LIEBERT® AC8™ - Emerson Network Power

LIEBERT® AC8™
Product Specification/Installation Sheet
Description
The Liebert AC8 is ideal for coordinated control of systems
with redundant equipment, such as multiple environmental
units or pumps. When the Liebert AC8 controller detects an
alarm in an operating device, the Liebert AC8 enables a
standby device and controls the device in alarm as
configured, either leaving the device operating or disabling it.
The Liebert AC8 controller can also balance usage of devices
by rotating units through Operating and Standby modes
according to a user-defined schedule. This helps keep
redundant equipment operating efficiently and only when
needed. The Liebert AC8 can perform routine testing of
standby devices and alert personnel if a standby device fails
an operating test and requires attention.
The staging feature permits standby devices to be turned on
or off when a sensor detects specified levels. For example, the
Liebert AC8 might be configured to turn on a fan when the
temperature reaches 75°F, then turn on a second fan at 80°F.
When the temperature falls below 80°F, the second fan is turned off; when it drops below 75°F,
the first fan is turned off. Liebert’s TW420 Temperature Transmitter may be connected to any of
the four analog sensor inputs for staging and other functions.
The Liebert AC8 can also monitor the status of connected devices and keep personnel apprised
through local alarming. The Liebert AC8 employs local alarming and remote paging services to
keep personnel on-site and at remote locations apprised of the equipment’s status.
The Liebert AC8 controller can interface
with anything that closes an electrical
contact. To improve process efficiency and
troubleshooting, the controller tracks data
in three types of logs: alarm, event and
trend.
Features and Benefits
• Custom configuration for specific applications
• Paging capability—up to four pager numbers
• Preconfigured on-board modem
The Liebert AC8 has both a local LCD
interface and a remote dial-up interface
for configuration and monitoring. Liebert’s
SiteScan® Web may also be used for
monitoring, as well as some configuration
functions.
• Alarm, Event and Trend logs with time and
date stamp
• Battery backup to ensure alarm notification
• Backup and download configuration files
• User interface via RS232 or modem connection
When an alarm condition arises, the
Liebert AC8 displays alarm information,
sounds an audible alarm, changes the
state of the common alarm relay and turns
connected devices on or off according to
user configuration. If configured, the
controller also sends pager notifications.
• On-board audible alarm
• Configuration data permanently stored in nonvolatile Electrically Erasable Programmable
Read Only Memory (EEPROM) for protection
against power loss
• Real-time clock
For other applications, contact your local
Liebert representative or call
1-800-222-5877.
• Status LEDs for verification and diagnostics
1
Hardware and Components
Controller Board
The controller board supports these connections:
• Eight devices, with 1 digital input and 1 digital
output per device
• Up to four zones, with staging for each zone
• Four 4-20mA analog inputs (one sensor per zone)
• Two programmable digital relay outputs
• Two Common Alarm outputs
• One EPOP input
Enclosure
The Liebert® AC8™ comes standard in an enclosure,
which features a key lock for added security. The
enclosure is made of metal to accommodate secure
conduit fittings and protect components against
environmental debris.
Liebert AC8 enclosure - External features
Knockouts and
access slots
on top and
bottom
The digital inputs are dry contacts. The analog
inputs are 4-20mA inputs. The digital outputs,
programmable relay outputs and Common Alarm
outputs are Form C contact relays. The Common
Alarm output is one output with two sets of contacts.
Key
lock
The point terminations are made using removable
terminal blocks. This allows for easier access to the
terminators, streamlining the process of connecting
external devices to the Liebert AC8.
LCD for
configuration
and operation
• The enclosure is designed for easy wire routing
and terminations. Access slots for communication
cables and network wires are located on both the
top and bottom of the enclosure.
• The enclosure is 2-3/4" deep, allowing for recess
mounting in a wall. The enclosure may also be
flush-mounted.
• The enclosure houses the controller board and
Transformer Module.
The controller board is a microprocessor-based
platform for program execution. The firmware may
be easily upgraded at the job site, simplifying the
process of installing new firmware as it becomes
available. Configuration data is stored in nonvolatile
EEPROM to protect against power loss.
An RS232 operator terminal port is included with
each controller board for operator devices such as a
simple CRT terminal or laptop PC.
An integrated on-board modem allows remote access
to the Liebert AC8. The modem is factoryconfigured, eliminating field configuration and
wiring requirements. An RJ11 phone modem jack is
also included.
Keypad Display
The keypad is a user interface
mounted on the enclosure door of
the Liebert AC8. The liquid crystal
display (LCD) permits complete
Keypad
monitoring and configuration of the
panel and is password-protected.
The keypad display permits the Liebert AC8 to
operate as a complete stand-alone panel.
An IGM422 connection permits access to Liebert’s
SiteScan® Web Enterprise Monitoring System. This
connection allows information and alarms to be
monitored from a centrally located command center.
Liebert AC8 Components and Key Features
Power On/Off switch
Audible horn
Battery pack
Common Alarm
connectors
Transformer
Module
TB5: COMMON ALARM
RELAY OUTPUTS
NO C NC (TOP)
NO C NC
Manual Override
Switch (outputs)
BOTTOM
LS1
+
TB7:
24V INPUT
START
P11
ENABLE
AUDIBLE
TB3, TB4, TB5
OUTPUT RELAY
RATINGS: 24V, 3A
CLASS 2 ONLY.
TB4:
TOP
Q11
LIEBERT
BAR CODE
P23:
BATTERY
BATTERY
(BOTTOM)
NC
C
NO
NC
C
NO
2
LCD
CONTRAST
TP1
VBATT
RELAY
OUTPUTS
GND
ON
S2
OFF
ON
1
2
DIP
3
4
5
6
7
OUTPUT1
OUTPUT2
OUTPUT3
OUTPUT4
OUTPUT5
OUTPUT6
OUTPUT7
OUTPUT8
CTRLLOCK
SENLOCK
CMN ALR
DS56
DS54
DS63
8
DS83
DS84
DS61
DS60
DS62
DS55
DS57
DS59
DS58
DS53
CAN TX
CAN RX
Modem
(BOTTOM)
(TOP)
4
3
MOP
F PROG
574 TX
574 RX
485 RX
485 TX
PFM2
1
7
6
5
REV
(BOTTOM)
(TOP)
4
Phone line
connector
3
2
ASS
1
TB1
8
7
5
EPOP
ON
P19
MODEM
DIS EN
J11: PHONE
PIN 3-TIP
PIN 4-RING
(TOP)
485
+
(BOTTOM)
—
422
+
—
+
—
+
+
—
—
+
—
AG TB9: ANALOG
GROUND
EPOP
Digital input
connectors
6
TB2:
CONTACT
INPUTS
EPOP INPUT
1-2 TOP
3-4 BOTTOM
Digital output
connectors
8
PFM5
R334
2
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
C71
DS70
DS67
DS66
DS65
DS64
MODEM
Power On/Off
switch
Control relay
outputs
EPOP contact
input
TB1: EPOP
CONTACT
INPUT
TB1, TB2 INPUTS:
DRY CONTACTS ONLY.
Power receptacle
Serial interface
connector (RS232 / EIA574)
2
SiteScan Web
connector (EIA422)
Analog input
connectors
Dimensions - Enclosure and Transformer Modules
ENCLOSURE
18"
(457.2mm)
TRANSFORMER MODULES (115V & 230V)
Front
view
Front
view
14"
(355.6mm)
18"
(457.2mm)
3.83"
(97.2mm)
Top/bottom
view
Top/bottom
view
2.85"
(72.39mm)
2.65"
(67.3mm)
Wiring Specifications
Connection
Supported Wire Type
Maximum Wire Length
Rating
750 ft. (225m)
Dry Contact
(24VDC,
10 mA)
Digital
Input/
EPOP
18-22 AWG Stranded & Unshielded
18 AWG* (recommended)
Non Plenum - Belden 9740
Plenum - Belden 89740
Digital
Output/
Control
Relay
18-22 AWG Stranded & Unshielded
18 AWG* (recommended)
Non Plenum - Belden 9740
Plenum - Belden 89740
Analog Input
2-Wire
Transducer
18-22 AWG Stranded & Unshielded
18 AWG* (recommended)
Non Plenum - Belden 9740
Plenum - Belden 89740
750 ft. (225m)
4-20 mA Signal
Input Selectable
Power Source
(12/24VDC)
Analog Input
4-Wire
Transducer
18-22 AWG Stranded & Unshielded
18 AWG* (recommended)
Non Plenum - Belden 8489
Plenum - Belden 88489
750 ft. (225m)
4-20 mA Signal
Input Selectable
Power Source
(12/24VDC)
Common
Alarm
Output
18-22 AWG Stranded & Unshielded
18 AWG* (recommended)
Non Plenum - Belden 9740
Plenum - Belden 89740
Communication
RS232
Null Modem Cable
Communication
EIA422
Liebert®
SiteScan®
Communication
EIA485
18 AWG*
(recommended)
20 AWG
22 AWG
@3A 50 ft. (15m)
@2A 100 ft. (30m)
@1A 200 ft. (60m)
@3A 40 ft. (12m)
@2A 60 ft. (18m)
@1A 100 ft. (30m)
@3A 25 ft. (7m)
@2A 35 ft. (10m)
@1A 75 ft. (23m)
18 AWG*
(recommended)
20 AWG
22 AWG
@3A 50 ft. (15m)
@2A 100 ft. (30m)
@1A 200 ft. (60m)
@3A 40 ft. (12m)
@2A 60 ft. (18m)
@1A 100 ft. (30m)
@3A 25 ft. (7m)
@2A 35 ft. (10m)
@1A 75 ft. (23m)
24VAC@3A
24VAC
@3A
50 ft. (15m)
N/A
18-22 AWG Stranded & Shielded
22 AWG* (recommended)
Non Plenum - Belden 9461
Plenum - Belden 88761
1000 ft. (300m)
N/A
18-22 AWG Stranded & Shielded
22 AWG* (recommended)
Non Plenum - Belden 9461
Plenum - Belden 88761
3000 ft. (900m)
N/A
N/A
N/A
150 ft. (45m)
24VAC
@1.3A
Phone/Modem
Line
4 Wire (Pins 3 & 4)
RJ11 Connector
24VAC Power
Connection
(TB7)
18-22 AWG Stranded & Shielded
18 AWG* (recommended)
Non Plenum - Belden 8770
Plenum - Belden 88770
Power Connections (Transformer Module)
115VAC
14 AWG Stranded & Unshielded
Non Plenum - Belden 5101UE
150 ft. (45m)
115VAC
@4A
230VAC
14 AWG Stranded & Unshielded
Non Plenum - Belden 5101UE
150 ft. (45m)
230VAC
@0.5A
* Recommended
3
Liebert® AC8™ Specifications
115VAC Transformer Module / UML11500
Power
Requirements
230VAC Transformer Module / UML23000
115VAC ±10% of nominal; 60Hz, 4A, 460VA 230VAC ±10% of nominal; 50Hz, 0.5A, 115VA
18 x 2-3/4 x 18 (457.2 x 69.85 x 457.2)
20.56 lb. (9.33 kg)
NEMA 1
Four line, 20 character, backlit
Building Wall or Structural Member
32ºF to 104ºF (0ºC to 40ºC) 0% RH to 95% RH (non-condensing)
Dimensions: W x D x H, in. (mm)
Weight (Assembled)
Enclosure Type
Liquid Crystal Display (LCD)
Mounting Surface
Ambient Operating Environment
Processor Specifics
Model
Clock speed
Total RAM
Total FLASH
Total EEPROM
A/D Resolution (Analog IN)
Modem Type Embedded
Clock Type
Clock battery backup type
Clock battery life
Modem battery backup type
Modem battery life
Communications
Local Communications
Remote: Modem (9600-N-8-1)
Remote: Supported pagers
SiteScan Web
Motorola XC68HC812A4
16MHz
256Kb
4M
4K
12 Bit
14.4K bps
Real-Time Clock
Lithium Cell (non-replaceable)
7 years, constant, no power
Nickel Cadmium (replaceable)
10 minutes at full load
RS232
Baud rate 9600 bps, Parity=None, Data bits=8, Stop bits=1
9600 E-7-1 supports TAPI protocol version 1.8
IGM Protocol, EIA422
115VAC Transformer Module (TM115)
230VAC Transformer Module (TM230)
Agency Listings
UL
CSA
CE
FCC Compliance
Inputs & Outputs (Quantity)
Digital Inputs (8)
Analog Inputs (4)
Digital Outputs (8)
Common Alarm Outputs (2)
UL1012
UL1585
C22.2 No. 66 and C22.2 No. 107.1
Yes
N/A
Dry Contact Closure 24VDC, 10 mA
4-20 mA signal input with selectable power source of 12VDC or 24VDC
24VAC, 3A
24VAC, 3A
Ordering Information
Quantity
Part #
AC8L115
AC8L230
201258P1
TW420
Description
Liebert AC8 controller board & Transformer Module 115VAC with two 24VAC outputs (40VA each) and
115VAC receptacle in enclosure
Liebert AC8 controller board & Transformer Module 230VAC with two 24VAC outputs (40VA each) in
enclosure
RS232 configuration cable
Temperature Transmitter Wall 4-20 mA @ 45°F to 96°F
Liebert Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Telephone: 1-800-877-9222
Facsimile: 1-614-841-6022
www.liebert.com
© 2005 Liebert Corporation
All rights reserved throughout the world. Specifications subject
to change without notice.
® Liebert and the Liebert logo are registered trademarks of
Liebert Corporation. All names referred to are trademarks or
registered trademarks of their respective owners.
SL-31101_REV1_02-13
4