Product Specification / Installation Sheet
Description
Liebert IntelliSlot 485 cards provides Liebert
SiteScan® Web or Building Management
Systems monitoring and control of your Liebert
equipment.
The card delivers Modbus or the Emerson
Protocol via the RS-485 port.
DTE/DB9F
serial port for
configuration
(requires
null-modem
connection)
RS-485
(for Modbus)
OR
RS-422 (for IGM)
Depends on
configuration
by user
Compatibility With Other Emerson Network Power Products
The Liebert IntelliSlot 485 Card family, formerly the Liebert OpenComms™ line, includes:
Liebert IntelliSlot Card
Part Number
Compatible with:
• Liebert GXT
• Liebert GXT2U™ • Liebert NX™
• Liebert GXT 6kVA&10kVA • Liebert Hinet™ • Liebert PowerSure PSI™
(before July 2008)
• Liebert Nfinity®
• Liebert GXT3™
™
Liebert IntelliSlot 485 Card
OC-485
Units with Liebert iCOM® Firmware prior to PA1.04.033.STD:
• Liebert Challenger 3000™ • Liebert Deluxe • Liebert PeX™
Liebert IntelliSlot 485 Card-LBDS OC485-LBDS • Liebert Challenger ITR™
System/3™
• Liebert XDC™ with
™
Liebert iCOM
• Liebert DS™
• Liebert CW
• Liebert XDF™
• Liebert HPC™
• Liebert HPM™
• Liebert APM™
• Liebert CRV™
• Liebert XDP™ with
Liebert iCOM
Units with Liebert iCOM Firmware PA1.04.033.STD or later:
• Liebert Challenger 3000
• Liebert Deluxe • Liebert PeX
System/3
• Liebert Challenger ITR
• Liebert XDC with
• Liebert DS
Liebert iCOM
• Liebert CW
Liebert IntelliSlot 485 Card-L
IS-485L
Liebert IntelliSlot 485 Card-S
IS-485S
Units with Liebert IntelliSlot support only:
• Liebert PPC™
• Liebert FDC™
• Liebert FPC™
• Liebert RDC™
Liebert IntelliSlot 485 Card-X
IS-485X
• Liebert NXL™ (SA, SR, SN, MM, CD), Alber® BDSU™
• Liebert RX™
Liebert IntelliSlot Card Communication Protocols
The 485 cards support the following protocols:
Communication Protocol
Liebert IntelliSlot Card
Part Number
Liebert IntelliSlot 485 Card
OC-485
Liebert IntelliSlot 485 Card-LBDS
OC485-LBDS
Liebert IntelliSlot 485 Card-L
IS-485L
Liebert IntelliSlot 485 Card-S
IS-485S
Liebert IntelliSlot 485 Card-X
IS-485X
1
MODBUS/485
IGM







—
—
—
Wiring Specifications
Supported Wire Type
Connection
RS-422 (IGM)
RS-485 (Modbus)
RS-232
DB-9F Connector
18-22 AWG Stranded & Shielded
18 AWG recommended
18-22 AWG Stranded & Shielded
18 AWG recommended
Null Modem Cable
DTE Null Modem Cable
Max. Wire Length
Non Plenum - Belden 9461
Plenum - Belden 88761
Non Plenum - Belden 9461
Plenum - Belden 88761
Null Modem Cable
DTE Null Modem Cable
1000 ft. (300m)
3000 ft. (915m)
50 ft. (15.3m)
Dimensions
Faceplate
TOP
VIEW
RS-232
port
FRONT VIEW
3"
(76mm)
4-3/4"
(121mm)
RS485
RS232
1-1/2"
(38mm)
-
+
1/2"
(11mm)
2-3/8"
(60.3mm)
Specifications
AC Inputs
DC Inputs
Power Consumption
Dimensions - W x D x H: in. (mm)
Net - oz. (kg)
Weight
Shipping - lb. (kg)
Ambient Operating Environment, °F (°C)
Ambient Storage Temperature, °F (°C)
Protection
Service Terminal (RS-232)
Communication
Modbus (RS-485)
Ports
IGM (RS-422)
Power
Requirements
18 - 24 VAC; 50/60 Hz
12 - 36VDC
6VA maximum (1.75W)
3 x 5-1/4 x 1-1/2 (76 x 134 x 38)
7 (0.2)
1.3 (0.6)
32 to 104 (0 to 40); 10% to 90% RH (non-condensing)
-4 to 140 (-20 to 60)
SELV Isolated User Connections, Watchdog Timer Circuitry
DB9F, DTE
2-Position Terminal Block
2-Position Terminal Block
Liebert Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Telephone: 1-800-877-9222
Facsimile: 1-614-841-6022
www.liebert.com
© 2007 Liebert Corporation
All rights reserved throughout the world. Specifications subject
to change without notice.
® Liebert is a registered trademark of Liebert Corporation. All
names referred to are trademarks or registered trademarks of
their respective owners.
SL-28160_REV8_08-13
2