DR-480/DRP-480 series - Total Power International

TOTAL POWER INT'L
480W Single Output Industrial DIN RAIL with PFC Function
(PFC function for DRP-480 only)
DR-480/DRP-480 series
Features :
Built-in passive PFC function compliance to EN61000-3-2(For DRP-480)
High efficiency 89% and low dissipation
Protections:Short circuit/Over load/Over voltage/Over temperature
Cooling by free air convection
Built-in constant current limiting circuit
Can be installed on DIN rail TS-35/7.5 or 15
UL 508(industrial control equipment)approved
EN61000-6-2(EN50082-2) industrial immunity level
100% full load burn-in test
3 years warranty
R
SPECIFICATION
MODEL
OUTPUT
INPUT
DR-480-24
DR-480-48
DRP-480-24
DRP-480-48
DC VOLTAGE
24V
48V
24V
48V
RATED CURRENT
20A
10A
20A
10A
CURRENT RANGE
0 ~ 20A
0 ~ 10A
0 ~ 20A
0 ~ 10A
RATED POWER
480W
480W
480W
480W
120mVp-p
120mVp-p
120mVp-p
48 ~ 53V
1.0%
24 ~ 28V
1.0%
48 ~ 53V
1.0%
RIPPLE & NOISE (max.) Note.2 120mVp-p
VOLTAGE ADJ. RANGE
24 ~ 28V
VOLTAGE TOLERANCE Note.3 1.0%
LINE REGULATION
0.5%
LOAD REGULATION
1.0%
0.5%
SETUP, RISE, HOLD TIME
1.0%
1200ms, 40ms, 16ms/230VAC at full load
VOLTAGE RANGE
180 ~ 264VAC
FREQUENCY RANGE
47 ~ 63Hz
POWER FACTOR
EFFICIENCY (Typ.)
89%
AC CURRENT
INRUSH CURRENT (max.)
6A/230VAC
COLD START 50A/230VAC
LEAKAGE CURRENT
OVER LOAD
PROTECTION OVER VOLTAGE
OVER TEMPERATURE
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
0.5%
0.5%
1.0%
1.0%
250 ~ 370VDC
0.7 (for DRP-480)
4A/230VAC
<3.5mA / 240VAC
105 ~ 150% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
54 ~60V
30 ~ 36V
30 ~ 36V
54 ~60V
Protection type : Shut down o/p voltage, re-power on to recover
100
5 (TSW : Detect on heatsink of power switch)
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
-20 ~ +70
(Refer to output load derating curve)
20 ~ 90% RH non-condensing
-20 ~ +85
, 10 ~ 95% RH
0.03%/ (0 ~ 50
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
UL508, TUV EN60950 Approved
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC
SAFETY & ISOLATION RESISTANCE
Compliance to EN55022 (CISPR22) Class B
EMI
CONDUCTION
&
RADIATION
EMC
(Note 4)
Compliance to EN61000-3-2,-3(For DRP-480)
HARMONIC CURRENT
EMS IMMUNITY
MTBF
OTHERS
DIMENSION
PACKING
NOTE
Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN61000-6-2 (EN50082-2) Heavy industry level, criteria A
180.9Khrs min. MIL-HDBK-217F (25
227*125.2*100mm (W*H*D)
2.4Kg; 6pcs/15Kg/1.75CUFT
)
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
480W Single Output Industrial DIN RAIL with PFC Function
(PFC function for DRP-480 only)
DR-480/DRP-480 series
Mechanical Specification
Case No.930
227
125.2
100
Unit:mm
TB1
3 2 1
TB2
4 3 2 1
LED
+V ADJ.
35
ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15
TB1 Terminal Pin. No Assignment
Pin No.
1
2
3
TB2 Terminal Pin. No Assignment
Pin No.
1,2
3,4
Assignment
AC/L
AC/N
FG
Derating Curve
Assignment
DC OUTPUT +V
DC OUTPUT -V
Output Derating VS Input Voltage
100
100
90
80
80
70
LOAD (%)
LOAD (%)
60
40
20
-20
0
10
20
30
40
AMBIENT TEMPERATURE (
50
)
60
70 (VERTICAL)
60
50
40
180
190
200
INPUT VOLTAGE (V) 60Hz
264