Liebert® DataMate™–1.5 to 3 Tons (5 to 10.5kW) Capacity Technical Data Manual– Air, Water/Glycol and Chilled Water Units, 50 & 60Hz TABLE OF CONTENTS 1.0 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 1.1 Designed to Match Computer and Electronic Equipment Needs—From Installation to Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 2.0 STANDARD FEATURES—1.5- TO 3-TON SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 2.1 Evaporator Section—Split-Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2.2 Condensing Unit Section—Remote Split-Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2.2.1 2.2.2 2.2.3 Indoor Centrifugal Fan Condensing Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Outdoor Prop Fan Condensing Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Indoor Remote Water/Glycol Condensing Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2.3 Condensing Unit Section—Close-Coupled . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2.4 Chilled Water Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2.5 System Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2.5.1 Other Standard Control Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 3.0 OPTIONAL FACTORY-INSTALLED FEATURES—EVAPORATOR/CHILLED WATER AND CONDENSING UNITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 3.1 Electric Reheat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 3.2 Humidifier/Electric Reheat Package . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 3.3 Optional Configurations—Prop Fan Condensing Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 3.4 Optional Configurations—Indoor Remote Water/Glycol Condensing Units . . . . . . . . . . . . . . 4 4.0 SHIP-LOOSE ACCESSORIES—FIELD-INSTALLED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 4.1 Remote Monitoring, Autochangeover and Leak Detection Equipment . . . . . . . . . . . . . . . . . . 6 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 FLEXIBLE CONFIGURATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7 AIR-COOLED SYSTEMS—CAPACITIES AND DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . .8 WATER/GLYCOL SYSTEMS—CAPACITIES AND DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . 14 CHILLED WATER SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 ELECTRICAL DATA—ALL UNITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 REFRIGERANT PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 GLYCOL LOOP PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 MODEL NUMBER NOMENCLATURE—ALL SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 GUIDE SPECIFICATIONS—FOR LIEBERT DATAMATE 1.5- TO 3-TON (5 TO 10.5KW). . . . . . . . . . . . 32 1.0 2.0 3.0 GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 PRODUCT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 EXECUTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 FIGURES Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6 Wall-box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Flexible configurations—All systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 General arrangement, air-cooled split systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Dimensions, evaporator unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Cabinet and floor planning dimensions—Outdoor air-cooled condensing units . . . . . . . . . . . . . . 12 Dimensions, indoor air-cooled condensing units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 i Figure 7 Figure 8 Figure 9 Figure 10 Figure 11 Figure 12 Figure 13 Figure 14 Figure 15 Figure 16 Figure 17 Figure 18 Figure 19 Figure 20 Figure 21 Figure 22 General arrangement, water/glycol, split systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . General arrangement, water/glycol systems, close-coupled condensing unit . . . . . . . . . . . . . . . . Dimensions, evaporator unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Dimensions and piping, close-coupled water/glycol condensing unit. . . . . . . . . . . . . . . . . . . . . . . Cabinet dimensions and piping data, water/glycol indoor remote condensing modules. . . . . . . . General arrangement—Chilled water systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Dimensions—Chilled water unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Step-down transformer for 277V input power applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Refrigerant piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Heat rejection loop, multiple drycoolers and multiple indoor units. . . . . . . . . . . . . . . . . . . . . . . . Model number nomenclature—Evaporator units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Model number nomenclature—Outdoor air-cooled condensing units . . . . . . . . . . . . . . . . . . . . . . Model number nomenclature—Indoor air-cooled condensing units. . . . . . . . . . . . . . . . . . . . . . . . Model number nomenclature, close-coupled water/glycol condensing units—60Hz only . . . . . . . Model number nomenclature—Indoor remote water/glycol-cooled condensing units. . . . . . . . . . Model number nomenclature—Chilled water units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 16 17 18 20 22 23 26 28 29 30 30 30 31 31 31 TABLES Table 1 Table 2 Table 3 Table 4 Table 5 Table 6 Table 7 Table 8 Table 9 Table 10 Table 11 Table 12 Table 13 Table 14 Table 15 Table 16 Table 17 Table 18 Table 19 Table 20 Table 21 Table 22 Table 23 Table 24 Table 25 Table 26 Table 27 60Hz capacities & typical specifications, air-cooled applications. . . . . . . . . . . . . . . . . . . . . . . . . . . 8 50Hz capacities & typical specifications, air-cooled applications. . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Evaporator section dimensions—air-cooled applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Evaporator unit refrigerant connections—pipe size/coupling number . . . . . . . . . . . . . . . . . . . . . 11 Propeller fan, air-cooled condensing unit dimensions, inches (mm) . . . . . . . . . . . . . . . . . . . . . . . 12 Remote centrifugal fan, air-cooled condensing, weight and dimensions . . . . . . . . . . . . . . . . . . . . 13 60Hz capacities & typical specifications, water-cooled and glycol-cooled applications. . . . . . . . . 14 50Hz capacities & typical specifications, water-cooled and glycol-cooled applications. . . . . . . . . 15 Evaporator section dimensions—water/ glycol-cooled applications . . . . . . . . . . . . . . . . . . . . . . . . 17 Evaporator unit refrigerant connections—pipe size/coupling number . . . . . . . . . . . . . . . . . . . . . 17 Unit refrigerant connection sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Net weight, water/glycol condensing units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Net weight, indoor water/glycol-cooled condensing unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Chilled water data, 50/60Hz. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Chilled water capacity correction factors based on 10°F (5.6°C) water rise . . . . . . . . . . . . . . . . . 22 Net weights and dimensions, chilled water units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Electrical data, split system evaporator or chilled water unit, 60/50Hz . . . . . . . . . . . . . . . . . . . . 24 60Hz electrical data, evaporator with close-coupled water/glycol condensing unit with common power feed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 60Hz electrical data, outdoor air-cooled condensing unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 50Hz electrical data, outdoor air-cooled condensing unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Electrical data, indoor air & water/glycol remote condensing units, 50 & 60Hz . . . . . . . . . . . . . 26 Refrigerant charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Recommended refrigerant line sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Pipe length and condenser elevation relative to evaporator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Refrigerant charge in Liebert pre-charged R-407C line sets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Line charges - refrigerant per 100 ft. (30m) of Type L copper tube . . . . . . . . . . . . . . . . . . . . . . . . 28 Equivalent lengths for various pipe fittings, ft (m). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 ii Introduction 1.0 INTRODUCTION 1.1 Designed to Match Computer and Electronic Equipment Needs—From Installation to Operation Installed on the floor or on the wall, Liebert DataMate Precision Cooling systems control the cooling, humidity and air distribution required by sensitive electronic equipment. A range of sizes and configurations is available to meet varying sites’ needs. The Liebert DataMate is also easy to use. Advanced microprocessor technology allows easy, precise control and menu-driven monitoring keeps you informed of system operation through the LCD readout. These features, combined with Emerson quality construction and reliable components, guarantee satisfaction from installation through operation. Liebert Precision Cooling Liebert Precision Cooling systems are designed to control the environment required for computers and other sensitive electronic equipment. The Liebert DataMate provides complete control on an around-the-clock basis and the high sensible heat ratio required by sensitive electronic equipment. Easy Installation The Liebert DataMate is a split-system evaporator combined with a remote air-, water- or glycol-cooled condensing unit or a close-coupled water/glycol-cooled condensing unit or is a self-contained, chilled water unit. Each split system has thermostat-type wiring to controls and condensing unit. System components are pre-charged with refrigerant using quick-connect fittings and can be easily connected together. Optional pre-charged line sets or sweat adapters for field refrigerant piping are available for remote condensing units. Easy to Service The Liebert DataMate is designed for front service access. Routine maintenance and service can be performed quickly and easily. Spare parts are always in Emerson inventory and available on short notice. Advanced Control Technology A menu-driven microprocessor control system provides precise temperature and humidity control and accurate alarm setpoints. Using touch-sensitive buttons, the wall-mounted monitor/control panel allows you to select and display temperature and other monitored parameters. High Efficiency High sensible heat ratio, scroll compressor and precise microprocessor control allow the system to operate efficiently. Space Saving Design Models available to fit any room without disrupting workstation layout. Requires 5 ft2 (0.5m2) or less of floor space or can be mounted on a wall. Reliable The Liebert DataMate installed base is a testimony to the system reliability. Agency Listed Standard 60Hz units are CSA certified to the harmonized U.S. and Canadian product safety standard, CSA C22.2 No 236/UL 1995 for “Heating and Cooling Equipment” and are marked with the CSA c-us logo. C 1 US Liebert® DataMate™ Standard Features—1.5- to 3-Ton Systems 2.0 STANDARD FEATURES—1.5- TO 3-TON SYSTEMS 2.1 Evaporator Section—Split-Systems The Liebert DataMate is available as a split system air, water/glycol-cooled unit or self-contained chilled water unit. Split-System Evaporator Section includes the evaporator coil, 2-speed centrifugal blower assembly, filter-drier, galvanized steel drain pan, R-407C refrigerant charge, cleanable filters and microprocessor control with wall-mounted display panel. The unit construction is galvanized steel with powder-coated, removable exterior panels. A reversible discharge grille provides the ability to redirect airflow. The evaporator can be floor- or wall-mounted. 2.2 Condensing Unit Section—Remote Split-Systems 2.2.1 Indoor Centrifugal Fan Condensing Units Indoor Air-Cooled Centrifugal Fan Condensing Units include scroll compressor, factory-mounted disconnect switch, condenser coil, R-407C unit charge, belt-driven centrifugal blower assembly, high-pressure switch, Liebert Lee-Temp™ head pressure control system, hot gas bypass and liquidline solenoid valve. Unit must be mounted indoors. Condensing unit is designed to use outdoor air with temperatures ranging from -30°F to 95°F (-34°C to 35°C). Available in 2- & 3-Ton models. 2.2.2 Outdoor Prop Fan Condensing Units Outdoor Prop Fan Condensing Units include scroll compressor, condenser coil, R-407C unit charge, prop fan, liquid-line solenoid valve, high pressure switch, Liebert Lee-Temp head pressure control and hot gas bypass. Condensing unit is designed for outdoor locations with operating ambients ranging from -30°F to 95°F (-34°C to 35°C). 2.2.3 Indoor Remote Water/Glycol Condensing Units Indoor Remote Water/Glycol Condensing Units include scroll compressor, R-407C unit charge, factory-mounted disconnect, coaxial condenser, hot gas bypass, high head pressure switch and two-way water regulating valve designed for 150psi (1034.3kPa). Condensing units can be used on either a water or glycol cooling loop. Available in 2- and 3-ton models. 2.3 Condensing Unit Section—Close-Coupled The Close-Coupled Water/Glycol Condensing Unit is designed to attach to the split-system evaporator to become a single wall- or floor-mounted unit. Indoor close-coupled water/glycol condensing units include scroll compressor, brazed plate condenser, R-407C refrigerant charge and 2-way water regulating valve. Unit is available in 60Hz models only. Design pressure is 150psi (1034kPa). 2.4 Chilled Water Units Self-Contained Chilled Water Models include a chilled water coil, a two-way, solenoid open, slow-close (On/Off) spring-return valve, two-speed centrifugal blower assembly, cleanable filters and microprocessor control with wall-mounted display panel. Design pressure is 300psi (2068kPa) with a maximum close-off pressure of 60psi (414kPa). Liebert® DataMate™ 2 Standard Features—1.5- to 3-Ton Systems 2.5 System Controls System controls include a microprocessor control board mounted in the evaporator/chilled water unit and a wall-mounted interface with a two-line, 16-character liquid crystal display. An eight-key, membrane keypad for setpoint/program control, unit On/Off, fan speed and alarm silence is below the LCD screen. It provides temperature setpoint and sensitivity adjustment, humidity setpoint and sensitivity adjustment, digital display of temperature, humidity, setpoints, sensitivities, fan speed and alarm conditions. The wall-box is field-wired to the microprocessor control using standard four-conductor thermostat wire (field-supplied). The temperature and humidity sensors are in the wall box, which can be installed up to 300 feet (91.4m) from the evaporator unit. The unit-mounted control board also includes common alarm terminals and shutdown terminals. The unit automatically restarts after a power outage. Figure 1 2.5.1 Wall-box Other Standard Control Features • Adjustable auto restart • Calibrate sensors • 5 day/2 day setback • Predictive humidity control • Password protection • Common alarm output • Alarm enable/disable • Remote shutdown terminals • Self-diagnostics 3 Liebert® DataMate™ Optional Factory-Installed Features—Evaporator/Chilled Water and Condensing Units 3.0 OPTIONAL FACTORY-INSTALLED FEATURES—EVAPORATOR/CHILLED WATER AND CONDENSING UNITS 3.1 Electric Reheat Electric low watt tubular reheat element with non-corrosive metal sheath provides one stage of non-ionizing reheat to maintain room dry bulb temperature. 3.2 Humidifier/Electric Reheat Package The humidifier and electric reheat are available as a package for complete humidity control. The canister humidifier includes a steam-generating type humidifier with automatic flushing circuit, inlet strainer, drain, 1" (25.4mm) air gap on fill line and solenoid valves. Humidifier problem alarm annunciates at the wall-mounted display panel. Maximum humidifier water supply pressure is 150psi (1034kPa). 3.3 Optional Configurations—Prop Fan Condensing Units Outdoor Prop Fan Condensing Units are also available in the following optional configurations: • High ambient models for providing catalog capacities at ambient temperatures up to 105°F (40°C): 2- and 3-ton models only. • Liebert Quiet-Line™ models for low noise level conditions (below 58 dBA) and for providing catalog capacities at ambient temperatures up to 95°F (35°C). • Condenser coils can be phenolic-coated for extended coil life in coastal areas. 3.4 Optional Configurations—Indoor Remote Water/Glycol Condensing Units Indoor Remote Water/Glycol Condensing Units are also available with the following piping options: • Two-way water regulating valve with 350psi (2413kPa) design pressure • Three-way water regulating valve with 150psi (1034kPa) design pressure • Three-way water regulating valve with 350psi (2413kPa) design pressure Liebert® DataMate™ 4 Ship-Loose Accessories—Field-Installed 4.0 SHIP-LOOSE ACCESSORIES—FIELD-INSTALLED The Condensate Pump is field-mounted internal to the unit and wired to the unit power block or is field-mounted external to the unit with power from unit or external power supply. Pump is complete with integral float switch, discharge check valve, pump, motor assembly and reservoir. A secondary float can be field-wired to shut down the unit upon high condensate level. The Canister Humidifier Kit can be field-installed to customize cooling only or reheat only units. The kit includes full installation instructions and are designed to be added to the evaporator unit before it is mounted on its wall or floor location. The 277V Step-Down Transformer is available for units needing 277-1-60 input power; one each for evaporator section and remote condensing section (37.5A max. each). Use one 37.5A transformer for 1-1/2 or 2-ton self-contained water/glycol systems; use 50A transformer for 3-ton self-contained water/glycol systems. Epoxy-encapsulated, transformer is suitable for either indoor or outdoor service. Pre-Charged Refrigerant Line Set (R-407C) contains an insulated copper suction line and a copper liquid line for interconnection of the indoor and outdoor sections. Available in 15-foot (4.5m) and 30-foot (9m) sections for interconnection of evaporator to remote condensing unit without brazing. Maximum recommended combined line set length is 45 ft.(13.7m). The Refrigerant-Line Sweat Adapter Kit contains two suction and two liquid line fittings that allow field-supplied refrigerant piping between the evaporator and condensing unit. A Remote Temperature and Humidity Sensor package includes sensors in an attractive case with 30 ft. (9 m) of cable. Can be wall or duct mounted. Remote sensors should be used when the wall box is not located in the space to be conditioned. NOTE Installing the remote sensors disables the sensors included in the wall box. 5 Liebert® DataMate™ Ship-Loose Accessories—Field-Installed 4.1 Remote Monitoring, Autochangeover and Leak Detection Equipment The Liebert RCM4™ is a four-point, normally open, dry contact monitoring panel. One Form-C, dry contact common alarm relay output (rated at 24 VAC, 3 Amp) is provided. Four red LEDs illuminate on the respective alarm and the alarm buzzer is silenced by a front panel switch. The RCM4 requires a 24VAC or 24VDC power source. Power supply is not included. The Liebert AC4™ Autochangeover Controller provides autochangeover and autosequence control for up to four Liebert DataMate units within a room. The Liebert AC4 will enable redundant units in an alarm condition, balance usage and test standby units at programmed intervals. Two common alarm relay outputs are available. A built-in LCD and RS-232 port for direct PC/terminal connection provides two options for configuration and monitoring of the product. The Liebert AC4 requires 24VAC input power. The Liebert AC8™ is ideal for coordinated control of systems with redundant units. The Liebert AC8 enables redundant devices during an alarm condition, balances usage of devices and tests standby devices at programmable intervals. Supports four zones and can use the 4-20mA temperature sensor (TW420) for temperature staging in each zone. Two programmable output control relays are available for auxiliary control such as humidity lockout. Emergency power operation input provided for device control during an emergency. Two common alarm relay outputs are available. A built-in LCD and RS-232 port for direct PC/terminal connection provides two options for configuration and monitoring of the product. The Liebert ENV-DO™ interface card provides 16 discrete outputs, corresponding to status and major alarm conditions of Environmental units. The Liebert ENV-DO-ENCL1 packages one Environmental DO interface card in its own steel enclosure and the ENV-DO-ENCL2 packages two Environmental DO interface cards in one enclosure for installation external to the Liebert DataMate. The self-contained kit includes an external 120VAC-to-24VAC power transformer. Wiring harnesses are not provided. Power and communication wiring is field-provided. The Liebert Liqui-tect® 410 Point Leak Detection Sensor detects the presence of conductive liquid using a pair of corrosion-resistant, gold-plated probes mounted in a painted, height-adjustable enclosure. Dual Form-C, dry contact common alarm relays (rated at 24VAC, 3A) signal a leak detected as well as loss of power and cable fault. The Liebert Liqui-tect 410 requires an external 24VAC or 24VDC power source. Liebert LT460 Zone Leak Detection Kits include one LT460 sensor, a specified length of LT500-xxY cable (maximum length is 100 ft [30.5m]) and a corresponding number of hold-down clips. The Liebert LT460 requires an external 24VAC, 0.12A power source, such as EXT-XFMR or XFMR24. Liebert SiteScan® is a monitoring solution that gives you decision-making power to effectively manage the equipment critical to your business. Liebert SiteScan enables communication from Liebert environmental and power units, as well as many other pieces of analog or digital equipment, to a front-end software package that provides real-time status and alarms so you can react quickly to changing situations. Liebert SiteScan is designed with flexibility for both small systems and large, complex systems such as those in computer rooms, telecommunications facilities or industrial process control rooms. Contact your local Emerson representative for assistance with a Liebert SiteScan system. The NIC-ENCL1 and NIC-ENCL2 packages have one or two Liebert IntelliSlot® Web/485 Cards with Adapters, respectively, in one steel enclosure. These are for installation external to the Liebert DataMate. The Liebert IntelliSlot Web/485 Card with Adapter provides communication with Liebert DataMate via SNMP, HTTP, RTU Modbus 485 and BACnet IP. The self-contained NIC-ENCL1 and NIC-ENCL2 kits include an external 120VAC-to-24VAC transformer as a power source. Wiring harnesses are not provided. Power and communication wiring is field-provided. Liebert® DataMate™ 6 Flexible Configurations 5.0 FLEXIBLE CONFIGURATIONS Figure 2 Flexible configurations—All systems Air-Cooled Systems L ie be rt ¨ ¨ Liebert OUTDOOR, AIR-COOLED CONDENSING UNIT Suitable for installation on a roof or at ground level. INDOOR AIR-COOLED CONDENSING UNIT For applications where roof or ground level locations are impractical. Water/Glycol-Cooled Systems L ie be ¨ Liebert WATER/GLYCOL-COOLED CLOSE-COUPLED A single power and water supply connection puts the unit in operation. rt ¨ WATER/GLYCOL-COOLED REMOTE Condensing unit is installed under raised floor or above dropped ceiling. Chilled Water Systems ¨ Liebert CHILLED WATER Connects to a chilled water loop for quick and easy installation. 7 Liebert® DataMate™ Air-Cooled Systems—Capacities and Dimensions 6.0 Table 1 AIR-COOLED SYSTEMS—CAPACITIES AND DIMENSIONS 60Hz capacities & typical specifications, air-cooled applications Evaporator Model DME020E PFH - Outdoor DME027E DME037E Condensing Unit Type DX Evaporator- Net Capacity Data - kW (Btuh) @ High Speed CFM 80°F DB, 62.8°F WB Total 5.50 (18,800) 7.20 (24,500) (26.7°C DB, 17.1°C Sensible 5.50 (18,800) 7.20 (24,500) WB) 38 %RH 75°F DB, 61°F WB Total 5.10 (17,400) 6.70 (22,800) (23.9°C DB, 16.1°C Sensible 5.05 (17,200) 6.65 (22,700) WB) 45 %RH MCD - Indoor PFH - Outdoor MCD - Indoor 6.90 (23,600) 10.25 (35,000) 9.70 (33,100) 6.90 (23,600) 9.95 (33,900) 9.60 (32,800) 6.45 (22,000) 9.80 (33,500) 9.25 (31,600) 6.40 (21,900) 8.90 (30,300) 8.60 (29,400) Total 72°F DB, 60°F WB (22.2°C DB, 15.5°C Sensible WB) 50 %RH Fan Data - Evaporator CFM (CMH) - High Speed CFM (CMH) - Low Speed PFH - Outdoor 4.90 (16,700) 6.40 (21,900) 6.20 (21,100) 9.60 (32,700) 9.05 (30,900) 4.70 (16,000) 6.20 (21,100) 6.05 (20,600) 8.20 (28,000) 7.95 (27,100) 870 (1478) 1230 (2090) 750 (1274) 1050 (1784) 1320 (2243) 1175(1996) Fan Motor hp (W) 0.16 (120) 0.20 (150)* 0.27 (200)** Evaporator Coil - Copper Tube/Aluminum Fin 2.44 (0.23) 3.92 (0.36) Face Area ft2 (m2) 3.92 (0.36) Coil Rows 4 3 4 Max Face Velocity-fpm (m/s) 356 (1.8) 313 (1.6) 336 (1.7) Unit Refrigerant Charge, oz. (kg) 4 (0.11) 5 (0.14) 6.5 (0.18) Unit Operating Weight, lb. (kg) 230 (104) 330 (150) 365 (165) Electric Reheat Capacities (Includes Fan Motor)-kW (Btuh) Input Voltage 230-1-60 2.7 (9215) 5.3 (18080) 5.5 (18765) Humidifier Data - Steam Generator Type Steam capacity - lb/hr (kg/hr) 3 (1.4) 3 (1.4) 3 (1.4) Electrical Input Power - kW 1 1 1 Evaporator Connection Sizes Liquid line Diameter - Aeroquip 3/8" 3/8" 3/8" Coupling Size, - #6 Female Suction Line Diameter - Aeroquip 1/2" 7/8" 7/8" Coupling Size, #11 Female Humidifier Supply, 1/4" 1/4" 1/4" OD Cu Compression Fitting Humidifier Drain, Barb Fitting 1/2" 1/2" 1/2" Evaporator Drain, Barb Fitting 3/4" 3/4" 3/4" Filter Washable Polypropylene/Aluminum, MERV4 PFH020A-_L7 PFH027A-_L7 MCD24AL_H7 PFH037A-_L7 MCD36AL_H7 Condensing Unit Model Number Condensing Unit Rating Conditions Coil Face Area ft2 (m2) Rows of Coil CFM (CMH) Motor, hp (W) External Static Pressure, in wg. (mm) Condensing Unit Refrigerant Charge, oz. (kg) Unit Operating Weight, lb. (kg) 4.1 (0.38) 2 2200 (3738) 0.20 (149) 95°F (35°C) Ambient 4.1 (0.38) 4.6 (0.43) 7.7 (0.72) 2 4 2 2200 (3738) 1000 (1699) 3000 (5097) 0.20 (149) 0.33 (246) 0.20 (149) N/A N/A 0.50 (13) N/A 4.6 (0.43) 4 1430 (2490) 0.5 (373) 0.50 (13) 134 (3.8) 134 (3.8) 134 (3.8) 213 (6.0) 213 (6.0) 200 (91) 351 (159) 449 (204) 351 (159) 449 (204) The net capacity data has fan motor heat factored in for all ratings and the entering air conditions of 75°F (23.9 °C), 45%RH, is the standard rating condition for ASHRAE 127-2007. All capacities are nominal values; actual performance will be ± 5%. * DME027 has two motors - 0.08 & 0.12 HP ** DME037 has two motors - 0.11 & 0.16 HP Liebert® DataMate™ 8 Air-Cooled Systems—Capacities and Dimensions Table 2 50Hz capacities & typical specifications, air-cooled applications DME037E Evaporator Model PFH - Outdoor MCD - Indoor Total 10.60 (36,200) 9.55 (32,600) Sensible 9.40 (32,100) 8.90 (30,400) Condensing Unit Type DX Evaporator- Net Capacity Data - kW (Btuh) @ High Speed CFM 80°F DB, 62.8°F WB (26.7°C DB, 17.1°C WB) 38 %RH 75°F DB, 61°F WB (23.9°C DB, 16.1°C WB) 45 %RH 72°F DB, 60°F WB (22.2°C DB, 15.5°C WB) 50 %RH Total 10.25 (34,900) 9.10 (31,400) Sensible 8.45 (28,800) 7.95 (27,100) Total 10.00 (34,100) 9.00 (30,700) Sensible 7.85 (26,700) 7.35 (25,100) Fan Data - Evaporator CFM (CMH) - High Speed 1100 (1869) CFM (CMH) - Low Speed 980 (1665) Fan Motor HP (W) 0.27 (200)** Face Area ft2 (m2) 3.92 (0.36) Evaporator Coil - Copper Tube/Aluminum Fin Coil Rows 4 Max Face Velocity-fpm (m/s) 336 (1.7) Unit Refrigerant Charge, oz. (kg) 6.5 (0.18) Unit Operating Weight, lb. (kg) 365 (165) Electric Reheat Capacities (Includes Fan Motor)-kW (Btuh) Input Voltage 230-1-50 5.5 (18765) Humidifier Data - Steam Generator Type Steam capacity - lb/hr (kg/hr) 3 (1.4) Electrical Input Power - kW 1 Evaporator Connection Sizes Liquid line Diameter - Aeroquip Coupling Size, #6 Female 3/8" Suction Line Diameter - Aeroquip Coupling Size, - #11 Female 7/8" Humidifier Supply, OD Cu Compression Fitting 1/4" Humidifier Drain, Barb Fitting 1/2" Evaporator Drain, Barb Fitting 3/4" Filter Washable Polypropylene/Aluminum, MERV4 PFH036A-_L7 MCD35AL_H7 7.7 (0.72) 4.6 (0.43) Rows of Coil 2 4 CFM (CMH) 2500 (4248) 1430 (2430) 0.20 (149) 0.5 (373) N/A 0.50 (13) Condensing Unit Refrigerant Charge, oz. (kg) 213 (6.0) 213 (6.0) Unit Operating Weight, lb. (kg) 351 (159) 449 (204) Condensing Unit Model Number Condensing Unit Rating Conditions Coil Face Area ft2 (m2) Motor, hp (W) External Static Pressure, in wg. (mm) The net capacity data has fan motor heat factored in for all ratings and the entering air conditions of 75°F (23.9 °C), 45%RH, is the standard rating condition for ASHRAE 127-2007. All capacities are nominal values; actual performance will be ± 5%. ** DME037 has two motors - 0.11 & 0.16 HP 9 Liebert® DataMate™ Air-Cooled Systems—Capacities and Dimensions Figure 3 General arrangement, air-cooled split systems Condenser Coil High Pressure Switch Scroll Compressor Hot Gas Bypass Solenoid Valve Liquid Injection Valve Bulb Suction Line Male Quick Connect Coupling Suction Line Female Quick Connect Coupling External Equalizer * Sensing Bulb Liquid Injection Valve s ypas as B Hot G ol Valve r Cont Liquid Line Solenoid Valve Service Access Ports Filter Drier 3 - Way Head Pressure Relief Valve 3/8" SAE 45° Male Flare Pressure Relief Valve Check Valve Sight Glass Liebert Lee-Temp Receiver * Liquid Line Male Quick Connect Coupling Liquid Line Female Quick Connect Coupling Expansion Valve Evaporator Coil * Use Liebert sweat adapter kit with field hard piping or use Liebert pre-charged line set. FIELD PIPING FACTORY PIPING Liebert® DataMate™ 10 DPN000261 REV 2 Air-Cooled Systems—Capacities and Dimensions Figure 4 Dimensions, evaporator unit Grilles are reversible to allow air direction changes as shown by the arrows Air Outlet A Removable Access Panel Shaded area indicates a recommended clearance of 34" (864mm) in front of the unit. Air Inlet 32" (813mm) Standard Refrigeration and Chilled Water Piping Opening 5/8" (16mm) FLOOR CUTOUT DIMENSIONS for Raised-Floor Piping 3-1/2" (89mm) A Cabinet Outline See Table 3 for Dimension A 1" (25mm) 10-7/8" (276mm) DPN000262 Rev. 0 Table 3 Evaporator section dimensions—air-cooled applications Model Weight lb (kg) Width - A in. (mm) Depth in. (mm) Height in. (mm) DME020E 230 (104) 46-1/2 (1181) 11-7/8 (302) 32 (813) DME027E 330 (150) 64-1/8 (1628) 11-7/8 (302) 32 (813) DME037E 365 (165) 64-1/8 (1628) 11-7/8 (302) 32 (813) Source: DPN000262, Rev. 0 Table 4 Evaporator unit refrigerant connections—pipe size/coupling number Model Liquid Line A Suction Line B DME020E 3/8" / #6 1/2" / #11 DME027E 3/8" / #6 7/8" / #11 DME037E 3/8" / #6 7/8" / #11 11 Liebert® DataMate™ Air-Cooled Systems—Capacities and Dimensions Figure 5 Cabinet and floor planning dimensions—Outdoor air-cooled condensing units Fan Rotation CCW (left side) Removable (right) panel for access to refrigeration component A Right Air Discharge Left Air Intake Shaded area indicates a minimum clearance of 18" (457mm) for proper air flow. B Shaded area indicates a recommended clearance of 24" (610mm) for component access and removal. C Shaded area indicates a minimum clearance of 18" (457mm) for proper air flow Table 5 Propeller fan, air-cooled condensing unit dimensions, inches (mm) Model Numbers 60Hz 50Hz PFH020A-L — PFH027A-L — PFH027A-H — PFHZ27A-L Removable panel for access to high-voltage and low-voltage connections and refrigeration components — PFH037A-L PFH036A-L PFH037A-H PFH036A-H PFHZ37A-L PFHZ36A-L Dimensional Data, inches (mm) A B C Module Net Weight, lb (kg) 40 (1016) 23-1/2 (597) 18 (457) 200 (91) 48 (1219) 31 (787) 18 (457) 241 (109) 53 (1343) 36 1/4 (918) 18 (457) 351 (159) Source: DPN000130, Rev. 1 Liebert® DataMate™ 12 DPN000130 Rev. 1 Air-Cooled Systems—Capacities and Dimensions Figure 6 Dimensions, indoor air-cooled condensing units Customer Supplied Threaded Rods for Module Support from Ceiling (typ. 4) 22-3/4" (578mm) Overall Dimension 50-1/4" (1276mm) Overall Dimension 21-1/2" (546mm) Cabinet Dimension 46-1/2" (1181mm) Cabinet Dimension 19-1/2" (495mm) Threaded Rod Centers 48-1/4" (1225mm) Threaded Rod Centers C 1/2" (13mm) D Air Outlet Duct Connection 20-3/4" (527mm) 22-1/2" (572mm) Cabinet Dimension 20-7/16" (519mm) Coil Inlet Duct Conn. Holes for Module Rigging (typ. 2 Integral each end) Hanging Bracket 30-1/8" (765mm) Coil Inlet Duct Connection Duct Flange 1" (25.4mm) Minimum Clearance 33" (838mm) This End for Component Access and Removal 7/8" (22.2mm) Dia. Electrical Entrance for Line Voltage Connection Air Outlet Duct Dimension B A Blower Motor Service Access Panel on Bottom of Unit Minimum Clearance 33" (838mm) for Component Access and Removal 2-1/4" (57mm) 7/8" (22.2mm) Dia. Electrical Entrance for Low-Voltage Connection Suction Line Male Quick Connect Liquid Line Male Quick Connect Table 6 DPN000206 Rev. 2 Remote centrifugal fan, air-cooled condensing, weight and dimensions Model Weight lb (kg) MC*24A MC*23A MC*35A MC*36A MC*39A MC*40A 230 (104) 230 (104) 240 (109) 240 (109) 240 (109) 240 (109) Dimensions, in (mm) A B C D 1-7/16 (37) 11-7/16 (290) 1/2 (13) 20-7/16 (519) 1-5/8 (41) 11-3/4 (298) 3/4 (19) 20-1/4 (109) Source: DPN000206, Rev. 2 13 Liebert® DataMate™ Water/Glycol Systems—Capacities and Dimensions 7.0 Table 7 WATER/GLYCOL SYSTEMS—CAPACITIES AND DIMENSIONS 60Hz capacities & typical specifications, water-cooled and glycol-cooled applications Evaporator Model DME020E WaterGlycolCooled Cooled @ High Speed CFM 5.90 (20,100) 5.15 (17,600) 5.80 (19,800) 5.15 (17,600) 5.50 (18,800) 4.80 (16,300) 5.15 (17,600) 4.75 (16,200) 5.35 (18,100) 4.60 (15,700) 4.75 (16,200) 4.35 (14,900) DME027E WaterGlycolCooled Cooled DME037E WaterGlycolCooled Cooled Condensing Unit Type DX Evaporator- Net Capacity Data - kW (Btuh) Total 7.95 (27,200) 6.75 (23,000) 11.4 (38,900) 9.65 (32,900) 80°F DB, 62.8°F WB (26.7°C DB, 17.1°C WB) 38 %RH Sensible 7.90 (27,000) 6.75 (23,000) 10.3 (35,300) 9.40 (32,100) Total 7.55 (25,800) 6.25 (21,300) 11.0 (37,400) 9.20 (31,400) 75°F DB, 61°F WB (23.9°C DB, 16.1°C WB) 45 %RH Sensible 7.10 (24,200) 6.25 (21,300) 9.20 (31,400) 8.35 (28,500) Total 7.35 (25,000) 6.00 (20,500) 10.7 (36,600) 8.95 (30,600) 72°F DB, 60°F WB (22.2°C DB, 15.5°C WB) 50 %RH Sensible 6.55 (22,300) 5.85 (19,900) 8.55 (29,100) 7.70 (26,300) Fan Data - Evaporator CFM (CMH) - High Speed 870 (1478) 1230 (2090) 1320 (2243) CFM (CMH) - Low Speed 750 (1274) 1050 (1784) 1175(1996) Fan Motor hp (W) 0.16 (120) 0.20 (150)* 0.27 (200)** Evaporator Coil - Copper Tube/Aluminum Fin 2.44 (0.23) 3.92 (0.36) 3.92 (0.36) Face Area ft2 (m2) 2.44 (0.23) Coil Rows 4 3 4 Max Face Velocity-fpm (m/s) 356 (1.8) 313 (1.6) 336 (1.7) Unit Refrigerant Charge, oz. (kg) 4 (0.11) 5 (0.14) 6.5 (0.18) Unit Operating Weight, lb. (kg) 230 (104) 330 (150) 365 (165) Electric Reheat Capacities (Includes Fan Motor)-kW (Btuh) Input Voltage 230-1-60 2.7 (9215) 5.3 (18080) 5.5 (18765) Humidifier Data - Steam Generator Type Steam capacity - lb/hr (kg/hr) 3 (1.4) 3 (1.4) 3 (1.4) Electrical Input Power - kW 1 1 1 Evaporator Connection Sizes Liquid Line Diameter - Aeroquip Coupling Size 3/8"- #6 Female 3/8" - #6 Female 3/8" - #6 Female Suction Line Diameter - Aeroquip Coupling Size 1/2" - #11 Female 7/8" - #11 Female 7/8" - #11 Female Humidifier Supply 1/4" OD Copper Compression Fitting Humidifier Drain, Barb Fitting 1/2" 1/2" 1/2" Evaporator Drain, Barb Fitting 3/4" 3/4" 3/4" Filter Washable Polypropylene/Aluminum, MERV4 DMC022WG DMC029WG DMC040WG Close-Coupled DMC Condensing Unit Model 110 (43.3) 110 (43.3) 110 (43.3) 85 (29.4) 85 (29.4) 85 (29.4) EGT - 40% EGT - 40% Condenser Fluid Requirements, °F (°C) EGT - 40% EWT EWT EWT PG PG PG THR - kW (Btuh) @ 75F/45%RH 7.30 (24,900) 7.10 (24,200) 9.60 (32,700) 9.10 (31,000) 13.9 (47,400) 13.2 (45,100) Flow Rate - GPM (l/m) 4.0 (15.2) 5.9 (22.4) 4.6 (17.4) 6.9 (26.2) 7.8 (29.6) 9.1 (34.5) 17.0 (50.8) 4.4 (13.2) 10.4 (31.1) 8.4 (25.1) 13.6 (40.7) Pressure Drop - ft. of H20 (kPa) 7.0 (20.9) Water-Cooled Condensing Temperature, °F (°C) 105 (40.6) N/A 105 (40.6) N/A 105 (40.6) N/A Water/Glycol Connection Sizes, in. (mm) OD 5/8 (15.9) 7/8 (22.2) Liquid Line Diameter - Aeroquip Coupling 3/8" - #6 Male 3/8" - #6 Male 3/8" - #6 Male Suction Line Diameter - Aeroquip Coupling 5/8" - #11 Male 5/8" - #11 Male 3/4" - #11 Male Unit Volume - Gal (l) 0.25 (0.95) 0.40 (1.5) 0.50 (1.9) Unit Refrigerant Charge, oz. (kg) 47 (1.33) 59 (1.67) 61 (1.72) Unit Operating Weight, lb. (kg) 169 (77) 169 (77) 172 (78) MCD26W MCD38W — — Remote MCD Condensing Unit Model # 110 (43.3) 110 (43.3) 85 (29.4) 85 (29.4) EGT - 40% EGT - 40% Condenser Fluid Requirements, °F (°C) N/A EWT EWT PG PG THR - kW (Btuh) @ 75F/45%RH — — 9.60 (32,700) 9.10 (31,000) 13.9 (47,400) 13.2 (45,100) Flow Rate - GPM (l/m) — — 7.7 (24.2) 8.9 (33.7) 6.5 (24.6) 12.1 (45.9) — — 16.6 (49.6) 26.0 (77.7) 11.6 (34.7) 44.7 (133.7) Pressure Drop - ft. of H20 (kPa) 105°F 105°F Water-Cooled Condensing Temperature — — N/A N/A (40.6°C) (40.6°C) Water/Glycol Connection Sizes, in. (mm) OD — — 7/8 (22.2) 7/8 (22.2) Unit Volume - Gal (l) — — 1.2 (4.5) 1.2 (4.5) Unit Refrigerant Charge, oz. (kg) — — 41 (1.16) 54 (1.54) Unit Operating Weight, lb. (kg) — — 175 (79) 220 (100) The net capacity data has fan motor heat factored in for all ratings and the entering air conditions of 75°F (23.9 °C), 45%RH, is the standard rating condition for ASHRAE 127-2007. All capacities are nominal values; actual performance will be ± 5%. * DME027 has two motors - 0.08 & 0.12 HP; ** DME037 has two motors - 0.11 & 0.16 HP Liebert® DataMate™ 14 Water/Glycol Systems—Capacities and Dimensions Table 8 50Hz capacities & typical specifications, water-cooled and glycol-cooled applications DME037E Evaporator Model Water-Cooled Glycol-Cooled Total 11.3 (38,700) 9.30 (31,800) Sensible 9.55 (32,600) 8.60 (29,300) Total 11.0 (37,400) 8.95 (30,500) Sensible 8.55 (29,200) 7.60 (26,000) Total 10.7 (36,600) 8.75 (29,900) Sensible 7.95 (27,200) 7.05 (24,000) Condensing Unit Type DX Evaporator- Net Capacity Data - kW (Btuh) @ High Speed CFM 80°F DB, 62.8°F WB (26.7°C DB, 17.1°C WB) 38 %RH 75°F DB, 61°F WB (23.9°C DB, 16.1°C WB) 45 %RH 72°F DB, 60°F WB (22.2°C DB, 15.5°C WB) 50 %RH Fan Data - Evaporator CFM (CMH) - High Speed 1100 (1869) CFM (CMH) - Low Speed 980 (1665) Fan Motor HP (W) 0.27 (200)** Face Area ft2 (m2) 3.92 (0.36) Evaporator Coil - Copper Tube/Aluminum Fin Coil Rows 4 Max Face Velocity-fpm (m/s) 336 (1.7) Unit Refrigerant Charge, oz. (kg) 6.5 (0.18) Unit Operating Weight, lb. (kg) 365 (165) Electric Reheat Capacities (Includes Fan Motor)-kW (Btu/H) Input Voltage 230-1-50 5.5 (18765) Humidifier Data - Steam Generator Type Steam capacity - lb/hr (kg/hr) 3 (1.4) Electrical Input Power - kW 1 Evaporator Connection Sizes Liquid Line Diameter - Aeroquip Coupling Size 3/8" - #6 Female Suction Line Diameter - Aeroquip Coupling Size 7/8" - #11 Female Humidifier Supply 1/4" OD Cu Compression Fitting Humidifier Drain, Barb Fitting 1/2" Evaporator Drain, Barb Fitting 3/4" Filter Washable Polypropylene/Aluminum, MERV4 MCD37W Remote MCD Condensing Unit Model # Condenser Fluid Requirements 85°F (29.4°C) EWT 110°F (43.3°C) EGT - 40% PG THR - kW (Btuh) @ 75F/45%RH 13.7 (46,700) 12.9 (44,000) 6.4 (24.3) 13.5 (51.2) 11.7 (35.0) 55.8 (166.8) 105 °F (40.6 °C) N/A Flow Rate - GPM (l/m) Pressure Drop - ft. of H20 (kPa) Water-Cooled Condensing Temperature Water/Glycol Connection Sizes, in. (mm) OD 7/8 (22.2) Unit Volume - Gal (l) 1.2 (4.5) Unit Refrigerant Charge, oz. (kg) 54 (1.54) Unit Operating Weight, lb. (kg) 220 (100) The net capacity data has fan motor heat factored in for all ratings and the entering air conditions of 75°F (23.9 °C), 45%RH, is the standard rating condition for ASHRAE 127-2007. All capacities are nominal values; actual performance will be ± 5%. ** DME037 has two motors - 0.11 & 0.16 hp 15 Liebert® DataMate™ Water/Glycol Systems—Capacities and Dimensions Figure 7 General arrangement, water/glycol, split systems High Pressure Scroll Compressor Switch Liquid Injection Valve Bulb Tube-in-Tube Condenser Hot Gas Bypass Solenoid Valve Suction Line Male Quick Connect Coupling Tube-in-Tube Condenser Suction Line Female Quick Hot Gas Bypass Water/Glycol * Connect Coupling Control Return Line Sensing Valve External Water/Glycol Bulb Liquid Fluid Return Equalizer Supply Line Injection From Unit Valve Shutoff ** Valve Fluid Service Access Supply Ports Liquid Line Shutoff ** To Unit Male Quick Filter * Valve 2 - Way Water Connect Dryer Regulating Valve Liquid Line Coupling Hose Bibs ** Female Quick Connect Expansion Coupling Valve Fluid Return FIELD PIPING From Unit FACTORY PIPING Evaporator Coil Figure 8 * Use Liebert sweat adapter kit with field hard piping or use Liebert pre-charged line set. ** Components are not supplied by Liebert but are required for proper circuit operation and maintenance. Fluid Supply To Unit 3 - Way Water Regulating Valve (Optional) DPN000260 Rev. 3 General arrangement, water/glycol systems, close-coupled condensing unit Field-Connected Service Access Ports Sensing Bulb Suction Line Female Quick Connect Coupling Scroll Compressor Suction Line Male Quick Connect Coupling Brazed Plate Condenser Water Supply Line Water Fluid Supply Return To Unit Line Liquid Line Male Quick Connect Coupling Shutoff * Valves External Evaporator Equalizer Coil High Pressure Switch Liquid Line Female Quick Hose* Connect Coupling Bibs Filter Dryer Fluid Return From Unit 2-Way Water Regulating Valve FIELD PIPING FACTORY PIPING Expansion Valve * Components are not supplied by Liebert but are required for proper DPN000259 circuit operation and maintenance Rev. 3 Liebert® DataMate™ 16 Water/Glycol Systems—Capacities and Dimensions Figure 9 Dimensions, evaporator unit Grilles are reversible to allow air direction changes as shown by the arrows Air Outlet A Removable Access Panel Shaded area indicates a recommended clearance of 34" (864mm) in front of the unit. Air Inlet 32" (813mm) Standard Refrigeration and Chilled Water Piping Opening 5/8" (16mm) FLOOR CUTOUT DIMENSIONS for Raised-Floor Piping 3-1/2" (89mm) A Cabinet Outline See Table 9 for Dimension A Table 9 1" (25mm) DPN000262 Rev. 0 Evaporator section dimensions—water/ glycol-cooled applications Width - A Depth Height Model Weight lb (kg) DME020E 230 (104) 46-1/2 (1181) 11-7/8 (302) 32 (813) DME027E 330 (150) 64-1/8 (1628) 11-7/8 (302) 32 (813) DME037E 365 (165) 64-1/8 (1628) 11-7/8 (302) 32 (813) Table 10 10-7/8" (276mm) in. (mm) in. (mm) in. (mm) Evaporator unit refrigerant connections—pipe size/coupling number Model Liquid Line A Suction Line B DME020E 3/8" / #6 1/2" / #11 DME027E 3/8" / #6 7/8" / #11 DME037E 3/8" / #6 7/8" / #11 17 Liebert® DataMate™ Water/Glycol Systems—Capacities and Dimensions Figure 10 Dimensions and piping, close-coupled water/glycol condensing unit el an ) P ss able ce Ac mov e (R 14" (356mm) Floor Liebert DataMate Evaporator 32" (813mm) Access Panel (Removable) Condensing Unit Access Panel (Removable) 12" (305mm) Unit Dimensions Shaded area indicates a recommended clearance of 34" (864mm) in front of the unit and 12" (305mm) on the left side for component access and removal. Minimum clearance is 1" (25mm) on left side and 18" (457mm) in front. Removable Panels Outline of Evaporator Module Piping Access Plate in Evaporator End Panel B - Suction Refrigerant Line Quick Connect Male Coupling Piping and Electrical Knockouts Located on Bottom and on Back of Unit C - Supply Entering Condenser Water/glycol A - Liquid Refrigerant Line Quick Connect Male Coupling D - Return Leaving Condenser Water/Glycol Piping and Electrical Knockouts Located on Bottom and on Back of Unit Liebert® DataMate™ Note: Do Not remove evaporator end panel from panel assembly when installing internal water/glycol condensing unit DPN000270 Rev. 2 18 14" (356mm) DPN000269 Rev. 0 Water/Glycol Systems—Capacities and Dimensions Table 11 Net weight, water/glycol condensing units Model Tons Weight DMC022WG 1-1/2 170lb (77kg) DMC029WG 2 170lb (77kg) DMC040WG 3 170lb (77kg) Source: DPN000269, Rev. 0 Table 12 Unit refrigerant connection sizes Unit Refrigerant Connections Internal Pipe Size/ Coupling No. Water/Glycol Piping Connection Sizes O.D. Cu Model Liquid Line A Suction Line B Supply C Return D DMC022WG 3/8 / #6 5/8 / #11 5/8 5/8 DMC029WG 3/8 / #6 5/8 / #11 7/8 7/8 DMC040WG 3/8 / #6 3/4 / #11 7/8 7/8 Source: DPN000270, Rev. 2 19 Liebert® DataMate™ Water/Glycol Systems—Capacities and Dimensions Figure 11 Cabinet dimensions and piping data, water/glycol indoor remote condensing modules 14" (356mm) Overall Cabinet Dimension 8-7/8" (225mm) 50-1/4" (1276mm) Overall Dimension 3-7/8" (98mm) 48-1/4" (1225mm) Threaded Rod Centers 181mm) 46-1/2" (1 ension Cabinet Dim 8-7/16" (214mm) 12" (305mm) Threaded Rod Centers 20-3/4" (527mm) 22-1/2" (572mm) Cabinet Dimension Customer Supplied Threaded Rods for Module Support from Ceiling (typ. 4) Outlet Inlet Holes for Module Rigging (typ. 2 each end) Note: Unit is Spaced Evenly in Reference to Threaded Rod Centers Integral Hanging Bracket Minimum Clearance 33" (838mm) This Side for Component Access and Removal DIMENSIONAL DATA 7/8" (22.2mm) OD CU Water/Glycol Outlet Connection Extends 3-1/2" (88.9mm) beyond panel exterior 7/8" (22mm) Dia. 7/8" (22.2mm) OD CU Electrical Entrance Water/Glycol Inlet Connection for High Voltage Extends 3-1/2" (88.9mm) Connection beyond panel exterior Suction Line Male Quick Connect Liquid Line Male Quick Connect 7/8" (22mm) Dia. Electrical Entrance for Low-Voltage Connection Table 13 PIPING CONNECTIONS Net weight, indoor water/glycol-cooled condensing unit Model Numbers 60Hz 50Hz Weight lb (kg) MC*26W — 175 (79) MC*38W MC*37W 220 (100) Source: DPN000208, Rev. 4 Liebert® DataMate™ 20 DPN000208 Rev. 4 Chilled Water Systems 8.0 CHILLED WATER SYSTEMS Table 14 Chilled water data, 50/60Hz DME044C 208/230-1-60 CW Model, 60 Hz 200/220-1-50 Net Capacity Data - kW (Btuh) based on 45°F (7.2°C) EWT & 10°F (5.6°C) temperature rise 80°F DB, 62.8°F WB (26.7°C DB, 17.1°C WB) 38 %RH Total 10.5 (35,800) 9.05 (30,900) Sensible 9.65 (33,000) 8.25 (28,200) 7.3 (27.7) 6.3 (23.9) Flow Rate, GPM (l/m) Pressure Drop, ft. water (kPa) 75°F DB, 61°F WB (23.9°C DB, 16.1°C WB) 45 %RH 12.5 (37.4) 9.7 (29.0) Total 8.75 (29,800) 7.55 (25,800) Sensible 7.95 (27,100) 6.85 (23,300) Flow Rate, GPM (l/m) 6.1 (23.1) 5.3 (20.1) Pressure Drop, ft. water (kPa) 9.1 (27.2) 7.0 (20.9) Total 7.65 (26,100) 6.6 (22,600) Sensible 6.90 (23,500) 5.9 (20,200) Flow Rate, GPM (l/m) 5.3 (20.1) 4.6 (17.4) Pressure Drop, ft. water (kPa) 7.2 (21.5) 5.6 (16.7) CFM (CMH) - High Speed 1320 (2243) 1100 (1869) CFM (CMH) - Low Speed 1175 (1996) 980 (1665) Fan Motor, hp (W) 0.27 (200)** 0.27 (200) 72°F DB, 60°F WB (22.2°C DB, 15.5°C WB) 50 %RH Fan Data - Evaporator CW Coil - Copper Tube/Aluminum Fin Face Area, ft2 (m2) 3.92 (0.36) Coil Rows Max Face Velocity-fpm (m/s) Electric Reheat Capacity (Includes Fan Motor), kW (Btuh) Input Voltage 230-1-60/50 3 336 (1.7) 281 (1.4) 5.5 (18,765) Humidifier Data - Steam Generator Type Steam capacity, lb/hr (kg/hr) Electrical Input Power, kW 3 (1.4) 1 Unit Connection Sizes CW supply and return connections, in (mm) OD Humidifier Supply Humidifier Drain, Barb Fitting Evaporator/Condensate Drain, Barb Fitting Unit Internal Fluid Volume, gal (l) Filter Unit Operating Weight, lb. (kg.) Unit Valve Types 7/8 (22.2) 1/4" OD Copper Compression Fitting 1/2" 3/4" 1.0 (3.8) Washable Polypropylene/Aluminum, MERV4 365 (165) On/Off Slow Close, 2-Way Valve Size Valve Cv Max. Water Static Operating Pressure, psi (kPa) Close-Off Pressure, psi (kPa) 3/4" 7 300 (2068) 60 (414) The net capacity data has fan motor heat factored in for all ratings and the entering air conditions of 75°F (23.9 °C), 45%RH, is the standard rating condition for ASHRAE 127-2007. All capacities are nominal values; actual performance will be ± 5%. ** DME044C has two motors - 0.11 & 0.16 HP 21 Liebert® DataMate™ Chilled Water Systems Table 15 Chilled water capacity correction factors based on 10°F (5.6°C) water rise 72°F (22.2°C) 50% 75°F (23.9°C) 45%RH EWT TCC SCC TCC SCC 42°F (5.6°C) 1.27 1.14 1.23 1.11 43°F (6.1°C) 1.17 1.09 1.15 1.07 44°F (6.7°C) 1.08 1.04 1.07 1.04 45°F (7.2°C) 1.00 1.00 1.00 1.00 46°F (7.8°C) 0.93 0.96 0.94 0.96 47°F (8.3°C) 0.86 0.92 0.88 0.93 48°F (8.9°C) 0.79 0.88 0.82 0.89 49°F (9.4°C) 0.74 0.83 0.77 0.85 Figure 12 General arrangement—Chilled water systems Bleed Valve Chilled Water Return Chilled Water Supply Chilled Water Control Valve Chilled Water Coil Shutoff * Valves Hose* Bibs Liebert® DataMate™ FIELD PIPING FACTORY PIPING * Components are not supplied by Liebert but are required for proper circuit operation and maintenance 22 DPN000259 Rev. 3 Chilled Water Systems Figure 13 Dimensions—Chilled water unit Grilles are reversible to allow air direction changes as shown by the arrows Air Outlet A Removable Access Panel Shaded area indicates a recommended clearance of 34" (864mm) in front of the unit. Air Inlet 32" (813mm) Standard Refrigeration and Chilled Water Piping Opening 5/8" (16mm) FLOOR CUTOUT DIMENSIONS for Raised-Floor Piping 3-1/2" (89mm) A Cabinet Outline 1" (25mm) Table 16 Model DME044C 10-7/8" (276mm) DPN000262 Rev. 0 Net weights and dimensions, chilled water units Dimensions W x D x H, in (mm) Weight lb (kg) Water Connection Sizes 64-1/8 x 11-7/8 x 32 (1628 x 302 x 813) 364 (165) 7/8" (22.2mm) OD Cu Source: DPN000262, Rev. 0 23 Liebert® DataMate™ Electrical Data—All Units 9.0 ELECTRICAL DATA—ALL UNITS Table 17 Electrical data, split system evaporator or chilled water unit, 60/50Hz 208/230V-1ph-60Hz Base Evaporator/ Chilled Water DME020E DME027E 200/220V-1-50 DME037E DME044C DME020E DME027E DME037E DME044C Cooling Only FLA 1.4 1.5 2.2 1.4 1.5 2.2 WSA 1.8 1.9 2.8 — — — OPD 15 15 15 — — — With Reheat FLA 11.8 22.3 23.0 11.8 22.3 23.0 WSA 14.8 27.9 28.8 — — — OPD 15 30 30 — — — With Reheat & Humidifier Table 18 FLA 18.8 29.3 30.0 18.8 29.3 30.0 WSA 23.5 36.6 37.5 — — — OPD 25 40 40 — — — 60Hz electrical data, evaporator with close-coupled water/glycol condensing unit with common power feed 1.5 2 3 Evaporator Model DME020E DME027E DME037E Condensing Model DMC022WG DMC029WG DMC040WG 208/230-1-60 208/230-1-60 208/230-1-60 FLA 12.1 13.5 19.3 WSA 14.8 16.5 23.6 OPD 25 25 40 Nominal Capacity, Tons Volt-Ph-Hz Cooling Only With Reheat or With Reheat & Humidifier Liebert® DataMate™ FLA 22.5 34.3 40.1 WSA 27.8 42.5 49.6 OPD 35 45 60 24 Electrical Data—All Units Table 19 60Hz electrical data, outdoor air-cooled condensing unit 1.5 Nom. Capacity, Tons 2 3 3 3 3 PFH037A-PL7 PFH037A-YL7 PFH037A-AL7 PFH037A-BL7 Standard 95°F (35°C) Propeller Fan Condensing Unit Model PFH020A-PL7 PFH027A-PL7 Volt-Ph-Hz 208/230-1-60 208/230-1-60 208/230-1-60 208/230-3-60 460-3-60 575-3-60 FLA 12.1 13.4 18.5 13.4 7.1 5.8 WSA 14.8 16.4 22.8 16.4 8.7 7.0 OPD 25 25 35 25 15 15 High Ambient Propeller Fan Condensing Unit Model N/A PFH027A-PH7 PFH037A-PH7 PFH037A-YH7 PFH037A-AH7 PFH037A-BH7 Volt-Ph-Hz N/A 208/230-1-60 208/230-1-60 208/230-3-60 460-3-60 575-3-60 FLA N/A 15.4 20.5 15.4 8.1 5.8 WSA N/A 18.4 24.8 18.4 9.7 7.0 OPD N/A 30 40 30 15 15 Quiet-Line Propeller Fan Condensing Unit Table 20 Model N/A PFHZ27A-PL7 PFHZ37A-PL7 PFHZ37A-YL7 PFHZ37A-AL7 — Volt-Ph-Hz N/A 208/230-1-60 208/230-1-60 208/230-3-60 460-3-60 — FLA N/A 12.9 18.0 12.9 7.1 — WSA N/A 15.9 22.3 15.9 8.7 — OPD N/A 25 40 30 15 — 50Hz electrical data, outdoor air-cooled condensing unit 3 Nominal Capacity, Tons 3 Standard 95°F (35°C) Propeller Fan Condensing Unit Model Volt-Ph-Hz FLA PFH036A-SL7 PFH036A-ML7 220-1-50 380/415-3-50 18.4 7.0 High Ambient Propeller Fan Condensing Unit Model Volt-Ph-Hz FLA PFH036A-SH7 PFH036A-MH7 220-1-50 380/415-3-50 20.5 8.1 Quiet-Line Propeller Fan Condensing Unit Model Volt-Ph-Hz FLA PFHZ36A-SL7 PFHZ36A-ML7 220-1-50 380/415-3-50 18.0 6.9 25 Liebert® DataMate™ Electrical Data—All Units Table 21 Electrical data, indoor air & water/glycol remote condensing units, 50 & 60Hz 60 Hz Model 208/230-1ph-60Hz 277-1ph-60Hz 50 Hz 208/230-3ph-60Hz 460-3ph-60Hz 220-1ph-50Hz 380/415-3ph-50Hz MC*24A MC*24A — — — — FLA 14.3 12.7 — — — — WSA 17.3 15.3 — — — — OPD 25 25 — — — — MC*36A MC*36A MC*36A MC*36A MC*35A MC*35A FLA 20.8 16.6 15.7 7.8 20.1 7.8 WSA 25.1 20.2 18.7 9.4 — — OPD 40 30 30 15 — — MC*26W MC*26W — — — — FLA 12.0 10.4 — — — — WSA 15.0 13.0 — — — — OPD 25 20 — — — — MC*38W MC*38W MC*38W MC*38W MC*37W MC*37W FLA 17.1 14.3 12.0 6.4 17.1 6.4 WSA 21.4 17.9 15.0 8.0 — — OPD 35 30 25 15 — — * Specify disconnect or no disconnect Figure 14 Step-down transformer for 277V input power applications .31" (8mm) Dia. For rigid mounting and shipping purposes .281" (7mm) Dia. For wall-mounting purposes 1D18214P1 10.3" (262mm) 1D18214P2 11.68" (297mm) 1/4-20 (2 screws & lock washers) use for rigid mounting and shipping purposes Remove screws & attach bracket 5.5" (140mm) 4.92" (125mm) Access to electrical connections from bottom RIGID MOUNTING WALL MOUNTING Notes: 1. 1D18214P1 = Acme catalog no. T-1-37921 for all small systems except 3-ton Liebert DataMate with integral condenser. 2. 1D18214P2 = Acme catalog no. T-1-37922 for 3-ton DataMate with integral condenser. 3. Epoxy encapsulated. Suitable for indoor/outdoor service. Horizontal or vertical mount. DPN000647 Totally enclosed, non-ventilated. Rev0 4. Both brackets are shipped loose with transformer. Liebert® DataMate™ 26 Refrigerant Piping 10.0 REFRIGERANT PIPING Table 22 Refrigerant charge 60 Hz 50 Hz Charge R-407C, oz (kg) DME020E — 4 (0.11) DME027E — 5 (0.14) DME037E DME037E 6.5 (0.18) MC*24AL_H7 — 134 (3.80) MC*36AL_H7 MC*35AL_H7 213 (6.04) MC*26W__H7 — 41 (1.16) MC*38W__H7 MC*37W__H7 54 (1.54) DMC022WG — 47 (1.33) DMC029WG — 59 (1.67) DMC040WG — 61 (1.72) PFH020A-_L7 — 134 (3.80) PFH027A-_L7 — 134 (3.80) PFH027A-_H7 — 213 (6.04) PFHZ27A-_L7 — 213 (6.04) PFH037A-_L7 PFH036A-_L7 213 (6.04) PFH037A-_H7 PFH036A-_H7 426 (12.08) PFHZ37A-_L7 PFHZ36A-_L7 426 (12.08) Table 23 Recommended refrigerant line sizes 1.5-Ton 2-Ton 3-Ton Equivalent Length, ft (m) Suction Liquid Suction Liquid Suction Liquid 50 (15.2) 5/8" 3/8" 7/8" 3/8" 7/8" 3/8" 1/2" 1-1/8" 2 1/2" 1/2" 2 1/2" 100 (30.5) 150 (45.7) 7/8" 3/8" 7/8" 7/8" 1/2" 7/8" 1-1/8" 1. Suction line and liquid line sizing based on < 3 psi pressure drop in each and horizontal suction line refrigerant velocities >700FPM (3.6m/s). 2. Suction sizes should be reduced one pipe size for vertical riser sections to maintain suction line velocity > 1000FPM (5.1m/s) for proper oil return. Table 24 Pipe length and condenser elevation relative to evaporator Nominal System Size Tons Max. Equiv. Pipe Length ft. (m) Maximum PFH Level Above Evaporator, ft. (m) Maximum PFH Level Below Evaporator, ft. (m) 1.5 & 2 150 (45) 40 (12) 15 (4.6) 3 150 (45) 50 (15) 15 (4.6) Maximum recommended total equivalent pipe length is 150 ft (46m). Suction and liquid lines may require additional specialty items when vertical lines exceed 20 ft. (6m) and/or condensing unit installation is more than 15 ft. (4.6m) below the evaporator. Contact Emerson Application Engineering for assistance. Table 25 Refrigerant charge in Liebert pre-charged R-407C line sets Line Size, in. 3/8 liquid 5/8 or 7/8 suction Length, ft. (m) Charge R-407C, oz (kg) 15 (4.5) 5 (0.14) 30 (9) 10 (0.28) 15 (4.5) 5 (0.14) 30 (9) 10 (0.28) 27 Liebert® DataMate™ Refrigerant Piping Table 26 Line charges - refrigerant per 100 ft. (30m) of Type L copper tube R-407C, lb/100 ft. (kg/30m) Line Size, O.D., in. Liquid Line Suction Line 3/8 3.7 (1.7) — 1/2 6.9 (3.1) — 5/8 11.0 (5.0) 0.4 (0.2) 3/4 15.7 (7.1) 0.6 (0.3) 7/8 23.0 (10.4) 1.0 (0.4) 1-1/8 — 1.7 (0.7) 1-3/8 — 2.7 (1.1) Figure 15 Refrigerant piping diagram Pitch down 1/2" (13mm) per 10 ft. (3m) NOTE When installing remote condensing units below the evaporator, the suction gas line should be trapped with an inverted trap to the height of the evaporator . This prevents refrigerant migration to the compressors during off cycles . Maximum recommended vertical level drop to condensing unit is 15 ft. (4.6m) . Evaporator Suction Line Piping Condensing Unit Below Evaporator Condensing Unit See Table 24 for recommended maximum vertical rise above evaporator/maximum vertical fall below evaporator. Condensing Unit Evaporator Suction Line Piping Condensing Unit Above Evaporator Traps recommended at the base of riser exceeding 5 ft (1.5m) and every 20 feet (6m) of vertical rise. Pitch down 1/2" (13mm) per 10 ft. (3m) Table 27 Equivalent lengths for various pipe fittings, ft (m) Copper Pipe OD, in. 90 Degree Elbow Copper 90 Degree Elbow Cast 45 Degree Elbow Tee Gate Valve Globe Valve Angle Valve 1/2 0.8 (0.24) 1.3 (0.39) 0.4 (0.12) 2.5 (0.76) 0.26 (0.07) 7.0 (2.13) 4.0 (1.21) 5/8 0.9 (0.27) 1.4 (0.42) 0.5 (0.15) 2.5 (0.76) 0.28 (0.08) 9.5 (2.89) 5.0 (1.52) 3/4 1.0 (0.3) 1.5 (0.45) 0.6 (0.18) 2.5 (0.76) 0.3 (0.09) 12.0 (3.65) 6.5 (1.98) 7/8 1.45 (0.44) 1.8 (0.54) 0.8 (0.24) 3.6 (1.09) 0.36 (0.1) 17.2 (5.24) 9.5 (2.89) 1-1/8 1.85 (0.56) 2.2 (0.67) 1.0 (0.3) 4.6 (1.4) 0.48 (0.14) 22.5 (6.85) 12.0 (3.65) 1-3/8 2.4 (0.73) 2.9 (0.88) 1.3 (0.39) 6.4 (1.95) 0.65 (0.19) 32.0 (9.75) 16.0 (4.87) 1-5/8 2.9 (0.88) 3.5 (1.06) 1.6 (0.48) 7.2 (2.19) 0.72 (0.21) 36.0 (10.97) 19.5 (5.94) Refrigerant trap = Four times equivalent length of pipe per this table Liebert® DataMate™ 28 Glycol Loop Piping 11.0 GLYCOL LOOP PIPING Contact Emerson Application Engineering for assistance in choosing correct drycooler models. Refer to Figure 16. Figure 16 Heat rejection loop, multiple drycoolers and multiple indoor units Expansion Tank ______ Gal. (L) HP GPM (l/s) ft. ____(kW) ____ Per Pump @ ____(kPa) FS PUMP PACKAGE Drycooler No. 1 Model ______ GPM (l/s) ____ P: ___ ft (kPa) See Note 3 Cooling Unit # Model GPM (l/s) P ft (kPa): Cooling Unit # Model GPM (l/s) P ft (kPa): Cooling Unit # Model GPM (l/s) P ft (kPa): Drycooler No. 2 Model ______ GPM (l/s) ____ P: ___ ft (kPa) Cooling Unit # Model GPM (l/s) P ft (kPa): LEGEND Gate Valve Check Valve Butterfly Valve Relief Valve Union Ball or Flow Control Valve FS P: Cooling Unit # Model GPM (l/s) P ft (kPa): Cooling Unit # Model GPM (l/s) P ft (kPa): Flow Switch Pressure Drop Strainer/Filter Notes: 1. Pressure and temperature gauges (or ports for same) are recommended to monitor component pressure drops and performance. 2. Flow measuring devices, drain and balancing valves to be supplied by others and located as required. 3. See product literature for installation guidelines and clearance dimensions. 4. Drawing shows dual pump package. Alternate pump packages with more pumps may be considered; consult supplier 29 Total GPM (L/s): _____ Pipe Diam.: _____ In. (mm) P: _____ Ft. (kPa) Cooling Unit # Model GPM (l/s) P ft (kPa): Cooling Unit # Model GPM (l/s) P ft (kPa): Cooling Unit # Model GPM (l/s) P ft (kPa): Cooling Unit # Model GPM (l/s) P ft (kPa): Cooling Unit # Model GPM (l/s) P ft (kPa): Cooling Unit # Model GPM (l/s) P ft (kPa): DPN000991 Rev. 0 Liebert® DataMate™ Model Number Nomenclature—All Systems 12.0 MODEL NUMBER NOMENCLATURE—ALL SYSTEMS Figure 17 Model number nomenclature—Evaporator units DME 037 E DME = Liebert DataMate Evaporator Unit P H 7 E = Evaporator C = Chilled Water H = With Humidifier & Reheat 0 = Reheat Only C = Cooling Only P = 208/230 1ph, 60Hz 7 = R-407C Refrigerant W = 200/220, 1ph, 50Hz Nominal capacity (kBtuh) Figure 18 Model number nomenclature—Outdoor air-cooled condensing units PFH 0 PFH = Prop Fan Condensing Unit with Hot Gas Bypass 37 A — Nominal Capacity (kBtuh) 0= Std. Sound Level Z= Quiet-Line P - = Std. Coil C = Coated Coil A = Air-Cooled L = 95 F Ambient. H = 105 F Ambient R-407C Refrigerant P=208/230/1/60 Y=208/2303/60 A=460/3/60 B=575/3/60 S=220-1-50 M=380/415/3/50 * Not all combinations are possible. 7 L Figure 19 Model number nomenclature—Indoor air-cooled condensing units Supply Power P = 208/230V - 1 ph - 60 Hz X = 277V - 1 ph - 60 Hz S = 220V - 1 ph - 50 Hz A = 460V - 3 ph - 60 Hz (3-ton only) Y = 208/230V - 3 ph - 60 Hz (3-ton only) M = 380/415V - 3ph - 50Hz MC = Liebert Mini-Mate2 Style Indoor Condensing Units D = Disconnect Switch 0 = No Disconnect Switch Nominal Capacity 24 = 2-ton, 60Hz 35 = 3-ton, 50Hz 36 = 3-ton, 60Hz Refrigerant 7 = R-407C Cooling Method A = Air-Cooled MC D 36 A L Head Pressure Controls L = Liebert Lee-Temp™ Receiver Liebert® DataMate™ 30 A H 7 H = Hot Gas Bypass Model Number Nomenclature—All Systems Figure 20 Model number nomenclature, close-coupled water/glycol condensing units—60Hz only Liebert DataMate Evaporator Section Nominal Capacity (kBtuh) WG = Water/Glycol P = 208/230/1/60 DMC 040 WG P 07 07 = R-407C Refrigerant Figure 21 Model number nomenclature—Indoor remote water/glycol-cooled condensing units Nominal Capacity 26 = 2-ton, 60Hz 37 = 3-ton, 50Hz 38 = 3-ton, 60Hz MC = Liebert Mini-Mate2 Style Indoor Condensing Units D = Disconnect Switch 0 = No Disconnect Switch MC D Cooling Method W = Water/Glycol 38 W 2 Supply Power P = 208/230V - 1 ph - 60 Hz X = 277V - 1ph - 60 Hz S = 220V - 1ph - 50 Hz A = 460V - 3ph - 60 Hz (3-ton only) Y = 208/230V - 3ph - 60 Hz (3-ton only) M = 380/415V – 3ph-50Hz A H Head Pressure Controls 2 = 2-Way Standard Pressure Water Reg Valve 3 = 3-Way Standard Pressure Water Reg Valve D = 2-Way High-Pressure Water Reg Valve T = 3-Way High-Pressure Water Reg Valve 7 Refrigerant 7 = R-407C H = Hot Gas Bypass Figure 22 Model number nomenclature—Chilled water units Liebert DataMate Cooling Unit Nominal Capacity (kBtuh) C— = Chilled Water P = 208/230/1/60 W = 200/220/1/50 DME 044 C— P H = With Humidifier and Reheat 0 = Reheat only C = Cooling only (no RH or HUM) 31 H 7 7 = Unit Revision Level Liebert® DataMate™ Guide Specifications—For Liebert DataMate 1.5- to 3-Ton (5 to 10.5kW) GUIDE SPECIFICATIONS—FOR LIEBERT DATAMATE 1.5- TO 3-TON (5 TO 10.5KW) 1.0 GENERAL 1.1 Summary These specifications describe requirements for an environmental control system. The system shall be designed to maintain temperature and relative humidity conditions within the room. The manufacturer shall design and furnish all equipment to be fully compatible with heat dissipation requirements of the site. System shall be supplied with CSA Certification to the harmonized U.S. and Canadian product safety standard CSA C22.2 No 236/UL 1995 for “Heating and Cooling Equipment” and marked with the CSA c-us logo (60 Hz only). 1.2 Design Requirements The environmental control system shall be a Liebert DataMate factory assembled unit. The refrigeration system shall be split, with the compressor located in a remote or close-coupled condensing unit. The evaporator section shall be specifically designed for floor or wall-mounted installation and serviceable from the front of the system. Condensing units shall be designed for outdoor or indoor mounting, below the raised floor, above-dropped-ceiling, or in room installation. Refer to Section 2.3 on page 35 and 36 for condensing unit guide specifications. Each system shall be capable of delivering ______ CFM. The circulating-air fan shall be two-speed for precise dehumidification control. The fan motor(s) shall total ______hp (kW). The system shall be designed for blow-through air arrangement. The system shall have a total cooling capacity of ______ Btu/hr (kW), and a sensible cooling capacity of _____ Btu/hr (kW), based on the entering air condition of ____ °F (°C) dry bulb, and ____ °F (°C) wet bulb. These units are to be supplied with ____ Volt, ____ PH, ____ Hz power supply. 1.3 Submittals Submittals shall be provided with the proposal and shall include: Single-Line Diagrams; Dimensional, Electrical, and Capacity data: Piping and Electrical Connection Drawings. 1.4 Quality Assurance The specified system shall be factory-tested before shipment. Testing shall include, but shall not be limited to: Quality Control Checks, “HiPot” Test (two times rated voltage plus 1000 volts, per NRTL agency requirements), and Metering Calibration Tests. The system shall be designed and manufactured according to world class quality standards. The manufacturer shall be ISO 9001 certified. 2.0 PRODUCT 2.1 Standard Features/All Systems 2.1.1 Evaporator Cabinet and Frame Construction The cabinet and chassis shall be constructed of heavy gauge, painted furniture steel. The cabinet shall be designed for easy installation and service access from the front only. 2.1.2 Air Distribution The air distribution system shall be constructed with a quiet, direct-drive fan assembly equipped with multiple double-inlet blowers, self-aligning sleeve bearings and lifetime lubrication. Fan motor(s) shall be permanent-split capacitor, high efficiency type, equipped with two speeds for air flow modulation. Dehumidification shall utilize the lower fan speed. Air filter shall be a cleanable polypropylene monofilament type over expanded aluminum with aluminum frame with a MERV 4 rating based on ASHRAE 52.2-2007. It shall be easily removable from the front of the system by means of quarter-turn fasteners and shall not require system shutdown for service. Liebert® DataMate™ 32 Guide Specifications—For Liebert DataMate 1.5- to 3-Ton (5 to 10.5kW) 2.1.3 Microprocessor Control System The control system shall be microprocessor-based, factory-wired into the system and tested prior to shipment. The wall-mounted control enclosure shall include a 2-line by 16-character LCD providing continuous display of operating status and alarm condition. An 8-key membrane keypad for setpoint/ program control, fan speed selection and unit On/Off shall be located below the display. The control display shall be field-wired to the control board using 4-conductor field-supplied thermostat wire. Temperature and humidity sensors shall be located in the wall box, which shall be capable of being located up to 300 ft (91.4m) from the evaporator unit. 2.1.3.1 Monitoring The LCD shall provide On/Off indication, operating mode indication (cooling, heating, humidifying, dehumidifying), fan speed indication and current day, time, temperature and humidity (if applicable) indication. The monitoring system shall be capable of relaying unit operating parameters and alarms to the Liebert SiteScan® monitoring system. 2.1.3.2 • • • • Control Setpoint Parameters Temperature Setpoint: 65-85°F (18 to 29°C) Temperature Sensitivity: 1 to 9.9°F (1 to 5°C) Humidity Setpoint: 20-80% RH Humidity Sensitivity: 1 to 30% RH The microprocessor can be set within these ranges; however, the unit may not be able to control to extreme combinations of temperature and humidity. 2.1.3.3 2.1.3.3.1 Unit Controls Compressor Short-Cycle Control The control system shall prevent compressor short-cycling by a 3-minute timer from compressor stop to the next start. 2.1.3.3.2 Common Alarm and Remote On/Off A common alarm relay shall provide a contact closure to a remote alarm device. Two (2) terminals shall also be provided for remote On/Off control. Individual alarms shall be “enabled” or “disabled” from reporting to the common alarm. 2.1.3.3.3 Setback Control The control shall be user-configurable to use a manual setpoint control or a programmable, timebased setback control. The setback control will be based on a 5 day/2 day programmed weekly schedule with capability of accepting 2 events per program day. 2.1.3.3.4 Temperature Calibration The control shall include the capabilities to calibrate the temperature and humidity sensors and adjust the sensor response delay time from 10 to 90 seconds. The control shall be capable of displaying temperature values in °F or °C. 2.1.3.3.5 System Auto Restart For startup after power failure, the system shall provide automatic restart with a programmable (up to 9.9 minutes in 6-second increments) time delay. Programming can be performed either at the wall-mounted controller or from the central, site-monitoring system. 33 Liebert® DataMate™ Guide Specifications—For Liebert DataMate 1.5- to 3-Ton (5 to 10.5kW) 2.1.4 Alarms 2.1.4.1 Unit Alarms The control system shall monitor unit operation and activate an audible and visual alarm in the event of the following factory preset alarm conditions. • • • • • • • • High Temperature (max 90°F, 32.2°C) Low Temperature (min 35°F, 1.7°C) High Humidity (max 85% RH) Low Humidity (min 15% RH) High Water Alarm - Lockout Unit Operation High Head Pressure Loss of Power Compressor Short Cycle 2.1.4.2 • • • • Custom Alarms (2x) Humidifier Problem Water Detected Custom Alarm (1) Custom Alarm (2) User-customized text can be entered for the two (2) custom alarms 2.1.4.3 Alarm Controls Each alarm (unit and custom) shall be individually enabled or disabled (except for high head pressure and high water in condensate pan) and can be programmed for a time delay of 0 to 255 seconds of continuous alarm condition to be recognized as an alarm. Each alarm shall also be enabled or disabled to activate the common alarm (except high head pressure and high water in condensate pan). 2.1.4.4 Audible Alarm The audible alarm shall annunciate at the LCD wall box any alarm that is enabled by the operator. 2.1.4.5 Common Alarm A programmable common alarm shall be provided to interface user selected alarms with a remote alarm device. 2.1.4.6 Remote Monitoring All alarms shall be communicated to the Liebert site monitoring system with the following information: date and time of occurrence, unit number and present temperature and humidity. 2.2 Chilled Water System Components 2.2.1 Chilled Water Control Valve The water circuit shall include a 2-way, slow-close On/Off solenoid valve. Design pressure shall be 300psi (2068kPa) with a maximum close-off pressure of 60psi (414kPa). Valve shall be spring return. 2.2.2 Chilled Water Coil The cooling coil shall have a minimum of 2.6 ft.2 (.24m2) face area, three rows deep. It shall be constructed of copper tubes and aluminum fins and be mounted in a galvanized condensate drain pan. The coil shall be designed for a maximum face velocity of _____FPM (m/s) at ___ CFM (CMH). The water circuit shall be designed to distribute water into the entire coil face area. The coil shall be supplied with ___ °F (°C) entering water temperature, with a ___°F (°C) temperature rise. The coil shall be supplied with ___ GPM (l/s) of chilled water and the pressure drop shall not exceed ______ psi (kPa). Liebert® DataMate™ 34 Guide Specifications—For Liebert DataMate 1.5- to 3-Ton (5 to 10.5kW) 2.2 Direct Expansion System Components 2.2.1 Direct Expansion Coil The evaporator section shall include an evaporator coil, thermostatic expansion valve and filter-drier. The evaporator coil shall have ___ ft2 (m2) face area, ___ rows deep. It shall be constructed of copper tubes and aluminum fins and have a maximum face velocity of ___ FPM (m/s) at _____ CFM (CMH). An externally equalized thermostatic expansion valve shall control refrigerant flow. The evaporator coil shall be factory-charged with R-407C refrigerant and sealed. The coil shall be provided with a galvanized steel drain pan. The evaporator unit can be coupled directly with a water/glycol condensing unit or mounted remote to the indoor or outdoor condensing unit. 2.3 Indoor Air-Cooled Centrifugal Fan Condensing Unit Condensing unit components shall include condenser coil, scroll compressor, high-pressure switch, Liebert Lee-Temp™ refrigerant receiver, head pressure control valve, hot gas bypass system and liquid line solenoid valve. The hot gas bypass circuit shall be provided to reduce compressor cycling and improve operation under low-load conditions. Units available for [(2-ton)(3-ton)] systems. All components shall be factory-assembled, charged with R-407C refrigerant and sealed. No internal piping, brazing, dehydration or charging shall be required. Condensing unit shall be designed for 95°F (35°C) ambient and be capable of operation to -30°F (-34°C). The condensing unit can be mounted directly to the evaporator or can be mounted remote to the evaporator. The condensing coil shall be constructed of copper tubes and aluminum fins. The condenser fan shall be centrifugal type, double inlet, direct drive and shall operate at 1050 rpm (890 rpm @ 50 Hz). The fan and motor shall be mounted on vibration isolators. The condenser fan shall be designed for ____CFM (CMH) at ____" (mm) w.g. external static pressure. 2.3 Outdoor Air-Cooled Prop Fan Condensing Unit Condensing unit components shall include a condenser coil, a direct-drive propeller-type fan, a scroll compressor, high-pressure switch, Liebert Lee-Temp receiver and head pressure control valve, hot gas bypass system and liquid line solenoid valve. A hot gas bypass system shall be provided to reduce compressor cycling and improve operation under low-load conditions. All components shall be factory-assembled, charged with R-407C refrigerant and sealed. No internal piping, brazing, dehydration or charging shall be required. Condensing unit shall be designed for 95°F (35°C) ambient and be capable of operation to -30°F (-34.4°C). The condenser coil shall be constructed of copper tubes and aluminum fins. (Option) The 2- or 3-ton condensing unit shall be designed to operate at a sound level less than 58dBA. (Option) The 2- or 3-ton condensing unit shall be designed for design ambient operation of 105°F (40.6°C). (Option) The condenser coil shall be phenolic-coated for extended coil life in coastal areas. 2.3 Indoor Close-Coupled Water/Glycol Condensing Unit The water/glycol-cooled condensing unit shall include a scroll compressor and a water/glycol cooled condenser, and shall be capable of being close-coupled to the evaporator module. The water/glycol cooled condenser shall be designed to balance the heat rejection at ______ °F (°C) entering water/glycol temperature with a flow rate of ___ GPM (l/s) and have a total system pressure drop of _____ ft of water (kPa). An adjustable two-way water regulating valve shall be included. The condenser water/glycol circuit shall be designed for a static operating pressure of 150psi (1034kPa). All components shall be factory assembled, charged with R-407C refrigerant, sealed and be capable of being connected to the evaporator section using quick connect refrigerant couplings and integral wiring harness for single-point power connection for close-coupled system. No refrigeration piping, brazing, dehydration or charging shall be required. 35 Liebert® DataMate™ Guide Specifications—For Liebert DataMate 1.5- to 3-Ton (5 to 10.5kW) 2.3 Indoor Remote Water/Glycol-Cooled Condensing Unit The water/glycol condensing unit shall include a scroll compressor, high-pressure switch, coaxial condenser, water-regulating valve, hot gas bypass system and liquid line solenoid valve. A hot gas bypass circuit shall be provided to reduce compressor cycling and improve operation under low-load conditions. All components shall be factory-assembled, charged with R-407C refrigerant and sealed. No internal piping, brazing dehydration or charging shall be required. Units available for [(2-ton)(3ton)] systems. The water/glycol condensing unit shall be equipped with a coaxial condenser having a total system pressure drop of ______ ft. of water (kPa) and a flow rate of ______ GPM (l/s) with ______ °F (°C) entering water/glycol temperature. The condenser circuit shall be pre-piped with a [(2-way) (3-way)] regulating valve that is head-pressure actuated. The condenser water/glycol circuit shall be designed for a static operating pressure of [(150psi (1034kPa)) (350 PSI (2413 kPa))]. 2.4 Factory-Installed Options 2.4.1 Electric Reheat The electric reheat shall be low-watt density, tubular element and shall include agency approved safety switch to protect the system from overheating. The capacity of the reheat coil shall be ______ BTU/HR, ____ kW, controlled in 1 stage. 2.4.2 Steam Generating Humidifier The environmental control system shall be equipped with a steam generating humidifier that is controlled by the microprocessor control system. It shall be complete with disposable canister, all supply and drain valves, 1" (25.4mm) air gap on fill line, inlet strainer, steam distributor and electronic controls. The need to change the canister shall be annunciated on the microprocessor wall box control panel. The humidifier shall have a capacity of 3 lb./hr. (1.4kg/h). An LED light on the humidifier assembly shall indicate cylinder full, overcurrent detection, fill system fault and end of cylinder life conditions. 2.5 Ship-Loose Accessories 2.5.1 Remote Sensors The unit shall be supplied with remote temperature and humidity sensors. The sensors shall be connected to the unit by a 30 ft. (9m) shielded cable. 2.5.2 Condensate Pump The condensate pump shall have the capacity of _____ GPH (___ l/h) at ___ ft. head (___ kPa). It shall be complete with integral float switch, discharge check valve, pump, motor assembly and reservoir. A secondary float switch shall be provided to permit field wiring to the unit control to shut down the evaporator upon a high water level condition. 2.5.3 Refrigerant Line Sets Pre-charged refrigerant line sets shall be provided by Emerson® in proper lengths for application. Line set length shall be (15 ft. [4.5m]) (30 ft. [9m]) not to exceed 45ft. (13.5m) in total length. 2.5.4 Refrigerant Line Sweat Adapter Kit Provide a sweat adapter kit to permit field brazing of refrigerant line connections for application to split systems. Liebert® DataMate™ 36 Guide Specifications—For Liebert DataMate 1.5- to 3-Ton (5 to 10.5kW) 2.5.5 Step-Down Transformer A step-down transformer shall be provided for [(Indoor Evaporator) (Close-Coupled Water/Glycol Condensing Unit) (Outdoor Air-Cooled Condensing Unit)] needing 277V input power voltage. The transformer shall be coated with epoxy and contained in an enclosed, non-ventilated electrical box with adaptable mounting brackets, suitable for [(indoor) (outdoor)] mounting. 2.5.6 Liebert Local Monitoring Systems, Autochangeover and Leak Detection Provide indicated quantities of the following: • ______ Leak Detection System(s) Model __________________________________ • ______ Remote Monitor(s) Model ________________________________________ • ______ Autochangeover Control(s) Model ________________________________ 2.5.7 Liebert SiteScan® Site Monitoring System A Liebert SiteScan Site Monitoring System Model __________________ shall be provided for remote monitoring of the Liebert DataMate unit and monitoring of other Liebert support equipment. The Liebert SiteScan shall have the capability to monitor and change (at the user direction) the temperature and humidity setpoints and sensitivities of each unit. The printer shall provide the user with chronological alarm information. It shall also be capable of being programmed to print out environmental conditions or operating modes at each unit. 2.5.8 Drycooler The Liebert drycooler shall be a low-profile, direct-drive propeller fan-type air-cooled unit. The drycooler shall be constructed with an aluminum cabinet and a copper-tube aluminum fin coil, and one or more direct drive fans. All electrical connections and controls shall be enclosed in an integral, NEMA 3R rated electrical panel section of the drycooler. The drycooler shall be quiet and corrosion resistant. The drycooler shall be designed for _____°F (°C) ambient. 2.5.9 Glycol Pump Package The system shall include a centrifugal pump mounted in a weatherproof and vented enclosure. The pump shall be rated for ____ gpm (l/s) at ____ ft. (kPa) of head, and operate on _____ volt, ____ phase, ______ Hz. 3.0 EXECUTION 3.1 Installation of Air Conditioning Units 3.1.1 General Install air conditioning units in accordance with manufacturer’s installation instructions. Install unit plumb and level, firmly anchored in locations indicated and maintain manufacturer's recommended clearances. 3.1.2 Electrical Wiring Install and connect electrical devices furnished by manufacturer but not specified to be factory-mounted. Furnish copy of manufacturer's electrical connection diagram submittal to electrical contractor. 3.1.3 Piping Connections Install and connect devices furnished by manufacturer but not specified to be factory-mounted. Furnish copy of manufacturer's piping connection diagram submittal to piping contractor. 3.1.4 Supply and Drain Water Piping Connect water supply and drains to air conditioning unit. Provide pitch and trap as manufacturer's instructions and local codes require. 3.2 Field Quality Control Startup air conditioning units in accordance with manufacturer's start up instructions. Test controls and demonstrate compliance with requirements. 37 Liebert® DataMate™ Guide Specifications—For Liebert DataMate 1.5- to 3-Ton (5 to 10.5kW) Liebert® DataMate™ 38 Technical Support / Service Web Site www.liebert.com Monitoring [email protected] 800-222-5877 Outside North America: +00800 1155 4499 Single-Phase UPS & Server Cabinets [email protected] 800-222-5877 Outside North America: +00800 1155 4499 Three-Phase UPS & Power Systems 800-543-2378 Outside North America: 614-841-6598 Environmental Systems 800-543-2778 Outside the United States: 614-888-0246 Locations While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2014 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners. SL-11035_REV8_10-14 Emerson Network Power Liebert www.emerson.com United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229 Europe Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy +39 049 9719 111 Fax: +39 049 5841 257 Asia 29/F, The Orient Square Building F. Ortigas Jr. Road, Ortigas Center Pasig City 1605 Philippines +63 2 687 6615 Fax: +63 2 730 9572