FMAB - 1-Phase Line Filters

FMAB
1-Phase Line Filters
www.schurter.com/PG84
AC Filter, Broad Band Attenuation
Description
-Chassis:
Screw-on mounting, from top
-Line-filter in standard version, 1‑stage, high attenuation
-High symmetrical and asymmetrical attenuation in the frequency range
from 10kHz up to 30MHz
Approvals
-VDE Certificate Number: 40004673
-UL File Number: E72928
Characteristics
-Designed for high current applications
-High attenuation at maximum resp. asymmetric load independent from
the line impedance
-Especially designed for industrial applications such as: Frequency Converters, Stepper Motor Drives, UPS-Systems, Inverters
-Suitable for use in equipment according to IEC/UL 60950
References
Alternative: Standard version Weblinks
pdf-datasheet, html-datasheet, General Product Information, Approvals,
CE declaration of conformity, RoHS, CHINA-RoHS, REACH, e-Shop,
SCHURTER-Stock-Check, Distributor-Stock-Check, Detailed request for
product
Technical Data
Ratings IEC
Ratings UL/CSA
Leakage Current
Dielectric Strength
Allowable Operation Temp.
Climatic Category
Protection Class
Terminal
Material: Housing
12 - 50 A @ Ta 40 °C / 250 VAC; 50 Hz
12 - 50 A @ Ta 40 °C / 125 VAC; 60 Hz
industrial < 5.2 mA (250 V / 60 Hz)
> 1.7 kVDC between L-N
> 2.7 kVDC between L/N-PE
Test voltage (2 sec)
-25 °C to 100 °C
25/100/21 acc. to IEC 60068-1
Suitable for appliances with protection
class I acc. to IEC 61140
Screw
Metal
Line Filter
MTBF
Industrial Version, IEC 60939, UL 1283,
CSA C22.2 no. 8
Technical Details
> 200'000 h acc. to MIL-HB-217 F
Connectors
1
FMAB
1-Phase Line Filters
www.schurter.com/PG84
Dimension
Case 24-2
Case 24-6
max. 137
max. 100
+0
95 -1
1)
2)
(29.5)
4)
max. 106
max. 86
2)
4)
M6
5.3 ±0.3
M6
5.3 ±0.3
3)
51 ±0.3
(17)
51 ±0.3
1) Line
2) Load
3) Nut torque 3...4 Nm
4) I/O Connections torque 0.6...0.8
1) Line
2) Load
3) Nut torque 3...4 Nm
4) I/O Connections torque 1.5...1.8
Case 79-2
+0
(32)
2)
(10)
max. 56
(10)
112 -1
max. 101
max. 127
max. 201
max. 151
1)
4)
6.5 ±0.3
85 ±0.3
M6
3)
(17)
1) Line
2) Load
3) Nut torque 3...4 Nm
4) I/O Connections torque 1.5...1.8
Diagrams
Standard version
1)
2)
1) Line
2) Load
2
max. 58
(2)
max. 86
max. 58
(7)
(29.5)
+0
1)
95 -1
max. 106
max. 137
max. 100
Connectors
3)
(17)
FMAB
1-Phase Line Filters
www.schurter.com/PG84
Attenuation Loss
- - - - differential mode _____ common mode
Industrial version
12 A
20 A
30 A
50 A
All Variants
Rated Current [A]
Filter-Type
Leakage Current [mA]
L [mH]
C1
(X2)
C2 (Y2)
[nF]
C3
(Y2)
C4
(X2)
R [MΩ]
Clamps
[mm2]
Weight
[g]
Housing Order Number
12
Industrial Version
5.2
2 x 10
2.2
10
47
1
1
4
927 g
24-2
5500.2064
20
Industrial Version
5.2
2 x 3.5
2.2
10
47
1
1
4
930 g
24-2
5500.2065
30
Industrial Version
5.6
2 x 1.5
2.2
15
47
1
1
6
970 g
24-6
5500.2066
50
Industrial Version
5.6
2 x 1.5
2.2
15
47
1
1
10
970 g
79-2
5500.2067
█
█ Most Popular.
Availability for all products can be searched real-time:http://www.schurter.com/en/Stock-Check/Stock-Check-SCHURTER
2 Pcs 04.03.2015
Packaging unit The specifications, descriptions and illustrations indicated in this document are based on current
information. All content is subject to modifications and amendments. Information furnished is believed
to be accurate and reliable. However, users should independently evaluate the suitability and test each
product selected for their own applications.
Connectors
3