DuroSite® Wallpack / Bulkhead Luminaire Installation

DIALIGHT
“WP SERIES LUMINAIRE” INSTALLATION GUIDE
This guide includes important information on how to safely install the luminaire.
WP Series Luminaire Product Information:The WP Series LED luminaire uses the latest in solid state lighting technology for long life, low maintenance and high
efficiency. The lighting fixture is designed for indoor and outdoor non-hazardous area use only and complies with the
following:•
•
•
EN55015:2006 / EN61547:2009 / EN60598:2009 / EN61000-3-2:2006
UL 1598 Luminaires suitable for wet locations / UL 1598A Luminaires suitable for marine locations.
IP66 RATED / NEMA 4X
Items you will need to complete the installation (*=items not included)
This installation guide
WP Luminaire
WP fixings and accessories (optional mounting bracket(s), body mounting bolts x 4, cable gland x 1 & gland stopper x 1)
* 3 Core mains cable for hardwired connection only (see specification information for cable and fusing/circuit breaker)
*Terminal screwdriver
*Torx screwdriver (SIZE T30 with TORQUE SETTING)
*Bracket mounting screws (recommended size 8)
Important Information:These instructions contain important safety information, read and follow them carefully. Dialight will not accept any
responsibility for injury, damage or loss which may occur due to incorrect installation, operation or maintenance.
WARNING: Risk of electric shock. Ensure that main power supply is switched off before installing or wiring the luminaires.
WARNING: Do not attempt to install or use the luminaire until you have read and understand these instructions.
WARNING: Risk of fire or electric shock. Luminaires wiring or other electrical parts may be damaged when drilling for
installation.
Check for enclosed wiring and components.
WARNING: Risk of fire or electric shock. Installation requires knowledge of luminaire electrical systems. If in doubt do not
attempt the installation. Contact a qualified electrician.
WARNING: To prevent wiring damage or abrasion, do not expose wiring to edges of metal or other sharp objects.
CAUTION: The luminaire has no serviceable parts. Do not attempt to open power supply unit or LED tray enclosure.
CAUTION: Do not use sharp tools near or on the light engine lens or cables.
NOTE: The instructions and precautions set forth within this guide are not necessarily all inclusive, or relevant to all
applications as the manufacturer cannot anticipate all conceivable or unique installation situations.
Installation (See illustrations)
1. Installation should be carried out by a qualified electrician in accordance with the local wiring regulations. Ensure that the
rated voltage and frequency of the luminaire, as indicated on the label are compatible with the mains supply.
2. Assemble the mounting bracket if purchased to the luminaire with the bolts provided. See Figure 1.
3. The assembled luminaire can now be located into position and mounted using suitable fixings (not supplied). See Figure 2.
4. With the luminaire fixed into position, unscrew the 4 TORX screws on the front of the Bulkhead (see tightening torques), the
front of the luminaire with LED tray can now be lowered and is supported by the ‘drop cable’. See Figure 3.
5. Single fixture connection, remove only one of the blanking grommets and fit the M20 cable gland provided, pass the mains
wiring cable through. Multiple fixture connection: Remove both of the blanking grommets and fit the M20 cable glands (only
one provided), pass the mains input cable through and pass another through the other gland for the mains output for the next
fixture. See Figure 4. (Adequately tighten the cable gland to maintain fixture IP rating).
6a. Single fitting connection: Connect the mains supply to the terminal block, ensure that the correct polarity is observed.
6b. Multiple fitting connection: Connect both pairs of the mains cables to the terminal block, ensure that the correct polarity is
observed. Ensure power is switched off until the last unit is connected as the EXIT CABLE will be LIVE. See Figure 5.
Dialight – LED Solutions for Industrial and Hazardous Applications
Tel: +44 (0)1638 665161 – Fax: +44 (0)1638 660718 – www.dialight.com
A80-000552-B
WARNING: LUMINAIRE MUST BE EARTHED
7. Check all connections are correct and there are no loose or un-terminated cables, replace LED tray ensuring that no cables
or that the drop cord is trapped, DO NOT OVERTIGHTEN. When complete re-connect the power supply and test for
operation.
IMPORTANT NOTE TO THE INSTALLER
THESE INSTRUCTIONS CONTAIN IMPORTANT SAFETY INFORMATION, PLEASE ENSURE THAT A COPY IS MADE
AVAILABLE TO THE USER AND/OR MAINTENANACE ENGINEER OF THESE PRODUCTS.
Fig. 3
Fig.1
Fig. 4
Fig. 2
Fig. 6
Fig. 5
Mains Input Connection
Mains Input Connection
Specification:-
Multiple Fixture Connection Example
Tightening torques:-
Supply Voltage
100-277VAC 50-60Hz
Front assembly to body
2.0Nm / 18.0 in lb
Supply Current
100mA @ 230VAC / 200mA @ 100VAC
Bracket to body
8.0Nm / 71.0 in lb
Operating Temperature Range
-40°C to +60°C
Input Terminal Block Capacity
0.52 – 4mm2 / 18-14 AWG
Additional cable gland if required
M20 x 1.5
Weight
4.5Kg / 10.0 lbs
(to IP 66 rating)
Maximum loop current
16A
Rated fuse/circuit breaker
Consult MCB manufacturer
Dialight – LED Solutions for Industrial and Hazardous Applications
Tel: +44 (0)1638 665161 – Fax: +44 (0)1638 660718 – www.dialight.com