DR-480/DRP-480 series 480W Single output industrial DIN RAIL with PFC function (PFC function for DRP-480 only) Built-in passive PFC function compliance to EN61000-3-2(For DRP-480) High efficiency 89% and low dissipation Protections:Short circuit/Over load/Over voltage/Over temperature Cooling by free air convection Built-in constant current limiting circuit Can be installed on DIN rail TS-35/7.5 or 15 UL 508(industrial control equipment)approved EN61000-6-2(EN50082-2) industrial immunity level 100% full load burn-in test 3 years warranty SPECIFICATION MODEL OUTPUT DR-480-24 DR-480-48 DRP-480-24 DRP-480-48 DC VOLTAGE 24V 48V 24V 48V RATED CURRENT 20A 10A 20A 10A CURRENT RANGE 0 ~ 20A 0 ~ 10A 0 ~ 20A 0 ~ 10A RATED POWER 480W 480W 480W 480W RIPPLE & NOISE (max.) Note.2 120mVp-p 120mVp-p 120mVp-p 120mVp-p VOLTAGE ADJ. RANGE 24 ~ 28V 48 ~ 53V 24 ~ 28V 48 ~ 53V VOLTAGE TOLERANCE Note.3 1% 1.0% 1% 1.0% LINE REGULATION 0.5% 0.5% 0.5% 0.5% LOAD REGULATION 1% 1.0% 1% 1.0% SETUP, RISE, HOLD TIME 1200ms, 40ms, 16ms/230VAC at full load VOLTAGE RANGE 180 ~ 264VAC FREQUENCY RANGE 47 ~ 63Hz POWER FACTOR INPUT EFFICIENCY (Typ.) 250 ~ 370VDC 0.7 (for DRP-480) 89% AC CURRENT 6A/230VAC INRUSH CURRENT (max.) COLD START 50A/230VAC LEAKAGE CURRENT OVER LOAD PROTECTION OVER VOLTAGE OVER TEMPERATURE 4A/230VAC <3.5mA / 240VAC 105 ~ 150% of rate load Protection type : Constant current limiting, recovers automatically after fault condition is removed 54 ~60V 30 ~ 36V 30 ~ 36V 54 ~60V Protection type : Shunt down o/p voltage, re-power on to recover 100 5 (TSW : Detect on heatsink of power switch) Protection type : Shun down o/p voltage, recovers automatically after temperature goes down WORKING TEMP., HUMIDITY -20 ~ +70 (Refer to output load derating curve), 20 ~ 90% RH non-condensing STORAGE TEMP., HUMIDITY ENVIRONMENT TEMP. COEFFICIENT -20 ~ +85 , 10 ~ 95% RH 0.03%/ (0 ~ 50 VIBRATION 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes SAFETY STANDARDS EMI CONDUCTION & RADIATION UL508, TUV EN60950 Approved Compliance to EN55022 (CISPR22) Class B SAFETY & HARMONIC CURRENT Compliance to EN61000-3-2,-3, Class D(For DRP-480) EMC EMS IMMUNITY WITHSTAND VOLTAGE Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN61000-6-2 (EN50082-2) Heavy industry level, criteria A I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC OTHERS MTBF 180.9Khrs min. DIMENSION 227*125.2*100mm (W*H*D) 2.1Kgs/pcs, 6pcs/12.6Kgs/1.75CUFT PACKING NOTE MIL-HDBK-217F (25 ) 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. File Name:DR-480,DRP-480-SPEC 2003-09-19 DR-480/D UR S P - 42 82 05 Mechanical Specification Case No.930 100 series Unit:mm 125.2 227 TB1 3 2 1 LED TB2 4 3 2 1 ADJ 35 8.5 Admissible Din Rail: TS35/7.5 or TS35/15 120 TB1 Terminal Pin. No Assignment Pin No. 1 2 3 54.25 TB2 Terminal Pin. No Assignment Pin No. 1,2 3,4 Assignment AC/L AC/N FG Derating Curve Assignment DC OUTPUT +V DC OUTPUT -V Output Derating VS Input Voltage 100 100 90 80 80 70 LOAD (%) LOAD (%) 60 40 20 -20 0 10 20 30 40 AMBIENT TEMPERATURE ( 50 ) 60 70 (VERTICAL) 60 50 40 180 190 200 264 INPUT VOLTAGE (V) 60Hz File Name:DR-480,DRP-480-SPEC 2003-09-19