0
108
134
150
166
189
244
273
329
362
9.9
15.7
25.8
38.2
50.2
72.0
124
153
171
190
216
278
313
376
414
90
11.2
17.6
29.0
43.0
56.4
81.0
127
154
174
200
243
353
409
501
540
SPH 100
100
12.4
19.6
32.2
47.7
62.7
90.0
142
171
193
222
270
393
454
556
600
SPH 115
115
14.3
22.5
37.0
54.9
72.1
104
163
197
222
256
311
451
522
640
690
SPH 130
130
16.1
25.5
41.9
62.1
81.5
117
184
223
251
289
351
510
590
723
780
SPH 150
150
18.6
29.4
48.3
71.6
94.0
135
212
257
290
333
405
589
681
834
900
SPH 170
170
21.1
33.3
54.8
81.1
107
153
241
291
328
378
459
667
772
946
1020
SPH 190
190
23.6
37.3
61.2
90.7
119
171
269
326
367
422
513
746
863
1060
1140
SPH 220
220
27.3
43.1
70.9
105
138
198
311
377
425
489
594
864
999
1220
1320
SPH 250
250
31.1
49.0
80.5
119
157
225
354
428
483
556
676
981
1140
1390
1500
SPH 280
280
34.8
54.9
90.2
134
176
252
396
480
541
622
757
1100
1270
1560
1680
SPH 300
300
37.3
58.8
96.6
143
188
270
425
514
580
667
811
1180
1360
1670
1800
SPH 320
320
39.8
62.7
103
153
201
288
453
549
618
711
865
1260
1450
1780
1920
Capacity
Hours
5
3
(C5Ah)
8
2
SPH 11
11
1.4
2.2
3.5
5.3
SPH 16
16
2.0
3.1
5.2
7.6
SPH 21
21
2.6
4.1
6.8
10.0
SPH 24
24
3.0
4.7
7.7
SPH 28
28
3.5
5.5
SPH 36
36
4.5
7.1
SPH 45
45
5.6
8.8
SPH 52
52
6.5
SPH 60
60
SPH 70
90
Minutes
20
15
60
30
6.9
9.9
17.6
22.5
10.0
14.4
25.5
32.8
13.2
18.9
33.5
11.5
15.0
21.6
9.0
13.4
17.6
11.6
17.2
22.6
14.5
21.5
10.2
16.7
7.5
11.8
70
8.7
SPH 80
80
SPH 90
Available amperes at +20°C ± 5°C (+68°F ± 9°F)
SPH
type
10
5
1
30
Seconds
5
1
20.8
23.8
27.6
37.3
43.0
53.9
60.1
30.3
34.6
40.1
54.3
62.5
78.4
87.5
35.1
39.8
45.4
52.6
71.2
82.1
103
115
33.0
40.1
45.4
51.9
60.1
81.4
93.8
118
131
21.9
38.5
46.8
53.0
60.5
70.1
95.0
109
137
153
21.1
28.2
49.5
60.1
68.2
77.8
90.2
122
141
176
197
26.3
35.3
61.9
75.1
85.2
97.3
113
153
176
221
246
23.5
30.4
40.7
71.5
86.8
98.5
112
130
176
203
255
284
18.5
27.1
35.1
47.0
77.7
91.6
101
112
126
172
194
236
260
13.5
21.6
31.7
40.9
54.8
90.7
107
118
131
147
200
227
276
303
9.8
15.4
24.7
36.2
46.8
62.7
104
122
134
150
168
229
259
315
346
90
11.0
17.4
27.8
40.7
52.6
70.5
101
119
135
157
192
294
342
422
464
SPH 100
100
12.3
19.3
30.9
45.2
58.5
78.3
112
133
151
175
213
327
380
469
516
SPH 115
115
14.1
22.2
35.5
52.0
67.3
90.1
128
153
173
201
245
376
437
539
593
SPH 130
130
15.9
25.1
40.1
58.8
76.0
102
145
173
196
227
277
425
494
609
670
SPH 150
150
18.4
29.0
46.3
67.9
87.7
118
168
199
226
262
320
490
569
703
774
SPH 170
170
20.8
32.8
52.5
76.9
99.4
133
190
226
256
297
362
555
645
797
877
SPH 190
190
23.3
36.7
58.6
86.0
111
149
212
252
286
332
405
621
721
890
980
SPH 220
220
27.0
42.5
67.9
99.5
129
172
246
292
331
384
469
719
835
1030
1130
SPH 250
250
30.6
48.3
77.2
113
146
196
279
332
376
436
533
817
949
1170
1290
SPH 280
280
34.3
54.1
86.4
127
164
219
313
372
421
489
596
915
1060
1310
1440
SPH 300
300
36.8
57.9
92.6
136
175
235
335
399
451
523
639
980
1140
1410
1550
SPH 320
320
39.2
61.8
98.8
145
187
251
357
425
482
558
682
1050
1210
1500
1650
Capacity
Hours
5
3
Final voltage: 1.14 V/cell
(C5Ah)
8
2
90
SPH 11
11
1.3
2.1
SPH 16
16
2.0
3.1
3.4
5.0
4.9
7.2
SPH 21
21
2.6
4.1
6.5
SPH 24
24
2.9
4.6
SPH 28
28
3.4
SPH 36
36
SPH 45
45
SPH 52
Minutes
20
15
60
30
6.4
8.6
15.1
18.4
9.4
12.5
22.0
26.7
9.5
12.3
16.5
28.9
7.4
10.9
14.0
18.8
5.4
8.6
12.7
16.4
4.4
6.9
11.1
16.3
5.5
8.7
13.9
20.4
52
6.4
10.0
16.0
SPH 60
60
7.4
11.6
SPH 70
70
8.6
SPH 80
80
SPH 90
11
SPH
type
Final voltage: 1.10 V/cell
Saft is committed to the highest standards of environmental stewardship.
Implementing this commitment to minimise the impact of its products and operations on the environment means that
Saft gives priority to recycled over unrecycled raw materials, reduces its plant releases into the environment year after
year, minimizes water usage, and ensures that its customers have recycling solutions for their batteries at the end of their lives.
Regarding industrial Ni-Cd batteries, Saft has had partnerships for many years with collection companies in most EU countries as
well as in North America. This collection network receives and dispatches our customers’ batteries at the end of their lives to fully
approved recycling facilities, in compliance with the Laws governing transboundary waste shipments. Saft offers these services free
of charge to its customers.
Please find a list of our collection points on our web site.
In other countries, Saft assists its customers in finding environmentally sound recycling solutions. Please contact your sales
representative for further information.
Africa
Export sales dpt,
France
Tel: +33 1 49 93 19 18
Fax: +33 1 49 93 19 56
Argentina
Energia Alcalina, Buenos Aires
Tel: +54 11 4334 9034/35
Fax: +54 11 4342 5024
Australia
Saft Australia Pty Ltd, Seven Hills
Tel: +61 2 9674 0700
Fax: +61 2 9620 9990
Austria
Statron GmbH, Wien
Tel: +43 1 617 40 60
Fax: +43 1 617 40 60/40
Belgium
AEG Belgium SA, Brussels
Tel: +32 2 529 6543
Fax: +32 2 529 6449
Brazil
Adelco Sistemas de Energia Ltda., Sao Paulo
Tel: +55 11 41997515
Fax: +55 11 41615307
Canada
Please contact USA office.
Chile
Techno Parts Ltda., Santiago
Tel: +56 (2) 249 6060
China
Saft (Zhuhai Free Trade Zone) Batteries Co Ltd,
Shanghai
Tel: +86 21 5866 6405
Fax: +86 21 5866 6403
Czech Republic
Saft Ferak a.s., Prague
Tel: +420 257 013 260
Fax: +420 257 013 261
Denmark
Scansupply A/S, Birkeroed
Tel: +45 45 82 50 90
Fax: +45 45 82 54 40
Finland
HansaBattery Oy, Espoo
Tel: +358 207 631880
Fax: +358 207 631889
Norway
Saft AS, Osteraas
Tel: +47 6716 4160
Fax: +47 6716 4170
France
Division France, Bagnolet
Tel: +33 1 49 93 19 18
Fax: +33 1 49 93 19 56
Russia
ZAO Alcatel, Moscow
Tel: +7 095 937 0967
Fax: +7 095 937 0906
Germany
Saft Batterien GmbH, Nürnberg
Tel: +49 911 94 174-0
Fax: +49 911 426 144
Singapore
Saft Batteries Pte Ltd,
Singapore
Tel: +65 6512 1500
Fax: +65 6749 7282
Hong Kong
Saft Ltd, Kowloon
Tel: +852 2796 99 32
Fax: +852 2798 06 19
India sub continent
AMCO-Saft India Ltd., Bangalore
India
Tel: +91 80 2 363 7790
Fax: +91 80 2 363 7716
Spain
Saft Baterias S.L.,
San Sebastian de los Reyes
Tel: +34 916 593 480
Fax: +34 916 593 490
Sweden
Saft AB, Oskarshamn
Tel: +46 491 680 00
Fax: +46 491 681 80
Italy
Saft Batterie Italia S.r.l.,
Segrate (Milano)
Tel: +39 02 89 28 07 47
Fax: +39 02 89 28 07 62
Switzerland
Statron AG, Mägenwil
Tel: +41 62 887 4 887
Fax: +41 62 887 4 888
Japan
Sumitomo Corp., Tokyo
Tel: +81 3 5144 9082
Fax: +81 3 5144 9267
United Kingdom
Saft Ltd, Harlow
Tel: +44 1279 772 550
Fax: +44 1279 420 909
Korea
Enersys Korea Co. Ltd, Kyunggi-Do
Tel: +82 2501 0033
Fax: +82 2501 0034
USA
Saft America Inc., North Haven (CT)
Tel: +1 203 239 4718
Fax: +1 203 234 7598
Mexico
Troop y Compania, SA de CV,
Mexico
Tel: +52 55 50 82 10 30
Fax: +52 55 50 82 10 39
Venezuela
Corporación INTELEC C.A.,
Caracas
Tel: +58 212 9631122
Middle East
Saft Nife ME Ltd, Limassol,
Cyprus
Tel: +357 25 820040
Fax: +357 25 748492
Western Asia
Export sales dpt.,
Sweden
Tel: +46 491 680 00
Fax: +46 491 681 80
Netherlands
Saft Batteries B.V., Haarlem
Tel: +31 23 750 5720
Fax: +31 23 750 5725
Saft
Industrial Battery Group
12, rue Sadi Carnot
93170 Bagnolet – France
Tel: +33 1 49 93 19 18
Fax: +33 1 49 93 19 64
Doc N° 21111-2- 0407
Edition: April 2007
Data in this document is subject to change without notice
and becomes contractual only after written confirmation.
Photo credits: Alstom Power, Thierry Balazuc, Comstock
Images/Alamy, Corbis, Digital Vision, Getty Images,
PhotoDisc, Peet Simard/Saft, Saft.
Société anonyme au capital de 31 944 000
RCS Bobigny B 383 703 873
www.saftbatteries.com
Prepared by Arthur Associates Limited.