Liebert® IntelliSlot® MultiPort

Infrastructure Management & Monitoring
For Business-Critical Continuity™
Liebert® IntelliSlot® MultiPort
User Manual
TABLE OF CONTENTS
1.0
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Inspecting Shipment on Receipt . . . . . . . . . . . . . . . . . . . . . . . . 2
Required Adapter Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.0
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Required Parts and Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.1
Connect the Liebert IntelliSlot MultiPort Card . . . . . . . . . . . . 3
2.2
Connect the UPS to a Liebert MultiLink computer . . . . . . . . . 4
2.3
Connect the UPS to an AS/400 System Unit . . . . . . . . . . . . . . 5
Figures
Figure 1
Figure 2
Figure 3
Computer protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
RJ45 connections: Liebert MultiLink computer to UPS. . . 4
RJ45 connections: AS/400 system to UPS . . . . . . . . . . . . . . 5
Tables
Table 1
Table 2
RJ45 connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Adapter kits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
i
Introduction
1.0
INTRODUCTION
The Liebert IntelliSlot MultiPort (IS-MULTIPORT) adds to the
Liebert line of shutdown solutions. The card provides easy-to-install
protection for up to four systems connected to a single UPS: computers
with Liebert MultiLink™ software installed or AS/400 system units.
The systems can simultaneously monitor the UPS status—utility
power failure and low battery.
This advanced power-management device is designed to function in
the Liebert IntelliSlot port of the following UPS units:
• Liebert Nfinity™
• Liebert NX™
• Liebert UPStation GXT3™
Note: The Liebert PSI is not supported.
Visit the Liebert Web site at www.liebert.com for the current list of
supported products.
When a Low Battery or Utility Figure 1 Computer protection
Fail condition is detected, the
UPS
IS-MULTIPORT
Liebert
Liebert IntelliSlot MultiPort
MultiLink
provides a signal to each
computers
connected system (Figure 1).
Connected Liebert MultiLink
AS/400
computers and AS/400 system
system
units can interpret the signal
units
and initiate operating system
shutdown according to configurations determined by the user.
Table 1 shows the pin configuration for the Table 1 RJ45 connector
RJ45 connectors on the Liebert IntelliSlot
Pin
Description
MultiPort.
A straight-through RJ45 Ethernet cable is
needed to connect the Liebert UPS to an
adapter on a Liebert MultiLink computer
or an AS/400 system unit.
Adapter kits are available separately (see
Required Adapter Kits on page 2 for
details).
1
2
3
4
5
6
7
8
Low Battery
Utility Fail
NOT USED
NOT USED
NOT USED
NOT USED
Low Battery Common
Utility Fail Common
NOTE
The UPS Output Off feature in Liebert MultiLink is NOT
available through the IS-MULTIPORT. See the Liebert
MultiLink user manual for operation of this feature.
1
Introduction
Inspecting Shipment on Receipt
Upon accepting shipment, inspect the packaging and product for any
damaged or missing parts. If any damage is observed, report it to the
shipping company and your local Emerson Network Power
representative. If any components are missing, contact your local
representative for replacement.
Items included with the shipment are:
• Liebert IntelliSlot MultiPort card protected by an anti-static bag
• User manual
Required Adapter Kits
The following adapter kits are available separately from Emerson
Network Power.
These kits contain adapters required for connecting an RJ45 cable to a
Liebert MultiLink computer or an AS/400 system unit.
Table 2
Adapter kits
Adapter Kit
P/N
Refer also to:
Liebert MultiLink
Cable Adapter Kit
MLADPT
• 2.2 - Connect the UPS to a Liebert
MultiLink computer
• Installation instructions (SL-31097)
Liebert AS/400
Cable Adapter Kit
AS400ADPT
• 2.3 - Connect the UPS to an AS/400
System Unit
• Installation instructions (SL-31096)
2
Installation
2.0
INSTALLATION
NOTE
Emerson Network Power recommends—although it is not
required—powering down your system and UPS before
continuing with the following procedures.
Required Parts and Tools
Make sure you have the following parts and tools before you begin.
• Liebert IntelliSlot MultiPort card (provided)
• #2 (medium) Phillips or small flathead screwdriver
2.1 Connect the Liebert IntelliSlot MultiPort Card
1. Locate the Liebert IntelliSlot port on the UPS, which is on the rear
of some units, as shown in the examples below. Refer to your UPS
user manual for port location and orientation.
Liebert IntelliSlot
MultiPort card
Remove
screws
2. Remove the two retaining screws from the Liebert IntelliSlot port
cover plate on the UPS. Save the screws for reassembly in Step 4.
3. As you insert the card, make sure the holes are aligned with those
on the UPS. Initially, the card should slide in freely as you
carefully align screw holes. As you feel it click into place, press
firmly to ensure solid seating in the slot.
4. Use the screwdriver to secure the Liebert IntelliSlot MultiPort
card to the UPS chassis with the two retaining screws removed in
Step 2. Make sure the screws are snug, not tight, to avoid damage
to the device.
3
Installation
2.2 Connect the UPS to a Liebert MultiLink computer
Connect the UPS and Liebert MultiLink computer as follows. For complete details, see the Liebert MultiLink Cable Adapter Kit, MLADPT,
installation instructions (SL-31097).
1. Connect the ML-ADP-04 adapter
Figure 2 RJ45 connections:
(included in the kit) to the serial
Liebert MultiLink
computer to UPS
communication port on the
MultiLink computer (see Figure 2).
Computer with
Liebert MultiLink
2. Connect one end of a properly
configured RJ45 cable to the
adapter.
A straight-through RJ45 Ethernet
cable will work.
3. Connect the other end of the RJ45
cable directly to an RJ45 port on the
Liebert IntelliSlot MultiPort on the
UPS.
ML-ADP-04 to
serial port on
MultiLink computer
RJ45 cable to
adapter ML-ADP-04
IS-MULTIPORT
Refer to the Liebert MultiLink user
manual (SL-53625), for software
installation and configuration
procedures.
UPS status polling failure (i.e., ON
BATTERY message is not transmitted
when AC failure occurs) may be caused
by either software or hardware error.
It is highly recommended that you first
attempt to troubleshoot the problem
(see troubleshooting recommendations
in the Liebert MultiLink user manual).
4
RJ45 cable
to RJ45 port on
IS-MULTIPORT
Installation
2.3 Connect the UPS to an AS/400 System Unit
Connect the UPS and AS/400 system as follows. For complete details,
see the Liebert AS/400 Cable Adapter Kit, AS400ADPT, installation
instructions (SL-31096).
1. The kit includes two types of
AS/400 adapters. Select the
appropriate adapter from the kit:
• AS-ADP-01 for connection
to a legacy AS/400
Figure 3 RJ45 connections:
AS/400 system
to UPS
AS/400
• AS-ADP-02 for connection
to an i5 Series AS/400
2. Connect the adapter to the UPS
port on the AS/400 (see Figure 3).
3. Connect one end of a properly
configured RJ45 cable to the
adapter.
A straight-through RJ45 Ethernet
cable will work.
AS-ADP-01 or
AS-ADP-02
to UPS port on
AS/400
RJ45 cable to
AS-ADP-01 or
AS-ADP-02
IS-MULTIPORT
4. Connect the other end of the RJ45
cable directly to an RJ45 port on the
Liebert IntelliSlot MultiPort on the
UPS.
Refer to the AS/400 user manual for
software installation and configuration
procedures.
5
RJ45 cable
to RJ45 port on
IS-MULTIPORT
Ensuring The High Availability
Of Mission-Critical Data And Applications.
Technical Support / Service
Web Site
www.liebert.com
Monitoring
[email protected]
800-222-5877
Outside North America: +00800 1155 4499
Single-Phase UPS & Server Cabinets
[email protected]
800-222-5877
Outside North America: +00800 1155 4499
Three-Phase UPS & Power Systems
800-543-2378
Outside North America: 614-841-6598
Environmental Systems
800-543-2778
Outside the United States: 614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
29/F, The Orient Square Building
F. Ortigas Jr. Road, Ortigas Center
Pasig City 1605
Philippines
+63 2 687 6615
Fax: +63 2 730 9572
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes
no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
© 2010 Liebert Corporation
All rights reserved throughout the world. Specifications subject to change without notice.
® Liebert is the registered trademark of Liebert Corporation.
All names referred to are trademarks or registered trademarks of their respective owners.
SL-51536_REV0_09-10
Emerson Network Power.
The global leader in enabling Business-Critical Continuity™
EmersonNetworkPower.com
AC Power
Outside Plant
Connectivity
Power Switching & Controls
DC Power
Precision Cooling
Embedded Computing
Racks & Integrated Cabinets
Embedded Power
Services
Infrastructure Management & Monitoring
Surge Protection
Emerson, Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are
trademarks and service marks of Emerson Electric Co. or one of its affiliated companies.
©2010 Emerson Electric Co.