LIEBERT MP™ ADVANCED POWER STRIPS

LIEBERT MP™ ADVANCED POWER STRIPS
QUICK-START GUIDE: OPENCOMMS EM
OR
MP ADVANCED ACCESS SERVER
WHAT’S INCLUDED
Make sure you have all the items that should be included with your Liebert MP Advanced Power Strip. If
any item is missing or damaged in shipping, file a damage claim immediately—see the user manual for
details.
•
•
•
•
RJ-45 to RJ-45 configuration cable, 5 ft. (1.5m)
RJ-45 to DB9 adapter for configuration cable
2 mounting brackets and 4 screws
Quick-start guide
DCN Power Port
Serial Ports - Connect either
to Power Strip EIA-232 Port
Sensor Sensor
Modem
2
1
DCN
Serial
2
Serial
Ethernet
1
Ethernet
Port
Liebert OpenComms EM
(EM PDU Controller)
Mounting
Bracket on
either side
Liebert MP
Advanced
Power Strip
(MP-C5120)
EIA-232
POWER
1 3 5 8
EIA-232 Port
2 4 6 8
CONFIGURATION WITH OPENCOMMS EM
1. Connect power to the DCN port on the OpenComms EM and to your MP Advanced Power Strip.
2. Connect the six-wire end of the serial cable provided with the OpenComms EM to the EIA-232 port of
your MP Advanced Power Strip.
3. Connect the other end (eight-wire) of the serial cable to either Serial 1 or Serial 2 of the
OpenComms EM.
4. Connect a straight-through CAT5 Ethernet cable from your network to the Ethernet port on the back
of the OpenComms EM.
ASSIGN AN IP ADDRESS
NOTE
These steps must be done on the same network segment where the OpenComms EM is connected.
If your network uses static IP addresses and your computer has a Windows operating system, follow the
steps below. Otherwise, consult the OpenComms EM user manual (SL-28210).
1. Obtain an IP address for the OpenComms EM from your network administrator.
2. Insert the OpenComms EM CD in your computer’s CD drive.
3. Click on the Start button, then on Run, then Browse to the file IPSET.exe on the CD and click
Open.
1
4. Click OK to open the IPSet window (at right).
5. In the Target area:
a. Enter the OpenComms EM IP address
b. Enter your network’s Subnet Mask
c. Enter your router’s IP address in the Default
box.
d. Enter the MAC address found on the bottom
of your OpenComms EM.
6. Apply the changes. If the device identification is
successful, the message “Successfully set IP
address” appears in the Status box. (If not, the
message “No response from target” appears in
the Status box.)
7. Click on the Close button.
Enter a
unique
IP address
Subnet
mask
Default
gateway
address
Enter the unit’s
MAC address
(look on
bottom of unit)
Apply button
OPEN THE WEB INTERFACE AND LOG IN
• Open an Internet browser and enter the unit’s IP address or hostname into the browser’s address bar
and press the Enter key. The Login window appears.
Address
bar
Login
window
User Name
default = “liebert”
Password
default = no password
• Enter the default user name—liebert— in the User Name box (case-sensitive).
• Leave the Password box blank (the default liebert user account has no password).
• Click OK. If the login is successful, a message appears. Click OK.
When ready to exit the user interface, click on the Summary tab at the top of the Web interface, then
click on the Log Out button in the left side of the window.
2
CONFIGURATION WITH LIEBERT MP ADVANCED ACCESS SERVER
Liebert MP Advanced
Power Strip
(MP-C5120)
Mounting
Bracket on
either side
EIA-232
POWER
1 3 5 8
EIA-232 Port
2 4 6 8
EIA-232 Port - Connect
to Power Strip EIA-232 Port
MP-DS74 Card With
Configurable
Communication Ports
Ethernet Port
Liebert MP Advanced
Access Server
(MP-S5138)
100-240VAC
??????????
0.21-0.12AMPS
DS74
CX1 CX2
1
2
3
4
CX3 CX4
EIA-232
I/0 MODULE
LINE
DS62
NETWORK
INTERFACE
ETHERNET
EIA-232
ROUTE
MADE IN USA
On/Off Switch
(not on all
Access Servers)
MAKE CONNECTIONS
1. Connect power to the Liebert MP Advanced Access Server and turn the unit On (the On/Off switch is
on the rear of the unit; some units do not have this switch; they are energized whenever their power
cord is plugged into a power source).
2. Attach the adapter (RS-232 to RJ-45) to one end of a silver configuration cable (included) and connect
that end of the cable to a COM port on a computer. Connect the other end of the cable to the EIA-232
port of the MP-DS62 card on your MP Advanced Access Server.
3. Plug one end of the second silver RJ-45 cable into any of the ports in the MP-DS74 module in your
Liebert MP Advanced Access Server; plug the other end of the cable into the EIA-232 port on your MP
Advanced Power Strip.
ESTABLISH COMMUNICATION WITH CARD
1. Use terminal emulation software, such as HyperTerminal™, to open a
direct connection to the MP-DS62 card. Use the settings at right. Press
Enter for the Main Menu, choose “C” and then “1” to configure the
MP-DS62 port.
2. Enter “8” for Network Port Configuration (below left), then “7,” then “N”
to disable DHCP (below right).
Choose “8” to change
Network Port
Configuration
HYPERTERMINAL SETTINGS
Baud Rate: 9600
Data Bits:
8
Parity:
None
Stop Bits:
1
Flow Control: N/A
Enter “N”
to disable
DHCP
Enter “7”
to change
DHCP setting
3
SET THE IP ADDRESS
1. Select “1” to set the IP Address for Module 1. Enter an IP address (below). The address must be
unique on your system (obtain this from your network administrator).
2. Press Enter to return to the Network Port Configuration menu.
Enter IP address
3. Choose “2” to set the Subnet Mask for your system (obtain this from your network administrator).
SET THE GATEWAY ADDRESS
1. Return to the Network Port Configuration menu and choose “3” to set the Gateway Address (the IP
address of your network router). Follow the prompts to exit HyperTerminal and save your changes.
2. Verify that your settings are correct and were saved by using a command prompt to ping the
MP-C/MP-S unit: Start>Run>CMD.
3. At the command prompt enter:
ping [IP address]
4. Press “Enter.”
Liebert Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Telephone: 1-800-877-9222
Facsimile: 1-614-841-6022
www.liebert.com