DuroSite® LED Linear Fixtures UL

INSTALLATION AND MAINTENANCE MANUAL
DUROSITE LED LINEAR FIXTURE
Document No: 9100-127-1890-99 Rev A
June, 2013
MODELS
(2 foot Versions)
LTM3C4D2P
LTM3C4B2D
(4 foot Versions)
LTM3C4M2P
LTM3C4H2D
These instructions contain important safety information, read and
follow them carefully. Dialight will not accept any responsibility for
injury, damage or loss which may occur due to incorrect installation,
operation or maintenance
1: Introduction
This Linear LED light is designed for illumination of industrial locations. It uses the latest in solid state
lighting technology for long life, low maintenance, and high efficiency.
The unique optical design focuses light downward to where it is needed, giving improved efficiency over
a conventional HID luminaire.
An internal, universal input, power-factor-corrected switch-mode supply allows it to be used from any
nominal 100V-277V, 50/60Hz AC supply without any variation in light output.
Models listed above are SUITABLE FOR WET LOCATIONS in unclassified locations:
Temperature Code: T5 for 2' model, T5 for 4' model
Ambient Temperature Range: -40C to +65C
Note: Save these instructions for future reference.
Document No: 9100-127-1890-99 Rev A
2: Installation
Warning:
To avoid the risk of fire, explosion, or electric shock, this product should be installed, inspected, and
maintained by a qualified electrician only, in accordance with all applicable electrical codes.
Warning:
To avoid electric shock:
•
Be certain electrical power is OFF before and during installation and maintenance.
•
Luminaire must be connected to a wiring system with an equipment-grounding conductor.
Warning:
•
•
•
•
•
DO NOT let power cord touch hot surfaces
DO NOT mount near gas or electric heaters
Equipment should be mounted in locations and at heights where it will not be subjected to
tampering by unauthorized personnel.
The use of accessory equipment not recommend by the manufacture may cause an unsafe
condition
DO NOT use this equipment for other than it’s intended use
Warning:
The technical data indicated on the Luminaire are to be observed.
•
Changes to the design and modifications of the Luminaire are not permitted
•
Only genuine Dialight replacement parts are to be used when unforeseen maintenance is required.
Consult factory at www.Dialight.com or authorized representative as required.
For supply connections use wire rated for at least 90ºC
Conduit thru Mount (Figure 2) Installation Steps:
•
•
For maximum long term reliability and light output, the light must be installed in free air.
o The Linear fixture design incorporates an over-temperature control circuit that reduces
input power should internal temperatures reach a maximum level. In this event, light
output may be reduced.
The Linear fixture is threaded for 3/4” NPT, at the center and each end of the Power Supply
Housing’s Junction Box Section, in order to be assembled to conduit.
o Remove the 3/4 NPT pipe plugs and attach conduit as shown in figure 2. Use
conductive pipe sealant for all fittings and conduit.
Page 2 of 7
1501 Route 34 South, Farmingdale, NJ 07727
Tel: (732) 919-3119 Fax: (732) 751-5778 www.dialight.com
Document No: 9100-127-1890-99 Rev A
o
o
o
Warning: If there is moisture present, or chance of it, in the conduit system then
necessary precautions should be taken by the installer to prevent the moisture from
entering thru the cable or conduit and entering the fixture. Failure to comply with the
above could void factory warranties.
Fixture is factory wired with LINE, NEUTRAL and GROUND leads. Remove the Power
Supply Junction Box Cover, which has captive screws, to attach incoming power to the
white (Neutral) wire, black (Line) and green (Ground) wire leads with wire nuts. Ensure that
the o-ring is properly seated in the groove; reattach the Cover. Tighten all screws to 15
in/lbs (1.75NewtonM’s)
Restore power and verify operation.
Figure 2.
JUNCTION BOX COVER
WITH CAPTIVE SCREWS
¾ NPT Plug in center
Conduit through
mounting
Conduit Pendant Mount (Figure 3) Installation Steps:
•
For maximum long term reliability and light output, the light must be installed in free air.
o The Linear fixture design incorporates an over-temperature control circuit that reduces
input power should internal temperatures reach a maximum level. In this event, light
output may be reduced.
o The Linear fixture is threaded for 3/4” NPT, at the center of the Power Supply
Housing’s Junction Box area in order to be assembled to conduit. Each end has a
factory installed 3/4 NPT pipe plug installed.
o Attach conduit as shown in figure 3. Use conductive pipe sealant for all fittings and
conduit.
Page 3 of 7
1501 Route 34 South, Farmingdale, NJ 07727
Tel: (732) 919-3119 Fax: (732) 751-5778 www.dialight.com
Document No: 9100-127-1890-99 Rev A
o
o
o
WARNING :If there is moisture present, or chance of it, in the conduit system then
necessary precautions should be taken by the installer to prevent the moisture from
entering thru the cable or conduit and entering the fixture. Failure to comply with the
above could void factory warranties.
Fixture is factory wired with LINE, NEUTRAL and GROUND leads. Remove the Power
Supply Junction Box Cover, which has captive screws, to attach incoming power to the
white (Neutral) wire, black (Line) and green (Ground) wire leads with wire nuts. Ensure that
the o-ring is properly seated in the groove; reattach the Cover. Tighten all screws to 15
in/lbs (1.75NewtonM’s)
Restore power and verify operation.
Figure 3.
Pendant Mount
¾ NPT Plugs in
both ends
Page 4 of 7
1501 Route 34 South, Farmingdale, NJ 07727
Tel: (732) 919-3119 Fax: (732) 751-5778 www.dialight.com
Document No: 9100-127-1890-99 Rev A
3: Maintenance
•
To avoid personal injury, disconnect power to the light and allow the unit to cool down before
performing maintenance.
Warning: No user serviceable parts inside of fixture. Risk of electric shock. Removal of the lens
will void the warranty.
1) We suggest performing visual, mechanical and electrical inspections on a regular basis. We
suggest routine checks to be made on a yearly basis. Frequency of use and environment
should determine this. It is recommended to follow an Electrical Preventive Maintenance
Program as described in NFPA 70B: Recommended Practice for Electrical Equipment.
2) If the lens (Figure 4 below) requires periodical cleaning to ensure continued photometric
performance. Clean the lens with a damp, non-abrasive, lint-free cloth. If not sufficient, use mild
soap and water.
3) Inspect the outside of the Luminaire housing to ensure that they are free of any obstructions or
contamination (i.e. excessive dust build-up). Clean with a non-abrasive cloth if needed.
4) Do not operate if the lens is cracked or damaged. All fasteners should be properly seated.
5) NOTE: Screws, other than the Junction Box area, are factory torqued and should not be
tampered with during installation or maintenance.
Figure 4.
Polycarbonate Lenses
Page 5 of 7
1501 Route 34 South, Farmingdale, NJ 07727
Tel: (732) 919-3119 Fax: (732) 751-5778 www.dialight.com
Document No: 9100-127-1890-99 Rev A
Specifications
Nominal AC Supply Voltage
Power consumption:
2’ version
4’ version
100-277VAC, 50-60Hz
32W nominal
64W nominal
Input Current: (Nominal)
.33Amps @100Vac (2 foot)
.66amps @100Vac (4 foot)
.12Amps @277Vac (2 foot)
.24Amps @277Vac (4 foot)
Operating temperature range
-40°F to +149°F [-40° C to +65°C]
T5 @ 149°F [65°C]
Power factor
>0.9
ATHD
<20%
Dimensions (L x W x H)
See Figure 5.
Weight
8 lbs [3.62 kg] (2’) 11 lbs [4.98 kg] (4’),
Intertek Certified to
UL-844 and C22.2 No. 137
Figure 5.
DIMENSIONS ARE FOR
REFERENCE ONLY:
All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy
or completeness thereof is not guaranteed. In accordance with Dialight Corporation “Terms and Conditions of Sale”, and since conditions of use are
outside our control, the purchaser should determine the suitability of the product for his intended use and assumes all risk and liability whatsoever in
connection therewith
Page 6 of 7
1501 Route 34 South, Farmingdale, NJ 07727
Tel: (732) 919-3119 Fax: (732) 751-5778 www.dialight.com
Document No: 9100-127-1890-99 Rev A
REV.
A
ECO No.
11185
DRN
WSL
CHK
KH
APP
SB
QA
RL
CM
JN
DATE
6/11/13
Page 7 of 7
1501 Route 34 South, Farmingdale, NJ 07727
Tel: (732) 919-3119 Fax: (732) 751-5778 www.dialight.com