Liebert Mini-Mate2 - Emerson Network Power

Precision Cooling
For Business-Critical Continuity™
Liebert Mini-Mate2™–1 & 1.5 Ton (3.5 & 5kW) Capacity
Technical Data Manual–Air, Water, Glycol, Chilled Water; 50 & 60 Hz
TABLE OF CONTENTS
1.0
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.1
Designed to Match Computer and Electronic Equipment Needs—From Installation to
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2.0
STANDARD FEATURES—1 & 1.5 TON SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
2.1
Self-Contained Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.1.1
2.1.2
2.1.3
Air-Cooled Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Water/Glycol-Cooled Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Chilled Water Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.2
Evaporator Section—Split Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.3
Condensing Unit Section—Split System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.4
System Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.4.1
Other Standard Control Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3.0
OPTIONAL FACTORY-INSTALLED FEATURES—SELF-CONTAINED AND EVAPORATOR
UNITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
3.1
Reheat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.2
Humidifier. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.3
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.4
Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.5
Free-Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.6
Optional Configuration—Prop Fan Condensing Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.7
Optional Configurations—Water/Glycol-Cooled Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.8
Optional Configuration—Chilled Water Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4.0
SHIP-LOOSE ACCESSORIES—FIELD-INSTALLED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
4.1
Remote Monitoring, Autochangeover and Leak Detection Equipment . . . . . . . . . . . . . . . . . . 6
5.0
FLEXIBLE CONFIGURATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
6.0
AIR-COOLED SYSTEMS—CAPACITIES AND DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . .9
7.0
WATER/GLYCOL SYSTEMS—CAPACITIES AND DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . 16
8.0
CHILLED WATER SYSTEMS—CAPACITIES AND DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . 21
9.0
ELECTRICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
10.0
REFRIGERANT PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
11.0
GLYCOL LOOP PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
12.0
MODEL NUMBER NOMENCLATURE—ALL SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
i
GUIDE SPECIFICATIONS FOR LIEBERT MINI-MATE2—1- AND 1.5-TON SYSTEMS . . . . . . . . . . . . . . 35
1.0
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
1.1
1.2
1.3
1.4
Summary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Design Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Submittals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Quality Assurance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.0
Product . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
2.1
2.2
2.3
2.4
Standard Features/All Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chilled Water System Components. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Factory-Installed Options/All Cooling Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ship-Loose Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.0
Execution. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
3.1
3.2
Installation of Air Conditioning Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Field Quality Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
35
35
35
35
35
37
39
40
FIGURES
Figure 1
Figure 2
Figure 3
Figure 4
Figure 5
Figure 6
Figure 7
Figure 8
Figure 9
Figure 10
Figure 11
Figure 12
Figure 13
Figure 14
Figure 15
Figure 16
Figure 17
Figure 18
Figure 19
Figure 20
Figure 21
Figure 22
Figure 23
Figure 24
Figure 25
Figure 26
Figure 27
Figure 28
Figure 29
Figure 30
Wall-mounted display box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Free cooling option—example. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Flexible configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
General arrangement—self contained air-cooled system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Free-cooling coil arrangement, air-cooled units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
General arrangement—Self-contained air-cooled unit with hot gas reheat . . . . . . . . . . . . . . . . . 11
General arrangement—Split systems with air-cooled condensing units. . . . . . . . . . . . . . . . . . . . 11
Dimensions—Air-cooled, self-contained and split systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Dimensions—Return filter box, all systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Dimensions—Supply/return grille kit, all systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Dimensions—Condenser fan module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Dimensions—Air-cooled systems, outdoor condensing unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
General arrangement—Self-contained water/glycol-cooled system . . . . . . . . . . . . . . . . . . . . . . . . 17
Free-cooling coil arrangement—Water/glycol-cooled units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
General arrangement, Self-contained water/glycol-cooled unit with hot gas reheat . . . . . . . . . . 18
Dimensions - Water/glycol self-contained units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Dimensions—Return filter box, all systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Dimensions—Supply/return grille kit, all systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
General arrangement—Self-contained chilled water units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
General arrangement—Hot water reheat coil, chilled water units . . . . . . . . . . . . . . . . . . . . . . . . 22
Dimensions—Chilled water unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Dimensions—Return filter box, all systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Dimensions—Supply/return grille kit, all systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Refrigerant piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Heat rejection loop, multiple drycoolers and multiple indoor units. . . . . . . . . . . . . . . . . . . . . . . . 30
Model number nomenclature—Self-contained, air-cooled units . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Model number nomenclature—Split evaporator air-cooled units . . . . . . . . . . . . . . . . . . . . . . . . . 32
Model number nomenclature—Outdoor air-cooled prop fan condensing units . . . . . . . . . . . . . . . 32
Model number nomenclature—Self-contained, water/glycol-cooled units . . . . . . . . . . . . . . . . . . . 33
Model number nomenclature—Chilled water units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
ii
TABLES
Table 1
Table 2
Table 3
Table 4
Table 5
Table 6
Table 7
Table 8
Table 9
Table 10
Table 11
Table 12
Table 13
Table 14
Table 15
Table 16
Table 17
Table 18
Table 19
Air-cooled data, 60Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Unit net weights—Air-cooled units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Net weight, condenser fan module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Dimensions and weight—Air-cooled systems, outdoor condensing unit . . . . . . . . . . . . . . . . . . . . 15
Water/Glycol data, 60Hz. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Unit net weights—Water/glycol self-contained units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Chilled water data, 50/60Hz. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Capacity correction factors (based on 10°F (5.6°C) water rise) . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Unit net weights—Chilled Water units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Electrical data, self-contained air-cooled units, 60Hz. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Electrical Data—Self-contained water/glycol-cooled units, 60Hz . . . . . . . . . . . . . . . . . . . . . . . . . 26
Electrical data—Split-evaporator or self-contained chilled water units, 50/60 Hz . . . . . . . . . . . . 27
Electrical data—Outdoor PFH condensing units, 60Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Refrigerant charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Recommended line sizes, OD Cu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Line charges—refrigerant per 100 ft. (30m) of Type L copper tube . . . . . . . . . . . . . . . . . . . . . . . . 28
Pipe length and condenser elevation relative to evaporator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Refrigerant charge in Liebert pre-charged R-407C line sets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Equivalent lengths for various pipe fittings, ft (m). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
iii
iv
Introduction
1.0
INTRODUCTION
1.1
Designed to Match Computer and Electronic Equipment Needs—From Installation
to Operation
Installed above the ceiling, the Liebert Mini-Mate2 system controls the cooling, humidity and air
distribution required by sensitive electronic equipment. A range of sizes and configurations are
available to meet site needs.
The Liebert Mini-Mate2 is also easy to use. Advanced microprocessor technology allows easy, precise
control, and menu-driven monitoring keeps you informed of system operation through the LCD
readout. These features, combined with Liebert quality construction and reliable components,
guarantee satisfaction from installation through operation.
Liebert Precision Cooling
Liebert Precision Cooling systems are designed to control the temperature and humidity required for
computers and other sensitive electronic equipment. Liebert Mini-Mate2 provides complete control on
an around-the-clock basis, as well as the high sensible heat ratio required by sensitive electronic
equipment.
Easy Installation
Self-contained systems have all refrigerant piping factory installed. Split-system evaporator and
outdoor condensing unit are pre-charged with refrigerant and are available with pre-charged
refrigerant lines or sweat adapters for field refrigerant piping. Thermostat-type wiring to control wall
box and condensing units, if applicable, further simplifies the installation.
Easy to Service
Low-maintenance components are easily accessed through removable panels. Spare parts are always
in Liebert’s inventory and available on short notice.
Advanced Control Technology
A menu-driven microprocessor control system provides precise temperature and humidity control and
accurate alarm setpoints. Using touch sensitive buttons, the wall-mounted monitor/control panel
allows you to display temperature and other monitored parameters.
High Efficiency
High system efficiency is a result of high sensible heat ratio, two selectable fan speeds and precise
microprocessor control.
Space Saving Design
All indoor components are installed above the ceiling, so no floor space is required.
Reliable
The Liebert Mini-Mate2 family installed base is a testimony to the system’s reliability. Components
include a rugged compressor, high-efficiency copper tube, aluminum fin evaporator coil and a double
inlet, direct drive fan.
Agency Listed
Standard 60Hz units are CSA Certified to the harmonized U.S. and Canadian
product safety standard CSA C22.2 No 236/UL 1995 for “Heating and Cooling
Equipment” and are marked with the CSA c-us logo.
Location
When determining installation locations, consider that these units contain water
and that water leaks can cause damage to sensitive equipment below. Do not mount these units above
sensitive equipment. A field-supplied pan with drain must be installed beneath ducted cooling units.
Do not install units in areas where normal unit operating sound might disturb the working
environment.
1
Liebert® Mini-Mate2™
Standard Features—1 & 1.5 Ton Systems
2.0
STANDARD FEATURES—1 & 1.5 TON SYSTEMS
2.1
Self-Contained Systems
The self-contained system is designed for ceiling installation. The cabinet and chassis are constructed
of heavy gauge galvanized steel. The unit can be serviced using only one side, increasing its
versatility in mounting locations. Mounting brackets are factory-attached to the cabinet. Internal
cabinet insulation meets ASHRAE 62.1 requirements for Mold Growth, Humidity & Erosion, tested
per UL 181 and ASTM 1338 standards. Unit can be configured with canister humidifier and/or reheat
and various sensor options.
2.1.1
Air-Cooled Unit
The air-cooled unit includes the evaporator coil, condenser coil, compressor, all refrigerant piping,
R-407C unit charge, hot gas bypass, filter drier, high head pressure switch, two-speed direct-drive
blower assembly, microprocessor control with wall-mounted control box and factory-mounted
disconnect switch. MM2CF is a centrifugal blower box with a fan speed controlled motor that ships
separately and field-mounts on the cabinet to provide condenser head pressure control down to -20°F
(-29°C) ambient.
2.1.2
Water/Glycol-Cooled Unit
The water/glycol-cooled unit includes the evaporator coil, coaxial condenser, compressor, all internal
refrigerant and water/glycol piping, R-407C unit charge, hot gas bypass, filter drier, high head
pressure switch, two-speed direct-drive blower assembly, microprocessor control with wall-mounted
control box and factory-mounted disconnect switch.
2.1.3
Chilled Water Unit
The chilled water unit includes the chilled water coil, two-speed, direct-drive centrifugal blower,
two-way, slow-close solenoid, spring-return valve and factory-mounted disconnect switch. Design
pressure is 300psi (2068 kPa) with a 25psi (172 kPa) close-off differential.
2.2
Evaporator Section—Split Systems
The split-system evaporator is designed for ceiling installation. The cabinet and chassis are
constructed of heavy gauge galvanized steel. The unit can be serviced using only one side increasing
its versatility in mounting locations. Mounting brackets are factory-attached to the cabinet. Internal
cabinet insulation meets ASHRAE 62.1 requirements for Mold Growth, Humidity & Erosion, tested
per UL 181 and ASTM 1338 standards. The evaporator section includes the evaporator coil, R-407C
unit charge, filter drier, two-speed direct-drive blower assembly, microprocessor control with
wall-mounted control box and factory-mounted disconnect switch. Unit can be configured with
canister humidifier and/or reheat and various sensor options.
2.3
Condensing Unit Section—Split System
The outdoor prop fan condensing unit includes compressor, condenser coil, R-407C unit charge, prop
fan, liquid-line solenoid valve, high-pressure switch, Liebert Lee-Temp™ head pressure control and
hot gas bypass. Condensing unit is designed for outdoor locations with operating ambients ranging
from -30°F to 95°F (-34°C to 35°C).
2.4
System Controls
System controls include a microprocessor control board mounted in the cooling unit and a
wall-mounted interface with a two-line, 16-character liquid crystal display. An eight-key, membrane
keypad for setpoint/program control, unit On/Off, fan speed and alarm silence is below the LCD
screen. It provides temperature setpoint and sensitivity adjustment, humidity setpoint and
sensitivity adjustment, digital display of temperature, humidity, setpoints, sensitivities, fan speed
and alarm conditions.
2
Liebert® Mini-Mate2™
Standard Features—1 & 1.5 Ton Systems
The wall-box is field-wired to the microprocessor control using standard four-conductor thermostat
wire (field-supplied). The temperature and humidity sensors are in the wall box, which can be
installed up to 300 feet (91.4m) from the evaporator unit. The unit-mounted control board also
includes common alarm terminals and shutdown terminals. The unit automatically restarts after a
power failure.
Figure 1
2.4.1
Wall-mounted display box
Other Standard Control Features
• Adjustable auto restart
• Calibrate sensors
• 5 day/2 day setback
• Predictive humidity control
• Password protection
• Common alarm output
• Alarm enable/disable
• Remote shutdown terminals
• Self-diagnostics
3
Liebert® Mini-Mate2™
Optional Factory-Installed Features—Self-Contained and Evaporator Units
3.0
OPTIONAL FACTORY-INSTALLED FEATURES—SELF-CONTAINED AND
EVAPORATOR UNITS
3.1
Reheat
Electric reheat includes 304/304 stainless steel finned tubular reheat elements for added durability
and corrosion resistance with a high limit safety switch.
SCR Reheat provides tight temperature control by rapidly pulsing the 304/304 stainless steel reheat
elements in small increments. A solid state relay is factory-installed and wired to the microprocessor
control. The compressor is locked On, with the reheat modulated to track the load. Not available on
chilled water, free-cooling or other reheat options.
Hot Water Reheat includes a hot water coil, two-way solenoid valve and Y-strainer. Available only
on chilled water units; not available with other reheat options.
Hot Gas Reheat can be ordered on self-contained models. This option includes the coil and necessary
piping and the control valve. This option is not available with chilled water, free-cooling or other
reheat options. Hot gas reheat operates only during dehumidification and cannot be used for space
heating.
3.2
Humidifier
The Canister Humidifier includes a steam-generating type humidifier with automatic flushing
circuit, inlet strainer, drain, 1" (25.4mm) air gap on fill line and solenoid valves. Humidifier problem
alarm annunciates at the wall-mounted display panel.
Remote Humidifier Contact allows the unit’s humidity controller to control a humidifier outside
the unit. Power to operate the remote humidifier does not come from the Liebert Mini-Mate2.
Available on units with or without internal humidifier.
3.3
Sensors
Smoke Sensor checks return air, shuts down the unit upon sensing smoke and activates visual and
audible alarms at the wall-box display. This smoke sensor is not intended to function as or replace
any smoke sensor system that may be required by local or national codes.
High-Temperature Sensor senses the return air temperature and shuts down unit if the
temperature reaches 125°F (52°C). This device is not meant to replace any fire detection system that
may be required by local or national codes.
3.4
Switches
Filter Clog senses pressure drop across the filters and activates visual and audible alarms at the
wall-box display. The wall-box display annunciates the alarm and flashes a notification upon reaching
a customer setpoint.
A Factory-Installed Non-Fused Disconnect Switch allows the unit to be turned off for
maintenance.
A disconnect switch is standard for the evaporators, chilled water units and indoor condensing units,
but these units may be specified without the switch.
4
Liebert® Mini-Mate2™
Optional Factory-Installed Features—Self-Contained and Evaporator Units
3.5
Free-Cooling
Free-cooling option includes separate cooling coil, three-way, slow-close valve and separate supply
and return piping. Free-cooling is activated when the water temperature reaches a field-adjustable
temperature, typically 45°F (7°C). The valve is rated for 300psi (2068kPa) working pressure.
Air-cooled units can be specified with free-cooling coils, allowing chilled water to be the primary
cooling and the air-cooled section to be the backup. Water/glycol units have two sets of piping, each
with three-way water regulating valves, increasing options of free-cooling sources, such as external
chilled water or glycol from a drycooler loop (see Figure 2). The free-cooling coil is designed for
closed-loop applications using properly treated and circulated fluid. Not available with SCR reheat
options.
NOTE
If free-cooling is applied to an open water tower, a heat exchanger must separate the tower
water from the free-cooling loop.
Figure 2
Free cooling option—example
Drycooler
A free-cooling coil allows the system to take advantage of a
primary chilled water source or colder water/glycol temperatures
available during colder outdoor temperatures. When the fluid
temperature goes below 45°F (7.2°C), cooling switches to
free-cooling operation, bypassing compressor operation.
Liebert Mini-Mate2
Free Cooling
Coil
Water Temperature
Sensor
Water/Glycol
Condenser
Field Piping
3.6
Optional Configuration—Prop Fan Condensing Units
Outdoor Prop Fan Condensing Units are also available in the following optional configurations:
• Condenser coils can be phenolic-coated for extended coil life in coastal areas.
3.7
Optional Configurations—Water/Glycol-Cooled Units
Water/glycol-cooled units are also available with the following piping options:
• Two-way water regulating valve with 350 psi (2413kPa) design pressure.
• Three-way water regulating valve with 150psi (1034kPa) design pressure.
• Three-way water regulating valve with 350psi (2413kPa) design pressure.
3.8
Optional Configuration—Chilled Water Units
Chilled water units are available with the following valve option:
• Three-way, slow-close, motorized chilled water valve rated for 300psi (2068kPa) working
pressure. Valve is non-spring return.
5
Liebert® Mini-Mate2™
Ship-Loose Accessories—Field-Installed
4.0
SHIP-LOOSE ACCESSORIES—FIELD-INSTALLED
Supply and Return Grille Kit includes supply and return grilles, 1" x 20" x 20"
(25mm x 508mm x 508mm) MERV 8 rated filter to ASHRAE 52.2-2007, for installation into a 2ft. x
4ft. (610mm x 1220mm) ceiling grid.
Duct Kit includes return air filter box with 1" duct collar, 1" duct collar for supply air, and air blockoff plates. Duct kit is supplied with a 4" x 16" x 20" (102mm x 406mm x 508mm) MERV 8 filter (based
on ASHRAE 52.2-2007)
Duct Collar Kit (no filter) includes 1" supply duct collar, a 1" return collar and the necessary
block-off plates to make the Liebert Mini-Mate2 a ducted configuration. Filter box and filter are not
included.
Condensate Pump is field-mounted on the outside of the cabinet, wired to the unit power block and
is equipped with a discharge check valve. A secondary float is field-wired to shut down the unit upon
high condensate level. Power can be obtained from the Liebert Mini-Mate2 electrical panel.
Pre-Charged Refrigerant Line Set (R-407C) contains an insulated copper suction line and a
copper liquid line for interconnection of the indoor and outdoor sections. Available in 15-foot (4.5m)
and 30-foot (9m) sections.
Refrigerant-Line Sweat Adapter Kit contains two suction and two liquid line fittings that allow
field-supplied refrigerant piping between the evaporator and condensing unit.
A Remote Temperature and Humidity Sensor package includes sensors in an attractive case
with 30 ft. (9m) of cable. Can be wall- or duct-mounted. Remote sensors should be used when the wall
box is not located in the space to be conditioned.
NOTE
Installing the remote sensors disables the sensors included in the wall box.
Field-Installed Kits available for filter clog, smoke sensor, high-temperature sensor, electric reheat
and humidifier. The kits include installation instructions and are designed to be added to the
evaporator unit before it is installed in the ceiling. Electric reheat kits cannot be installed in units
with free-cooling.
4.1
Remote Monitoring, Autochangeover and Leak Detection Equipment
The Liebert RCM4™ is a four-point, normally open, dry contact monitoring panel. One Form-C, dry
contact common alarm relay output (rated at 24 VAC, 3 Amp) is provided. Four red LEDs illuminate
on the respective alarm and the alarm buzzer is silenced by a front panel switch. The RCM4 requires
a 24VAC or 24VDC power source. Power supply is not included.
The Liebert AC4™ Autochangeover Controller provides autochangeover and autosequence
control for up to four Liebert Mini-Mate2 units within a room. The Liebert AC4 will enable redundant
units in an alarm condition, balance usage and test standby units at programmed intervals. Two
common alarm relay outputs are available. A built-in LCD and RS-232 port for direct PC/terminal
connection provides two options for configuration and monitoring of the product. The Liebert AC4
requires 24VAC input power.
The Liebert AC8™ is ideal for coordinated control of systems with redundant units. The Liebert AC8
enables redundant devices during an alarm condition, balances usage of devices and tests standby
devices at programmable intervals. Supports four zones and can use the 4-20mA temperature sensor
(TW420) for temperature staging in each zone. Two programmable output control relays are available
for auxiliary control such as humidity lockout. Emergency power operation input provided for device
control during an emergency. Two common alarm relay outputs are available. A built-in LCD and
RS-232 port for direct PC/terminal connection provides two options for configuration and monitoring
of the product.
Liebert® Mini-Mate2™
6
Ship-Loose Accessories—Field-Installed
The Liebert ENV-DO™ interface card provides 16 discrete outputs, corresponding to status and
major alarm conditions of Environmental units. The Liebert ENV-DO-ENCL1 packages one
Environmental DO interface card in its own steel enclosure and the ENV-DO-ENCL2 packages two
Environmental DO interface cards in one enclosure for installation external to the Liebert
Mini-Mate2™. The self-contained kit includes an external 120VAC-to-24VAC power transformer.
Wiring harnesses are not provided. Power and communication wiring is field-provided.
The Liebert Liqui-tect® 410 Point Leak Detection Sensor detects the presence of conductive
liquid using a pair of corrosion-resistant, gold-plated probes mounted in a painted, height-adjustable
enclosure. Dual Form-C, dry contact common alarm relays (rated at 24VAC, 3A) signal a leak
detected as well as loss of power and cable fault. The Liebert Liqui-tect 410 requires an external
24VAC or 24VDC power source.
Liebert LT460 Zone Leak Detection Kits include one LT460 sensor, a specified length of
LT500-xxY cable (maximum length is 100 ft [30.5m]) and a corresponding number of hold-down clips.
The Liebert LT460 requires an external 24VAC, 0.12A power source, such as EXT-XFMR or XFMR24.
Liebert SiteScan® is a monitoring solution that gives you decision-making power to effectively
manage the equipment critical to your business.
Liebert SiteScan enables communication from Liebert environmental and power units, as well as
many other pieces of analog or digital equipment, to a front-end software package that provides
real-time status and alarms so you can react quickly to changing situations.
Liebert SiteScan is designed with flexibility for both small systems and large, complex systems such
as those in computer rooms, telecommunications facilities or industrial process control rooms.
Contact your local Emerson representative for assistance with a Liebert SiteScan system.
The NIC-ENCL1 and NIC-ENCL2 package one or two Liebert IntelliSlot® Web/485 Cards with
Adapters, respectively, in one steel enclosure for installation external to the Liebert Mini-Mate2. The
Liebert IntelliSlot Web/485 Card with Adapter provides communication with Liebert Mini-Mate2 via
SNMP, HTTP, RTU Modbus 485 and BACnet IP. The self-contained kit includes an external
120VAC-to-24VAC transformer as a power source. Wiring harnesses are not provided. Power and
communication wiring are field-provided.
7
Liebert® Mini-Mate2™
Flexible Configurations
5.0
FLEXIBLE CONFIGURATIONS
Figure 3
Flexible configurations
Self-Contained Air-Cooled Ducted
Self-Contained Air-Cooled Grille
Water-Cooled Ducted
Water-Cooled Grille
Glycol System Grille
Glycol System Ducted
Chilled Water Grille
Chilled Water Ducted
Liebert® Mini-Mate2™
8
Air-Cooled Systems—Capacities and Dimensions
6.0
Table 1
AIR-COOLED SYSTEMS—CAPACITIES AND DIMENSIONS
Air-cooled data, 60Hz
MMD12A
MMD12E
MMD18A
MMD18E
Self-Contained
Split System
Self-Contained
Split System
3.70 (12,600)
3.60 (12,300)
3.50 (12,000)
3.25 (11,100)
3.45 (11,700)
3.00 (10,200)
4.25 (14,400)
3.95 (13,500)
4.00 (13,700)
3.55 (12,100)
3.90 (13,300)
3.25 (11,100)
5.55 (18,900)
5.30 (18,100)
5.30 (18,100)
4.75 (16,300)
5.15 (17,600)
4.40 (15,000)
5.65 (19,300)
5.35 (18,300)
5.40 (18,500)
4.85 (16,500)
5.25 (18,000)
4.45 (15,200)
Evaporator Model
Cabinet Type
DX Evaporator- Net Capacity Data - kW (Btu/hr) @ High Speed CFM
Total
80°F DB, 62.8°F WB (26.7°C DB,
17.1°C WB) 38% RH
Sensible
Total
75°F DB, 61°F WB (23.9°C DB,
16.1°C WB) 45% RH
Sensible
Total
72°F DB, 60°F WB (22.2°C DB,
15.5°C WB) 50% RH
Sensible
Fan Data - Evaporator
CFM (CMH) - High Speed
CFM (CMH) - Low Speed
Fan Motor hp (W)
External Static Pressure, in. (mm) water gauge
Evaporator Coil - Copper Tube/Aluminum Fin
Face Area ft.2 (m2)
Coil Rows
Max Face Velocity-fpm (m/s)
Unit Refrigerant Charge, oz. (kg)
Unit Operating Weight
Electric & SCR Reheat Capacities (Includes Fan Motor)-kW (Btu/hr)
Input Voltage 208-1-60
Input Voltage 230-1-60
Input Voltage 277-1-60
Hot Gas Reheat Capacities - kW (Btu/hr) *
Based on 103°F (39.4°C) return gas temperature
Humidifier Data - Steam Generator Type
Steam capacity - lb./hr (kg/hr)
Electrical Input Power - kW
Evaporator Connection Sizes
Liquid line Diameter - Aeroquip Coupling Size
Suction Line Diameter - Aeroquip Coupling Size
Humidifier Supply
Evaporator/Condensate Drain
MERV 8 Filter, Supply/Return Grille, qty. (1),
Nom. Size-in. (mm)
MERV 8 Filter, Return Air Filter Box, qty. (1),
Nom. Size-in. (mm)
600 (1019)
480 (816)
0.2 (149)
0.3 (8)
750 (1274)
600 (1019)
0.2 (149)
0.3 (8)
2.44 (0.23)
2
232 (1.2)
2.44 (0.23)
3
291 (1.5)
42 (1.19)
265 (120)
3 (0.09)
220 (100)
49 (1.39)
300 (136)
3.6 (12160)
4.4 (14875)
4.8 (16285)
4.7 (16050)
3.6 (12160)
4.4 (14875)
4.8 (16285)
N/A
4.7 (16050)
2.5 (1.14)
0.88
3/8" - #6 Female
5/8" - #11 Female
1/4" OD Cu Compression Fitting
3/4" NPT-Female
1x20x20 (25x508x508)
1x16x20 (25x406x508)
Condenser Fan Model Number
N/A
2.5 (1.14)
0.88
N/A
Condensing Unit Model Number
4 (0.11)
225 (102)
3/8" - #6 Female
5/8" - #11 Female
1/4" OD Cu Compression Fitting
3/4" NPT-Female
N/A
1x20x20 (25x508x508)
1x16x20 (25x406x508)
N/A
PFH014A-_L7
N/A
PFH020A-_L7
MM2CF
N/A
MM2CF
N/A
2.25 (0.21)
4.1 (0.38)
2.25 (0.21)
4.1 (0.38)
Condenser Coil Face Area ft.2 (m2)
Rows of Coil
3
2
3
2
CFM (CMH)
950 (1614)
2200 (3738)
950 (1614)
2200 (3738)
Motor hp (W)
0.25 (186)
0.20 (149)
0.25 (186)
0.20 (149)
External Static Pressure, in wg. (mm)
0.5 (13)
N/A
0.5 (13)
N/A
Condensing Unit Refrigerant Charge, oz. (kg)
N/A
134 (3.8)
N/A
134 (3.8)
Unit Operating Weight, lb. (kg)
63 (29)
200 (91)
63 (29)
200 (91)
Free-Cooling Coil Option Net Capacity Data - kW (Btu/hr) using 45°F EWT
Total
3.70 (12,600)
4.25 (14,500)
80°F DB, 62.8°F WB (26.7°C DB,
17.1°C WB) 38% RH
Sensible
3.70 (12,600)
4.25 (14,500)
Total
3.15 (10,800)
3.60 (12,300)
75°F DB, 61°F WB (23.9°C DB,
16.1°C WB) 45% RH
Sensible
3.10 (10,600)
3.60 (12,300)
Total
2.85 (9,700)
3.25 (11,100)
72°F DB, 60°F WB (22.2°C DB,
15.5°C WB) 50% RH
Sensible
2.75 (9,300)
3.15 (10,800)
Flow Rate - GPM (l/m)
2.3 (8.7)
2.6 (9.9)
Pressure Drop - ft. water (kPa)
5.2 (15.5)
6.6 (19.7)
Free-Cooling Coil - Copper Tube/Aluminum Fin
2.44 (0.23)
2.44 (0.23)
Face Area ft.2 (m2)
Coil Rows
2
2
Max Face Velocity-fpm (m/s)
232 (1.2)
291 (1.5)
Internal Fluid Volume - gal (l)
1.7 (6.4)
1.7 (6.4)
Water supply and return connections, in. (mm) OD
5/8 (15.9)
5/8 (15.9)
The net capacity data has fan motor heat factored in for all ratings and the entering air conditions of 75°F (23.9°C), 45% RH, is the standard rating condition for
ASHRAE 127-2007. All capacities are nominal values; actual performance will be ±5%.
* Hot Gas Reheat operates only during dehumidification. Capacity shown is offset by cooling capacity; cannot be used for space heating and is for reference only.
Liebert® Mini-Mate2™
9
Air-Cooled Systems—Capacities and Dimensions
Figure 4
General arrangement—self contained air-cooled system
High Pressure
Switch
Compressor
Condenser Coil
External
Equalizer
Filter
Drier
Sensing
Bulb
Hot Gas Bypass
Solenoid Valve
Evaporator
Coil
Hot Gas Bypass
Control Valve
Expansion Valve
DPN000168
Rev. 0
Figure 5
Free-cooling coil arrangement, air-cooled units
Bleed Valve
Fluid
Supply
Shutoff
Valve *
Fluid
Return
Free Cooling
Control Valve
Free Cooling
Coil
Temperature Stat
FIELD PIPING
FACTORY PIPING
DPN000169
Rev. 2
Hose
Bibs *
Liebert® Mini-Mate2™
10
Air-Cooled Systems—Capacities and Dimensions
Figure 6
General arrangement—Self-contained air-cooled unit with hot gas reheat
High
Pressure
Switch
Solenoid Valve
Provided With
Optional Hot
Gas Reheat
Check
Valve
Compressor
Condenser
Coil
External Equalizer
Filter Drier
Sensing
Bulb
Hot Gas Reheat Coil
(Optional)
Hot Gas Bypass
Control Valve
Expansion Valve
NOTE: Hot gas
reheat is available only on
self-contained “DX” modules.
Air-cooled piping shown, also
available on water and glycol
models.
Figure 7
Coaxial condenser
not shown
Hot Gas Bypass
Solenoid Valve
DPN000169
Rev. 2
Evaporator Coil
General arrangement—Split systems with air-cooled condensing units
Compressor
Liquid Injection
Valve Bulb
Condenser Coil
High Pressure
Switch
Hot Gas Bypass
Solenoid Valve
3/8" SAE 45° Male Flare (MCD)
or Atmospheric (PFH)
Pressure Relief Valve
Suction Line Male Quick
Connect Coupling
Suction Line Female Quick
Connect Coupling
*
Sensing Bulb
Liquid
Injection
Valve
External Equalizer
3-Way Head
Pressure
Control Valve
Hot Gas Bypass
Control Valve
Liquid Line
Solenoid Valve
Service Access
Ports
*
Filter
Drier
Expansion
EEValve
Liquid Line Male Quick
Connect Coupling
Liquid Line Female Quick
Connect Coupling
FIELD PIPING
FACTORY PIPING
Pressure
Balancing
Valve
Lee - Temp
Receiver
* Use Liebert sweat adapter kit with
field hard piping or use Liebert
pre-charged line set.
DPN000165
Rev. 1
Evaporator Coil
Liebert® Mini-Mate2™
Sight Glass
Check
Valve
11
Air-Cooled Systems—Capacities and Dimensions
Figure 8
Dimensions—Air-cooled, self-contained and split systems
Threaded Rod
Centers Left End
56"(1422mm)
Threaded Rod Centers
"
2 7 m)
m
6
(68
Condenser blower
box location for
Self-Contained,
Air-Cooled Units
only. See Figure 11
for dimensions.
Removable
Access
Panels
Customer-supplied
threaded rods for
module support from
ceiling (typ. 4)
3/8" (10mm) holes
for module rigging.
(typ. 2 each end)
1" (25.4mm)
22"
(559mm)
Threaded
Unit hanging
Rod Centers supports
Right End
Shaded area indicates
a recommended clearance
of 24" (610mm) for
component access
and removal
58" (1473mm)
Overall Dimension
Access Panel for Blower/Motor located
on the bottom of the unit. Allow a
Evaporator Supply
minimum clearance of 9" (229mm)
(ducted only)
below unit for access to Blower/Motor.
30"
54"
(782mm)
(1371mm)
Condenser Inlet duct
Cabinet
Cabinet
connection for
Dimension
Dimension
Self-Contained,
Air-Cooled Unit only.
1" (25.4mm) flange
16-3/4"
(425mm)
30"
FRONT
(762mm)
OF UNIT
Overall
Dimension
Evaporator Return
(ducted only)
14-1/2"
(368mm)
11"
(279mm)
20"
(508mm)
Cabinet
Dimension
1-7/8" (48mm)
4-7/8"
(124mm)
3-1/16"
(78mm)
7-1/2"
(190mm)
Table 2
14"
(356mm)
15"
(381mm)
3-1/4"
(82mm)
Unit net weights—Air-cooled units
Model #
60Hz
50Hz
Net Weight
lb (kg)
MM*12E
MM*12A
MM*18E
220 (100)
NA
MM*18A
265 (120)
225 (102)
300 (136)
Source: DPN000172, Rev. 5
Liebert® Mini-Mate2™
12
3-3/8"
(86mm)
18"
(457mm)
BACK OF UNIT
DPN000172
Rev. 5
Air-Cooled Systems—Capacities and Dimensions
Figure 9
Dimensions—Return filter box, all systems
20-1/4"
(514mm)
7-5/8"
(194mm)
8" (203mm)
2-1/4"
(57mm)
14"
(357mm)
16"
(406mm)
1-1/4"
(32mm)
3/4" (19mm)
Flange
18"
(457mm)
1"
(25.4mm)
Shaded area indicates a recommended
clearance of 30" (762mm) for component
access and removal.
DPN000173
Rev. 1
Figure 10 Dimensions—Supply/return grille kit, all systems
Cabinet dimensions
same as DPN000172
Front of
Unit
2"
(51mm)
One Way
Air Return
to Unit
5"
(127mm)
Liebert® Mini-Mate2™
Removable for filter
access and removal.
13
Three-Way
Unit Discharge
1"
(25.4mm)
DPN000173
Rev. 1
Air-Cooled Systems—Capacities and Dimensions
Figure 11
Dimensions—Condenser fan module
20"
(508mm)
High & Low Voltage
Wire Harness see
unit schematic for
wiring.
4-11/16"
(119mm)
Blower Motor &
Controller
access cover
17-1/4"
(438mm)
Blower & Motor Assembly
Fan Speed Controller
12"
(305mm)
Capillary tube from
fan speed controller
Screw onto access
valve in discharge
line (inside ceiling unit).
Shaded area indicates a
recommended clearance
of 24" (610mm) for component
access and removal.
5-1/4"
(133mm)
12"
(305mm)
18-5/8"
(473mm)
DPN000159
Rev. 6
Table 3
Net weight, condenser fan module
Model #
Net Weight, lb (kg)
MM2CF
63 (29)
Source: DPN000159, Rev. 6
Liebert® Mini-Mate2™
14
Air-Cooled Systems—Capacities and Dimensions
Figure 12 Dimensions—Air-cooled systems, outdoor condensing unit
Fan Rotation
CCW
(left side)
Removable (right) panel
for access to
refrigeration component
A
Right Air Discharge
Left Air Intake
B
Shaded area
indicates a recommended
clearance of 24" (610mm)
for component access and
removal.
C
Shaded area
indicates a minimum
clearance of 18" (457mm)
for proper air flow
Table 4
Shaded area
indicates a minimum
clearance of 18" (457mm)
for proper air flow.
Removable panel for access
to high-voltage and low-voltage
connections and refrigeration
components
DPN000130
Rev. 1
Dimensions and weight—Air-cooled systems, outdoor condensing unit
Model Numbers
60Hz
PFH014A-L
PFH020A-L
Dimensions, in. (mm)
50Hz
A
B
C
Module Net
Weight, lb. (kg)
NA
40 (1016)
23-1/2 (597)
18 (457)
200 (91)
Source: DPN000130, Rev. 1
Liebert® Mini-Mate2™
15
Water/Glycol Systems—Capacities and Dimensions
7.0
Table 5
WATER/GLYCOL SYSTEMS—CAPACITIES AND DIMENSIONS
Water/Glycol data, 60Hz
MMD14W
Evaporator Model (Self-Contained)
MMD20W
Water-Cooled
Glycol-Cooled
Water-Cooled
Glycol-Cooled
Condensing Unit Fluid
DX Evaporator- Net Capacity Data - kW (Btu/hr) @ High Speed CFM
80°F DB, 62.8°F WB (26.7°C DB,
Total
4.05 (13,800)
3.50 (11,900)
6.40 (21,800)
5.20 (17,800)
17.1°C WB) 38% RH
Sensible
3.85 (13,100)
3.45 (11,800)
5.80 (19,800)
5.10 (17,400)
75°F DB, 61°F WB (23.9°C DB,
Total
3.85 (13,100)
3.30 (11,300)
6.15 (21,000)
5.00 (17,000)
16.1°C WB) 45% RH
Sensible
3.45 (11,800)
3.10 (10,600)
5.20 (17,700)
4.55 (15,600)
72°F DB, 60°F WB (22.2°C DB,
Total
3.80 (12,900)
3.20 (11,000)
6.00 (20,500)
4.85 (16,600)
15.5°C WB) 50% RH
Sensible
3.15 (10,800)
2.90 (9,800)
4.80 (16,400)
4.10 (14,000)
Fan Data - Evaporator
CFM (CMH) - High Speed
600 (1019)
750 (1274)
CFM (CMH) - Low Speed
480 (816)
600 (1019)
Fan Motor hp (W)
0.2 (149)
0.2 (149)
External Static Pressure, in. (mm) water gauge
0.3 (8)
0.3 (8)
Evaporator Coil - Copper Tube/Aluminum Fin
2.44 (0.23)
2.44 (0.23)
Face Area ft.2 (m2)
Coil Rows
2
3
Max Face Velocity-fpm (m/s)
232 (1.2)
291 (1.5)
Unit Refrigerant Charge, oz. (kg)
27 (0.77)
34 (0.96)
Unit Operating Weight
260 (118)
295 (134)
Electric & SCR Reheat Capacities (Includes Fan Motor)-kW (Btu/hr)
Input Voltage 208-1-60
3.6 (12160)
3.6 (12160)
Input Voltage 230-1-60
4.4 (14875)
4.4 (14875)
Input Voltage 277-1-60
4.8 (16285)
4.8 (16285)
Hot Gas Reheat Capacities - kW (Btu/hr) *
Based on 103°F (39.4°C) return gas temperature
4.7 (16050)
4.7 (16050)
Humidifier Data - Steam Generator Type
Steam capacity - lb./hr (kg/hr)
2.5 (1.14)
2.5 (1.14)
Electrical Input Power - kW
0.88
0.88
Unit Connection Sizes
Water/Glycol Condenser Connection Sizes, in. (mm) OD
1/2 (12.7)
1/2 (12.7)
Humidifier Supply
1/4" OD Cu Compression Fitting
1/4" OD Cu Compression Fitting
Evaporator/Condensate Drain
3/4" NPT-Female
3/4" NPT-Female
MERV 8 Filter, Supply/Return Grille, qty. (1),
1x20x20 (25x508x508)
1x20x20 (25x508x508)
Nom. Size - in. (mm)
MERV 8 Filter, Return Air Filter Box, qty. (1),
1x16x20 (25x406x508)
1x16x20 (25x406x508)
Nom. Size - in. (mm)
85°F (29.4°C)
110°F (43.3°C)
85°F (29.4°C)
110°F (43.3°C)
Condenser Fluid Requirements
EWT
EGT - 40% PG
EWT
EGT - 40% PG
THR - kW (Btu/hr) @ 75°F/45% RH
5.15 (17,500)
4.80 (16,400)
7.85 (26,700)
7.35 (25,000)
Flow Rate - GPM (l/m)
1.5 (5.7)
2.6 (9.9)
3.3 (12.5)
4.6 (17.4)
1.9 (5.7)
5.3 (15.8)
7.0 (20.9)
14.1 (42.2)
Pressure Drop - ft. of H20 (kPa)
Water-Cooled Condensing Temperature
105°F (40.6°C)
NA
105°F (40.6°C)
NA
Water/Glycol Condenser Loop Volume - gal (l)
0.5 (1.9)
0.5 (1.9)
Free-Cooling Coil Option Net Capacity Data - kW (Btu/hr) using 45°F EWT
Total
3.70 (12,600)
2.80 (9,600)
4.25 (14,500)
3.55 (12,100)
80°F DB, 62.8°F WB (26.7°C DB,
17.1°C WB) 38% RH
Sensible
3.70 (12,600)
2.80 (9,600)
4.25 (14,500)
3.55 (12,100)
Total
3.15 (10,800)
2.35 (8,100)
3.60 (12,300)
3.00 (10,200)
75°F DB, 61°F WB (23.9°C DB,
16.1°C WB) 45% RH
Sensible
3.10 (10,600)
2.35 (8,100)
3.60 (12,300)
3.00 (10,200)
Total
2.85 (9,700)
2.10 (7,200)
3.25 (11,100)
2.65 (9,100)
72°F DB, 60°F WB (22.2°C DB,
15.5°C WB) 50% RH
Sensible
2.75 (9,300)
2.10 (7,200)
3.15 (10,800)
2.65 (9,100)
Flow Rate - GPM (l/m)
2.3 (8.7)
2.6 (9.9)
2.6 (9.9)
4.6 (17.4)
Pressure Drop - ft. water (kPa)
5.2 (15.5)
9.9 (29.6)
6.6 (19.7)
29.0 (86.7)
Free-Cooling Coil - Copper Tube/Aluminum Fin
2.44 (0.23)
2.44 (0.23)
Face Area ft.2 (m2)
Coil Rows
2
2
Max Face Velocity-fpm (m/s)
232 (1.2)
291 (1.5)
Internal Fluid Volume - gal (l)
1.7 (6.4)
1.7 (6.4)
Free-Cooling Coil supply and return connections,
5/8 (15.9)
5/8 (15.9)
in. (mm) OD
The net capacity data has fan motor heat factored in for all ratings and the entering air conditions of 75°F (23.9°C), 45% RH, is the standard rating condition for
ASHRAE 127-2007. All capacities are nominal values; actual performance will be ±5%.
* Hot Gas Reheat operates only during dehumidification. Capacity shown is offset by cooling capacity; cannot be used for space heating and is for reference only.
Liebert® Mini-Mate2™
16
Water/Glycol Systems—Capacities and Dimensions
Figure 13 General arrangement—Self-contained water/glycol-cooled system
High
Pressure
Switch
Compressor
Tube-in-Tube
Condenser
External
Equalizer
Evaporator
Coil
Tube-in-Tube
Condenser
Water/Glycol
Return Line
Filter Drier
Sensing
Bulb
Water/Glycol
Supply Line
Fluid Return
Hot Gas Bypass
From Unit
Solenoid Valve
Hot Gas Bypass
Control Valve
Fluid Supply
To Unit
Expansion
Shut- Off *
Valve
Valve
Shutoff
2-Way Water
Valve *
Regulating Valve
Hose Bibs *
FIELD PIPING
Fluid Return
From Unit
FACTORY PIPING
* Components are not supplied by Emerson,
but are recommended for proper
circuit operation and maintenance.
DPN000166
Rev. 1
Fluid Supply
To Unit
Figure 14 Free-cooling coil arrangement—Water/glycol-cooled units
Bleed Valve
Fluid
Supply
Shutoff
Valve *
Fluid
Return
Free Cooling
Control Valve
Free Cooling
Coil
Temperature Stat
FIELD PIPING
FACTORY PIPING
DPN000169
Rev. 2
Hose
Bibs *
Liebert® Mini-Mate2™
17
3 - Way Water
Regulating Valve
(Optional)
Water/Glycol Systems—Capacities and Dimensions
Figure 15 General arrangement, Self-contained water/glycol-cooled unit with hot gas reheat
High
Pressure
Switch
Solenoid Valve
Provided With
Optional Hot
Gas Reheat
Check
Valve
Compressor
Condenser
Coil
External Equalizer
Filter Drier
Sensing
Bulb
Hot Gas Reheat Coil
(Optional)
NOTE: Hot gas
reheat is available only on
self-contained “DX” modules.
Air-cooled piping shown, also
available on water and glycol
models.
Liebert® Mini-Mate2™
Hot Gas Bypass
Solenoid Valve
Coaxial condenser
not shown
Hot Gas Bypass
Control Valve
Expansion Valve
DPN000169
Rev. 2
Evaporator Coil
18
Water/Glycol Systems—Capacities and Dimensions
Figure 16 Dimensions - Water/glycol self-contained units
Threaded Rod
Centers Left End
56"(1422mm)
Threaded Rod Centers
"
2 7 m)
m
6
(68
Condenser blower
box location for
Self-Contained,
Air-Cooled Units
only. See Figure 11
for dimensions.
Removable
Access
Panels
Customer-supplied
threaded rods for
module support from
ceiling (typ. 4)
3/8" (10mm) holes
for module rigging.
(typ. 2 each end)
1" (25.4mm)
22"
(559mm)
Threaded
Unit hanging
Rod Centers supports
Right End
Shaded area indicates
a recommended clearance
of 24" (610mm) for
component access
and removal
58" (1473mm)
Overall Dimension
Access Panel for Blower/Motor located
on the bottom of the unit. Allow a
Evaporator Supply
minimum clearance of 9" (229mm)
(ducted only)
below unit for access to Blower/Motor.
30"
54"
(782mm)
(1371mm)
Condenser Inlet duct
Cabinet
Cabinet
connection for
Dimension
Dimension
Self-Contained,
Air-Cooled Unit only.
1" (25.4mm) flange
16-3/4"
(425mm)
30"
FRONT
(762mm)
OF UNIT
Overall
Dimension
Evaporator Return
(ducted only)
14-1/2"
(368mm)
11"
(279mm)
20"
(508mm)
Cabinet
Dimension
1-7/8" (48mm)
4-7/8"
(124mm)
3-1/16"
(78mm)
7-1/2"
(190mm)
Table 6
14"
(356mm)
15"
(381mm)
3-1/4"
(82mm)
3-3/8"
(86mm)
18"
(457mm)
BACK OF UNIT
Unit net weights—Water/glycol self-contained units
Model Numbers
60Hz
50Hz
MM*14W
N/A
MM*20W
Net Weight, lb (kg)
260 (118)
295 (134)
Source: DPN000172, Rev. 5
Liebert® Mini-Mate2™
19
DPN000172
Rev. 5
Water/Glycol Systems—Capacities and Dimensions
Figure 17 Dimensions—Return filter box, all systems
20-1/4"
(514mm)
7-5/8"
(194mm)
8" (203mm)
2-1/4"
(57mm)
14"
(357mm)
16"
(406mm)
1-1/4"
(32mm)
3/4" (19mm)
Flange
18"
(457mm)
1"
(25.4mm)
Shaded area indicates a recommended
clearance of 30" (762mm) for component
access and removal.
DPN000173
Rev. 1
Figure 18 Dimensions—Supply/return grille kit, all systems
Cabinet dimensions
same as DPN000172
Front of
Unit
2"
(51mm)
One Way
Air Return
to Unit
5"
(127mm)
Liebert® Mini-Mate2™
Removable for filter
access and removal.
20
Three-Way
Unit Discharge
1"
(25.4mm)
DPN000173
Rev. 1
Chilled Water Systems—Capacities and Dimensions
8.0
Table 7
CHILLED WATER SYSTEMS—CAPACITIES AND DIMENSIONS
Chilled water data, 50/60Hz
Model Number, 50 & 60 Hz
MMD23C/MMD22C
Net Capacity Data - kW (Btu/hr) based on 45°F (7.2°C) EWT & 10°F (5.6°C) temp. rise
Total
4.85 (16,400)
80°F DB, 62.8°F WB (26.7°C DB,
17.1°C WB) 38% RH
Sensible
4.80 (16,300)
Flow Rate - GPM (l/m)
3.4 (12.9)
Pressure Drop - ft. water (kPa)
10.7 (32.0)
Total
3.85 (13,100)
75°F DB, 61°F WB (23.9°C DB,
16.1°C WB) 45% RH
Sensible
3.80 (13,000)
Flow Rate - GPM (l/m)
2.8 (10.6)
Pressure Drop - ft. water (kPa)
7.2 (21.5)
Total
3.20 (11,000)
72°F DB, 60°F WB (22.2°C DB,
15.5°C WB) 50% RH
Sensible
3.20 (10,900)
Flow Rate - GPM (l/m)
2.3 (8.7)
Pressure Drop - ft. water (kPa)
5.3 (15.8)
Fan Data - Evaporator
CFM (CMH) - High Speed
CFM (CMH) - Low Speed
Fan Motor hp (W)
External Static Pressure, in. (mm) water gauge
750 (1274)
600 (1019)
0.2 (149)
0.3 (8)
CW Coil - Copper Tube/Aluminum Fin
Face Area ft.2 (m2)
Coil Rows
Max Face Velocity-fpm (m/s)
2.44 (0.23)
2
291 (1.5)
Electric Reheat Capacity (Includes Fan Motor)-kW (Btu/hr)
Input Voltage 208-1-60
Input Voltage 230-1-60
Input Voltage 277-1-60
Input Voltage-220-1-50
3.6 (12160)
4.4 (14875)
4.8 (16285)
4.0 (13640)
Hot Water Reheat Coil - Copper Tube/Aluminum Fin
Capacity (with fan motor heat)
using 180°F (82°C) EWT-kW (Btu/hr)
Flow Rate - GPM (l/m)
Pressure Drop - ft. water (kPa)
Face Area ft.2 (m2)
Coil Rows
HWRH supply and return connections, in. (mm) OD
Humidifier Data - Steam Generator Type
Steam capacity - lb./hr (kg/hr)
Electrical Input Power - kW
9.5 (32,400)
1.5 (5.7)
1.5 (4.5)
2.44 (0.23)
1
5/8 (15.9)
2.5 (1.14)
0.88
Unit Connection Sizes
CW supply and return connections, in. (mm) OD
5/8 (15.9)
Humidifier Supply 1/4" OD Cu Compression Fitting
Evaporator/Condensate Drain
3/4" NPT-Female
Unit Internal Fluid Volume - gal (l)
1.7 (6.4)
MERV 8 Filter, Supply/Return Grille, qty. (1),
1x20x20 (25x508x508)
Nom. Size-in. (mm)
MERV 8 Filter, Return Air Filter Box, qty. (1),
1x16x20 (25x406x508)
Nom. Size-in. (mm)
Unit Operating Weight, lb. (kg.)
220 (99.8)
Unit Valve Types On/Off Slow Close - 2 & 3-Way
Valve Size
1/2"
Valve Cv
2.5
Max. Static Operating Pressure, psi (kPa)
300 (2068)
Close-Off Pressure, psi (kPa)
25 (172)
The net capacity data has fan motor heat factored in for all ratings and the entering air conditions of 75°F (23.9°C), 45% RH, is the standard
rating condition for ASHRAE 127-2007. All capacities are nominal values; actual performance will be ±5%.
Liebert® Mini-Mate2™
21
Chilled Water Systems—Capacities and Dimensions
Table 8
Capacity correction factors (based on 10°F (5.6°C) water rise)
72°F (22.2°C) 50% RH 75°F (23.9°C) 45% RH
EWT
TCC
SCC
TCC
SCC
42°F (5.6°C)
43°F (6.1°C)
44°F (6.7°C)
45°F (7.2°C)
46°F (7.8°C)
47°F (8.3°C)
48°F (8.9°C)
49°F (9.4°C)
1.30
1.19
1.09
1.00
0.94
0.88
0.82
0.75
1.14
1.10
1.05
1.00
0.95
0.89
0.82
0.75
1.25
1.17
1.08
1.00
0.95
0.90
0.85
0.80
1.11
1.07
1.04
1.00
0.96
0.90
0.85
0.81
Figure 19 General arrangement—Self-contained chilled water units
Bleed Valve
Chilled Water
Control Valve
Chilled
Water
Chilled Supply
Water
Return
Chilled Water
Valve
FIELD PIPING
Shutoff
Valves**
FACTORY PIPING
*
*
Hose
Bibs **
* Field piping refers to the use of hard
piping using sweat adapter kit or
precharged line set.
** Components are not supplied by
Emerson, but are recommended for
proper circuit operation and
maintenance.
DPN000167
Rev. 1
Figure 20 General arrangement—Hot water reheat coil, chilled water units
Bleed Valve
Water
Return
Shutoff
Valve *
Hose Bibs *
Water
Supply
Hot Water Reheat
Control Valve
Hot Water
Reheat Coil
Y-Strainer
FIELD PIPING
FACTORY PIPING
* Components are not supplied by
Emerson, but are recommended for proper
circuit operation and maintenance.
HOT WATER REHEAT COIL ONLY
AVAILABLE ON CHILLED WATER UNITS
Liebert® Mini-Mate2™
22
DPN000169
Rev. 2
Chilled Water Systems—Capacities and Dimensions
Figure 21 Dimensions—Chilled water unit
Threaded Rod
Centers Left End
56"(1422mm)
Threaded Rod Centers
"
2 7 m)
m
6
(68
Condenser blower
box location for
Self-Contained,
Air-Cooled Units
only. See Figure 11
for dimensions.
Removable
Access
Panels
Customer-supplied
threaded rods for
module support from
ceiling (typ. 4)
3/8" (10mm) holes
for module rigging.
(typ. 2 each end)
1" (25.4mm)
22"
(559mm)
Threaded
Unit hanging
Rod Centers supports
Right End
Shaded area indicates
a recommended clearance
of 24" (610mm) for
component access
and removal
58" (1473mm)
Overall Dimension
Access Panel for Blower/Motor located
on the bottom of the unit. Allow a
Evaporator Supply
minimum clearance of 9" (229mm)
(ducted only)
below unit for access to Blower/Motor.
30"
54"
(782mm)
(1371mm)
Condenser Inlet duct
Cabinet
Cabinet
connection for
Dimension
Dimension
Self-Contained,
Air-Cooled Unit only.
1" (25.4mm) flange
16-3/4"
(425mm)
30"
FRONT
(762mm)
OF UNIT
Overall
Dimension
Evaporator Return
(ducted only)
14-1/2"
(368mm)
11"
(279mm)
20"
(508mm)
Cabinet
Dimension
1-7/8" (48mm)
4-7/8"
(124mm)
3-1/16"
(78mm)
7-1/2"
(190mm)
Table 9
14"
(356mm)
15"
(381mm)
3-1/4"
(82mm)
3-3/8"
(86mm)
18"
(457mm)
BACK OF UNIT
DPN000172
Rev. 5
Unit net weights—Chilled Water units
Model #
60Hz
50Hz
Net Weight
lb (kg)
MM*23C
MM*22C
220 (100)
Source: DPN000172, Rev. 5
23
Liebert® Mini-Mate2™
Chilled Water Systems—Capacities and Dimensions
Figure 22 Dimensions—Return filter box, all systems
20-1/4"
(514mm)
7-5/8"
(194mm)
8" (203mm)
2-1/4"
(57mm)
14"
(357mm)
16"
(406mm)
1-1/4"
(32mm)
3/4" (19mm)
Flange
18"
(457mm)
1"
(25.4mm)
Shaded area indicates a recommended
clearance of 30" (762mm) for component
access and removal.
DPN000173
Rev. 1
Figure 23 Dimensions—Supply/return grille kit, all systems
Cabinet dimensions
same as DPN000172
Front of
Unit
2"
(51mm)
One Way
Air Return
to Unit
5"
(127mm)
Liebert® Mini-Mate2™
Three-Way
Unit Discharge
Removable for filter
access and removal.
24
1"
(25.4mm)
DPN000173
Rev. 1
Electrical Data
9.0
ELECTRICAL DATA
Table 10
Electrical data, self-contained air-cooled units, 60Hz
Base Evaporator
Model Number
208/230 - 1Ph - 60Hz
277 - 1Ph - 60Hz
MM*12A
MM*18A
MM*12A
MM*18A
FLA
8.2
14.2
6.8
11.8
WSA
9.4
16.9
7.8
14.0
OPD
15
25
15
20
FLA
27.0
33.0
23.1
28.1
WSA
32.9
40.4
28.2
34.4
OPD
35
45
30
35
FLA
27.0
33.0
23.1
28.1
WSA
32.9
40.4
28.2
34.4
OPD
35
45
30
35
FLA
13.0
19.0
10.4
15.4
WSA
14.2
21.7
11.4
17.6
OPD
15
30
15
25
Cooling Only
with Electric Reheat
with SCR Reheat 6
with Humidifier
with Electric Reheat and Humidifier
FLA
27.0
33.0
23.1
28.1
WSA
32.9
40.4
28.2
34.4
OPD
35
45
30
35
with SCR Reheat and Humidifier 6
1.
2.
3.
4.
5.
6.
FLA
31.8
37.8
26.7
31.7
WSA
37.7
45.2
31.8
38.0
OPD
40
50
35
40
Electrical values are not affected by hot gas reheat or free-cooling options
FLA = Full Load Amps, WSA = Wire Size Amps, OPD = Maximum Overcurrent Protection Device
* = Specify “D” for disconnect, “0” for no disconnect.
Self-contained air-cooled units include MM2CF blower box.
Hot Gas Reheat not available with Electric or SCR Reheat or Free-cooling options
SCR Reheat not available with Free-cooling models.
Liebert® Mini-Mate2™
25
Electrical Data
Table 11
Electrical Data—Self-contained water/glycol-cooled units, 60Hz
Base Evaporator
Model Number
208/230 - 1Ph - 60Hz
277 - 1Ph - 60Hz
MM*14W
MM*20W
MM*14W
MM*20W
FLA
6.1
12.1
5.3
10.3
WSA
7.3
14.8
6.3
12.5
OPD
15
25
15
20
FLA
24.9
30.9
21.6
26.6
WSA
30.8
38.3
26.7
32.9
OPD
35
40
30
35
FLA
24.9
30.9
21.6
26.6
WSA
30.8
38.3
26.7
32.9
OPD
35
40
30
35
FLA
10.9
16.9
8.9
13.9
WSA
12.1
19.6
9.9
16.1
OPD
15
30
15
25
Cooling Only
with Electric Reheat
with SCR Reheat 5
with Humidifier
with Electric Reheat and Humidifier
FLA
25.0
30.9
21.6
26.6
WSA
31.3
38.3
26.7
32.9
OPD
35
40
30
35
with SCR Reheat and Humidifier 5
1.
2.
3.
4.
5.
FLA
29.7
35.7
25.2
30.2
WSA
35.6
43.1
30.3
36.5
OPD
40
45
35
40
Electrical values are not impacted by Hot Gas Reheat, and Free-cooling options
FLA = Full Load Amps, WSA = Wire Size Amps, OPD = Maximum Overcurrent Protection Device
* = Specify “D” for disconnect, “0” for no disconnect.
Hot Gas Reheat not available with Electric or SCR Reheat or Free-cooling options
SCR Reheat not available with free-cooling models.
Liebert® Mini-Mate2™
26
Electrical Data
Table 12
Electrical data—Split-evaporator or self-contained chilled water units, 50/60 Hz
208/230 - 1Ph - 60Hz
277 - 1Ph - 60Hz
220- 1Ph - 50Hz
MM*12E; MM*18E; MM*23C
MM*12E; MM*18E; MM*23C
MM*22C
FLA
1.4
1.4
1.4
WSA
1.8
1.8
—
OPD
15
15
—
FLA
20.2
17.7
20.2
WSA
25.3
22.1
—
OPD
30
25
—
FLA
20.2
17.7
20.2
WSA
25.3
22.1
—
OPD
30
25
—
FLA
6.2
5.0
6.0
WSA
7.8
6.3
—
OPD
15
15
—
FLA
25.0
21.3
24.8
WSA
31.3
26.6
—
OPD
35
30
—
FLA
25.0
21.3
24.8
WSA
31.3
26.6
—
OPD
35
30
—
Base Evaporator
Model Number
Cooling Only
with Electric Reheat
with SCR Reheat 5
with Humidifier
with Electric Reheat and Humidifier
with SCR Reheat and Humidifier 5
1. For units with Hot Water Reheat (available only on MM*22C & MM*23C), use appropriate values from “Cooling Only” or “with Humidifier”
categories.
2. FLA = Full Load Amps, WSA = Wire Size Amps, OPD = Maximum Overcurrent Protection Device
3. * = Specify “D” for disconnect, “0” for no disconnect.
4. Use MM*12E or MM*18E values for models with Free-Cooling options, except with SCR Reheat.
5. SCR Reheat not available with Free-cooling models.
Table 13
Model #
Electrical data—Outdoor PFH condensing units, 60Hz
Nominal
Capacity
Tons
14
20
*
1
1.5
* Electrical
Characteristic
Input Voltage
Phase
208/230-1
FLA
9.1
WSA
11.0
OPD
15
FLA
12.1
WSA
14.8
OPD
25
FLA = Full Load Amps
WSA = Wire Size Amps (minimum supply circuit current capacity)
OPD = Maximum Overcurrent Protection Device (fuse or circuit breaker)
Liebert® Mini-Mate2™
27
Refrigerant Piping
10.0 REFRIGERANT PIPING
Table 14
Refrigerant charge
Model #
60Hz
Unit Type
50Hz
Charge R-407C *
oz (kg)
Self Contained-Air
MM*12A/F
—
42 (1.19)
Self Contained-Water
MM*14W/G
—
27 (0.77)
Split Evaporator-Air
MM*12E/K
—
3 (0.085)
Self Contained-Air
MM*18A/F
—
49 (1.39)
Self Contained-Water
MM*20W/G
—
28 (0.79)
Split Evaporator-Air
MM*18E/K
—
4 (0.11)
Split Condensing Unit
PFH014A-_L7
—
134 (3.80)
Split Condensing Unit
PFH020A-_L7
—
134 (3.80)
Self-contained DX units, split-system evaporators and split-system condensing units are pre-charged with R-407C refrigerant. Use
Table 16 to determine charge to be added to field-fabricated refrigerant lines.
* For units with Hot Gas Reheat coil, add 18oz (0.51kg) refrigerant to listed values.
Table 15
Recommended line sizes, OD Cu
PFH_14A
PFH_20A
Equivalent
ft. (m)
Suction
Liquid
Suction
Liquid
50 (15.2)
5/8"
3/8"
5/8"
3/8"
75 (22.9)
5/8"
3/8"
7/8"
3/8"
100 (30.5)
7/8"
3/8"
7/8"
3/8"
125 (38.1)
7/8"
3/8"
7/8"
1/2"
150 (45.7)
7/8"
3/8"
7/8"
1/2"
* Suction line and liquid line sizing based on < 3 psi pressure drop in each and suction line refrigerant velocities >700FPM (3.6m/s),
horizontal and 1000FPM (5.1m/s), vertical.
Table 16
Line charges—refrigerant per 100 ft. (30m) of Type L copper tube
R-407C, lb/100 ft. (kg/30m)
Line Size,
O.D., in.
Liquid Line
Suction Line
3/8
3.7 (1.7)
—
1/2
6.9 (3.1)
—
5/8
11.0 (5.0
0.4 (0.2)
3/4
15.7 (7.1)
0.6 (0.3)
7/8
23.0 (10.4)
1.0 (0.4)
1-1/8
—
1.7 (0.7)
1-3/8
—
2.7 (1.1)
Table 17
Pipe length and condenser elevation relative to evaporator
Nominal System
Size, Tons
Maximum Equiv.
Pipe Length, ft. (m)
Maximum PFH
Level Above
Evaporator, ft. (m)
Maximum PFH
Level Below
Evaporator, ft. (m)
1 or 1.5
150 (45)
40 (12)
15 (4.6)
Maximum recommended total equivalent pipe length is 150 ft (46m). Suction and liquid lines may require additional specialty
items when vertical lines exceed 20 ft. (6m) and/or condensing unit installation is more than 15 ft. (4.6m) below the evaporator.
Contact Emerson Application Engineering for assistance.
Liebert® Mini-Mate2™
28
Refrigerant Piping
Table 18
Refrigerant charge in Liebert pre-charged R-407C line sets
Line Size, in.
3/8 liquid
5/8 or 7/8 suction
Table 19
Length, ft. (m)
Charge R-407C, oz (kg)
15 (4.5)
5 (0.14)
30 (9)
10 (0.28)
15 (4.5)
5 (0.14)
30 (9)
10 (0.28)
Equivalent lengths for various pipe fittings, ft (m)
Copper Pipe
OD, in.
90 Degree
Elbow Copper
90 Degree
Elbow Cast
45 Degree
Elbow
Tee
Gate
Valve
Globe
Valve
Angle
Valve
1/2
0.8 (0.24)
1.3 (0.39)
0.4 (0.12)
2.5 (0.76)
0.26 (0.07)
7.0 (2.13)
4.0 (1.21)
5/8
0.9 (0.27)
1.4 (0.42)
0.5 (0.15)
2.5 (0.76)
0.28 (0.08)
9.5 (2.89)
5.0 (1.52)
3/4
1.0 (0.3)
1.5 (0.45)
0.6 (0.18)
2.5 (0.76)
0.3 (0.09)
12.0 (3.65)
6.5 (1.98)
7/8
1.45 (0.44)
1.8 (0.54)
0.8 (0.24)
3.6 (1.09)
0.36 (0.1)
17.2 (5.24)
9.5 (2.89)
1-1/8
1.85 (0.56)
2.2 (0.67)
1.0 (0.3)
4.6 (1.4)
0.48 (0.14)
22.5 (6.85)
12.0 (3.65)
1-3/8
2.4 (0.73)
2.9 (0.88)
1.3 (0.39)
6.4 (1.95)
0.65 (0.19)
32.0 (9.75)
16.0 (4.87)
1-5/8
2.9 (0.88)
3.5 (1.06)
1.6 (0.48)
7.2 (2.19)
0.72 (0.21)
36.0 (10.97)
19.5 (5.94)
Refrigerant trap = Four times equivalent length of pipe per this table
Figure 24 Refrigerant piping diagram
Pitch down 1/2" (13mm) per 10 ft. (3m)
Evaporator
Suction Line Piping
Condensing Unit
Below Evaporator
NOTE
When installing remote condensing units below the
evaporator, the suction gas line should be trapped with
an inverted trap to the height of the evaporator . This
prevents refrigerant migration to the compressors
during off cycles . Maximum recommended vertical
level drop to condensing unit is 15 ft. (4.6m) .
Condensing
Unit
Condensing
Unit
Evaporator
See Table 17 for recommended maximum
vertical rise above/fall below evaporator.
Suction Line Piping
Condensing Unit Above Evaporator
Traps recommended at the base of riser exceeding
5 ft (1.5m) and every 20 feet (6m) of vertical rise.
Pitch down 1/2" (13mm) per 10 ft. (3m)
Liebert® Mini-Mate2™
29
Glycol Loop Piping
11.0 GLYCOL LOOP PIPING
Contact Emerson Application Engineering for assistance in choosing correct drycooler models. Refer
to Figure 25.
Figure 25 Heat rejection loop, multiple drycoolers and multiple indoor units
Expansion Tank
______ Gal. (L)
HP
GPM (l/s)
ft.
____(kW) ____ Per Pump @ ____(kPa)
FS
PUMP PACKAGE
Drycooler No. 1 Model ______
GPM (l/s) ____ P: ___ ft (kPa)
See Note 3
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
Drycooler No. 2 Model ______
GPM (l/s) ____ P: ___ ft (kPa)
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
LEGEND
Gate Valve
Check Valve
Butterfly Valve
Relief Valve
Union
Ball or Flow Control Valve
FS
P:
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
Flow Switch
Pressure Drop
Strainer/Filter
Notes:
1. Pressure and temperature gauges (or ports for same) are
recommended to monitor component pressure drops and performance.
2. Flow measuring devices, drain and balancing valves to be supplied
by others and located as required.
3. See product literature for installation guidelines and clearance dimensions.
4. Drawing shows dual pump package. Alternate pump packages with more
pumps may be considered; consult supplier
Liebert® Mini-Mate2™
30
Total
GPM
(L/s): _____
Pipe
Diam.: _____ In. (mm)
P: _____ Ft. (kPa)
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
DPN000991
Rev. 0
Model Number Nomenclature—All Systems
12.0 MODEL NUMBER NOMENCLATURE—ALL SYSTEMS
Figure 26 Model number nomenclature—Self-contained, air-cooled units
Liebert Mini-Mate2
D = Disconnect Switch
0 = No Disconnect Switch
Nominal Capacity, kBtu/hr
12 & 18 (60Hz)
MM
D
18
A
—
P
H
E
7
A
Unit Type
A = Air-Cooled
F = Air-Cooled with
Free-Cooling Coil
— = Placeholder
Supply Power
P = 208/230-1-60
X = 277-1-60
Humidification
H = Canister Humidifier
0 = No Humidifier
R = Remote Humidifier Contact
J = Canister Humidifier and Remote
Humidifier Contact
Reheat Type
0 = No Reheat
E = Electric Reheat
S = SCR Reheat
G = Hot Gas Reheat (Not available
with Free-Cooling Option)
Refrigerant & Hot Gas Bypass
7 = R-407C & Hot Gas Bypass
Sensor Packages
0 = None
A = Filter Clog
B = Smoke Sensor
C = High-Temperature Sensor
D = Filter Clog and Smoke Sensor
E = Filter Clog and High-Temperature Sensor
F = Smoke Sensor and High-Temperature Sensor
G = Filter Clog, Smoke Sensor and High-Temperature Sensor
Liebert® Mini-Mate2™
31
Model Number Nomenclature—All Systems
Figure 27 Model number nomenclature—Split evaporator air-cooled units
Liebert Mini-Mate2
Humidification
H = Canister Humidifier
0 = No Humidifier
R = Remote Humidifier Contact
J = Canister Humidifier and Remote
Humidifier Contact
D = Disconnect Switch
0 = No Disconnect Switch
Nominal Capacity, kBtu/hr
12 & 18 (60Hz)
MM
D
18
E
7
P
H
E
0
A
Unit Type
E = Split Evaporator
K = Split Evaporator
with Free-Cooling
Refrigerant
7 = R-407C (E/K Unit Types)
Supply Power
P = 208/230-1-60
X = 277-1-60
Reheat Type
0 = No Reheat
E = Electric Reheat
S = SCR Reheat (E Unit Type only)
Hot Gas Bypass
0 = Not Contained in Unit
Sensor Packages
0 = None
A = Filter Clog
B = Smoke Sensor
C = High-Temperature Sensor
D = Filter Clog and Smoke Sensor
E = Filter Clog and High-Temperature Sensor
F = Smoke Sensor and High-Temperature Sensor
G = Filter Clog, Smoke Sensor and High-Temperature Sensor
Figure 28 Model number nomenclature—Outdoor air-cooled prop fan condensing units
PFH = Prop Fan Condensing Unit with Hot Gas Bypass
0 = Std. Sound Level
PFH
0
Refrigerant
7 = R-407C
Nominal Capacity,
Cooling Method
A = Air-Cooled
20
— = Standard Coil
C = Coated Coil
A
—
P = 208/230V - 1ph - 60Hz
32
P
L
7
L = 95°F Ambient,
Liebert Lee-Temp™
Liebert® Mini-Mate2™
Model Number Nomenclature—All Systems
Figure 29 Model number nomenclature—Self-contained, water/glycol-cooled units
Liebert Mini-Mate2
D = Disconnect Switch
0 = No Disconnect Switch
Humidification
H = Canister Humidifier
0 = No Humidifier
R = Remote Humidifier Contact
J = Canister Humidifier and Remote
Humidifier Contact
Nominal Capacity, kBtu/hr
14 & 20 (60 Hz)
Unit Type
W = Water/Glycol-Cooled
G = Water/Glycol-Cooled
with Free-Cooling Coil
MM
D
20
W
2
P
H
E
7
A
Valve Type
2 = 2-Way Std. Pressure Fluid Regulating Valve
3 = 3-Way Std. Pressure Fluid Regulating Valve
D = 2-Way High Pressure Fluid Regulating Valve
T = 3-Way High Pressure Fluid Regulating Valve
Supply Power
P = 208/230-1-60
X = 277-1-60
Reheat Type
0 = No Reheat
E = Electric Reheat
S = SCR Reheat
G = Hot Gas Reheat (Not available
with Free-Cooling Option)
Refrigerant & Hot Gas Bypass
7 = R-407C & Hot Gas Bypass
Sensor Packages
0 = None
A = Filter Clog
B = Smoke Sensor
C = High-Temperature Sensor
D = Filter Clog and Smoke Sensor
E = Filter Clog and High-Temperature Sensor
F = Smoke Sensor and High-Temperature Sensor
G = Filter Clog, Smoke Sensor and High-Temperature Sensor
33
Liebert® Mini-Mate2™
Model Number Nomenclature—All Systems
Figure 30 Model number nomenclature—Chilled water units
Liebert Mini-Mate2
Humidification
H = Canister Humidifier
0 = No Humidifier
R = Remote Humidifier Contact
J = Canister Humidifier and Remote
Humidifier Contact
D = Disconnect Switch
0 = No Disconnect Switch
Nominal Capacity, kBtu/hr
23 (60Hz)
22 (50Hz)
MM
D
23
C
2
P
H
E
0
A
Unit Type
C = Chilled Water
Valve Type
2 = 2-Way Valve (Std Close-off)
D = 2-Way Valve (High Close-off)
Reheat Type
0 = No Reheat
E = Electric Reheat
H = Hot Water Reheat
Supply Power
P = 208/230-1-60
X = 277-1-60
S = 220-1-50
Hot Gas Bypass
0 = Not Contained in Unit
Sensor Packages
0 = None
A = Filter Clog
B = Smoke Sensor
C = High-Temperature Sensor
D = Filter Clog and Smoke Sensor
E = Filter Clog and High-Temperature Sensor
F = Smoke Sensor and High-Temperature Sensor
G = Filter Clog, Smoke Sensor and High-Temperature Sensor
34
Liebert® Mini-Mate2™
Guide Specifications for Liebert Mini-Mate2—1- and 1.5-Ton Systems
GUIDE SPECIFICATIONS FOR LIEBERT MINI-MATE2—1- AND 1.5-TON SYSTEMS
1.0
GENERAL
1.1
Summary
These specifications describe requirements for an environmental control system. The system shall be
designed to control temperature and relative humidity conditions within the room.
The manufacturer shall design and furnish all equipment in the quantities and configurations shown
on the project drawings.
Standard 60Hz units are CSA Certified to the harmonized U. S. and Canadian product safety
standard CSA C22.2 No 236/UL 1995 for “Heating and Cooling Equipment” and are marked with the
CSA c-us logo.
The system model number(s) shall be:
Self-Contained Unit:_____________________
Split Evaporator: _______________________
Condensing Unit: _______________________
Chilled Water Unit:______________________
1.2
Design Requirements
The environmental control system shall be a Liebert Mini-Mate2 factory assembled unit. On direct
expansion models, the refrigeration system shall be self-contained or shall be split, with the
compressor located in a remote air-cooled condensing unit.
The self-contained and split evaporator units shall be designed for above-dropped-ceiling installation
and serviceable from the front and bottom of the system. Condensing unit for split system shall be
designed for outdoor installation.
The system shall have a total cooling capacity of _______ Btu/hr (kW), and a sensible cooling capacity
of ________ Btu/hr (kW), based on the entering air condition of _____°F (°C) dry bulb, and _____°F (°C)
wet bulb.
The unit is to be supplied for operation using a ______ volt, ______ phase, ______ Hz power supply.
1.3
Submittals
Submittals shall be provided with the proposal and shall include: Single-Line Diagrams;
Dimensional, Electrical and Capacity data; Piping and Electrical Connection Drawings.
1.4
Quality Assurance
The specified system shall be factory-tested before shipment. Testing shall include, but shall not be
limited to: Quality Control Checks, “HiPot” Test (two times rated voltage plus 1000 volts, per NRTL
agency requirements) and Metering Calibration Tests. The system shall be designed and
manufactured according to world class quality standards. The manufacturer shall be ISO 9001
certified.
2.0
PRODUCT
2.1
Standard Features/All Systems
2.1.1
Cabinet Construction
The cabinet and chassis shall be constructed of heavy gauge galvanized steel and designed for easy
installation and service access from front and bottom of unit only (water cooled units require end
access). Mounting brackets shall be factory-attached to the cabinet. Internal cabinet insulation shall
meet ASHRAE 62.1 requirements for Mold Growth, Humidity & Erosion, tested per UL 181 and
ASTM 1338 standards.
35
Liebert® Mini-Mate2™
Guide Specifications for Liebert Mini-Mate2—1- and 1.5-Ton Systems
2.1.2
Air Distribution
The air distribution system shall be constructed with a quiet, direct-drive fan assembly equipped with
double-inlet blower, self-aligning ball bearings and lifetime lubrication. Fan motor shall be
1/5hp (149W), permanent-split capacitor, high efficiency type, equipped with two speeds for air flow
modulation for precise dehumidification control. Dehumidification shall utilize the lower fan speed.
Air delivery shall be minimum ____ CFM (____ CMH) at high fan speed. For ducted applications air
delivery shall be ____ CFM (____ CMH) at _____ " (______mm) external static pressure.
System shall be suitable for plenum or ducted air distribution. Refer to 2.4.2 - Supply and Return
Grille, 2.4.3 - Filter Box and Duct Kit and 2.4.4 - Duct Collar Kit.
2.1.3
Microprocessor Control
The control system shall be microprocessor-based, factory-wired into the system and tested prior to
shipment. The wall-mounted control enclosure shall include a 2-line by 16-character LCD providing
continuous display of operating status and alarm condition. An 8-key membrane keypad for setpoint/
program control, fan speed selection and unit On/Off shall be located below the display. The control
display shall be field-wired to the control board using 4-conductor field-supplied thermostat wire.
Temperature and humidity sensors shall be located in the wall box, which shall be capable of being
located up to 300 ft (91.4m) from the evaporator unit.
2.1.3.1
Monitoring
The LCD shall provide On/Off indication, operating mode indication (cooling, heating, humidifying,
dehumidifying), fan speed indication and current day, time, temperature and humidity (if applicable)
indication. The monitoring system shall be capable of relaying unit operating parameters and alarms
to the Liebert SiteScan™ monitoring system.
2.1.3.2
•
•
•
•
Control Setpoint Parameters
Temp. Setpoint 65-85°F (18-29°C)
Temp. Sensitivity 1-9.9°F (1-5°C)
Humidity Setpoint 20-80% RH
Humidity Sensitivity 1-30% RH
2.1.3.3
2.1.3.3.1
Unit Controls
Compressor Short-Cycle Control
The control system shall prevent compressor short-cycling by a 3-minute timer from compressor stop
to the next start.
2.1.3.3.2
Common Alarm and Remote On/Off
A common alarm relay shall provide a contact closure to a remote alarm device. Two (2) terminals
shall also be provided for remote On/Off control. Individual alarms shall be “enabled” or “disabled”
from reporting to the common alarm.
2.1.3.3.3
Setback Control
The control shall be user-configurable to use a manual setpoint control or a programmable,
time-based setback control. The setback control will be based on a 5 day/2 day programmed weekly
schedule with capability of accepting 2 events per program day.
2.1.3.3.4
Temperature Calibration
The control shall include the capabilities to calibrate the temperature and humidity sensors and
adjust the sensor response delay time from 10 to 90 seconds. The control shall be capable of displaying
temperature values in °F or °C.
2.1.3.3.5
System Auto Restart
For startup after power failure, the system shall provide automatic restart with a programmable (up
to 9.9 minutes in 6-second increments) time delay. Programming can be performed either at the
wall-mounted controller or from the central, site-monitoring system.
36
Liebert® Mini-Mate2™
Guide Specifications for Liebert Mini-Mate2—1- and 1.5-Ton Systems
2.1.4
Alarms
2.1.4.1
Unit Alarm
The control system shall monitor unit operation and activate an audible and visual alarm in the event
of the following factory preset alarm conditions:
•
•
•
•
•
•
•
•
High Temperature
Low Temperature
High Humidity
Low Humidity
High Water Alarm - Lockout Unit Operation
High Head Pressure
Loss of Power
Compressor Short Cycle
2.1.4.2
•
•
•
•
•
•
Custom Alarms (2x)
Humidifier Problem
Filter Clog
Water Detected
Smoke Detected
Custom Alarm #1
Custom Alarm #2
User-customized text can be entered for the two (2) custom alarms.
2.1.4.3
Alarm Controls
Each alarm (unit and custom) shall be separately enabled or disabled, selected to activate the
common alarm (except for high head pressure).
2.1.4.4
Audible Alarm
The audible alarm shall annunciate any alarm that is enabled by the operator.
2.1.4.5
Common Alarm
A programmable common alarm shall be provided to interface user selected alarms with a remote
alarm device.
2.1.4.6
Remote Monitoring
All alarms shall be communicated to the Liebert site monitoring system with the following
information: date and time of occurrence, unit number, and present temperature and humidity.
2.2
Chilled Water System Components
2.2.1
Chilled Water Control Valve
The control valve shall be a solenoid-operated, slow-close, spring-return type to reduce water
hammer. Design pressure shall be 300psi (2067kPa) static pressure, with a maximum close-off
pressure of 25psi (172kPa).
(Option) The control valve shall be a motorized, slow-close, non-spring-return type to reduce water
hammer. Design pressure shall be 300psi (2067kPa) static pressure, with a maximum close-off
pressure of 100psi (689kPa).
2.2.2
Chilled Water Coil
The cooling coil shall have a minimum of 2.4 sq.ft. (0.23 sq.m) face area, 2 rows deep. It shall be
constructed of copper tubes and aluminum fins and have a maximum face velocity of ____ ft. per
minute (___ m/s) at ____ CFM (____ CMH). The coil shall be supplied with 45°F (7.2°C) entering water
temperature. The coil shall be supplied with ______ GPM (l/s) of chilled water and the pressure drop
shall not exceed ______ PSI (kPa). The coil assembly shall be mounted in a condensate drain pan with
an internally trapped drain line. The evaporator drain pan shall include a factory-installed float
switch to shut down the evaporator upon high water condition.
37
Liebert® Mini-Mate2™
Guide Specifications for Liebert Mini-Mate2—1- and 1.5-Ton Systems
2.2
Direct Expansion Self-Contained System Components
2.2.1
Refrigeration System
The refrigeration system shall consist of a (scroll) (rotary) compressor with vibration isolating
grommets, evaporator coil, condenser coil, externally equalized thermostatic expansion valve, high
pressure safety switch, filter drier, hot gas bypass circuit, factory R-407C refrigerant charge and
externally equalized expansion valve. Hot gas bypass shall be provided to reduce compressor cycling
and optimize performance under low load conditions.
2.2.2
Evaporator Coil
The evaporator coil shall have 2.4 sq.ft. (0.23 sq.m) face area, ____ rows deep. It shall be constructed
of copper tubes and aluminum fins and have a maximum face velocity of ___ ft. per minute (____ m/s)
at ___ CFM ( ____ CMH). The coil shall be provided with a condensate drain pan with an internally
trapped drain line. The evaporator drain pan shall include a factory-installed float switch to shut
down the evaporator upon high water condition.
2.2.3
Air-Cooled Condenser Coil
The air-cooled condenser section shall contain a factory mounted and piped condenser coil constructed
of copper tubes and aluminum fins. No piping, brazing, dehydration or charging shall be required.
The condenser coil shall be factory mounted within the unit cabinet.
2.2.3.1
Air-Cooled Condenser Fan
A factory-supplied condenser fan shall be field-mounted to the end of the evaporator cabinet. The
system shall be provided with a fan speed control system to permit operation at -20°F (-28.9°C) inlet
ambient air temperature and sized to provide full rated cooling capacity at 95°F (35°C) entering air
from plenum space. The centrifugal condenser fan shall deliver ____CFM (____ CMH) at ____inches
(___mm) external static pressure at maximum speed.
Condenser fan electrical and refrigerant pressure connections shall be field attached to the cooling
chassis using factory provided wiring harness and capillary tube/fitting.
2.2.3
Water/Glycol-Cooled Condenser
The water/glycol-cooled condenser section shall contain a factory-mounted and piped coaxial
condenser constructed of steel and copper tubing. No piping, brazing, dehydration or charging of
refrigerant shall be required. The condenser coil shall be factory-mounted within the unit cabinet.
The total system pressure drop of the water/glycol system shall be______ ft. of water (kPa) and a flow
rate of ______ GPM (l/s) with ______ °F (°C) entering water/glycol temperature.
The condenser circuit shall be pre-piped with a [(2-way) (3-way)] regulating valve which is headpressure actuated.
The condenser water/glycol circuit shall be designed for a static operating pressure of [(150PSI
(1034kPa)) (350PSI (2413kPa))].
Liebert® Mini-Mate2™
38
Guide Specifications for Liebert Mini-Mate2—1- and 1.5-Ton Systems
2.2
Direct Expansion Split System Components
2.2.1
Evaporator Unit
The evaporator section shall include evaporator coil, thermostatic expansion valve and filter drier.
The evaporator coil shall have 2.4 sq.ft. (0.23 sq.m) face area, __ rows deep. It shall be constructed of
copper tubes and aluminum fins and have a maximum face velocity of ___ ft. per minute (____ m/s) at
___ CFM ( ____ CMH). An externally equalized thermostatic expansion valve shall control refrigerant
flow. The evaporator coil shall be factory-charged with R-407C refrigerant and sealed.The coil shall be
provided with a condensate drain pan, with an internally trapped drain line. The evaporator drain
pan shall include a factory-installed float switch to shut down the evaporator upon high water
condition.
2.2.2
Outdoor Air-Cooled Prop Fan Condensing Unit
Condensing unit components shall include a condenser coil, a direct-drive propeller-type fan, a (scroll)
(reciprocating) compressor with vibration-isolating grommets, high pressure switch, Liebert
Lee-Temp™ receiver and head pressure control valve, hot gas bypass system and liquid line solenoid
valve. The condenser coil shall be constructed of copper tubes and aluminum fins.
A hot gas bypass system shall be provided to reduce compressor cycling and improve operation under
low load conditions.
All components shall be factory-assembled, charged with R-407C refrigerant, sealed and be capable of
being connected to the evaporator section using pre-charged refrigerant line sets. No internal piping,
brazing, dehydration or charging shall be required. Condensing unit shall be designed for 95°F (35°C)
ambient and be capable of operation to -30°F (-34.4°C).
(Option) The coils shall be phenolic-coated for extended coil life in coastal areas.
2.3
Factory-Installed Options/All Cooling Units
2.3.1
Steam Generating Humidifier
The environmental control system shall be equipped with a steam generating humidifier that is
controlled by the microprocessor control system. It shall be complete with disposable canister, all
supply and drain valves, 1" (25.4mm) air gap on fill line, inlet strainer, steam distributor and
electronic controls. The need to change canister shall be annunciated on the microprocessor wall box
control panel. The humidifier shall have a capacity of 2.5 lb/hr (1.1 kg/h). An LED light on the
humidifier assembly shall indicate cylinder full, overcurrent detection, fill system fault and end of
cylinder life conditions.
2.3.2
Electric Reheat
The electric reheat shall be low-watt density, 304/304 stainless steel, finned-tubular and shall be capable
of maintaining room dry bulb conditions when the system is calling for dehumidification. The reheat
section shall include a UL-approved safety switch to protect the system from overheating. The capacity of
the reheat coils shall be ______ Btu/hr (kW), with input power of ______ V, controlled in one stage.
2.3.3
Hot Water Reheat
The hot water reheat coil shall have copper tubes and aluminum fins with a capacity of ______ Btu/hr
(kW) when supplied with ______°F (°C) entering water temperature at _______ GPM (l/s) flow rate.
Maximum pressure drop shall be ______ PSI (kPa). The control system shall be factory pre-piped with
a two-way solenoid valve and cleanable Y-strainer. The hot water reheat coil shall only be available
on chilled water units.
2.3.4
SCR Electric Reheat
The electric reheat shall be low-watt density, 304/304 stainless steel, finned-tubular and shall be
capable of maintaining room dry bulb conditions when the system is calling for dehumidification. The
reheat section shall include a UL-approved safety switch to protect the system from overheating.
The SCR (Silicon Controlled Rectifier) controller shall proportionally control the reheat elements to
maintain the selected room temperature. The rapid cycling made possible by the SCR controller
provides precise temperature control, and the more constant element temperature improves heater
life. The unit microprocessor control shall operate the SCR controller, while cooling is locked on. The
capacity of the reheat coils shall be ______ Btu/hr (kW), with input power of ______ V. Not available on
chilled water or free-cooling units.
39
Liebert® Mini-Mate2™
Guide Specifications for Liebert Mini-Mate2—1- and 1.5-Ton Systems
2.3.5
Hot Gas Reheat
The complete hot gas reheat system shall include a copper tube, aluminum fin coil, three-way
solenoid valve, and refrigerant check valve. The capacity of the coil shall be ______ Btu/hr (kW). Hot
gas reheat shall operate only during dehumidification and capacity shall be offset by cooling coil
capacity. Hot gas reheat shall not be used for space heating.
2.3.6
Disconnect Switch, Non-Locking
The non-automatic, non-locking, molded case circuit interrupter shall be factory-mounted in the
high-voltage section of the electrical panel. The switch handle shall be accessible from the unit front
and mounted on the indoor cooling unit.
2.3.7
High-Temperature Sensor
The high-temperature sensor shall immediately shut down the system when high temperatures are
detected. The high-temperature sensor shall be mounted with the sensing element in the return air.
2.3.8
Smoke Sensor
The smoke detector shall immediately shut down the environmental control system and activate the
alarm system when activated. The sensing element shall be located in the return air compartment.
This smoke sensor shall not function or replace any room smoke detection system that may be
required by local or national codes.
2.3.9
Filter Clog Switch
The filter clog switch senses pressure drop across the filters and shall annunciate the wall box display
upon reaching the adjustable setpoint.
2.3.10 Free-Cooling/Dual Cooling Source
A free-cooling coil shall be integral to the evaporator cabinet, and shall be constructed of copper tubes
and aluminum fins. The coil shall be rated at ______ Btu/hr (kW) sensible cooling capacity with a 45°F
(22°C), ___% glycol solution. The coil shall require ______ GPM (l/s) and the total unit pressure drop
shall not exceed ______ feet of water (kPa) when in the free cooling mode. Free-cooling shall be
activated by an adjustable aquastat, and shall include a factory-piped, three-way valve and separate
supply and return piping.
Coil is designed for closed-loop applications using properly treated and circulated fluid. A
field-supplied heat exchanger system is required to prevent premature corrosion if applied to open
water tower loop. Not available with SCR reheat.
2.4
Ship-Loose Accessories
2.4.1
Remote Sensors
The unit shall be supplied with remote temperature and humidity sensors. The sensors shall be
connected to the unit by a 30 ft. (9m) shielded cable.
2.4.2
Supply and Return Grille
A factory-supplied supply and return grille kit shall be provided for supply and return air delivery
through a 2' x 4' (0.6m x 0.6m) T-bar ceiling grid. Kit shall include an air baffle plate, supply grille,
hinged return grille, 1" x 20 x 20" (25.4mm x 508mm x 508mm) MERV 8 (ASHRAE 52.2-2007) filter
and mounting frame.
2.4.3
Filter Box and Duct Kit
A return air filter box shall be provided with hinged filter access, and 1" (25.4 mm) duct flange. A
1" (25.4 mm) duct flange shall also be provided for air discharge. Filters shall be 1" x 16" x 20"
(25.4mm x 406mm x 508mm) MERV 8 per ASHRAE 52.2-2007.
2.4.4
Duct Collar Kit
1" (25.4 mm) duct flanges shall be provided for each of the discharge and return air openings. Filters
and filter box must be field supplied.
Liebert® Mini-Mate2™
40
Guide Specifications for Liebert Mini-Mate2—1- and 1.5-Ton Systems
2.4.5
Condensate Pump
The condensate pump shall have the capacity of _____ GPH (___ l/h) at ___ ft. head (___ kPa). It shall
be complete with integral float switch, discharge check valve, pump, motor assembly and reservoir. A
secondary float switch shall be provided to permit field wiring to the unit control to shut down the
evaporator upon a high water level condition.
2.4.6
Refrigerant Line Sets
Pre-charged refrigerant line sets shall be provided by Emerson in proper lengths for application to
air-cooled split systems. Line set length shall be [(15 ft. (4.5m)) (30 ft. (9m))], not to exceed 45 ft.
(13.5m) in total length.
2.4.7
Refrigerant Line Sweat Adapter Kit
Provide a sweat adapter kit to permit field brazing of refrigerant line connections for application to
air-cooled split systems.
2.4.8
Liebert SiteScan™ Site Monitoring System
A Liebert SiteScan Site Monitoring System Model __________________ shall be provided for remote
monitoring of the Liebert Mini-Mate2 unit and monitoring of other Liebert support equipment. The
Liebert SiteScan shall have the capability to monitor and change (at the user direction) the
temperature and humidity setpoints and sensitivities of each unit. The printer shall provide the user
with chronological alarm information. It shall also be capable of being programmed to print out
environmental conditions or operating modes at each unit.
Provide indicated quantities of the following:
• Leak Detection System(s) Model
• Remote Monitor(s) Model
• Auto-changeover Control(s) Model
2.4.9
Drycooler
The Liebert drycooler shall be a low-profile, direct-drive propeller fan-type air-cooled unit. The
drycooler shall be constructed with an aluminum cabinet and a copper-tube aluminum fin coil and
single direct drive fan. All electrical connections and controls shall be enclosed in an integral, NEMA
3R rated electrical panel section of the drycooler. The drycooler shall be quiet and corrosion resistant.
The drycooler shall be designed for _____°F (___°C) ambient.
2.4.10 Glycol Pump Package
The system shall include a centrifugal pump mounted in a weatherproof and vented enclosure. The
pump shall be rated for ____ GPM (l/s) at ____ ft. (kPa) of head, and operate on ____ volt, _____ phase,
____ Hz.
41
Liebert® Mini-Mate2™
Guide Specifications for Liebert Mini-Mate2—1- and 1.5-Ton Systems
3.0
EXECUTION
3.1
Installation of Air Conditioning Unit
3.1.1
General
Install air conditioning unit in accordance with manufacturer's installation instructions. Install unit
plumb and level, firmly anchored in location indicated, and maintain manufacturer's recommended
clearances.
3.1.2
Electrical Wiring
Install and connect electrical devices furnished by manufacturer but not specified to be factorymounted. Furnish copy of manufacturer’s electrical connection diagram submittal to electrical
contractor. Install and wire per local and national codes.
3.1.3
Piping Connections
Install and connect devices furnished by manufacturer but not specified to be factory-mounted.
Furnish copy of manufacturer’s piping connection diagram submittal to piping contractor.
3.1.4
Supply and Drain Water Piping
Connect water supply and drains to air conditioning unit. Unit drain shall be trapped internally and
shall not be trapped externally.
3.1.5
Field-Supplied Pan
A field-supplied pan with drain shall be installed beneath ducted cooling units.
3.2
Field Quality Control
Startup air conditioning unit in accordance with manufacturer's start up instructions. Test controls
and demonstrate compliance with requirements.
Liebert® Mini-Mate2™
42
Guide Specifications for Liebert Mini-Mate2—1- and 1.5-Ton Systems
NOTES
43
Liebert® Mini-Mate2™
Guide Specifications for Liebert Mini-Mate2—1- and 1.5-Ton Systems
Liebert® Mini-Mate2™
44
Ensuring The High Availability
Of Mission-Critical Data And Applications.
Emerson Network Power, a business of Emerson (NYSE:EMR),
is the global leader in enabling Business-Critical Continuity™
from grid to chip for telecommunication networks, data centers,
health care and industrial facilities. Emerson Network Power
provides innovative solutions and expertise in areas including
AC and DC power and precision cooling systems, embedded
computing and power, integrated racks and enclosures,
power switching and controls, infrastructure management,
and connectivity. All solutions are supported globally by local
Emerson Network Power service technicians. Liebert AC power,
precision cooling and monitoring products and services
from Emerson Network Power deliver Efficiency Without
Compromise™ by helping customers optimize their data center
infrastructure to reduce costs and deliver high availability.
Technical Support / Service
Web Site
www.liebert.com
Monitoring
[email protected]
800-222-5877
Outside North America: +00800 1155 4499
Single-Phase UPS & Server Cabinets
[email protected]
800-222-5877
Outside North America: +00800 1155 4499
Three-Phase UPS & Power Systems
800-543-2378
Outside North America: 614-841-6598
Environmental Systems
800-543-2778
Outside the United States: 614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
29/F, The Orient Square Building
F. Ortigas Jr. Road, Ortigas Center
Pasig City 1605
Philippines
+63 2 687 6615
Fax: +63 2 730 9572
While every precaution has been taken to ensure the accuracy
and completeness of this literature, Liebert Corporation assumes no
responsibility and disclaims all liability for damages resulting from use of
this information or for any errors or omissions.
© 2009 Liebert Corporation
All rights reserved throughout the world. Specifications subject to change
without notice.
® Liebert is a registered trademark of Liebert Corporation.
All names referred to are trademarks
or registered trademarks of their respective owners.
SL-10525_REV7_05-13
Emerson Network Power.
The global leader in enabling Business-Critical Continuity™
AC Power
Connectivity
Embedded Computing
Embedded Power
DC Power
Infrastructure Management & Monitoring
Outside Plant
Power Switching & Controls
Precision Cooling
EmersonNetworkPower.com
Racks & Integrated Cabinets
Services
Surge Protection
Emerson, Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks of Emerson Electric Co. or one of its affiliated companies.
©2009 Emerson Electric Co.