UPStation GXT™ - Emerson Network Power

UPStation GXT™
6 & 10 kVA
Optional Battery Cabinet
USER MANUAL
English
IMPORTANT SAFETY INSTRUCTIONS
WARNING: Do not attempt to service this product yourself. Opening or
removing the cover will expose you to dangerous voltages. Refer all
servicing to qualified service personnel.
SAVE THESE INSTRUCTIONS. THIS MANUAL CONTAINS IMPORTANT
INSTRUCTIONS THAT SHOULD BE FOLLOWED DURING INSTALLATION
AND MAINTENANCE OF THE BATTERY CABINET AND UNINTERRUPTIBLE
POWER SYSTEM (UPS).
1.
This battery cabinet option is designed for use with Liebert Uninterruptible
Power System (UPS) models GXT 6/10 kVA and for installation by qualified
electrical personnel only. The battery cabinet must be installed in
accordance with local/national electrical codes.
§
Up to two optional battery cabinets may be connected to the UPS to
provide additional run time.
§
Battery cabinet models GXT240VBATT and GXT240VBATTUL are
safety approved for use with GXT6000 models only.
§
Battery cabinet models GXT240VLRT and GXT240VLRTUL are safety
approved for use with GXT10000 models only.
2.
Read all safety and operating instructions before operating the UPS and
battery cabinet. Adhere to all warnings on the unit and in this manual. Follow
all operating and user instructions.
3.
These battery cabinets are very heavy. Use adequate handling procedures
to move these cabinets into position, especially when maneuvering across
carpeted areas or uneven surfaces. If this cabinet is to be installed on a
suspended floor, check that the total floor loading presented by the UPS and
its battery cabinets and the localized point loading presented by the leveling
feet are within acceptable limits for the flooring.
4.
This battery cabinet must be installed in an area with unrestricted airflow
away from water, flammable liquids, gases, corrosives, or conductive
contaminants, in an ambient temperature range of 0 – 40º C. NOTE: Battery
cabinet operation in ambient temperatures exceeding 25º C reduces battery
life. Competent personnel should be consulted if liquid spills into the product.
Slits and openings in the cabinet are provided for ventilation. Never block or
insert objects into these ventilation holes or openings.
5.
CAUTION: A BATTERY PRESENTS A RISK OF ELECTRICAL SHOCK
FROM A SHORT CIRCUITED CURRENT. Servicing of batteries should be
performed or supervised by personnel knowledgeable of batteries and the
required precautions. Refer all servicing to qualified service personnel.
WHEN REPLACING THE BATTERIES AT END OF LIFE, USE THE SAME
NUMBER AND TYPE OF BATTERIES.
PROPER DISPOSAL OF
BATTERIES IS REQUIRED. REFER TO YOUR LOCAL CODES FOR
DISPOSAL REQUIREMENTS.
6.
Turn the UPS and battery cabinet OFF before cleaning. Use only a soft
cloth, never liquid or aerosol cleaners. Keep the front and rear vents free of
dust accumulation that could restrict airflow.
2
GLOSSARY OF SYMBOLS
Indicates Caution: Note the accompanying
instructions
Requests the user to consult the manual for
additional information
-
+
PbH2SO4
Indicates that the unit contains a valve regulated lead
acid battery
Indicates Caution: Risk of electrical shock
SYSTEM DESCRIPTION AND OPERATION
Congratulations on your choice of the UPStation GXT™ Uninterruptible Power
System (UPS) Battery Cabinet. The battery cabinets greatly extend the backup
time of your UPS during a power outage. Either one or two optional cabinets
may be connected to the UPS.
When the UPS manual instructs the operator to close the battery circuit breaker
on the rear of the UPS, the operator should also close all of the circuit breakers
on the rear of the battery cabinets. Likewise, when the operator is instructed to
open the UPS battery circuit breaker, the circuit breakers on the optional battery
cabinets should also be opened.
CAUTION: When the UPS manual instructs the operator to open all circuit
breakers to fully isolate the UPS, be sure to open the circuit breakers on the
battery cabinets also.
MAINTENANCE
The UPStation GXT battery cabinets require very little maintenance. The
batteries are valve regulated, nonspillable, lead acid and should be kept charged
to obtain their designed life. The UPS continuously charges the batteries when
connected to the AC power supply.
When storing the UPS for any length of time, it is recommended to apply power
to the UPS for at least 24 hours every four to six months to ensure full recharge
of the batteries. In no case should the unit be stored in excess of nine months
without recharge. Periodically, examine the vents on the front and rear of the
cabinet, and remove any obstructions from the surface of the vents.
3
INSTALLATION INSTRUCTIONS
INSTALLATION CONSIDERATIONS
Detailed instructions to help you install the batteries are provided in the following
pages; however, you should give some consideration to the proposed
environment in which the UPS is to be installed, and carry out some preparatory
work.
WARNING: 240V BATTERIES – RISK OF ELECTRICAL SHOCK
Before installing, ensure that the UPS is shutdown, all circuit breakers on the rear
of the UPS and battery cabinets are off and the mains supply is locked off. For
safety, check with a DC voltmeter that no voltages exist on the battery positivenegative terminals of both the UPS and the battery cabinets. Also check voltages
between these terminals and ground (earth) before touching or wiring to these
terminals.
UNPACKING AND INSPECTION
Follow unloading instructions printed on the carton. Do not discard any
packaging until installation is complete, check that you have removed to a safe
place the user manual, stabilizing brackets, and any other items shipped with the
unit to be used in its installation.
CAUTION: The GXT240VBATT models weigh up to 160 kg (353 lbs) and the
GXT240VLRT models weigh up to 395 kg (871 lbs). Use adequate handling aids
when moving or installing the UPS. The cabinet is fitted with castor wheels for
easy movement. Take care when the cabinet is removed from its packing and
being wheeled across an uneven floor without the stabilizers fitted so that it does
not tip over.
Before you install the battery cabinets, give it a thorough visual examination to
ensure it has not been subjected to shipping damage. If it is not in perfect
condition, you should advise both the shipper and the supplier immediately. DO
NOT ATTEMPT TO INSTALL A DAMAGED BATTERY CABINET.
LOCATION
Locate the batteries indoors in a controlled environment next to the UPS. Locate
it in an area with unrestricted airflow, away from water, flames, flammable liquids,
gases, corrosives, or conductive contaminants.
Give consideration to the airflow requirements and allow at least 150 mm (6
inches) free space around the cabinet, with a minimum of 300 mm (12 inches) at
the back to enable easy operator access to the rear panel mounted circuit
breakers.
Electrical maintenance/servicing requires access to all four sides of the battery
cabinets. Provide the necessary free space or use a flexible wiring system to
allow the cabinet to be pulled forward.
Maintain an ambient temperature range of 0 - 40° C (32-104° F)
Note: Operation in temperatures above 25°C (77°F) reduces battery life.
4
ELECTRICAL CONNECTIONS
The UPS and battery cabinets are supplied with battery terminals on the rear of
the UPS within a cable box. (see outline drawing) The cable box (gland plate)
can be removed to enable knockouts to be removed, or new holes drilled, to
secure the cables.
The cable sizes and distribution methods used during installation are subject to
local/national electrical codes of practice, and therefore are not detailed here.
Refer to the tables and wiring diagram in the UPS manual for your specific
model. Information is also provided on the battery cabinet rating plate. Rigid or
flexible conduit is recommended for all battery wiring.
The battery cabinet terminals will accept wire sizes up to the values below:
GXT6000 = 10 mm2 (8 AWG)
Recommended for all GXT6000 wiring.
GXT10000 = 16 mm2 (6 AWG)
Recommended for all GXT10000 wiring.
(75º C copper wire)
Terminal tightening torque is 40 cm-kg (35 in-lb).
In no case should the voltage drop on the battery cables exceed 2.0 volts at the
battery cabinet’s rated load.
Properly grounded (earthed) equipment provide multiple benefits.
High quality ground (earth) connections are required for the equipment ground
conductors (protective earth) and grounding electrode conductor (power system
earth connection) to reduce electrical noise and provide for safe operation of the
UPS and connected loads. Conduit used alone without a grounding conductor
wire is not an acceptable connection. Size ground (protective earth) conductors
equal to circuit conductors.
GXT 6&10 kVA
GXT 6&10
Battery Cabinets
STABILIZERS / LEVELING FEET
When the battery cabinet is located in its final position before or after wiring, it is
necessary to fit stabilizer brackets and, if necessary, adjust the leveling feet. If
the UPS is wired using a rigid wiring system, then movement of the UPS must be
prevented by winding down the 4 leveling feet under the UPS as shown below.
For UPS wired with flexible cables, this is optional.
Adjust the leveling feet as necessary using a 12mm open-ended wrench. DO
NOT LOOSEN THE LARGER NUT ABOVE, AS THIS FIXES THE LEVELING
FEET TO THE CHASSIS.
Attach the stabilizing brackets as follows.
GXT240VBATT or GXT240VBATTUL models:
1. Using a Phillips-head screwdriver, remove the screws (4) from each of the
bottom corners of the side panels.
2. Attach the stabilizing brackets to each corner using screws just removed.
GXT240VLRT or GXT240VLRTUL models:
1. Using a Phillips-head screwdriver, remove the two inner-most screws at the
base of both side panels.
2. Attach the stabilizers fixing with the screws just removed.
240VBATT
240VLRT
12 mm
Leveling Feet Adjustment Diagram
6
COMMISSIONING THE UPS WITH OPTIONAL BATTERIES
1.
2.
3.
4.
5.
BEFORE STARTING THE UPS OR CLOSING ANY CIRCUIT BREAKERS,
verify the proper wiring of the optional battery cabinets. Using a continuity
meter, verify that positive (+) terminals are only connected to positive
terminals on the rear of the UPS and battery cabinets. Again, check that
negative (-) terminals are only connected to negative terminals. Be sure to
check every wire interconnecting the UPS and optional battery cabinets.
Verify that the positive and negative terminals are not in contact with ground
(earth).
WARNING: REVERSING THE BATTERY CONNECTIONS CREATES A
SERIOUS HAZARD TO BOTH THE EQUIPMENT AND SERVICE
TECHNICIAN. CHECK THESE CONNECTIONS CAREFULLY BEFORE
TURNING ON ANY CIRCUIT BREAKERS.
Install the covers on the cable entry boxes.
Leave the circuit breakers on the rear of the battery cabinets off. Perform all
UPS commissioning instructions in the UPS manual using only the internal
batteries controlled by the circuit breaker on the rear of the UPS.
Next, commission the UPS again while leaving open the battery circuit
breaker on the rear of the UPS and closing all circuit breakers on the rear of
the optional battery cabinets.
Finally, check the UPS with all battery circuit breakers closed. The system is
now ready for normal operation.
SPECIFICATIONS
Model
Number
Rating
Battery
Type
GXT240VBATT
GXT240VBATTUL
240VDC / 32A
12V x 20 (x2); 7.0 or 7.2 Ah;
Valve-regulated, nonspillable, lead acid
Weight: kg (lbs)
125 (275.6)
Unit
157 (346)
Shipping
Dimensions: mm (in)
260x612x703
Unit
(10.2x24.1x27.7)
(W x D x H)
400x850x965
Shipping
(15.8x33.5x38)
(W x D x H)
GXT240VLRT
GXT240VLRTUL
240VDC / 50A
12V x 20; 40 Ah;
Valve-regulated, nonspillable, lead
acid
128 (282.2)
160 (353)
365 (804.8)
395 (871)
260x612x803
(10.2x24.1x31.6)
400x850x1065
(15.8x33.5x42)
380x726x965
(15.0x28.6x38.0)
560x850x1235
(22.1x33.5x48.7)
7
LIMITED WARRANTY
Liebert Corporation extends the following LIMITED WARRANTY to the
purchaser and to its customer (collectively referred to as the "Purchaser"): the
enclosed Battery Cabinet and components are free from defects in materials
and workmanship under normal use, service, and maintenance FOR A
PERIOD OF TWO YEARS FROM THE DATE OF ORIGINAL PURCHASE from
Liebert or the Liebert dealer or retailer. THE FOREGOING WARRANTY IS
THE ONLY WARRANTY GIVEN AND NO OTHER WARANTY IS PROVIDED,
EXPRESS
OR
IMPLIED,
INCLUDING
WITHOUT
LIMITATION,
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Certain
aspects of disclaimers are not applicable to consumer products acquired by
individuals and used for personal, family, or household purposes (as
distinguished from industrial or other purposes). Local laws may not allow
limitations on how long an implied warranty lasts, so the above limitation may
not apply to you. This warranty gives you specific legal rights, and you may
have other rights, which vary according to local law.
Certain repairs or services are the responsibility of the Purchaser and the
Purchaser is expected to pay for them. This warranty does not extend either to
products with removed or altered serial numbers or to any losses or damages
due to act of God or source external to the product, misuse, accident, abuse,
neglect, negligence, unauthorized modification, alteration, or repair, use beyond
rated capacity, or improper installation, maintenance, application or use,
including, without limitation, use in a manner contrary to the accompanying
instructions or applicable codes. WARNING: Warranty is void if the battery is
allowed to discharge below the minimum battery cutoff point. The battery must
be recharged every four (4) to six (6) months when not in use.
If the Battery Cabinet fails to conform with the above warranty within the two
year warranty period, Liebert will repair or replace the Battery Cabinet, at
Liebert's option. Repairs or replacements are warranted for the remainder of
the original warranty period. Purchaser, to make a warranty claim, should call
1-800-222-5877 to obtain a Returned Goods Authorization number and
shipping instructions. Return transportation costs to Liebert are the
responsibility of the Purchaser.
8
UPStation GXT™
6 & 10 kVA
Optional Battery Cabinet
Technical Support
Global Services
Applications U.S.A.
Outside the U.S.A.
U.K.
France
Germany
Italy
Netherlands
E-mail
Web site
Worldwide FAX tech support
1-800-LIEBERT
1-800-222-5877
614-841-6755
+44 (0) 1793 553355
+33 (0) 1 43 60 01 77
+49 89 99 19 220
+39 2 98250 1
+31 (0) 475 503333
[email protected]
http://www.liebert.com
+614-841-5471
The Company Behind The Products
With more than 500,000 installations around
the globe, Liebert is the world leader in
computer protection systems.
Since its
founding in 1965, Liebert has developed a
complete range of support and protection
systems for sensitive electronics:
While every precaution has been taken to
ensure accuracy and completeness of this
literature, Liebert Corporation assumes no
responsibility, and disclaims all liability for
damages resulting from use of this information
or for any errors or omissions.
•
Environmental systems: close-control
conditioning from 1.5 to 60 tons.
©1999 Liebert Corporation All rights reserved
throughout the world. Specifications subject
to change without notice.
•
Power conditioning and UPS with power
ranges from 250 VA to more than 1000 kVA.
•
Integrated systems that provide both
environmental and power protection in a
single, flexible package.
•
Monitoring and control — on-site or remote —
from systems of any size or location
Service and support, through more than 100
service centers around the world, and a 24hour Customer Response Center.
•
air
9
® Liebert and the Liebert logo are registered
trademarks of Liebert Corporation. All names
referred to are trademarks or registered
trademarks of their respective owners.
SLI-23147 (9/99) Rev. 0