Data Sheet DB EN UT 6-TMC M

UT 6-TMC M...
Thermomagnetic circuit breakers
CLIPLINE
Data sheet
103943_en_04
1
© PHOENIX CONTACT 2010-08-18
Description
The UT 6-TMC M circuit breaker is a single-position
overload circuit breaker with thermomagnetic tripping. It is a
space-saving circuit breaker with trip-free mechanism in the
event of overload and short circuits within the maximum
interrupting rating. The UT 6-TMC M is mounted on an
NS 35 DIN rail.
UT 6-TMC M thermomagnetic circuit breakers feature a
compact design, large labeling areas, and a double plug-in
bridge shaft.
The circuit breakers provide a high level of system
availability thanks to their reclosure function and clear status
display.
Eleven nominal current versions can be selected from 0.5 A
to 16 A. The large center labeling area enables clear
assignment of the relevant circuit breaker.
NOTE: The magnetic tripping ranges differ for alternating currents (AC) and direct currents (DC) (see page 3). The
magnetic operating currents for direct currents (DC) are approximately 1.6 times higher.
NOTE: When mounted in rows with simultaneous load, a mutual thermal effect occurs (see page 4).
Calibration is required for an ambient temperature of +23°C. A correction factor must be used to determine the
nominal current for a lower or higher ambient temperature (see page 5).
Make sure you always use the latest documentation.
It can be downloaded at www.phoenixcontact.net/catalog.
This data sheet is valid for all products listed on the following page:
UT 6-TMC M...
2
Ordering data
Circuit breakers
Description
Nominal current
Type
Order No.
Thermomagnetic circuit breaker, 1-pos.
0.5 A
UT 6-TMC M 0,5A
0916603
6
Thermomagnetic circuit breaker, 1-pos.
1A
UT 6-TMC M 1A
0916604
6
Pcs./Pkt.
Thermomagnetic circuit breaker, 1-pos.
2A
UT 6-TMC M 2A
0916605
6
Thermomagnetic circuit breaker, 1-pos.
4A
UT 6-TMC M 4A
0916606
6
Thermomagnetic circuit breaker, 1-pos.
5A
UT 6-TMC M 5A
0916607
6
Thermomagnetic circuit breaker, 1-pos.
6A
UT 6-TMC M 6A
0916608
6
Thermomagnetic circuit breaker, 1-pos.
8A
UT 6-TMC M 8A
0916609
6
Thermomagnetic circuit breaker, 1-pos.
10 A
UT 6-TMC M 10A
0916610
6
Thermomagnetic circuit breaker, 1-pos.
12 A
UT 6-TMC M 12A
0916611
6
Thermomagnetic circuit breaker, 1-pos.
15 A
UT 6-TMC M 15A
0916612
6
Thermomagnetic circuit breaker, 1-pos.
16 A
UT 6-TMC M 16A
0916613
6
Accessories
Description
Type
Order No.
Pcs./Pkt.
Plug-in bridge, for cross connection in the bridge shaft, red, 2-pos.
FBS 2-6
3030336
50
Plug-in bridge, for cross connection in the bridge shaft, red, 3-pos.
FBS 3-6
3030242
50
Plug-in bridge, for cross connection in the bridge shaft, red, 4-pos.
FBS 4-6
3030255
50
Plug-in bridge, for cross connection in the bridge shaft, red, 5-pos.
FBS 5-6
3030349
50
Plug-in bridge, for cross connection in the bridge shaft, red, 10-pos.
FBS 10-6
3030271
10
Plug-in bridge, for cross connection in the bridge shaft, red, 20-pos.
FBS 20-6
3030365
10
Warning label, for UT series, yellow
WS UT 6
3047345
10
Screwdriver
SZS 1,0X4,0
1205066
10
UniCard sheet, for labeling
UC-TM 12
(See CLIPLINE catalog)
Zack marker strip, for labeling
ZB 12
(See CLIPLINE catalog)
3
Electrical data
Nominal current, nominal voltage, and additional electrical data
Rated insulation voltage
440 V AC
Rated frequency
50/60 Hz (at 240 V AC)
Nominal voltage
240 V AC, 28 V DC
Nominal current AC/DC
Depending on module: 0.5 A, 1 A, 2 A, 4 A, 5 A, 6 A, 8 A, 10 A, 12 A, 15 A, 16 A
Operating voltage range
50 V AC ... 264 V AC, 5 V DC ... 30.8 V DC
Operating frequency range
48 Hz ... 62 Hz
Insulation resistance (main circuit)
> 100 MΩ
Insulation resistance
50 Hz: 2000 V
Surge voltage category
II
Pollution degree
2
Pulse: 2800 V
AC
DC
6000 cycles at 1 x In
6000 cycles at 1 x In
Switching cycles
Service life under load
Overload according to IEC 60943
Overload according to UL 1077
40 cycles at 6 x In
40 cycles at 6 x In
50 cycles at 1.5 x In
50 cycles at 1.5 x In
Short-circuit switching capacity (Inc)
200 A
400 A
Conditional short-circuit switching capacity (Inc)[Backup fuse]
2000 A
2000 A
103943_en_04
PHOENIX CONTACT
2
UT 6-TMC M...
Backup fuse
Nominal current
UT 6-TMC M
Maximum backup fuse
NOTE: If in the application the maximum short-circuit switching capacity (Icn) could be exceeded in the event of an error, a backup fuse
must be used in combination with the circuit breaker.
The following maximum backup fuse values are recommended according to
characteristic gG (VDE 0636, IEC 269)
0.5 A
16 A
1A
16 A
2A
16 A
4A
16 A
5A
20 A
6A
20 A
8A
25 A
10 A
25 A
12 A
25 A
15 A
25 A
16 A
25 A
Tripping characteristics
Type of actuation
Manual ON/OFF (S type)
Tripping method
Thermomagnetic (TM)
Tripping type
Trip-free mechanism
Specified non-tripping current (no tripping within an hour)
1.05 x In
Specified tripping current (tripping within an hour)
1.32 x In
Instantaneous non-tripping current
6 x In (AC)
Instantaneous tripping current
12 x In (AC)
NOTE: The magnetic tripping ranges differ for alternating currents (AC) and direct currents (DC). Please observe the tripping characteristics
shown in Figure 1.
The magnetic operating currents for direct currents (DC) are approximately 1.6 times higher.
3.1
Tripping characteristics
10000
< 7.0A
> 7.0A
1000
100
10
DC tripping characteristics
Switching time [s]
Switching time [s]
AC tripping characteristics
10000
1000
100
10
1
1
0.1
0.1
0.01
0.01
0.001
1
2
3 4
6 8 10
20
40 60 100
Multiples of IN
Figure 1
103943_en_04
< 7.0A
> 7.0A
0.001
1
2
3 4
6 8 10
20
40 60 100
Multiples of IN
AC and DC tripping characteristics
PHOENIX CONTACT
3
UT 6-TMC M...
3.2
Effect on thermal tripping of mounting in rows
NOTE: When mounted in rows with simultaneous
load, a mutual thermal effect occurs.
The mutual thermal effect is tantamount to an increase in the
ambient temperature (see page 5). This depends on the
following:
– The nominal current
– The ambient temperature
– The number of devices
– The distance between devices
Calculation example for overdimensioning
5 circuit breakers with In = 10 A are to be mounted in rows.
The ambient temperature is +23°C.
Nominal current when not mounted
in rows
Typical correction factor
Theoretical nominal current when
mounting in rows
3.3
Since the thermal effect varies for each planned installation
when mounting in rows, the correction factors must be
defined individually and tested.
df = 1.25
In row = 10 A X 1.25
= 12.5 A
Internal resistance of the UT 6-TMC M
Nominal current
0.5 A
1.0 A
2.0 A
4.0 A
5.0 A
6.0 A
8.0 A
10.0 A
12.0 A
15.0 A
16.0 A
The nominal device current can be either overdimensioned
or limited. When the UT 6-TMC M is mounted in rows, the
correction factor is usually in the range of 1.25 or at
80% (reciprocal) in relation to the limiting nominal current.
These values apply in the event of continuous load and at an
ambient temperature of +23°C.
In = 10 A
Resistance
4.37 Ω
0.95 Ω
0.33 Ω
88.0 mΩ
55.8 mΩ
41.7 mΩ
22.2 mΩ
12.3 mΩ
10.9 mΩ
8.3 mΩ
7.7 mΩ
Measurement between the LINE and LOAD connections.
Tolerance: ±10%
4
Mechanical data
Fixing
Mounting method
On a DIN rail according to DIN EN 60715, NS 35N/7,5 or NS 35/15
The tripping characteristics are not dependent on the mounting position.
Plug-in bridge, for cross connection in the bridge shaft
FBS x-6 plug-in bridge (see "Accessories" on page 2)
Connection polarity
Independent polarity (for DC) for the LINE and LOAD connections
Suitability
"Factory wiring"
Weight
51 g
Housing material
PA 66
Fuse type
Medium blow fuse
Inflammability class according to UL 94
V0
Maximum number of cycles
6000 at 1 x In
Connection terminal block
Screw connection
Connection capacity
1 conductor
M4
Solid
Stranded
With ferrule
0.2 mm² ... 10 mm²
0.2 mm² ... 10 mm²
0.25 mm² ... 6 mm²
0.2 mm² ... 2.5 mm²
0.25 mm² ... 1.5 mm²
2 conductors (two conductors with same cross-section, ferrule without
plastic sleeve)
2 stranded conductors with a TWIN ferrule
0.5 mm² ... 4 mm²
Stripping length
12 mm
Tightening torque (EN 60934)
1.5 Nm ... 1.8 Nm
103943_en_04
PHOENIX CONTACT
4
UT 6-TMC M...
5.3
5
Environmental influences
5.1
Temperature range, influence on the ambient
temperature
NOTE: Calibration is required for an ambient
temperature of +23°C.
Temperature range
-30°C … +60°C
Reference temperature +23°C
The following typical correction factors must be observed to
calculate the nominal current:
Correction factors
Shock resistance according to EN 60068-2-27,
Test Ea [3 shocks in each direction (= 18 shocks)]
Peak G
Pulse length Pulse form
50g
11 ms
Half-sine
Vibration resistance according to EN 60068-2-6,
Test Fc - frequency range: 5 Hz ... 500 Hz
< 60 Hz
> 60 Hz
(constant amplitude)
(constant acceleration)
0.15 mm
2g
5.4
°C
In [A]
-30
-20
-10
0
10
23
30
40
50
60
0.5
0.77
0.81
0.84
0.87
0.90
1.00
1.03
1.08
1.15
1.21
1
0.77
0.81
0.84
0.87
0.90
1.00
1.03
1.06
1.13
1.19
2
0.77
0.81
0.84
0.87
0.90
1.00
1.03
1.08
1.15
1.21
4
0.77
0.81
0.84
0.87
0.90
1.00
1.03
1.08
1.15
1.21
5
0.77
0.81
0.84
0.87
0.90
1.00
1.03
1.08
1.15
1.25
6
0.70
0.73
0.78
0.84
0.90
1.00
1.03
1.08
1.15
1.21
8
0.70
0.73
0.78
0.84
0.90
1.00
1.03
1.06
1.13
1.21
10
0.78
0.81
0.84
0.87
0.90
1.00
1.05
1.15
1.21
1.30
12
0.77
0.80
0.85
0.90
0.95
1.00
1.03
1.08
1.15
1.21
15
0.73
0.73
0.78
0.84
0.90
1.00
1.03
1.08
1.11
1.21
16
0.70
0.73
0.78
0.84
0.90
1.00
1.03
1.08
1.15
1.21
ø
0.75 0.78 0.82 0.86 0.90 1.00 1.03 1.08 1.15 1.22
Resistance to vibrations and shocks
Approvals
Certification body
VDE
UL
UL
CSA
6
Standard License
Approved as
number
IEC 60934 400028127 Circuit Breaker for
Equipment
UL 1077
E140459
Supplementary
Protector
CSA 22.2 E140459
Supplementary
No.235
Protector
CSA 22.2 250505
Supplementary
No.235
Protector
Dimensions
Example calculation:
A circuit breaker with In = 4 A is to be used at an ambient
temperature of +60°C.
Nominal current at +23°C In (+23°C) = 4 A
Ambient temperature
Tamb = +60°C
Correction factor
df = 1.21
Theoretical nominal current at +60°C
In (+60°C) = 4 A x 1.21 = 4.84 A
At +60°C, a nominal current of 5 A should be selected.
5.2
IP protection class
IP protection class
Actuation area
Connection area
IP40
IP20
Figure 2
103943_en_04
Dimensions (in mm)
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49 - 52 35 - 30 0
PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300
www.phoenixcontact.com
5