Liebert® Mini-Mate2 - Emerson Network Power

Liebert® Mini-Mate2™–2 & 3 Ton (7 & 10.5 kW) Capacity
Technical Data Manual–Air, Water, Glycol, Chilled Water, 50 & 60Hz
TABLE OF CONTENTS
1.0
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.1
Designed to Match Computer and Electronic Equipment Needs—From Installation
to Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2.0
STANDARD FEATURES—2 & 3 TON SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
2.1
Evaporator Section - Split Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.2
Condensing Unit Section—Split Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.2.1
2.2.2
2.2.3
Indoor Centrifugal Fan Condensing Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Outdoor Prop Fan Condensing Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Indoor Water/Glycol Condensing Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.3
Chilled Water Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.4
System Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.4.1
Other Standard Control Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3.0
OPTIONAL FACTORY-INSTALLED FEATURES—EVAPORATOR/CHILLED WATER UNITS . . . . . .4
3.1
Reheat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.2
Humidifier. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.3
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.4
Switches and Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.5
Free-Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.6
Optional Configurations—Prop Fan Condensing Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.7
Optional Configurations—Water/Glycol Condensing Units . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.8
Optional Configurations—Chilled Water Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4.0
SHIP-LOOSE ACCESSORIES—FIELD-INSTALLED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
4.1
Remote Monitoring, Autochangeover, and Leak Detection Equipment . . . . . . . . . . . . . . . . . 6
5.0
FLEXIBLE CONFIGURATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
6.0
AIR-COOLED SYSTEMS—CAPACITIES AND DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . .9
7.0
WATER/GLYCOL SYSTEMS—CAPACITIES AND DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . 16
8.0
CHILLED WATER SYSTEMS—CAPACITIES AND DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . 22
9.0
ELECTRICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
10.0
REFRIGERANT PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
11.0
GLYCOL LOOP PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
12.0
MODEL NUMBER NOMENCLATURE—ALL SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
GUIDE SPECIFICATIONS FOR LIEBERT MINI-MATE2—2- AND 3-TON SYSTEMS . . . . . . . . . . . . . . . . 43
1.0
2.0
3.0
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
PRODUCT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
EXECUTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
i
FIGURES
Figure 1
Figure 2
Figure 3
Figure 4
Figure 5
Figure 6
Figure 7
Figure 8
Figure 9
Figure 10
Figure 11
Figure 12
Figure 13
Figure 14
Figure 15
Figure 16
Figure 17
Figure 18
Figure 19
Figure 20
Figure 21
Figure 22
Figure 23
Figure 24
Figure 25
Figure 26
Figure 27
Figure 28
Wall-box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Free-cooling arrangement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Air-cooled condensing units—split systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Water/glycol condensing units—split systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Chilled water units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
General arrangement, air-cooled split systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Free-cooling arrangement, air-cooled units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Dimensions, evaporator units with direct drive blower . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Dimensions, evaporator units with optional belt drive blower assembly . . . . . . . . . . . . . . . . . . . 13
Dimensions, indoor air-cooled condensing unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Cabinet and floor planning dimensional data, outdoor condensing unit . . . . . . . . . . . . . . . . . . . . 15
General arrangement, water/glycol split systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
General arrangement, free-cooling coil with water/glycol condensing units . . . . . . . . . . . . . . . . . 18
Dimensions, evaporator units with direct drive blower . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Dimensions, evaporator units with optional belt drive blower assembly . . . . . . . . . . . . . . . . . . . 20
Cabinet dimensions and piping data, water/glycol indoor condensing module . . . . . . . . . . . . . . . 21
General arrangement, chilled water split systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
General arrangement, hot water reheat, chilled water units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Dimensions, chilled water units with direct drive blower . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Dimensions, chilled water units with optional belt drive blower assembly . . . . . . . . . . . . . . . . . 25
Single-point power kit - optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Refrigerant piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Heat rejection loop, multiple drycoolers and multiple indoor units. . . . . . . . . . . . . . . . . . . . . . . . 39
Model number nomenclature—Evaporator units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Model number nomenclature—Air-cooled, indoor condensing units . . . . . . . . . . . . . . . . . . . . . . . 40
Model number nomenclature—Outdoor air-cooled prop fan condensing units . . . . . . . . . . . . . . . 41
Model number nomenclature—Water/glycol-cooled condensing units. . . . . . . . . . . . . . . . . . . . . . 41
Model number nomenclature—Chilled water units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
ii
TABLES
Table 1
Table 2
Table 3
Table 4
Table 5
Table 6
Table 7
Table 8
Table 9
Table 10
Table 11
Table 12
Table 13
Table 14
Table 15
Table 16
Table 17
Table 18
Table 19
Table 20
Table 21
Table 22
Table 23
Table 24
Table 25
Table 26
Table 27
Table 28
Table 29
Table 30
Table 31
Table 32
Table 33
Table 34
Table 35
Air-cooled data, 60Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Air-cooled data, 50Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Net weights—split system evaporator units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Net weight, high static blower module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Dimensions and net weights, indoor air-cooled condensing units . . . . . . . . . . . . . . . . . . . . . . . . . 14
Dimensions and net weights—air-cooled outdoor condensing units . . . . . . . . . . . . . . . . . . . . . . . 15
Water/glycol data, 60Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Water/glycol data, 50Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Net weights—split system evaporator units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Net weight, high static blower module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Net weight, indoor water/glycol-cooled condensing unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Chilled water data, 60 and 50Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Capacity Correction Factors (based on 10°F (5.6°C) water rise) . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Chilled water units with direct drive blower weights. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Net weight, high static blower module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Direct drive split system evaporator or chilled water unit electrical data, 60Hz . . . . . . . . . . . . . 26
Belt drive split system evaporator or chilled water electrical data, with high static blower
box, 60Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Direct drive split system evaporator or chilled water electrical data, 50Hz . . . . . . . . . . . . . . . . . 28
Belt drive split system evaporator or chilled water electrical data, 50Hz. . . . . . . . . . . . . . . . . . . 28
Indoor condensing unit electrical data, 60 and 50Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Outdoor condensing unit electrical data, 60 and 50Hz. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Electrical data, 60Hz air-cooled systems using single-point power kit, evaporator with
direct-drive blowers and indoor condensing unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Electrical data, 60Hz air-cooled systems using single-point power kit, evaporator with
belt-drive blowers and indoor condensing unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Electrical data, 50Hz air-cooled systems using single-point power kit, evaporator with
direct-drive blowers and indoor condensing unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Electrical data, 50Hz air-cooled systems using single-point power kit, evaporator with
belt-drive blowers and indoor condensing unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Electrical data, 60Hz water/glycol-cooled systems using single-point power kit, evaporator
with direct-drive blowers and indoor condensing unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Electrical data, 60Hz water/glycol-cooled systems using single-point power kit, evaporator
with belt-drive blowers and indoor condensing unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Electrical data, 50Hz water/glycol-cooled systems using single-point power kit, evaporator
with direct-drive blowers and indoor condensing unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Electrical data, 50Hz water/glycol-cooled systems using single-point power kit, evaporator
with belt-drive blowers and indoor condensing unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Refrigerant charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Recommended refrigerant line sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Pipe length and condenser elevation relative to evaporator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Line charges - refrigerant per 100 ft. (30m) of Type L copper tube . . . . . . . . . . . . . . . . . . . . . . . . 37
Refrigerant charge in Liebert pre-charged R-407C line sets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Equivalent lengths for various pipe fittings, ft (m). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
iii
iv
Introduction
1.0
INTRODUCTION
1.1
Designed to Match Computer and Electronic Equipment Needs—From Installation
to Operation
Installed above the ceiling, Liebert Mini-Mate2 Thermal Management systems control the cooling,
humidity and air distribution required by sensitive electronic equipment. A range of sizes and
configurations is available to meet varying sites’ needs.
The Liebert Mini-Mate2 is also easy to use. Advanced microprocessor technology allows easy, precise
control, and menu-driven monitoring keeps you informed of system operation through the LCD
readout. These features, combined with Emerson quality construction and reliable components,
guarantee satisfaction from installation through operation.
Liebert Thermal Management
Liebert Thermal Management systems are designed to control the environment required for
computers and other sensitive electronic equipment. The Liebert Mini-Mate2 provides complete
control on a round-the-clock basis and the high sensible heat ratio required by sensitive electronic
equipment.
Easy Installation
The Liebert Mini-Mate2 is a split-system evaporator combined with an air-, water- or glycol-cooled
condensing unit or is a self-contained, chilled water unit. Each split system has thermostat-type
wiring to controls and condensing unit. System components are pre-charged with refrigerant and can
be connected together with optional pre-charged line sets or optional sweat adapters for field
refrigerant piping.
Easy to Service
Low-maintenance components are easily accessed through removable front panels. Spare parts are
always in Emerson inventory and available on short notice.
Advanced Control Technology
A menu-driven microprocessor control system provides precise temperature and humidity control and
accurate alarm setpoints. Using touch-sensitive buttons, the wall-mounted monitor/control panel
allows you to select and display temperature and other monitored parameters.
High Efficiency
High sensible heat ratio, scroll compressor and precise microprocessor control allow the system to
operate efficiently.
Space Saving Design
All indoor components are installed above the ceiling, so no floor space is required.
Reliable
The Liebert Mini-Mate2 family installed base is a testimony to the system reliability. Components
include a rugged scroll compressor, high-efficiency copper tube, aluminum-fin evaporator coil and a
double inlet, direct drive fan.
Agency Listed
Standard 60Hz units are CSA certified to the harmonized U.S. and
Canadian product safety standard, CSA C22.2 No 236/UL 1995 for
“Heating and Cooling Equipment” and are marked with the CSA c-us logo.
Location
When considering installation locations, consider that these units contain
water and that water leaks can cause damage to sensitive equipment
below. Do not mount these units above sensitive equipment. A fieldsupplied pan with drain must be supplied beneath cooling units and water/glycol condensers.
Do not mount units in areas where normal unit operating sound might disturb the working
environment.
1
Liebert® Mini-Mate2™
Standard Features—2 & 3 Ton Systems
2.0
STANDARD FEATURES—2 & 3 TON SYSTEMS
2.1
Evaporator Section - Split Systems
The evaporator section is designed for ceiling installation. The cabinet and chassis are constructed of
heavy gauge galvanized steel. The unit can be serviced using only one side increasing its versatility in
mounting locations. Mounting brackets are factory-attached to the cabinet. Internal cabinet
insulation meets ASHRAE 62.1 requirements for Mold Growth, Humidity & Erosion, tested per
UL 181 and ASTM 1338 standards.
The evaporator section includes the evaporator coil, R-407C unit charge, filter-drier, factory-mounted
disconnect switch, two-speed direct-drive blower assembly and microprocessor control with wallmounted control box. The unit is provided with supply and return air openings for field-supplied
ducting or supply/return plenum. Evaporators can be configured with canister humidifier and/or
reheat. An indoor or outdoor condensing unit must be selected for each evaporator.
2.2
Condensing Unit Section—Split Systems
2.2.1
Indoor Centrifugal Fan Condensing Units
Indoor Air-Cooled Centrifugal Fan Condensing Units include scroll compressor, factory-mounted
disconnect switch, condenser coil, R-407C unit charge, belt-driven centrifugal blower assembly,
high-pressure switch, Liebert Lee-Temp™ head pressure control system, hot gas bypass and liquidline solenoid valve. Unit must be mounted indoors. Condensing unit is designed to use outdoor air
with temperatures ranging from -30°F to 95°F (-34°C to 35°C).
2.2.2
Outdoor Prop Fan Condensing Units
Outdoor Prop Fan Condensing Units include scroll compressor, condenser coil, R-407C unit charge,
prop fan, liquid-line solenoid valve, high pressure switch, Liebert Lee-Temp head pressure control
and hot gas bypass. Condensing unit is designed for outdoor locations with operating ambients
ranging from -30°F to 95°F (-34°C to 35°C).
2.2.3
Indoor Water/Glycol Condensing Units
Indoor Water/Glycol Condensing Units includes scroll compressor, R-407C unit charge,
factory-mounted disconnect, coaxial condenser, hot gas bypass, high head pressure switch and
two-way water regulating valve designed for 150psi (1034.3kPa). Condensing units can be used on
either a water or glycol cooling loop.
2.3
Chilled Water Units
Chilled Water Units are designed for ceiling installation. The cabinet and chassis are constructed of
heavy gauge galvanized steel. The unit can be serviced using only one side increasing its versatility in
mounting locations. Mounting brackets are factory-attached to the cabinet. Internal cabinet
insulation meets ASHRAE 62.1 requirements for Mold Growth, Humidity & Erosion, tested per
UL 181 and ASTM 1338 standards. Chilled water models are self-contained and include a chilled
water coil, two-speed, direct-drive centrifugal blower, factory-mounted disconnect switch and twoway, slow-close motorized valve. Design pressure is 300psi (2068kPa), 60psi (414kPa) close-off
differential.
2
Liebert® Mini-Mate2™
Standard Features—2 & 3 Ton Systems
2.4
System Controls
System controls include a microprocessor control board mounted in the evaporator/chilled water unit
and a wall-mounted interface with a two-line, 16-character liquid crystal display. An eight-key,
membrane keypad for setpoint/program control, unit On/Off, fan speed and alarm silence is below the
LCD screen. It provides temperature setpoint and sensitivity adjustment, humidity setpoint and
sensitivity adjustment, digital display of temperature, humidity, setpoints, sensitivities, fan speed
and alarm conditions.
The wall-box is field-wired to the microprocessor control using standard four-conductor thermostat
wire (field-supplied). The temperature and humidity sensors are in the wall box, which can be
installed up to 300 feet (91.4m) from the evaporator unit. The unit-mounted control board also
includes common alarm terminals and shutdown terminals. The unit automatically restarts after a
power outage.
Figure 1
2.4.1
Wall-box
Other Standard Control Features
• Adjustable auto restart
• Calibrate sensors
• 5 day/2 day setback
• Predictive humidity control
• Password protection
• Common alarm output
• Alarm enable/disable
• Remote shutdown terminals
• Self-diagnostics
3
Liebert® Mini-Mate2™
Optional Factory-Installed Features—Evaporator/Chilled Water Units
3.0
OPTIONAL FACTORY-INSTALLED FEATURES—EVAPORATOR/CHILLED WATER
UNITS
3.1
Reheat
Electric Reheat includes 304/304 stainless steel finned tubular reheat elements, with high limit
safety switch.
SCR Electric Reheat uses an SCR controller and unit control software to provide full cooling with
modulating of the electric reheat elements to control air temperatures. Reheat capacity is up-sized to
offset the cooling capacity. (The SCR Electric Reheat is not available on chilled water, free-cooling or
575V units.)
Hot Water Reheat includes hot water coil, 2-way solenoid valve and Y-strainer.
NOTE
This option is available only on Chilled Water units, but not with other reheat options.
3.2
Humidifier
The Canister Humidifier includes a steam-generating type humidifier with automatic flushing
circuit, inlet strainer, drain, 1" (25.4mm) air gap on fill line and solenoid valves. Humidifier problem
alarm annunciates at the wall-mounted display panel.
Remote Humidifier Contact allows the unit’s humidity controller to control a humidifier outside
the unit. Power to operate the remote humidifier does not come from the Liebert Mini-Mate2.
Available on units with or without internal humidifier.
3.3
Sensors
Smoke Sensor checks return air, shuts down the unit upon sensing smoke and activates visual and
audible alarms at the wall-box display. This smoke sensor is not intended to function as or replace
any smoke sensor system that may be required by local or national codes.
High-Temperature Sensor senses the return air temperature and shuts down unit if the
temperature reaches 125°F (52°C). This device is not meant to replace any fire detection system that
may be required by local or national codes.
3.4
Switches and Motors
Filter Clog senses pressure drop across the filters and activates visual and audible alarms at the
wall-box display. The wall-box display annunciates the alarm and flashes a notification upon reaching
a customer setpoint.
A Factory-Installed Non-Fused Disconnect Switch allows unit to be turned off for maintenance.
A disconnect switch is standard for the evaporators, chilled water units and indoor condensing units,
but these units may be specified without the switch.
Direct-Drive blower can be factory-eliminated from the evaporator/chilled water cabinet for high
static applications (0.9 to 1.5in. [23 to 38mm] w.g.). See 4.0 - Ship-Loose Accessories—FieldInstalled for the optional, externally mounted high static blower assembly.
3.5
Free-Cooling
Free-cooling option includes separate cooling coil, three-way slow-close valve and separate supply and
return piping. Free-cooling is activated when the water temperature reaches a field-adjustable
temperature, typically 45°F (7°C). The valve is rated for 300psi (2068kPa) working pressure.
Air-cooled condensing units can be matched with evaporators using free-cooling coils with chilled
water sources to serve as backup cooling. When matched with a water/glycol condensing unit, a
three-way water regulating valve is recommended for the condensing unit to simplify piping to the
main supply pipes. The coil is designed for closed-loop applications using properly treated and
circulated fluid. Not available with SCR reheat options.
4
Liebert® Mini-Mate2™
Optional Factory-Installed Features—Evaporator/Chilled Water Units
Figure 2
Free-cooling arrangement
Drycooler
Free-cooling option: A second
cooling coil allows the system to take
advantage of colder outdoor
temperatures and bypass compressor
operation.
When the water temperature goes
below 45°F (7°C), cooling switches
over to free-cooling operation. A
separate chilled water source can
also be used with air-cooled systems.
Liebert Mini-Mate2
Free Cooling
Coil
Water Temperature
Sensor
Water/Glycol
Condenser
Field Piping
NOTE
If free-cooling is applied to an open water tower, an optional cupro-nickel (CuNi) coil is
required to prevent premature corrosion, or a heat exchanger must separate the tower water
from the free-cooling loop. The cupro-nickel coil requires an extended lead time.
3.6
Optional Configurations—Prop Fan Condensing Units
Outdoor Prop Fan Condensing Units are also available in the following optional configurations:
• High ambient models for providing catalog capacities at ambient temperatures up to 105°F
(40°C).
• Quiet-Line models for low noise level conditions (below 58 dBA) and for providing catalog
capacities at ambient temperatures up to 95°F (35°C).
• Condenser coils can be phenolic-coated for extended coil life in coastal areas.
3.7
Optional Configurations—Water/Glycol Condensing Units
Indoor Water/Glycol Condensing Units are also available with the following piping options:
• Two-way water reg. valve with 350 psi (2413kPa) design pressure.
• Three-way water reg. valve with 150psi (1034kPa) design pressure.
• Three-way water reg. valve with 350psi (2413kPa) design pressure.
3.8
Optional Configurations—Chilled Water Units
Chilled Water Units are also available with the following valve option:
• Three-way, slow-close, motorized chilled water valve rated for 300 psi (2068 kPa) working
pressure. Valve is non-spring return.
5
Liebert® Mini-Mate2™
Ship-Loose Accessories—Field-Installed
4.0
SHIP-LOOSE ACCESSORIES—FIELD-INSTALLED
A High Static Blower Assembly can be field-attached to the evaporator to provide up to 2.0"
(51mm) of external static pressure on the discharge side of the evaporator. The blower box contains a
centrifugal-type double-inlet blower. This blower is equipped with a belt drive and 1.5 hp single speed
motor mounted to an adjustable motor base. Note: Unit must be ordered without the internal direct
drive motor and the high static blower disables the two-speed fan operation feature.
Filter box kit (for ducted applications) includes filter box with duct flange connection, one
MERV 8 (ASHRAE 52.2-2007) filter (20"x20"x4" [508mm x 508mm x 102mm]), and a duct flange for
use on the supply air opening of the unit.
Air Distribution Plenum includes molded plastic three-way discharge plenum, 16"x25"x4"
(406mm x 535mm x 102mm) MERV 8 filter (ASHRAE 52.2-2007), and sheet metal block-off plates for
covering the duct openings on the evaporator unit. Plenum mounting requires T-bar ceiling grid.
The Condensate Pump is field-mounted external to the cabinet, wired to the unit power block and is
equipped with a check valve. A secondary float can be field-wired to shut down the unit upon high
condensate level.
A Remote Temperature and Humidity Sensor package includes sensors in an attractive case
with 30 ft. (9 m) of cable. Can be wall or duct mounted. Remote sensors should be used when the wall
box is not located in the space to be conditioned.
NOTE
Installing the remote sensors disables the sensors included in the wall box.
Field-Installed Kits available for filter clog, smoke sensor, high-temperature sensor, electric reheat
and humidifier. The kits include installation instructions and are designed to be added to the
evaporator unit before it is installed in the ceiling. Electric reheat kits cannot be installed in units
with free-cooling.
277-to-208V step-down transformer (37.5 amps) allows use of 277-1-60 supply power with a
208-1-60 Prop Fan Condensing unit. The transformer is coated with epoxy and contained in an
enclosed, non-ventilated electrical box with adaptable mounting brackets.
Single-Point Power Kit contains the necessary electrical components to interconnect the
high-voltage sections of a close-coupled evaporator and an MCD condensing unit.
Pre-Charged Refrigerant Line Set (R-407C) contains an insulated copper suction line and a
copper liquid line for interconnection of the indoor and outdoor sections. Available in 15-foot (4.5m)
and 30-foot (9m) sections.
The Refrigerant-Line Sweat Adapter Kit contains two suction and two liquid line fittings that
allow field-supplied refrigerant piping between the evaporator and condensing unit.
4.1
Remote Monitoring, Autochangeover, and Leak Detection Equipment
The Liebert RCM4™ is a four-point, normally open, dry contact monitoring panel. One Form-C, dry
contact common alarm relay output (rated at 24 VAC, 3 Amp) is provided. Four red LEDs illuminate
on the respective alarm and the alarm buzzer is silenced by a front panel switch. The RCM4 requires
a 24VAC or 24VDC power source. Power supply is not included.
The Liebert AC4™ Autochangeover Controller provides autochangeover and autosequence
control for up to four Liebert Mini-Mate2 units within a room. The Liebert AC4 will enable redundant
units in an alarm condition, balance usage and test standby units at programmed intervals. Two
common alarm relay outputs are available. A built-in LCD and RS-232 port for direct PC/terminal
connection provides two options for configuration and monitoring of the product. The Liebert AC4
requires 24VAC input power.
Liebert® Mini-Mate2™
6
Ship-Loose Accessories—Field-Installed
The Liebert® AC8™ is ideal for coordinated control of systems with redundant units. The Liebert
AC8 enables redundant devices during an alarm condition, balances usage of devices and tests
standby devices at programmable intervals. Supports four zones and can use the 4-20mA
temperature sensor (TW420) for temperature staging in each zone. Two programmable output control
relays are available for auxiliary control such as humidity lockout. Emergency power operation input
provided for device control during an emergency. Two common alarm relay outputs are available. A
built-in LCD and RS-232 port for direct PC/terminal connection provides two options for configuration
and monitoring of the product.
The Liebert ENV-DO™ interface card provides 16 discrete outputs, corresponding to status and
major alarm conditions of Environmental units. The Liebert ENV-DO-ENCL1 packages one
Environmental DO interface card in its own steel enclosure and the ENV-DO-ENCL2 packages two
Environmental DO interface cards in one enclosure for installation external to the Liebert
Mini-Mate2™. The self-contained kit includes an external 120VAC-to-24VAC power transformer.
Wiring harnesses are not provided. Power and communication wiring is field-provided.
The Liebert Liqui-tect® 410 Point Leak Detection Sensor detects the presence of conductive
liquid using a pair of corrosion-resistant, gold-plated probes mounted in a painted, height-adjustable
enclosure. Dual Form-C, dry contact common alarm relays (rated at 24VAC, 3A) signal a leak
detected as well as loss of power and cable fault. The Liebert Liqui-tect 410 requires an external
24VAC or 24VDC power source.
Liebert LT460 Zone Leak Detection Kits include one LT460 sensor, a specified length of
LT500-xxY cable (maximum length is 100 ft [30.5m]) and a corresponding number of hold-down clips.
The Liebert LT460 requires an external 24VAC, 0.12A power source, such as EXT-XFMR or XFMR24.
Liebert SiteScan® is a monitoring solution that gives you decision-making power to effectively
manage the equipment critical to your business.
Liebert SiteScan enables communication from Liebert environmental and power units, as well as
many other pieces of analog or digital equipment, to a front-end software package that provides
real-time status and alarms so you can react quickly to changing situations.
Liebert SiteScan is designed with flexibility for both small systems and large, complex systems such
as those in computer rooms, telecommunications facilities or industrial process control rooms.
Contact your local Emerson representative for assistance with a Liebert SiteScan system.
The NIC-ENCL1 and NIC-ENCL2 package one or two Liebert IntelliSlot® Web/485 Cards with
Adapters, respectively, in one steel enclosure for installation external to the Liebert Mini-Mate2. The
Liebert IntelliSlot Web/485 Card with Adapter provides communication with Liebert Mini-Mate2 via
SNMP, HTTP, RTU Modbus 485 and BACnet IP. The self-contained kit includes an external
120VAC-to-24VAC transformer as a power source. Wiring harnesses are not provided. Power and
communication wiring is field-provided.
7
Liebert® Mini-Mate2™
Flexible Configurations
5.0
FLEXIBLE CONFIGURATIONS
Figure 3
Air-cooled condensing units—split systems
Air Plenum
Figure 4
Air Ducted
Water/glycol condensing units—split systems
Air Plenum
Figure 5
Air Ducted
Chilled water units
Air Ducted
Air Plenum
Liebert® Mini-Mate2™
8
Air-Cooled Systems—Capacities and Dimensions
6.0
Table 1
AIR-COOLED SYSTEMS—CAPACITIES AND DIMENSIONS
Air-cooled data, 60Hz
MMD24E or MMD24K
Evaporator Model
Condensing Unit Type
DX Evaporator- Net Capacity Data - kW (Btuh) @ High Speed CFM
Total
80°F DB, 62.8°F WB (26.7°C DB, 17.1°C WB) 38%RH
Sensible
Total
75°F DB, 61°F WB (23.9°C DB, 16.1°C WB) 45%RH
Sensible
Total
72°F DB, 60°F WB (22.2°C DB, 15.5°C WB) 50%RH
Sensible
Fan Data - Evaporator
CFM (CMH) - High Speed
CFM (CMH) - Low Speed
Fan Motor, HP (W)
External Static Pressure, in (mm) water gauge
Evaporator Coil - Copper Tube/Aluminum Fin
Face Area, ft2 (m2)
Coil Rows
Max Face Velocity, fpm (m/s)
Unit Refrigerant Charge, oz. (kg)
Unit Operating Weight
Electric Reheat Capacity (Includes Fan Motor), kW (Btuh)
Input Voltage 208-1-60
Input Voltage 230-1-60
Input Voltage 277-1-60
Input Voltage 208-3-60
Input Voltage 230-3-60
Input Voltage 460-3-60
Humidifier Data - Steam Generator Type
Steam capacity, lb/hr (kg/hr)
Electrical Input Power, kW
Evaporator Connection Sizes
Liquid line Diameter - Aeroquip Coupling Size
Suction Line Diameter - Aeroquip Coupling Size
Humidfier Supply
Evaporator/Condensate Drain
MERV 8 Filter, External Filter Box, qty (1), Nom. Size, in. (mm)
MERV 8 Filter, Air Distribution Plenum, qty (1), Nom. Size-in. (mm)
Condensing Unit Model Number
Condensing Unit Rating Conditions
MMD36E or MMD36K
PFH - Outdoor
MCD - Indoor
PFH - Outdoor
MCD - Indoor
6.70 (22,900)
6.50 (22,200)
6.40 (21,800)
5.70 (19,500)
6.20 (21,200)
5.20 (17,800)
6.50 (22,200)
6.35 (21,700)
6.15 (20,900)
5.60 (19,100)
5.95 (20,300)
5.10 (17,400)
9.90 (33,800)
9.40 (32,100)
9.55 (32,500)
8.30 (28,400)
9.30 (31,800)
7.70 (26,200)
9.35 (31,900)
9.10 (31,000)
8.95 (30,600)
8.05 (27,500)
8.75 (29,900)
7.40 (25,300)
885 (1504)
800 (1359)
0.5 (0.38)
0.3 (8)
1250 (2124)
1000 (1699)
0.5 (0.38)
0.3 (8)
3.1 (0.29)
3
277 (1.4)
7 (0.20)
225 (102)
3.1 (0.29)
3
394 (2.0)
7 (0.20)
225 (102)
Standard
SCR
Standard
SCR
4.7 (16040)
5.8 (19800)
6.3 (21500)
5.6 (19100)
6.8 (23200)
7.3 (24900)
4.7 (16040)
5.8 (19800)
6.3 (21500)
5.6 (19100)
6.8 (23200)
7.3 (24900)
7.9 (27000)
9.5 (32400)
10.3 (35200)
7.9 (27000)
9.5 (32400)
10.3 (35200)
N/A
4.3 (2.0)
1.5
4.3 (2.0)
1.5
3/8" - #6 Female
3/8" - #6 Female
7/8" - #11 Female
7/8" - #11 Female
1/4" OD Copper Compression Fitting
3/4" NPT-Female
4x20x20 (102x508x508)
4x16x25 (102x406x635)
PFH027A-_L7
MCD24AL_H7
PFH037A-_L7
MCD36AL_H7
95°F (35°C) Ambient
Coil Face Area ft2 (m2)
4.1 (0.38)
4.6 (0.43)
7.7 (0.72)
4.6 (0.43)
Rows of Coil
2
2
2
3
CFM (CMH)
2200 (3738)
1000 (1698)
3000 (5097)
1430 (2429)
Motor Hp (W)
0.20 (149)
0.33 (246)
0.20 (149)
0.5 (373)
External Static Pressure, in wg. (mm)
N/A
0.50 (13)
N/A
0.50 (13)
Unit Refrigerant Charge, oz. (kg)
134 (3.8)
134 (3.8)
213 (6.0)
213 (6.0)
Unit Operating Weight, lb. (kg)
200 (91)
230 (104)
241 (109)
240 (109)
Free-Cooling Coil Option Net Capacity Data - kW (Btuh) using 45°F EWT
Total
7.10 (24,200)
9.50 (32,400)
80°F DB, 62.8°F WB (26.7°C DB, 17.1°C WB) 38%RH
Sensible
6.60 (22,600)
9.05 (30,800)
Total
6.15 (20,900)
8.20 (28,000)
75°F DB, 61°F WB (23.9°C DB, 16.1°C WB) 45%RH
Sensible
5.55 (18,900)
7.60 (25,900)
Total
5.55 (18,900)
7.45 (25,400)
72°F DB, 60°F WB (22.2°C DB, 15.5°C WB) 50%RH
Sensible
4.85 (16,600)
6.70 (22,900)
Flow Rate, GPM (l/m)
4.5 (17.1)
5.9 (22.4)
Pressure Drop, ft. water (kPa)
5.6 (16.7)
9.1 (27.2)
Free-Cooling Coil - Copper Tube/Aluminum Fin
Face Area, ft2 (m2)
3.1 (0.28)
3.1 (0.28)
Coil Rows
3
3
Max Face Velocity, fpm (m/s)
294 (1.5)
394 (2.0)
Internal Fluid Volume, gal (l)
2.0 (7.6)
2.0 (7.6)
Water supply/return connections, in (mm) OD
7/8 (22.2)
7/8 (22.2)
The net capacity data has fan motor heat factored in for all ratings and the entering air conditions of 75°F (23.9°C), 45%RH, is the standard rating condition for
ASHRAE 127-2007. All capacities are nominal values; actual performance will be ±5%.
Liebert® Mini-Mate2™
9
Air-Cooled Systems—Capacities and Dimensions
Table 2
Air-cooled data, 50Hz
MMD35E or MMD35K
Evaporator Model
Condensing Unit Type
DX Evaporator- Net Capacity Data - kW (Btuh) @ High Speed CFM
80°F DB, 62.8°F WB (26.7°C DB, 17.1°C WB) 38%RH
75°F DB, 61°F WB (23.9°C DB, 16.1°C WB) 45%RH
72°F DB, 60°F WB (22.2°C DB, 15.5°C WB) 50%RH
Total
Sensible
Total
Sensible
Total
Sensible
PFH - Outdoor
MCD - Indoor
9.95 (34,000)
9.40 (32,100)
9.60 (32,700)
8.35 (28,500)
9.35 (31,900)
7.70 (26,200)
9.50 (32,400)
9.15 (31,300)
9.10 (31,100)
8.15 (27,800)
8.90 (30,400)
7.45 (25,500)
Fan Data - Evaporator
CFM (CMH) - High Speed
CFM (CMH) - Low Speed
Fan Motor HP (W)
External Static Pressure, in (mm) water gauge
Evaporator Coil - Copper Tube/Aluminum Fin
Face Area, ft2 (m2)
Coil Rows
Max Face Velocity, fpm (m/s)
Unit Refrigerant Charge, oz. (kg)
Unit Operating Weight, lb (kg)
Electric Reheat Capacity (Includes Fan Motor)-kW (Btuh)
Input Voltage 220-1-50
Input Voltage 380-3-50
SCR Reheat Capacity (Includes Fan Motor)-kW (Btuh)
Input Voltage 220-1-50
Input Voltage 380-3-50
Humidifier Data - Steam Generator Type
Steam capacity lb/hr (kg/hr)
Electrical Input Power, kW
Evaporator Connection Sizes
Liquid line Diameter - Aeroquip Coupling Size
Suction Line Diameter - Aeroquip Coupling Size
Humidifier Supply
Evaporator/Condensate Drain
MERV 8 Filter, External Filter Box, qty (1), Nom. Size, in. (mm)
MERV 8 Filter, Air Distribution Plenum, qty (1), Nom. Size, in. (mm)
Condensing Unit Model Number
1250 (2124)
1000 (1699)
0.5 (0.38)
0.3 (8)
3.1 (0.29)
3
394 (2.0)
7 (0.20)
225 (102)
5.3 (18090)
7.3 (24900)
8.7 (29700)
10.3 (35100)
4.3 (2.0)
1.5
3/8" - #6 Female
7/8" - #11 Female
1/4" OD Copper Compression Fitting
3/4" NPT-Female
4x20x20 (102x508x508)
4x16x25 (102x406x635)
PFH036A-_L7
MCD35AL_H7
Condensing Unit Rating Conditions
95°F (35°C) Ambient
Coil Face Area, ft2 (m2)
7.7 (0.72)
4.6 (0.43)
Rows of Coil
2
3
CFM (CMH)
2500 (4248)
1430 (2429)
Motor, Hp (W)
0.20 (149)
0.5 (373)
External Static Pressure, in wg. (mm)
N/A
0.50 (13)
Unit Refrigerant Charge, oz. (kg)
213 (6.0)
213 (6.0)
Unit Operating Weight, lb. (kg)
241 (109)
240 (109)
Free-Cooling Coil Option Net Capacity Data - kW (Btuh) using 45°F EWT
Total
9.50 (32,400)
80°F DB, 62.8°F WB (26.7°C DB, 17.1°C WB) 38%RH
Sensible
9.05 (30,800)
Total
8.20 (28,000)
75°F DB, 61°F WB (23.9°C DB, 16.1°C WB) 45%RH
Sensible
7.60 (25,900)
Total
7.45 (25,400)
72°F DB, 60°F WB (22.2°C DB, 15.5°C WB) 50%RH
Sensible
6.70 (22,900)
Flow Rate - GPM (l/m)
5.9 (22.4)
Pressure Drop - ft. water (kPa)
9.1 (27.2)
Free-Cooling Coil - Copper Tube/Aluminum Fin
Face Area ft2 (m2)
3.1 (0.28)
Coil Rows
3
Max Face Velocity-fpm (m/s)
394 (2.0)
Internal Fluid Volume - gal (l)
2.0 (7.6)
Water supply and return connections, in (mm) OD
7/8 (22.2)
The net capacity data has fan motor heat factored in for all ratings and the entering air conditions of 75°F (23.9°C), 45%RH, is the standard rating
condition for ASHRAE 127-2007. All capacities are nominal values; actual performance will be ±5%.
Liebert® Mini-Mate2™
10
Air-Cooled Systems—Capacities and Dimensions
Figure 6
General arrangement, air-cooled split systems
Condenser
Coil
High Pressure
Switch
Scroll
Compressor
Liquid Injection
Valve Bulb
Hot Gas Bypass
Solenoid Valve
Suction Line Male Quick
Connect Coupling
Suction Line Female Quick
Connect Coupling
*
Sensing Bulb
External Equalizer
3/8" SAE 45° Male Flare
(MCD) or Atmospheric (PFH)
Pressure Relief Valve
ad
ay He
3 - W re
su
Pres Valve
lief
e
R
pass
as By
Hot G Valve
l
Contro
Check
Valve
Sight Glass
Liquid Injection
Valve
Service Access
Ports
Liquid Line
Solenoid Valve
*
Receiver
Heater
Pressure
Limiting
Switch
Liquid Line Male Quick
Connect Coupling
Liquid Line Female Quick
Connect Coupling
Expansion Valve
* Use Liebert sweat adapter kit with field
hard piping or use Liebert pre-charged
line set. Close-coupling option
available with MCD.
Lee - Temp
Receiver
Pressure Balancing
Valve
Field Piping
Factory Piping
DPN000191
Rev. 2
Evaporator Coil
Figure 7
Free-cooling arrangement, air-cooled units
Bleed Valve
Fluid
Return
Fluid
Supply From Unit
To Unit
Shutoff
Valves *
Free-Cooling
Control
Valve
Free Cooling
Coil
Temperature Stat
FIELD PIPING
Hose
Bibs *
FACTORY PIPING
* Components are not supplied
by Liebert but are recommended
for proper circuit operation and
maintenance.
Liebert® Mini-Mate2™
11
DPN000197
Rev. 2
Air-Cooled Systems—Capacities and Dimensions
Figure 8
Dimensions, evaporator units with direct drive blower
1-7/16"
1"
(25.4mm)
3-7/8"
(98mm)
11"
(279mm)
20" (50
15"
(381mm)
1-7/16"
(37mm)
10-7/8"
(276mm)
Removable
Access
Panels
Optional discharge air
duct flange supplied when
optional filter box is ordered
18"
(457mm)
18" (457mm)
14"
(356mm)
24"
(610mm)
18"
Cabinet (457mm)
Dimension
8mm)
18" (457mm)
54"
(1372mm)
Cabinet
57-13/16"
Dimension
(1468mm)
19-7/8"
(505mm)
Hanging
Bracket
18"
(457mm)
Duct
Flange
14"
(356mm)
Customer-Supplied (37mm)
30"
Threaded Rods for
(762mm)
Module Suport from
Cabinet
Ceiling (Typ. 4)
Dimension
27-13/16"
(706mm)
11-1/8"
Threaded Rod
(283mm)
Centers
14"
(356mm)
3/4"
(19mm)
Cabinet Outline
1"
(25.4mm)
Filter Box (optional)
Cover Plate
Supplied With
Plenum
55-13/16"
(1418mm)
Threaded
Rod
Centers
11-5/8"
(295mm)
7/8" (22mm) holes
for module rigging
(typ. 2 each end).
Shaded area
indicates a recommended
clearance of 30" (762mm)
for access and filter removal
Cabinet Dimension
same as above
Overall
Dimension
Shaded area indicates a
recommended clearance
of 30" (762mm) for access
and filter removal
Note: Unit is spaced evenly in
reference to threaded rod centers
Module Dimensions
Removable panel on
side of plenum.
Minimum clearance
30" (762mm) for flter
access and removal
6" (152mm)
5"
(127mm)
Air Discharge out
sides of plenum
48"
(1219mm)
Overall
Dimension
24"
(610mm)
Overall
Dimension
Air Discharge out
Sides of Plenum
3-1/4"
(83mm)
Air Inlet through
grille in center of plenum
Optional Air Distribution Plenum
All piping and electrical field connections are the same
Table 3
Net weights—split system evaporator units
Model #
60Hz
50Hz
Weight, lb (kg)
MM*24E
—
225 (102)
MM*24K
—
245 (111)
MM*36E
MM*35E
225 (102)
MM*36K
MM*35K
245 (111)
Liebert® Mini-Mate2™
12
DPN000193
Rev. 3
Air-Cooled Systems—Capacities and Dimensions
Figure 9
Dimensions, evaporator units with optional belt drive blower assembly
29-7/8" (759mm)
Threaded
Rod Centers
16-13/16" (427mm)
Threaded Rod Centers
57-13/16" (1468mm)
Overall Dimension
30" (762mm)
Blower Box
Dimension
19" (483mm)
Blower Box
Dimension
55-13/16" (1418mm)
Threaded Rod Centers
High Static
Blower
Module
9-3/4" Outlet
(248mm)
Evaporator
Unit
24" (610mm)
Cabinet
Dimension
5-7/8"
(149mm)
6-7/8" (175mm)
6-5/16" (160mm) Outlet
4-29/32" (125mm)
Threaded Rod
To Threaded Rod
3-7/32"
(82mm)
Base to
Base
4-29/32" (125mm)
Cabinet to Cabinet
54" (1372mm)
Cabinet Dimension
14"
(356mm)
Outlet
Dimension
30" (762mm)
Cabinet
Dimension
18 "
(457mm)
Outlet
Dimension
DPN000194
Rev. 3
Table 4
Net weight, high static blower module
Unit
High Static
Blower Module
Liebert® Mini-Mate2™
Net Weight
lb (kg)
85 (39)
13
Air-Cooled Systems—Capacities and Dimensions
Figure 10 Dimensions, indoor air-cooled condensing unit
Customer Supplied
Threaded Rods
for Module Support
from Ceiling (typ. 4)
22-3/4" (578mm)
Overall Dimension
21-1/2 " (546mm)
Cabinet Dimension
19-1/2" (495mm)
Threaded Rod
Centers
50-1/4" (1276mm)
Overall Dimension
46-1/2" (1181mm)
Cabinet Dimension
48- 1/4" (1225mm)
Threaded Rod Centers
C
1/2" (13mm)
D
20-3/4"
(527mm)
22-1/2"
(572mm)
Cabinet
Dimension
20-7/16"
(519mm)
Coil Inlet
Duct Conn.
B
Integral
Hanging Bracket
Minimum Clearance 33" (838mm)
This End for Component Access
and Removal
Duct Flange
1"
(25.4mm)
Air Outlet
Duct Dimension
A
Blower Motor Service Access
Panel on Bottom of Unit
Minimum Clearance 33" (838mm)
for Component Access and Removal.
30-1/8"
(765mm)
Coil Inlet
Duct Connection
Holes for Module
Rigging (typ. 2 each end)
Air Outlet
Duct Connection
2-1/4"
(57mm)
Note: Unit is evenly spaced in
reference to threaded rod centers.
DIMENSIONAL DATA
7/8" (22.2mm) Dia.
Electrical Entrance
for Line Voltage
Connection.
7/8" (22.2mm) Dia.
Electrical Entrance
for Low Voltage
Connection.
Suction Line
Male Quick
Connect
Liquid Line Male
Quick Connect
DPN000206
Rev. 1
Table 5
Dimensions and net weights, indoor air-cooled condensing units
Dimensions, in (mm)
Model #
A
B
C
D
1- 7/16 (37)
11-7/16 (290)
1/2 (13)
20-7/16 (519)
MC*24A
MC*23A
MC*36A
Net Weight
lb (kg)
230 (104)
240 (109)
MC*35A
Liebert® Mini-Mate2™
14
Air-Cooled Systems—Capacities and Dimensions
Figure 11
Cabinet and floor planning dimensional data, outdoor condensing unit
Fan Rotation
CCW
(left side)
Removable (right) panel
for access to
refrigeration component
A
Right Air Discharge
Left Air Intake
Shaded area
indicates a minimum
clearance of 18" (457mm)
for proper air flow.
B
Shaded area
indicates a recommended
clearance of 24" (610mm)
for component access and
removal.
C
Shaded area
indicates a minimum
clearance of 18" (457mm)
for proper air flow
Table 6
Removable panel for access
to high-voltage and low-voltage
connections and refrigeration
components
Dimensions and net weights—air-cooled outdoor condensing units
Model Numbers
60Hz
50Hz
A
B
C
Module Net
Weight
lb (kg)
PFH027A-L
—
40 (1016)
23-1/2 (597)
18 (457)
200 (91)
PFH027A-H
—
48 (1219)
31 (787)
18 (457)
241 (109)
53 (1343)
36-1/4 (918)
18 (457)
351 (159)
PFHZ27A-L
—
PFH037A-L
PFH036A-L
PFH037A-H
PFH036A-H
PFHZ37A-L
PFHZ36A-L
Liebert® Mini-Mate2™
Dimensional Data, inches (mm)
15
DPN000130
Rev. 1
Water/Glycol Systems—Capacities and Dimensions
7.0
Table 7
WATER/GLYCOL SYSTEMS—CAPACITIES AND DIMENSIONS
Water/glycol data, 60Hz
MMD24E or MMD24K
Evaporator Model
Water-Cooled
Glycol-Cooled
Condensing Unit Fluid
DX Evaporator - Net Capacity Data - kW (Btuh) @ High Speed CFM
Total
7.60 (26,000)
6.25 (21,300)
80°F DB, 62.8°F WB (26.7°C DB,
17.1°C WB) 38%RH Sensible
6.95 (23,700)
6.20 (21,200)
Total
7.30 (24,900)
5.90 (20,200)
75°F DB, 61°F WB (23.9°C DB, 16.1°C
WB) 45%RH Sensible
6.15 (20,900)
5.50 (18,800)
Total
7.10 (24,300)
5.75 (19,700)
72°F DB, 60°F WB (22.2°C DB, 15.5°C
WB) 50%RH Sensible
5.65 (19,300)
5.00 (17,100)
Fan Data - Evaporator
CFM (CMH), High Speed
885 (1504)
CFM (CMH), Low Speed
800 (1359)
Fan Motor, hp (W)
0.5 (0.38)
External Static Pressure, in (mm) water gauge
0.3 (8)
Evaporator Coil - Copper Tube/Aluminum Fin
Face Area, ft2 (m2)
3.1 (0.29)
Coil Rows
3
Max Face Velocity, fpm (m/s)
277 (1.4)
Unit Refrigerant Charge, oz. (kg)
7 (0.20)
Unit Operating Weight, lb (kg)
225 (102)
Electric Reheat Capacity
Standard
SCR
(Includes Fan Motor), kW (Btuh)
Input Voltage 208-1-60
Input Voltage 230-1-60
Input Voltage 277-1-60
Input Voltage 208-3-60
Input Voltage 230-3-60
Input Voltage 460-3-60
Humidifier Data - Steam Generator Type
Steam capacity - lbs/hr (kg/hr)
Electrical Input Power, kW
Evaporator Connection Sizes
Liquid line Diameter - Aeroquip Coupling Size
Suction Line Diameter - Aeroquip Coupling Size
Humidifier Supply
Evaporator/Condensate Drain
MERV 8 Filter, External Filter Box, qty (1), Nom.
Size, in. (mm)
MERV 8 Filter, Air Distribution Plenum, qty (1), Nom.
Size, in. (mm)
4.7 (16040)
5.8 (19800)
6.3 (21500)
5.6 (19100)
6.8 (23200)
7.3 (24900)
N/A
N/A
MMD36E or MMD36K
Water-Cooled
Glycol-Cooled
11.0 (37,600)
9.95 (33,900)
10.6 (36,300)
8.85 (30,200)
10.4 (35,500)
8.20 (27,900)
9.05 (30,900)
8.95 (30,500)
8.70 (29,600)
7.95 (27,100)
8.45 (28,900)
7.30 (24,900)
1250 (2124)
1000 (1699)
0.5 (0.38)
0.3 (8)
3.1 (0.29)
3
394 (2.0)
7 (0.20)
225 (102)
Standard
SCR
4.7 (16040)
5.8 (19800)
6.3 (21500)
5.6 (19100)
6.8 (23200)
7.3 (24900)
7.9 (27000)
9.5 (32400)
10.3 (35200)
7.9 (27000)
9.5 (32400)
10.3 (35200)
4.3 (2.0)
1.5
4.3 (2.0)
1.5
3/8" - #6 Female
7/8" - #11 Female
1/4" OD Copper Compression Fitting
3/4" NPT-Female
3/8" - #6 Female
7/8" - #11 Female
1/4" OD Copper Compression Fitting
3/4" NPT-Female
4x20x20 (102x508x508)
4x20x20 (102x508x508)
4x16x25 (102x406x635)
4x16x25 (102x406x635)
MCD26W
MCD38W
Condensing Unit Model Number
Condenser Fluid Requirements 85°F (29.4°C) EWT 110°F (43.3°C) EGT - 40% PG 85°F (29.4°C) EWT 110°F (43.3°C) EGT - 40% PG
THR - kW (Btuh) @ 75F/45%RH
9.55 (32,500)
9.05 (30,800)
13.7 (46,700)
13.0 (44,400)
Flow Rate, GPM (l/m)
8.1 (30.7)
8.5 (32.2)
6.6 (25.0)
10.9 (41.3)
Pressure Drop, ft. of H20 (kPa)
17.8 (53.2)
23.9 (71.5)
12.3 (36.8)
36.1 (107.9)
Water-Cooled Condensing Temperature
105°F (40.6°C)
N/A
105°F (40.6°C)
N/A
Connection Sizes, in. (mm) OD
7/8 (22.2)
7/8 (22.2)
Unit Volume, Gal (l)
1.2 (4.5)
1.2 (4.5)
Unit Refrigerant Charge, oz. (kg)
41 (1.16)
54 (1.54)
Unit Operating Weight, lb. (kg)
175 (79)
220 (100)
Free-Cooling Coil Option Net Capacity Data - kW (Btuh) using 45°F EWT
Entering Fluid Conditions 45°F (29.4°C) EWT
45°F EGT - 40% PG
45°F (29.4°C) EWT
45°F EGT - 40% PG
Total
7.10 (24,200)
5.85 (19,900)
9.50 (32,400)
7.90 (26,900)
80°F DB, 62.8°F WB (26.7°C DB, 17.1°C
WB) 38%RH Sensible
6.60 (22,600)
5.85 (19,900)
9.05 (30,800)
7.90 (26,900)
Total
6.15 (20,900)
4.90 (16,800)
8.20 (28,000)
6.70 (22,800)
75°F DB, 61°F WB (23.9°C DB, 16.1°C
WB) 45%RH Sensible
5.55 (18,900)
4.90 (16,800)
7.60 (25,900)
6.70 (22,800)
Total
5.55 (18,900)
4.45 (15,100)
7.45 (25,400)
6.00 (20,400)
72°F DB, 60°F WB (22.2°C DB, 15.5°C
WB) 50%RH Sensible
4.85 (16,600)
4.35 (14,900)
6.70 (22,900)
6.00 (20,400)
Flow Rate - GPM (l/m)
4.5 (17.1)
8.5 (32.2)
5.9 (22.4)
10.9 (41.3)
Pressure Drop, ft. water (kPa)
5.6 (16.7)
23.9 (71.5)
9.1 (27.2)
36.2 (108.2)
Free-Cooling Coil - Copper Tube/Aluminum Fin
Face Area, ft2 (m2)
3.1 (0.28)
3.1 (0.28)
Coil Rows
3
3
Max Face Velocity, fpm (m/s)
294 (1.5)
394 (2.0)
Internal Fluid Volume, gal (l)
2.0 (7.6)
2.0 (7.6)
Water supply and return connections, in (mm) OD
7/8 (22.2)
7/8 (22.2)
The net capacity data has fan motor heat factored in for all ratings and the entering air conditions of 75°F (23.9°C), 45%RH, is the standard rating condition for
ASHRAE 127-2007. All capacities are nominal values; actual performance will be ±5%.
Liebert® Mini-Mate2™
16
Water/Glycol Systems—Capacities and Dimensions
Table 8
Water/glycol data, 50Hz
MMD35E or MMD35K
Evaporator Model
Condensing Unit Fluid
DX Evaporator- Net Capacity Data - kW (Btuh) @ High Speed CFM
Total
80°F DB, 62.8°F WB (26.7°C DB, 17.1°C WB) 38%RH
Sensible
Total
75°F DB, 61°F WB (23.9°C DB, 16.1°C WB) 45%RH
Sensible
Total
72°F DB, 60°F WB (22.2°C DB, 15.5°C WB) 50%RH
Sensible
Fan Data - Evaporator
CFM (CMH), High Speed
CFM (CMH), Low Speed
Fan Motor HP (W)
External Static Pressure, in (mm) water gauge
Evaporator Coil - Copper Tube/Aluminum Fin
Face Area, ft2 (m2)
Coil Rows
Max Face Velocity, fpm (m/s)
Unit Refrigerant Charge, oz. (kg)
Unit Operating Weight, lb (kg)
Electric Reheat Capacity (Includes Fan Motor)-kW (Btuh)
Input Voltage 220-1-50
Input Voltage 380-3-50
SCR Reheat Capacity (Includes Fan Motor)-kW (Btuh)
Input Voltage 220-1-50
Input Voltage 380-3-50
Humidifier Data - Steam Generator Type
Steam capacity - lbs/hr (kg/hr)
Electrical Input Power, kW
Evaporator Connection Sizes
Liquid line Diameter - Aeroquip Coupling Size
Suction Line Diameter - Aeroquip Coupling Size
Humidifier Supply
Evaporator/Condensate Drain
MERV 8 Filter, External Filter Box, qty (1), Nom. Size, in. (mm)
MERV 8 Filter, Air Distribution Plenum, qty (1), Nom. Size, in. (mm)
Condensing Unit Model Number
Water-Cooled
Glycol-Cooled
11.3 (38,700)
10.1 (34,400)
11.0 (37,400)
9.00 (30,700)
10.7 (36,600)
8.30 (28,400)
9.20 (31,400)
9.00 (30,700)
8.80 (30,100)
8.00 (27,300)
8.60 (29,400)
7.35 (25,100)
1250 (2124)
1000 (1699)
0.5 (0.38)
0.3 (8)
3.1 (0.29)
3
394 (2.0)
7 (0.20)
225 (102)
5.3 (18090)
7.3 (24900)
8.7 (29700)
10.3 (35100)
4.3 (2.0)
1.5
3/8" - #6 Female
7/8" - #11 Female
1/4" OD Copper Compression Fitting
3/4" NPT-Female
4x20x20 (102x508x508)
4x16x25 (102x406x635)
MCD37W
Condenser Fluid Requirements
85°F (29.4°C) EWT
110°F (43.3°C) EGT - 40% PG
THR - kW (Btuh) @ 75F/45%RH
14.0 (47,800)
13.2 (44,900)
Flow Rate, GPM (l/m)
6.6 (25.0)
11.9 (45.1)
Pressure Drop, ft. of H20 (kPa)
11.9 (35.6)
43.2 (129.2)
Water-Cooled Condensing Temperature
105°F (40.6°C)
N/A
Connection Sizes, in. (mm) OD
7/8 (22.2)
Unit Volume, Gal (l)
1.2 (4.5)
Unit Refrigerant Charge, oz. (kg)
54 (1.54)
Unit Operating Weight, lb. (kg)
220 (100)
Free-Cooling Coil Option Net Capacity Data - kW (Btuh) using 45°F EWT
Entering Fluid Conditions
45°F (29.4°C) EWT
45°F EGT - 40% PG
Total
9.50 (32,400)
8.25 (28,000)
80°F DB, 62.8°F WB (26.7°C DB, 17.1°C WB) 38%RH
Sensible
9.05 (30,800)
8.25 (28,000)
Total
8.20 (28,000)
7.00 (23,800)
75°F DB, 61°F WB (23.9°C DB, 16.1°C WB) 45%RH
Sensible
7.60 (25,900)
7.00 (23,800)
Total
7.45 (25,400)
6.30 (21,500)
72°F DB, 60°F WB (22.2°C DB, 15.5°C WB) 50%RH
Sensible
6.70 (22,900)
6.30 (21,500)
Flow Rate - GPM (l/m)
5.9 (22.4)
11.9 (45.1)
Pressure Drop - ft. water (kPa)
9.1 (27.2)
44.3 (132.5)
Free-Cooling Coil - Copper Tube/Aluminum Fin
3.1 (0.28)
Face Area, ft2 (m2)
Coil Rows
3
Max Face Velocity, fpm (m/s)
394 (2.0)
Internal Fluid Volume, gal (l)
2.0 (7.6)
Water supply and return connections, in (mm) OD
7/8 (22.2)
The net capacity data has fan motor heat factored in for all ratings and the entering air conditions of 75°F (23.9°C), 45%RH, is the standard rating condition for
ASHRAE 127-2007. All capacities are nominal values; actual performance will be ± 5%.
Liebert® Mini-Mate2™
17
Water/Glycol Systems—Capacities and Dimensions
Figure 12 General arrangement, water/glycol split systems
Scroll
Compressor
High Pressure
Scroll Switch
Liquid Injection
Valve Bulb
Hot Gas
Bypass
Solenoid
Valve
Suction Line Male Quick
Connect Coupling
Suction Line Female Quick
Connect Coupling
ss
ypa
s B ve
a
G
l
Hot trol Va
Con
*
Sensing Bulb
External Equalizer
Tube in Tube
Condenser
Liquid Injection
Valve
ServiceAccess
Ports
Shutoff **
Liquid Line
Valves
Male Quick
*
Hose Bibs **
Connect
Liquid Line Coupling
Female Quick
Connect
Expansion Coupling
Valve
Fluid Supply
To Unit
Filter
Drier
Evaporator Coil
Tube in Tube
Condenser
Water/Glycol
Return Line
Water/Glycol
Fluid Return
Supply Line
From Unit
* Use Liebert sweat adapter kit with field
hard piping or use Liebert pre-charged line
set. Close-coupling option available with
MCD.
** Components are not supplied by Liebert
but are recommended for proper circuit
operation and maintenance.
2 - Way Water
Regulating Valve
Fluid
Return
From Unit
Fluid Supply
To Unit
FIELD PIPING
FACTORY PIPING
3 - Way Water
Regulating Valve
(Optional)
DPN000190
REV 1
Figure 13 General arrangement, free-cooling coil with water/glycol condensing units
Tube-in-Tube
Condenser
Bleed Valve
Fluid
Return
From Unit
Fluid
Supply
To Unit
Shutoff
Valves *
Free Cooling
Control
Valve
Temperature
Stat
Hose
Bibs *
Free Cooling
Coil
Shutoff
Valves *
NOTE: Recommended piping for systems
using water/glycol loop for free-cooling coil option.
FIELD PIPING
Fluid
Supply
To Unit
3-Way Water
Regulating Valve
(Optional)
* Components are not supplied
by Liebert but are recommended
for proper circuit operation and
maintenance.
DPN000197
Rev. 2
FACTORY PIPING
Liebert® Mini-Mate2™
Hose
Bibs *
Fluid
Return
From
Unit
18
Water/Glycol Systems—Capacities and Dimensions
Figure 14 Dimensions, evaporator units with direct drive blower
1-7/16"
1"
(25.4mm)
3-7/8"
(98mm)
11"
(279mm)
20" (50
15"
(381mm)
1-7/16"
(37mm)
10-7/8"
(276mm)
Removable
Access
Panels
Optional discharge air
duct flange supplied when
optional filter box is ordered
18"
(457mm)
18" (457mm)
14"
(356mm)
24"
(610mm)
18"
Cabinet (457mm)
Dimension
8mm)
18" (457mm)
54"
(1372mm)
Cabinet
57-13/16"
Dimension
(1468mm)
19-7/8"
(505mm)
Hanging
Bracket
18"
(457mm)
Duct
Flange
14"
(356mm)
Customer-Supplied (37mm)
30"
Threaded Rods for
(762mm)
Module Suport from
Cabinet
Ceiling (Typ. 4)
Dimension
27-13/16"
(706mm)
11-1/8"
Threaded Rod
(283mm)
Centers
14"
(356mm)
3/4"
(19mm)
Cabinet Outline
1"
(25.4mm)
Filter Box (optional)
Cover Plate
Supplied With
Plenum
55-13/16"
(1418mm)
Threaded
Rod
Centers
11-5/8"
(295mm)
7/8" (22mm) holes
for module rigging
(typ. 2 each end).
Shaded area
indicates a recommended
clearance of 30" (762mm)
for access and filter removal
Cabinet Dimension
same as above
Overall
Dimension
Shaded area indicates a
recommended clearance
of 30" (762mm) for access
and filter removal
Note: Unit is spaced evenly in
reference to threaded rod centers
Module Dimensions
Removable panel on
side of plenum.
Minimum clearance
30" (762mm) for flter
access and removal
6" (152mm)
5"
(127mm)
Air Discharge out
sides of plenum
48"
(1219mm)
Overall
Dimension
24"
(610mm)
Overall
Dimension
Air Discharge out
Sides of Plenum
3-1/4"
(83mm)
Air Inlet through
grille in center of plenum
Optional Air Distribution Plenum
All piping and electrical field connections are the same
Table 9
Net weights—split system evaporator units
Model #
60Hz
50Hz
Weight
lb (kg)
MM*24E
—
225 (102)
MM*24K
—
245 (111)
MM*36E
MM*35E
225 (102)
MM*36K
MM*35K
245 (111)
Liebert® Mini-Mate2™
19
DPN000193
Rev. 3
Water/Glycol Systems—Capacities and Dimensions
Figure 15 Dimensions, evaporator units with optional belt drive blower assembly
29-7/8" (759mm)
Threaded
Rod Centers
16-13/16" (427mm)
Threaded Rod Centers
57-13/16" (1468mm)
Overall Dimension
30" (762mm)
Blower Box
Dimension
19" (483mm)
Blower Box
Dimension
55-13/16" (1418mm)
Threaded Rod Centers
High Static
Blower
Module
9-3/4" Outlet
(248mm)
Evaporator
Unit
24" (610mm)
Cabinet
Dimension
5-7/8"
(149mm)
6-7/8" (175mm)
6-5/16" (160mm) Outlet
4-29/32" (125mm)
Threaded Rod
To Threaded Rod
3-7/32"
(82mm)
Base to
Base
4-29/32" (125mm)
Cabinet to Cabinet
54" (1372mm)
Cabinet Dimension
14"
(356mm)
Outlet
Dimension
30" (762mm)
Cabinet
Dimension
18 "
(457mm)
Outlet
Dimension
DPN000194
Rev. 3
Table 10
Net weight, high static blower module
Unit
High Static
Blower Module
Liebert® Mini-Mate2™
Net Weight
lb (kg)
85 (39)
20
Water/Glycol Systems—Capacities and Dimensions
Figure 16 Cabinet dimensions and piping data, water/glycol indoor condensing module
8-7/8" (225mm)
14" (356mm)
Overall Cabinet
Dimension
50-1/4" (1276mm)
Overall Dimension
3-7/8" (98mm)
48-1/4" (1225mm)
Threaded Rod Centers
8-7/16"
(214mm)
12" (305mm)
Threaded Rod
Centers
46-1/2" (1181mm)
Cabinet Dimension
Customer-Supplied
Threaded Rods for
Module Support
from Ceiling (typ. 4)
20-3/4"
(527mm)
22-1/2"
(572mm) Cabinet
Dimension
Outlet
Inlet
Holes for Module
Rigging (typ. 2 each end)
Integral
Hanging
Bracket
Note:
Unit is spaced evenly in
reference to threaded rod centers
DIMENSIONAL DATA
7/8" (22.2mm) OD CU
Water/Glycol Inlet Connection
Extends 3-1/2" (88.9mm) beyond
7/8" (22.2mm) OD CU
panel exterior
7/8" (22mm) Dia.
Water/Glycol Outlet Connection
Electrical Entrance
Extends 3-1/2" (88.9mm) beyond
for High Voltage
panel exterior
Connection
Suction Line
Male Quick
Connect
Liquid Line
Male Quick
Connect
7/8" (22mm) Dia.
Electrical Entrance
for Low Voltage
Connection
Table 11
PIPING CONNECTIONS
Net weight, indoor water/glycol-cooled condensing unit
Model #
60Hz
50Hz
Weight
lb (kg)
MC*26W
—
175 (79)
MC*38W
MC*37W
220 (100)
Liebert® Mini-Mate2™
21
DPN000208
Rev. 4
Minimum Clearance
33" (838mm) this side
for component access
and removal.
Chilled Water Systems—Capacities and Dimensions
8.0
CHILLED WATER SYSTEMS—CAPACITIES AND DIMENSIONS
Table 12
Chilled water data, 60 and 50Hz
MMD40C/MMD39C
CW Model, 50 & 60Hz
Net Capacity Data - kW (Btuh) based on 45°F (7.2°C) EWT & 10°F (5.6°C) temperature rise
Total
10.1 (34,600)
80°F DB, 62.8°F WB (26.7°C DB, 17.1°C WB) 38%RH
Sensible
9.40 (32,100)
Flow Rate, GPM (l/m)
7.2 (27.3)
Pressure Drop, ft. water (kPa)
13.1 (39.2)
Total
8.25 (28,200)
75°F DB, 61°F WB (23.9°C DB, 16.1°C WB) 45%RH
Sensible
7.60 (26,000)
Flow Rate, GPM (l/m)
5.9 (22.4)
Pressure Drop - ft. water (kPa)
9.3 (27.8)
Total
7.10 (24,200)
72°F DB, 60°F WB (22.2°C DB, 15.5°C WB) 50%RH
Sensible
6.50 (22,200)
Flow Rate, GPM (l/m)
5.2 (19.7)
Pressure Drop, ft. water (kPa)
7.2 (21.5)
Fan Data - Evaporator
CFM (CMH)
1250 (2124)
CFM (CMH), Low Speed
1000 (1699)
Fan Motor, hp (kW)
0.5 (0.38)
External Static Pressure, in (mm) water gauge
0.3 (8)
CW Coil - Copper Tube/Aluminum Fin
Face Area ft2 (m2)
3.1 (0.29)
Coil Rows
3
Max Face Velocity, fpm (m/s)
391 (2.0)
Electric Reheat Capacity (Includes Fan Motor)-kW (Btuh)
Input Voltage 208-1-60
4.7 (16040)
Input Voltage 230-1-60
5.8 (19800)
Input Voltage 277-1-60
6.3 (21500)
Input Voltage 208-3-60
5.6 (19100)
Input Voltage 230-3-60
6.8 (23200)
Input Voltage 460-3-60
7.3 (24900)
Input Voltage-220-1-50
5.3 (18090)
Input Voltage-380-3-50
7.3 (24900)
Hot Water Reheat Coil - Copper Tube/Aluminum Fin
Capacity (with fan motor heat) using 180°F (82°C) EWT, kW (Btuh)
16.1 (54,900)
Flow Rate - GPM (l/m)
4.0 (15.2)
Pressure Drop, ft. water (kPa)
8.5 (25.4)
Face Area ft2 (m2)
3.1 (0.29)
Coil Rows
1
HWRH supply and return connections, in (mm) OD
5/8 (15.9)
Humidifier Data - Steam Generator Type
Steam capacity - lbs/hr (kg/hr)
4.3 (2.0)
Electrical Input Power, kW
1.5
Unit Connection Sizes
CW supply and return connections, in (mm) OD
7/8 (22.2)
Humidifier Supply
1/4" OD Copper Compression Fitting
Evaporator/Condensate Drain
3/4" NPT-Female
Unit Internal Fluid Volume, gal (l)
2.0 (7.6)
MERV 8 Filter, External Filter Box, qty (1), Nom. Size, in. (mm)
4x20x20 (102x508x508)
MERV 8 Filter, Air Distribution Plenum, qty (1), Nom. Size, in. (mm)
4x16x25 (102x406x635)
Unit Operating Weight
230 (104)
Unit Valve Types
On/Off Slow Close: 2- & 3-Way
Valve Size
1"
Valve Cv
7.0
Max. Static Operating Pressure, psi (kPa)
300 (2068)
Close-Off Pressure, psi (kPa)
60 (414)
The net capacity data has fan motor heat factored in for all ratings and the entering air conditions of 75°F (23.9°C), 45%RH, is
the standard rating condition for ASHRAE 127-2007. All capacities are nominal values; actual performance will be ±5%.
Liebert® Mini-Mate2™
22
Chilled Water Systems—Capacities and Dimensions
Table 13
Capacity Correction Factors (based on 10°F (5.6°C) water rise)
72°F (22.2°C) /50%
75°F (23.9°C) /45%RH
EWT
TCC
SCC
TCC
SCC
42°F (5.6°C)
1.25
1.13
1.23
1.12
43°F (6.1°C)
1.15
1.09
1.14
1.08
44°F (6.7°C)
1.07
1.04
1.07
1.04
45°F (7.2°C)
1.00
1.00
1.00
1.00
46°F (7.8°C)
0.92
0.96
0.94
0.96
47°F (8.3°C)
0.85
0.91
0.87
0.92
48°F (8.9°C)
0.78
0.85
0.82
0.88
49°F (9.4°C)
0.74
0.81
0.77
0.83
Figure 17 General arrangement, chilled water split systems
Bleed Valve
Chilled
Water
Chilled Supply
Water
Return
Chilled Water
Control Valve
Chilled Water Coil
3 - Way Chilled Water
Control Valve
(Optional)
Shutoff Valves *
Hose Bibs *
FIELD PIPING
** Components are not supplied by
Emerson but are recommended for
proper circuit operation and
maintenance.
FACTORY PIPING
DPN000191
Rev. 2
Figure 18 General arrangement, hot water reheat, chilled water units
Bleed Valve
Water
Water
Supply
Return
To Unit
From Unit
Shutoff
Valves *
Hot Water
Reheat
Control
Valve
Hot Water
Reheat
Coil
Y-Strainer
Hose
Bibs *
* Components are not supplied
by Liebert but are recommended
for proper circuit operation and
maintenance.
FIELD PIPING
FACTORY PIPING
NOTE: Hot water reheat only available
on chilled water units.
DPN000197
Rev. 2
23
Liebert® Mini-Mate2™
Chilled Water Systems—Capacities and Dimensions
Figure 19 Dimensions, chilled water units with direct drive blower
1-7/16"
1"
(25.4mm)
3-7/8"
(98mm)
11"
(279mm)
20" (5
15"
(381mm)
1-7/16"
(37mm)
10-7/8"
(276mm)
Removable
Access
Panels
Optional discharge air
duct flange supplied when
optional filter box is ordered
18"
(457mm)
18" (457mm)
14"
(356mm)
24"
(610mm)
18"
Cabinet (457mm)
Dimension
08mm)
18" (457mm)
54"
(1372mm)
Cabinet
57-13/16"
Dimension
(1468mm)
19-7/8"
(505mm)
Hanging
Bracket
18"
(457mm)
Duct
Flange
14"
(356mm)
Customer-Supplied (37mm)
30"
Threaded Rods for
(762mm)
Module Suport from
Cabinet
Ceiling (Typ. 4)
Dimension
27-13/16"
(706mm)
11-1/8"
Threaded Rod
(283mm)
Centers
14"
(356mm)
3/4"
(19mm)
Cabinet Outline
1"
(25.4mm)
Filter Box (optional)
Cover Plate
Supplied With
Plenum
55-13/16"
(1418mm)
Threaded
Rod
Centers
11-5/8"
(295mm)
7/8" (22mm) holes
for module rigging
(typ. 2 each end).
Shaded area
indicates a recommended
clearance of 30" (762mm)
for access and filter removal
Cabinet Dimension
same as above
Overall
Dimension
Shaded area indicates a
recommended clearance
of 30" (762mm) for access
and filter removal
Note: Unit is spaced evenly in
reference to threaded rod centers
Module Dimensions
Removable panel on
side of plenum.
Minimum clearance
30" (762mm) for flter
access and removal
6" (152mm)
5"
(127mm)
Air Discharge out
sides of plenum
48"
(1219mm)
Overall
Dimension
24"
(610mm)
Overall
Dimension
Air Discharge out
Sides of Plenum
3-1/4"
(83mm)
Air Inlet through
grille in center of plenum
Optional Air Distribution Plenum
All piping and electrical field connections are the same
Table 14
Chilled water units with direct drive blower weights
Model #
60Hz
50Hz
Net Weight
lb (kg)
MM*40C
MM*39C
230 (104)
Liebert® Mini-Mate2™
24
DPN000193
Rev. 3
Chilled Water Systems—Capacities and Dimensions
Figure 20 Dimensions, chilled water units with optional belt drive blower assembly
29-7/8" (759mm)
Threaded
Rod Centers
16-13/16" (427mm)
Threaded Rod Centers
57-13/16" (1468mm)
Overall Dimension
30" (762mm)
Blower Box
Dimension
19" (483mm)
Blower Box
Dimension
55-13/16" (1418mm)
Threaded Rod Centers
High Static
Blower
Module
9-3/4" Outlet
(248mm)
Evaporator
Unit
24" (610mm)
Cabinet
Dimension
5-7/8"
(149mm)
6-7/8" (175mm)
6-5/16" (160mm) Outlet
4-29/32" (125mm)
Threaded Rod
To Threaded Rod
3-7/32"
(82mm)
Base to
Base
4-29/32" (125mm)
Cabinet to Cabinet
54" (1372mm)
Cabinet Dimension
14"
(356mm)
Outlet
Dimension
30" (762mm)
Cabinet
Dimension
18 "
(457mm)
Outlet
Dimension
DPN000194
Rev. 3
Table 15
Net weight, high static blower module
Unit
High Static
Blower Module
Liebert® Mini-Mate2™
Net Weight
lb (kg)
85 (39)
25
Electrical Data
9.0
ELECTRICAL DATA
Table 16
Direct drive split system evaporator or chilled water unit electrical data, 60Hz
Base Evaporator
Model Number
208/230 - 1 Ph - 60Hz
277 - 1 Ph - 60Hz
208/230 - 3 Ph - 60Hz
460 - 3 Ph - 60Hz
MM*24E
MM*36E
MM*24E
MM*36E
MM*24E
MM*36E
MM*24E
MM*36E
FLA
2.8
2.8
2.3
2.3
—
2.8
—
1.4
WSA
3.5
3.5
2.9
2.9
—
3.5
—
1.8
OPD
15
15
15
15
—
15
—
15
FLA
27.8
27.8
24.0
24.0
—
19.6
—
9.8
WSA
34.8
34.8
30.0
30.0
—
24.5
—
12.3
OPD
35
35
35
35
—
25
—
15
FLA
32.0
44.5
27.6
38.4
—
26.9
—
13.5
WSA
40.0
55.6
34.5
48.0
—
33.6
—
16.9
OPD
45
60
35
50
—
35
—
20
FLA
9.2
9.2
8.0
8.0
—
9.2
—
4.8
WSA
11.5
11.5
10.0
10.0
—
11.5
—
6.0
OPD
15
15
15
15
—
15
—
15
Cooling Only
with Electric Reheat
with SCR Reheat 4
with Humidifier
with Electric Reheat and Humidifier
FLA
34.2
34.2
29.7
29.7
—
26.0
—
13.2
WSA
42.8
42.8
37.1
37.1
—
32.5
—
16.5
OPD
45
45
40
40
—
35
—
20
with SCR Reheat 4 and Humidifier
FLA
38.4
50.9
33.3
44.1
—
33.3
—
16.9
WSA
48.0
63.6
41.6
55.1
—
41.6
—
21.1
OPD
50
70
45
60
—
45
—
25
* Specify disconnect or no disconnect
Notes:
1. Use MM*36E electrical data for MM*40C chilled water units
2. For units with Hot Water Reheat (available only on MM*40C units), use appropriate values from “Cooling only” or “with Humidifier”
categories.
3. Use MM*24E and MM*36E for MM*24K & MM*36K, respectively, except with SCR reheat.
4. SCR Reheat not available with MM*24K, MM*36K or MM*40C.
Liebert® Mini-Mate2™
26
Electrical Data
Table 17
Belt drive split system evaporator or chilled water electrical data, with high static blower box,
60Hz
Base Evaporator
Model Number
208/230 - 1 Ph - 60Hz
277 - 1 Ph - 60Hz
208/230 - 3 Ph - 60Hz
460 - 3 Ph - 60Hz
MM*24E
MM*36E
MM*24E
MM*36E
MM*24E
MM*36E
MM*24E
MM*36E
FLA
9.2
9.2
6.4
6.4
—
4.8
—
2.1
WSA
11.5
11.5
8.0
8.0
—
6.0
—
2.6
OPD
20
20
15
15
—
15
—
15
FLA
34.2
34.2
28.1
28.1
—
21.6
—
10.5
WSA
42.8
42.8
35.1
35.1
—
27.0
—
13.1
OPD
45
45
40
40
—
30
—
15
FLA
38.4
50.9
31.7
42.5
—
28.9
—
14.2
WSA
48.0
63.6
39.6
53.1
—
36.1
—
17.8
OPD
50
70
40
60
—
40
—
20
FLA
15.6
15.6
12.1
12.1
—
11.2
—
5.5
WSA
19.5
19.5
15.1
15.1
—
14.0
—
6.9
OPD
25
25
20
20
—
15
—
15
—
28.0
—
13.9
Cooling Only
with Electric Reheat
with SCR Reheat
5
with Humidifier
with Electric Reheat and Humidifier
FLA
40.6
40.6
33.8
33.8
WSA
50.8
50.8
42.3
42.3
—
35.0
—
17.4
OPD
60
60
45
45
—
40
—
20
—
35.3
—
17.6
5
with SCR Reheat and Humidifier
FLA
44.8
57.3
37.4
48.2
WSA
56.0
71.6
46.8
60.3
—
44.1
—
22.0
OPD
60
80
50
70
—
45
—
25
* Specify disconnect or no disconnect
Notes:
1. Belt drive data includes externally mounted high static blower box, powered from unit.
2. Use MM*36E electrical data for MM*40C chilled water units.
3. For units with Hot Water Reheat (available only on MM*40C units), use appropriate values from “Cooling only” or “with Humidifier”
categories.
4. Use MM*24E and MM*36E for MM*24K & MM*36K, respectively, except with SCR reheat.
5. SCR Reheat not available with MM*24K, MM*36K or MM*40C.
Liebert® Mini-Mate2™
27
Electrical Data
Table 18
Direct drive split system evaporator or chilled water electrical data, 50Hz
220 - 1Ph - 50Hz
380/415 - 3Ph-50Hz
MM*35E
MM*35E
FLA
2.8
1.4
FLA
27.8
11.1
FLA
44.6
15.3
FLA
9.2
5.1
34.2
14.8
50.9
19.0
Base Evaporator Model Number
Cooling Only
with Electric Reheat
with SCR Reheat 4
with Humidifier
with Electric Reheat and Humidifier
FLA
with SCR Reheat and Humidifier
4
FLA
* Specify disconnect or no disconnect
Notes:
1. Use MM*35E electrical data for MM*39C chilled water units.
2. For units with Hot Water Reheat (available only on MM*39C units), use appropriate values from “Cooling only” or “with Humidifier”
categories.
3. Use MM*35E for MM*35K, except with SCR reheat.
4. SCR Reheat not available with MM*35K or MM*39C.
Table 19
Belt drive split system evaporator or chilled water electrical data, 50Hz
220 - 1 Ph - 50Hz
380/415 - 3 Ph - 50Hz
MM*35E
MM*35E
FLA
7.0
2.6
FLA
32.0
12.3
FLA
48.7
16.5
FLA
13.4
6.3
38.4
16.0
55.1
20.2
Base Evaporator Model Number
Cooling Only
with Electric Reheat
with SCR Reheat 5
with Humidifier
with Electric Reheat and Humidifier
FLA
with SCR Reheat and Humidifier
5
FLA
* Specify disconnect or no disconnect
Notes:
1. Belt drive data includes externally mounted high static blower box, powered from unit.
2. Use MM*35E electrical data for MM*39C chilled water units.
3. For units with Hot Water Reheat (available only on MM*39C units), use appropriate values from “Cooling only” or “with Humidifier”
categories.
4. Use MM*35E for MM*35K, except with SCR reheat.
5. SCR Reheat not available with MM*35K or MM*39C.
Liebert® Mini-Mate2™
28
Electrical Data
Table 20
Indoor condensing unit electrical data, 60 and 50Hz
60Hz
Model 208/230-1ph-60Hz 277-1ph-60Hz
50Hz
208/230-3ph-60Hz
460-3ph-60Hz
220-1ph-50Hz
380/415-3ph-50Hz
MC*24A
MC*24A
MC*24A
MC*24A
—
—
FLA
14.3
12.7
—
—
13.2
5.7
WSA
17.3
15.3
—
—
—
—
OPD
25
25
—
—
N/A
N/A
MC*36A
MC*36A
MC*36A
MC*36A
MC*35A
MC*35A
FLA
20.8
16.6
15.7
7.8
20.1
7.8
WSA
25.1
20.2
18.7
9.4
—
—
OPD
40
30
30
15
—
—
MC*26W
MC*26W
MC*26W
MC*26W
—
—
FLA
12.0
10.4
—
—
—
—
WSA
15.0
13.0
—
—
—
—
OPD
25
20
—
—
—
—
MC*38W
MC*38W
MC*38W
MC*38W
MC*37W
MC*37W
FLA
17.1
14.3
12.0
6.4
17.1
6.4
WSA
21.4
17.9
15.0
8.0
—
—
OPD
35
30
25
15
—
—
* Specify disconnect or no disconnect
Table 21
Outdoor condensing unit electrical data, 60 and 50Hz
Model #
Nominal
60Hz
50Hz
Capacity
Electrical
Tons
Characteristic 208/230-1-60 208/230-3-60 460-3-60 575-3-60 220-1-50 380/415-3-50
Standard 95°F (35°C) ambient
PFH027A_ _L7
PFH037A_ _L7
PFH036A_ _L7
2
3
FLA
13.4
—
—
—
—
—
WSA
16.4
—
—
—
—
—
OPD
25
—
—
—
—
—
FLA
18.5
13.4
7.1
5.8
18.4
7.0
WSA
22.8
16.4
8.7
7.0
—
—
OPD
35
25
15
15
—
—
FLA
15.4
—
—
—
—
—
WSA
18.4
—
—
—
—
—
OPD
30
—
—
—
—
—
High Ambient 105°F (41°C) ambient
PFH027A_ _H7
PFH037A_ _H7
PFH036A_ _H7
2
3
FLA
20.5
15.4
8.1
5.8
20.5
8.1
WSA
24.8
18.4
9.7
7.0
—
—
OPD
40
30
15
15
—
—
FLA
12.9
—
—
—
—
—
WSA
15.9
—
—
—
—
—
Quiet-Line 95°F (35°C) ambient
PFHZ27A_ _L7
PFHZ37A_ _L7
PFHZ36A_ _L7
2
3
Liebert® Mini-Mate2™
OPD
25
—
—
—
—
—
FLA
18.0
12.9
7.1
—
18.0
6.9
WSA
22.3
15.9
8.7
—
—
—
OPD
35
25
15
—
—
—
29
Electrical Data
Figure 21 Single-point power kit - optional
Close Coupled
Centrifugal Air-Cooled or
Water/Glycol-Cooled Condenser
Electric Service
(not by Emerson)
Condenser
Evaporator
Evaporator Unit
Electric Box
Single Point Power Kit Option
factory-supplied, field-installed
and field-wired
Line Voltage
Electrical Power
Supply Entrance
(Optional Field-Installed
Single Point Power Kit)
Note: Single point power kit should be
mounted inside the evaporator before
installing the unit in the ceiling.
Liebert® Mini-Mate2™
DPN000196
Rev. 0
30
Electrical Data
Table 22
Electrical data, 60Hz air-cooled systems using single-point power kit, evaporator with
direct-drive blowers and indoor condensing unit
208/230 - 1 Ph - 60Hz
277 - 1 Ph - 60Hz
208/230 - 3 Ph - 60Hz
460 - 3 Ph - 60Hz
Base Evaporator
Model Number
MM*24E
MM*36E
MM*24E
MM*36E
MM*24E
MM*36E
MM*24E
MM*36E
Condensing Unit
Model Number
MC*24A
MC*36A
MC*24A
MC*36A
MC*24A
MC*36A
MC*24A
MC*36A
FLA
17.1
23.6
15.0
18.9
—
18.5
—
9.2
WSA
20.1
27.9
17.6
22.5
—
21.5
—
10.8
OPD
30
40
25
35
—
30
—
15
FLA
42.1
48.6
36.7
40.6
—
35.3
—
17.6
WSA
51.4
59.1
44.7
49.6
—
42.5
—
21.3
OPD
60
60
45
50
—
50
—
25
FLA
46.3
65.3
40.3
55.0
—
42.6
—
21.3
WSA
56.6
80.0
49.2
67.6
—
51.6
—
25.9
OPD
60
80
50
70
—
50
—
30
FLA
23.5
30.0
20.7
24.6
—
24.9
—
12.6
WSA
26.5
34.3
23.3
28.2
—
27.9
—
14.2
OPD
35
50
30
40
—
35
—
20
—
35.3
—
17.6
Cooling Only
with Electric Reheat
with SCR Reheat
2
with Humidifier
with Electric Reheat and Humidifier
FLA
42.1
48.6
36.7
40.6
WSA
51.4
59.1
44.7
49.6
—
42.5
—
21.3
OPD
60
60
45
50
—
50
—
25
—
49.0
—
24.7
with SCR Reheat and Humidifier
2
FLA
52.7
71.7
46.0
60.7
WSA
63.0
86.4
54.9
73.3
—
58.0
—
29.3
OPD
70
90
60
80
—
60
—
30
* Specify disconnect or no disconnect
Note:
1. Use MM*24E and MM*36E for MM*24K & MM*36K, respectively, except with SCR reheat.
2. SCR Reheat not available with MM*24K or MM*36K.
Liebert® Mini-Mate2™
31
Electrical Data
Table 23
Electrical data, 60Hz air-cooled systems using single-point power kit, evaporator with belt-drive
blowers and indoor condensing unit
208/230 - 1 Ph - 60Hz
277 - 1 Ph - 60Hz
208/230 - 3 Ph - 60Hz
460 - 3 Ph - 60Hz
Base Evaporator
Model Number
MM*24E
MM*36E
MM*24E
MM*36E
MM*24E
MM*36E
MM*24E
MM*36E
Condensing Unit
Model Number
MC*24A
MC*36A
MC*24A
MC*36A
MC*24A
MC*36A
MC*24A
MC*36A
FLA
23.5
30.0
19.1
23.0
—
20.5
—
9.9
WSA
26.5
34.3
21.7
26.6
—
23.5
—
11.5
OPD
35
50
30
40
—
35
—
15
FLA
48.5
55.0
40.8
44.7
—
37.3
—
18.3
WSA
57.8
65.5
48.8
53.7
—
44.5
—
22.0
OPD
60
70
50
60
—
50
—
25
FLA
52.7
71.7
44.4
59.1
—
44.6
—
22.0
WSA
63.0
86.4
53.3
71.7
—
53.6
—
26.6
OPD
70
90
60
80
—
60
—
30
FLA
29.9
36.4
24.8
28.7
—
26.9
—
13.3
WSA
32.9
40.7
27.4
32.3
—
29.9
—
14.9
OPD
40
50
35
45
—
40
—
20
Cooling Only
with Electric Reheat
with SCR Reheat
3
with Humidifier
with Electric Reheat and Humidifier
FLA
48.5
55.0
40.8
44.7
—
37.3
—
18.3
WSA
57.8
65.5
48.8
53.7
—
44.5
—
22.0
OPD
60
70
50
60
—
50
—
25
with SCR Reheat and Humidifier
3
FLA
59.1
78.1
50.1
64.8
—
51.0
—
25.4
WSA
69.4
92.8
59.0
77.4
—
60.0
—
30.0
OPD
70
100
60
80
—
70
—
35
* Specify disconnect or no disconnect
Notes:
1. Belt drive data includes externally mounted high static blower box, powered from evaporator unit.
2. Use MM*24E and MM*36E for MM*24K & MM*36K, respectively, except with SCR reheat.
3. SCR Reheat not available with MM*24K or MM*36K.
32
Liebert® Mini-Mate2™
Electrical Data
Table 24
Electrical data, 50Hz air-cooled systems using single-point power kit, evaporator with
direct-drive blowers and indoor condensing unit
220 - 1 Ph - 50Hz
380/415 - 3 Ph - 50Hz
Base Evaporator Model Number
MM*35E
MM*35E
Condensing Unit Model Number
MC*35A
MC*35A
FLA
22.9
9.2
FLA
47.9
18.9
FLA
64.6
23.1
FLA
29.3
12.9
47.9
18.9
71.0
26.8
Cooling Only
with Electric Reheat
with SCR Reheat
2
with Humidifier
with Electric Reheat and Humidifier
FLA
with SCR Reheat and Humidifier
2
FLA
* Specify disconnect or no disconnect
Notes:
1. Use MM*35E for MM*35K, except with SCR reheat.
2. SCR Reheat not available with MM*35K.
Table 25
Electrical data, 50Hz air-cooled systems using single-point power kit, evaporator with belt-drive
blowers and indoor condensing unit
220 - 1 Ph - 50Hz
380/415 - 3 Ph - 50Hz
Base Unit Model Number
MM*35E
MM*35E
Condensing Unit Model Number
MC*35A
MC*35A
FLA
27.1
10.4
FLA
52.1
20.1
FLA
68.8
24.3
FLA
33.5
14.1
52.1
20.1
75.2
28.0
Cooling Only
with Electric Reheat
with SCR Reheat
3
with Humidifier
with Electric Reheat and Humidifier
FLA
with SCR Reheat and Humidifier 3
FLA
* Specify disconnect or no disconnect
Notes:
1. Belt drive data includes externally mounted high static blower box, powered from evaporator unit.
2. Use MM*35E for MM*35K, except with SCR reheat.
3. SCR Reheat not available with MM*35K.
33
Liebert® Mini-Mate2™
Electrical Data
Table 26
Electrical data, 60Hz water/glycol-cooled systems using single-point power kit, evaporator with
direct-drive blowers and indoor condensing unit
208/230 - 1 Ph - 60Hz
277 - 1 Ph - 60Hz
208/230 - 3 Ph - 60Hz
460 - 3 Ph - 60Hz
Base Unit
Model Number
MM*24E
MM*36E
MM*24E
MM*36E
MM*24E
MM*36E
MM*24E
MM*36E
Condensing Unit
Model Number
MC*26W
MC*38W
MC*26W
MC*38W
MC*26W
MC*38W
MC*26W
MC*38W
FLA
14.8
19.9
12.7
16.6
—
14.8
—
7.8
WSA
17.8
24.2
15.3
20.2
—
17.8
—
9.4
OPD
25
40
25
30
—
25
—
15
FLA
39.8
44.9
34.4
38.3
—
31.6
—
16.2
WSA
49.1
55.4
42.4
47.3
—
38.8
—
19.9
OPD
50
60
45
50
—
45
—
20
FLA
44.0
61.6
38.0
52.7
—
38.9
—
19.9
WSA
54.3
76.3
46.9
65.3
—
47.9
—
24.5
OPD
60
80
50
70
—
50
—
25
FLA
21.2
26.3
18.4
22.3
—
21.2
—
11.2
WSA
24.2
30.6
21.0
25.9
—
24.2
—
12.8
OPD
35
45
30
40
—
35
—
15
—
31.6
—
16.2
Cooling Only
with Electric Reheat
with SCR Reheat
2
with Humidifier
with Electric Reheat and Humidifier
FLA
39.8
44.9
34.4
38.3
WSA
49.1
55.4
42.4
47.3
—
38.8
—
19.9
OPD
50
60
45
50
—
45
—
20
—
45.3
—
23.3
with SCR Reheat and Humidifier
2
FLA
50.4
68.0
43.7
58.4
WSA
60.7
82.7
52.6
71.0
—
54.3
—
27.9
OPD
70
90
60
80
—
60
—
30
* Specify disconnect or no disconnect
Notes:
1. Use MM*24E and MM*36E for MM*24K & MM*36K, respectively, except with SCR reheat.
2. SCR Reheat not available with MM*24K or MM*36K.
34
Liebert® Mini-Mate2™
Electrical Data
Table 27
Electrical data, 60Hz water/glycol-cooled systems using single-point power kit, evaporator with
belt-drive blowers and indoor condensing unit
208/230 - 1 Ph - 60Hz
277 - 1 Ph - 60Hz
208/230 - 3 Ph - 60Hz
460 - 3 Ph - 60Hz
Base Evaporator
Model Number
MM*24E
MM*36E
MM*24E
MM*36E
MM*24E
MM*36E
MM*24E
MM*36E
Condensing Unit
Model Number
MC*26W
MC*38W
MC*26W
MC*38W
MC*26W
MC*38W
MC*26W
MC*38W
FLA
21.2
26.3
16.8
20.7
—
16.8
—
8.5
WSA
24.2
30.6
19.4
24.3
—
19.8
—
10.1
OPD
35
45
25
35
—
30
—
15
FLA
46.2
51.3
38.5
42.4
—
33.6
—
16.9
WSA
55.5
61.8
46.5
51.4
—
40.8
—
20.6
OPD
60
70
50
60
—
45
—
20
FLA
50.4
68.0
42.1
56.8
—
40.9
—
20.6
WSA
60.7
82.7
51.0
69.4
—
49.9
—
25.2
OPD
70
90
60
70
—
50
—
30
FLA
27.6
32.7
22.5
26.4
—
23.2
—
11.9
WSA
30.6
37.0
25.1
30.0
—
26.2
—
13.5
OPD
40
50
35
40
—
35
—
15
Cooling Only
with Electric Reheat
with SCR Reheat
3
with Humidifier
with Electric Reheat and Humidifier
FLA
46.2
51.3
38.5
42.4
—
33.6
—
16.9
WSA
55.5
61.8
46.5
51.4
—
40.8
—
20.6
OPD
60
70
50
60
—
45
—
20
with SCR Reheat and Humidifier
3
FLA
56.8
74.4
47.8
62.5
—
47.3
—
24.0
WSA
67.1
89.1
56.7
75.1
—
56.3
—
28.6
OPD
70
90
60
80
—
60
—
30
* Specify disconnect or no disconnect
Notes:
1. Belt drive data includes externally mounted high static blower box, powered from evaporator unit.
2. Use MM*24E and MM*36E for MM*24K & MM*36K, respectively, except with SCR reheat.
3. SCR Reheat not available with MM*24K or MM*36K.
35
Liebert® Mini-Mate2™
Electrical Data
Table 28
Electrical data, 50Hz water/glycol-cooled systems using single-point power kit, evaporator with
direct-drive blowers and indoor condensing unit
220 - 1 Ph - 50Hz
380/415 - 3 Ph - 50Hz
Base Evaporator Model Number
MM*35E
MM*35E
Condensing Unit Model Number
MC*37W
MC*37W
FLA
19.9
7.8
FLA
44.9
17.5
FLA
61.6
21.7
FLA
26.3
11.5
44.9
17.5
68.0
25.4
Cooling Only
with Electric Reheat
with SCR Reheat
2
with Humidifier
with Electric Reheat and Humidifier
FLA
with SCR Reheat and Humidifier
2
FLA
* Specify disconnect or no disconnect
Notes:
1. Use MM*35E for MM*35K, except with SCR reheat.
2. SCR Reheat not available with MM*35K.
Table 29
Electrical data, 50Hz water/glycol-cooled systems using single-point power kit, evaporator with
belt-drive blowers and indoor condensing unit
220 - 1 Ph - 50Hz
380/415 - 3 Ph - 50Hz
Base Evaporator Model Number
MM*35E
MM*35E
Condensing Unit Model Number
MC*37W
MC*37W
FLA
24.1
9.0
FLA
49.1
18.7
FLA
65.8
22.9
FLA
30.5
12.7
49.1
18.7
72.2
26.6
Cooling Only
with Electric Reheat
with SCR Reheat 3
with Humidifier
with Electric Reheat and Humidifier
FLA
with SCR Reheat and Humidifier
3
FLA
* Specify disconnect or no disconnect
Notes:
1. Belt drive data includes externally mounted high static blower box, powered from evaporator unit.
2. Use MM*35E for MM*35K, except with SCR reheat.
3. SCR Reheat not available with MM*35K.
36
Liebert® Mini-Mate2™
Refrigerant Piping
10.0 REFRIGERANT PIPING
Table 30
Refrigerant charge
Model #
60Hz
MM*24E/K
MM*36E/K
50Hz
Charge R-407C
oz (kg)
—
7 (0.198)
MM*35E/K
MC*24AL_H7
MC*36AL_H7
—
134 (3.80)
MC*35AL_H7
MC*26W__H7
MC*38W__H7
7 (0.198)
213 (6.04)
—
41 (1.16)
MC*37W__H7
54 (1.54)
PFH027-_L7
—
134 (3.80)
PFH027-_H7
—
213 (6.04)
PFHZ27-_L7
—
213 (6.04)
PFH037-_L7
PFH036-_L7
213 (6.04)
PFH037-_H7
PFH036-_H7
426 (12.08)
PFHZ37-_L7
PFHZ36-_L7
426 (12.08)
Table 31
Recommended refrigerant line sizes
2 Ton
3 Ton
Equivalent
Length, ft (m)
Suction
Liquid
Suction
Liquid
50 (15.2)
7/8"
3/8"
7/8"
1/2"
1/2"
1-1/8" 2
1/2"
1/2"
2
1/2"
100 (30.5)
150 (45.7)
7/8"
7/8"
1-1/8"
1. Suction line and liquid line sizing based on < 3 psi pressure drop in each and
horizontal suction line refrigerant velocities >700FPM (3.6m/s).
2. Suction size should be reduced one pipe size for vertical riser sections to
maintain suction line velocity > 1000FPM (5.1m/s) for proper oil return.
Table 32
Pipe length and condenser elevation relative to evaporator
Nominal
System Size
Tons
Max. Equiv.
Pipe Length
ft. (m)
Maximum PFH
Level Above
Evaporator, ft. (m)
Maximum PFH
Level Below
Evaporator, ft. (m)
2
150 (45)
40 (12)
15 (4.6)
3
150 (45)
50 (15)
15 (4.6)
Maximum recommended total equivalent pipe length is 150 ft (46m). Suction and liquid lines may require additional specialty
items when vertical lines exceed 20 ft. (6m) and/or condensing unit installation is more than 15 ft. (4.6m) below the evaporator.
Contact Emerson Application Engineering for assistance.
Table 33
Line charges - refrigerant per 100 ft. (30m) of Type L copper tube
R-407C, lb/100 ft. (kg/30m)
Line Size,
O.D., in.
Liquid Line
Suction Line
3/8
3.7 (1.7)
—
1/2
6.9 (3.1)
—
5/8
11.0 (5.0
0.4 (0.2)
3/4
15.7 (7.1)
0.6 (0.3)
7/8
23.0 (10.4)
1.0 (0.4)
1-1/8
—
1.7 (0.7)
1-3/8
—
2.7 (1.1)
37
Liebert® Mini-Mate2™
Refrigerant Piping
Table 34
Refrigerant charge in Liebert pre-charged R-407C line sets
Line Size, in.
Length, ft. (m)
3/8 liquid
5/8 or 7/8 suction
Table 35
Charge R-407C, oz (kg)
15 (4.5)
5 (0.14)
30 (9)
10 (0.28)
15 (4.5)
5 (0.14)
30 (9)
10 (0.28)
Equivalent lengths for various pipe fittings, ft (m)
Copper Pipe
OD, in.
90 Degree
Elbow Copper
90 Degree
Elbow Cast
45 Degree
Elbow
Tee
Gate
Valve
Globe
Valve
Angle
Valve
1/2
0.8 (0.24)
1.3 (0.39)
0.4 (0.12)
2.5 (0.76)
0.26 (0.07)
7.0 (2.13)
4.0 (1.21)
5/8
0.9 (0.27)
1.4 (0.42)
0.5 (0.15)
2.5 (0.76)
0.28 (0.08)
9.5 (2.89)
5.0 (1.52)
3/4
1.0 (0.3)
1.5 (0.45)
0.6 (0.18)
2.5 (0.76)
0.3 (0.09)
12.0 (3.65)
6.5 (1.98)
7/8
1.45 (0.44)
1.8 (0.54)
0.8 (0.24)
3.6 (1.09)
0.36 (0.1)
17.2 (5.24)
9.5 (2.89)
1-1/8
1.85 (0.56)
2.2 (0.67)
1.0 (0.3)
4.6 (1.4)
0.48 (0.14)
22.5 (6.85)
12.0 (3.65)
1-3/8
2.4 (0.73)
2.9 (0.88)
1.3 (0.39)
6.4 (1.95)
0.65 (0.19)
32.0 (9.75)
16.0 (4.87)
1-5/8
2.9 (0.88)
3.5 (1.06)
1.6 (0.48)
7.2 (2.19)
0.72 (0.21)
36.0 (10.97)
19.5 (5.94)
Refrigerant trap = Four times equivalent length of pipe per this table.
Figure 22 Refrigerant piping diagram
Pitch down 1/2" (13mm) per 10 ft. (3m)
Evaporator
Suction Line Piping
Condensing Unit
Below Evaporator
NOTE
When installing remote condensing units below the
evaporator, the suction gas line should be trapped with
an inverted trap to the height of the evaporator . This
prevents refrigerant migration to the compressors
during off cycles . Maximum recommended vertical
level drop to condensing unit is 15 ft. (4.6m) .
Condensing
Unit
Condensing
Unit
Evaporator
Suction Line Piping
Condensing Unit Above Evaporator
Traps recommended at the base of riser exceeding
5 ft (1.5m) and every 20 feet (6m) of vertical rise.
Pitch down 1/2" (13mm) per 10 ft. (3m)
Liebert® Mini-Mate2™
See Table 32 for recommended
maximum vertical rise above
evaporator/maximum vertical
fall below evaporator.
38
Glycol Loop Piping
11.0 GLYCOL LOOP PIPING
Contact Emerson Application Engineering for assistance in choosing correct drycooler models. Refer
to Figure 23.
Figure 23 Heat rejection loop, multiple drycoolers and multiple indoor units
Expansion Tank
______ Gal. (L)
HP
GPM (l/s)
ft.
____(kW) ____ Per Pump @ ____(kPa)
FS
PUMP PACKAGE
Drycooler No. 1 Model ______
GPM (l/s) ____ P: ___ ft (kPa)
See Note 3
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
Drycooler No. 2 Model ______
GPM (l/s) ____ P: ___ ft (kPa)
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
LEGEND
Gate Valve
Check Valve
Butterfly Valve
Relief Valve
Union
Ball or Flow Control Valve
FS
P:
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
Flow Switch
Pressure Drop
Strainer/Filter
Notes:
1. Pressure and temperature gauges (or ports for same) are
recommended to monitor component pressure drops and performance.
2. Flow measuring devices, drain and balancing valves to be supplied
by others and located as required.
3. See product literature for installation guidelines and clearance dimensions.
4. Drawing shows dual pump package. Alternate pump packages with more
pumps may be considered; consult supplier
39
Total
GPM
(L/s): _____
Pipe
Diam.: _____ In. (mm)
P: _____ Ft. (kPa)
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
DPN000991
Rev. 0
Liebert® Mini-Mate2™
Model Number Nomenclature—All Systems
12.0 MODEL NUMBER NOMENCLATURE—ALL SYSTEMS
Figure 24
Model number nomenclature—Evaporator units
MM = Liebert Mini-Mate2
Blower Type
D = Direct Drive
Internal Blower
B = Belt Drive
External Blower
D = Disconnect Switch
0 = No Disconnect Switch
Nominal Capacity
Unit Type
E = Split Evaporator
K = Split Evaporator with Free-Cooling
MM
D
Refrigerant
7 = R-407C
36
E
7
A
Supply Power
P = 208/230V - 1 ph - 60Hz
X = 277V - 1 ph - 60Hz
S = 220V - 1 ph - 50Hz (3-ton only)
A = 460V - 3 ph - 60Hz (3-ton only)
Y = 208/230V - 3 ph - 60Hz (3-ton only)
M = 380/415V - 3ph - 50Hz (3-ton only)
H
E
D
A
Reheat Type
0 = No Reheat
E = Electric Reheat
S = SCR Reheat (not available
with free-cooling)
Humidification
H = Canister Humidifier
0 = No Humidifier
R = Remote Humidifier Contact
J = Canister Humidifier and Remote
Humidifier Contact
Sensor Packages
0 = None
A = Filter Clog
B = Smoke Sensor
C = High-Temperature Sensor
D = Filter Clog & Smoke Sensor
E = Filter Clog & High-Temperature Sensor
F = Smoke Sensor & High-Temperature Sensor
G = Filter Clog, Smoke Sensor & High-Temperature Sensor
Figure 25 Model number nomenclature—Air-cooled, indoor condensing units
Supply Power
P = 208/230V - 1 ph - 60Hz
X = 277V - 1 ph - 60Hz
S = 220V - 1 ph - 50Hz (3-ton only)
A = 460V - 3 ph - 60Hz (3-ton only)
Y = 208/230V - 3 ph - 60Hz (3-ton only)
M = 380/415V - 3ph - 50Hz (3-ton only)
MC = Liebert Mini-Mate2 indoor condensing units
D = Disconnect Switch
0 = No Disconnect Switch
Nominal Capacity
24 = 2-ton, 60Hz
35 = 3-ton, 50Hz
36 = 3-ton, 60Hz
Refrigerant
7 = R-407C
Cooling Method
A = Air-Cooled
MC
D
36
A
L
Head Pressure Controls
L = Liebert Lee-Temp™ Receiver
Liebert® Mini-Mate2™
40
A
H
7
H = Hot Gas
Bypass
Model Number Nomenclature—All Systems
Figure 26 Model number nomenclature—Outdoor air-cooled prop fan condensing units
PF = Prop Fan Condensing Unit with Hot Gas Bypass
0 = Std. Sound Level
Z = Quiet-Line
PFH
0
Refrigerant
7 = R-407C
Nominal Capacity, kBtuh
Cooling Method
A = Air-Cooled
37
— = Standard Coil
C = Coated Coil
A
—
P
P = 208/230V - 1ph - 60Hz
Y = 208/230V - 3ph - 60Hz (3-ton only)
A = 460V - 3ph - 60Hz (3-ton only)
B = 575V - 3ph - 60Hz (3-ton only)
S = 220V - 1ph - 50Hz (3-ton only)
M = 380/415V - 3ph - 50Hz (3-ton only)
L
7
L = 95°F Ambient,
Liebert Lee-Temp™
H = 105°F High Ambient,
Liebert Lee-Temp
Figure 27 Model number nomenclature—Water/glycol-cooled condensing units
Nominal Capacity
26 = 2-ton, 60Hz
37 = 3-ton, 50Hz
38 = 3-ton, 60Hz
MC = Liebert Mini-Mate2
indoor condensing
units
D = Disconnect Switch
0 = No Disconnect Switch
MC
D
Cooling Method
W = Water/Glycol
38
W
2
Supply Power
P = 208/230V - 1 ph - 60Hz
X = 277V - 1ph - 60Hz
S = 220V - 1ph - 50Hz (3-ton only)
A = 460V - 3ph - 60Hz (3-ton only)
Y = 208/230V - 3ph - 60Hz (3-ton only)
M = 380/415V – 3ph-50Hz (3-ton only)
A
Head Pressure Controls
2 = 2-Way Standard Pressure Water Reg Valve
3 = 3-Way Standard Pressure Water Reg Valve
D = 2-Way High-Pressure Water Reg Valve
T = 3-Way High-Pressure Water Reg Valve
41
H
7
Refrigerant
7 = R-407C
H = Hot Gas Bypass
Liebert® Mini-Mate2™
Model Number Nomenclature—All Systems
Figure 28 Model number nomenclature—Chilled water units
MM = Liebert Mini-Mate2
D = Disconnect Switch
0 = No Disconnect Switch
Cooling Method
C = Chilled Water
Nominal Capacity
39 = 3-ton, 50Hz
40 = 3-ton, 60Hz
MM
D
Supply Power
P = 208/230V - 1 ph - 60Hz
X = 277V - 1ph - 60Hz
S = 220V - 1ph - 50Hz
A = 460V - 3ph - 60Hz
Y = 208/230V - 3ph - 60Hz
M = 380/415V – 3ph-50Hz
Liebert® Mini-Mate2™
40
Blower Type
D = Direct Drive Internal Blower
B = Belt Drive External Blower
Valve Type
2 = 2-Way Chilled Water Valve
3 = 3-Way Chilled Water Valve
C
3
A
H
E
D
A
Reheat Type
Humidification
0 = No Reheat
H = Canister Humidifier
E = Electric Reheat
0 = No Humidifier
H = Hot Water Reheat
R = Remote Humidifier Contact
J = Canister Humidifier and Remote
Humidifier Contact
Sensor Packages
0 = None
A = Filter Clog
B = Smoke Sensor
C = High-Temperature Sensor
D = Filter Clog & Smoke Sensor
E = Filter Clog & High-Temperature
Sensor
F = Smoke Sensor & High
Temperature Sensor
G = Filter Clog, Smoke Sensor & HighTemperature Sensor
42
Guide Specifications for Liebert Mini-Mate2—2- and 3-Ton Systems
GUIDE SPECIFICATIONS FOR LIEBERT MINI-MATE2—2- AND 3-TON SYSTEMS
1.0
GENERAL
1.1
Summary
These specifications describe requirements for an environmental control system. The system shall be
designed to control temperature and relative humidity conditions within the room.
The manufacturer shall design and furnish all equipment in the quantities and configurations shown
on the project drawings.
System shall be supplied with CSA Certification to the harmonized U.S. and Canadian product safety
standard CSA C22.2 No 236/UL 1995 for “Heating and Cooling Equipment” and marked with the CSA
c-us logo (60Hz only).
The system model number(s) shall be:
Evaporator: _______________________
Condensing Unit: _______________________
Chilled Water Unit:__________________
1.2
Design Requirements
The environmental control system shall be a Liebert Mini-Mate2 factory assembled unit. On direct
expansion models, the refrigeration system shall be split, with the compressor located in a remote or
close-coupled condensing unit.
The evaporator section shall be designed for above dropped-ceiling installation. Condensing units
shall be designed for either outdoor or above-dropped-ceiling installation.
The system shall have a total cooling capacity of _______ BTU/hr (kW) and a sensible cooling capacity of
________ BTU/hr (kW), based on the entering air condition of _____°F (°C) dry bulb and _____°F (°C) wet bulb.
The unit is to be supplied for operation on a ______ volt, ______ phase, ______ Hz power supply.
1.3
Submittals
Submittals shall be provided with the proposal and shall include: Dimensional, Electrical and
Capacity data; and Piping and Electrical Connection Drawings.
1.4
Quality Assurance
The specified system shall be factory-tested before shipment. Testing shall include, but shall not be
limited to: Quality Control Checks, “Hi-Pot” Test (two times rated voltage plus 1000 volts, per NRTL
agency requirements), and Metering Calibration Tests. The system shall be designed and manufactured
according to world-class quality standards. The manufacturer shall be ISO 9001 certified.
2.0
PRODUCT
2.1
Standard Features/All Systems
2.1.1
Evaporator Cabinet Construction
The cabinet and chassis shall be constructed of heavy gauge galvanized steel, and shall be serviceable
from one side. Mounting brackets shall be factory-attached to the cabinet. Internal cabinet insulation
shall meet ASHRAE 62.1 requirements for Mold Growth, Humidity & Erosion, tested per UL 181 and
ASTM 1338 standards.
2.1.2
Air Distribution
The air distribution system shall be constructed with a quiet, direct-drive fan assembly equipped with
double-inlet blower, self-aligning ball bearings and lifetime lubrication. Fan motor shall be
permanent-split capacitor, high-efficiency type, equipped with two speeds for airflow modulation.
Dehumidification shall utilize the lower fan speed.
Each system shall be capable of delivering ____CFM (____ CMH) at high fan speed. The
circulating-air fan shall be two-speed for precise dehumidification control. The fan motor shall be
____ HP (____ W).
System shall be suitable for plenum or ducted air distribution. Refer to 2.5.2 - Air Filter Box, 2.5.3 Air Distribution Plenum and 2.5.4 - High Static Blower Assembly.
43
Liebert® Mini-Mate2™
Guide Specifications for Liebert Mini-Mate2—2- and 3-Ton Systems
2.1.3
Microprocessor Control
The control system shall be microprocessor-based, factory-wired into the system and tested prior to
shipment. The wall-mounted control enclosure shall include a 2-line by 16-character LCD providing
continuous display of operating status and alarm condition. An 8-key membrane keypad for setpoint/
program control, fan speed selection and unit On/Off shall be located below the display. The control
display shall be field-wired to the control board using 4-conductor field-supplied thermostat wire.
Temperature and humidity sensors shall be located in the wall box, which shall be capable of being
located up to 300 ft (91.4m) from the evaporator unit.
2.1.3.1
Monitoring
The LCD shall provide On/Off indication, operating mode indication (cooling, heating, humidifying,
dehumidifying), fan speed indication and current day, time, temperature and humidity (if applicable)
indication. The monitoring system shall be capable of relaying unit operating parameters and alarms
to the Liebert SiteScan® monitoring system.
2.1.3.2
•
•
•
•
Control Setpoint Parameters
Temp. Setpoint 65-85°F (18-29°C)
Temp. Sensitivity 1-9.9°F (1-5°C)
Humidity Setpoint 20-80% RH
Humidity Sensitivity 1-30% RH
2.1.3.3
2.1.3.3.1
Unit Controls
Compressor Short-Cycle Control
The control system shall prevent compressor short-cycling by a 3-minute timer from compressor stop
to the next start.
2.1.3.3.2
Common Alarm and Remote On/Off
A common alarm relay shall provide a contact closure to a remote alarm device. Two (2) terminals
shall also be provided for remote On/Off control. Individual alarms shall be “enabled” or “disabled”
from reporting to the common alarm.
2.1.3.3.3
Setback Control
The control shall be user-configurable to use a manual setpoint control or a programmable,
time-based setback control. The setback control will be based on a 5 day/2 day programmed weekly
schedule with capability of accepting 2 events per program day.
2.1.3.3.4
Temperature Calibration
The control shall include the capabilities to calibrate the temperature and humidity sensors and
adjust the sensor response delay time from 0 to 90 seconds. The control shall be capable of displaying
temperature values in °F or °C.
2.1.3.3.5
System Auto Restart
For startup after power failure, the system shall provide automatic restart with a programmable (up
to 9.9 minutes in 6-second increments) time delay. Programming can be performed either at the
wall-mounted controller or from the central, site-monitoring system.
Liebert® Mini-Mate2™
44
Guide Specifications for Liebert Mini-Mate2—2- and 3-Ton Systems
2.1.4
Alarms
2.1.4.1
Unit Alarm
The control system shall monitor unit operation and activate an audible and visual alarm in the event
of the following factory preset alarm conditions:
•
•
•
•
•
•
•
•
High Temperature
Low Temperature
High Humidity
Low Humidity
High Water Alarm - Lockout Unit Operation
High Head Pressure
Loss of Power
Compressor Short Cycle
2.1.4.2
•
•
•
•
Custom Alarms (2x)
Humidifier Problem
Filter Clog
Water Detected
Smoke Detected
User-customized text can be entered for the two (2) custom alarms.
2.1.4.3
Alarm Controls
Each alarm (unit and custom) shall be separately enabled or disabled, selected to activate the
common alarm (except for high head pressure).
2.1.4.4
Audible Alarm
The audible alarm shall annunciate any alarm that is enabled by the operator.
2.1.4.5
Common Alarm
A programmable common alarm shall be provided to interface user selected alarms with a remote
alarm device.
2.1.4.6
Remote Monitoring
All alarms shall be communicated to the Liebert site monitoring system with the following
information: date and time of occurrence, unit number, and present temperature and humidity.
2.2
Direct Expansion System Evaporator Components
2.2.1
Direct Expansion Coil
The evaporator section shall include evaporator coil, thermostatic expansion valve and filter drier.
The evaporator coil shall have 3.1 sq. ft. (0.29 sq.m) face area, 3 rows deep. It shall be constructed of
copper tubes and aluminum fins and have a maximum face velocity of ____ fpm (m/s) at ____ CFM
(CMH). An externally equalized thermostatic expansion valve shall control refrigerant flow. The
evaporator coil shall be factory-charged with R-407C refrigerant and sealed. The evaporator unit can
be coupled directly with a ceiling mounted condensing unit or mounted remote to the condensing unit.
The coil shall be provided with a condensate drain pan with an internally trapped drain line. The
evaporator drain pan shall include a factory-installed float switch to shut down the evaporator upon
high water condition.
45
Liebert® Mini-Mate2™
Guide Specifications for Liebert Mini-Mate2—2- and 3-Ton Systems
2.2
Chilled Water System Components
2.2.1
Chilled Water Control Valve
The control valve shall be a motorized, slow-close On/Off type to reduce water hammer. Design
pressure shall be 300 psig (2068 kPa) static pressure, with a maximum close-off pressure of 60 psig
(414 kPa). Valve shall be non-spring return.
2.2.2
Chilled Water Coil
The cooling coil shall have a minimum of 3.1 sq.ft. (0.29 sq.m) face area, 3 rows deep. It shall be
constructed of copper tubes and aluminum fins and have a maximum face velocity of 391fpm (2.0 m/s)
at 1250 CFM (2124 CMH). The coil shall be supplied with 45°F (7.2°C) entering water temperature.
The coil shall be supplied with ______ GPM (l/s) of chilled water and the pressure drop shall not
exceed ______ PSI (kPa). The coil assembly shall be mounted in a condensate drain pan with an
internally trapped drain line. The evaporator drain pan shall include a factory-installed float switch
to shut down the evaporator upon high water condition.
2.3
Indoor Air-Cooled Centrifugal Fan Condensing Unit
Condensing unit components shall include condenser coil, scroll compressor, high-pressure switch,
Lieber Lee-Temp™ refrigerant receiver, head pressure control valve, hot gas bypass system and liquid
line solenoid valve. The hot gas bypass circuit shall be provided to reduce compressor cycling and
improve operation under low-load conditions.
All components shall be factory-assembled, charged with R-407C refrigerant and sealed. No internal
piping, brazing, dehydration or charging shall be required. Condensing unit shall be designed for
95°F (35°C) ambient and be capable of operation to -30°F (-34°C). The condensing unit can be
mounted directly to the evaporator or can be mounted remote to the evaporator.
The condensing coil shall be constructed of copper tubes and aluminum fins. The condenser fan shall
be centrifugal type, double inlet, direct drive and shall operate at 1050 RPM (890 RPM @ 50Hz). The
condenser fan shall be designed for ____CFM (CMH) at ____" (mm) w.g. external static pressure.
2.3
Outdoor Air-Cooled Prop Fan Condensing Unit
Condensing unit components shall include a condenser coil, a direct-drive propeller-type fan, a scroll
compressor, high-pressure switch, Liebert Lee-Temp receiver and head pressure control valve, hot
gas bypass system and liquid line solenoid valve. A hot gas bypass system shall be provided to reduce
compressor cycling and improve operation under low load conditions.
All components shall be factory-assembled, charged with R-407C refrigerant and sealed. No internal
piping, brazing, dehydration or charging shall be required. Condensing unit shall be designed for
95°F (35°C) ambient and be capable of operation to -30°F (-34.4°C).
The condenser coil shall be constructed of copper tubes and aluminum fins.
(Option) The condensing unit shall be designed to operate at a sound level less than 58 dBA.
(Option) The outdoor condensing unit shall be designed for design ambient operation of 105°F
(40.6°C).
2.3
Indoor Water/Glycol-Cooled Condensing Unit
The water/glycol condensing unit shall include a scroll compressor, high-pressure switch, coaxial
condenser, water-regulating valve, hot gas bypass system and liquid line solenoid valve. A hot gas
bypass circuit shall be provided to reduce compressor cycling and improve operation under low-load
conditions. All components shall be factory-assembled, charged with R-407C refrigerant and sealed.
No internal piping, brazing dehydration or charging shall be required.
The water/glycol condensing unit shall be equipped with a coaxial condenser having a total system
pressure drop of ______ ft. of water (kPa) and a flow rate of ______ GPM (l/s) with ______ °F (°C)
entering water/glycol temperature.
The condenser circuit shall be pre-piped with a [(2-way) (3-way)] regulating valve which is
head-pressure actuated.
The condenser water/glycol circuit shall be designed for a static operating pressure of
[(150 PSI (1034kPa)) (350 PSI (2413 kPa))].
Liebert® Mini-Mate2™
46
Guide Specifications for Liebert Mini-Mate2—2- and 3-Ton Systems
2.4
Factory-Installed Options
2.4.1
Steam Generating Humidifier
The environmental control system shall be equipped with a steam generating humidifier that is
controlled by the microprocessor control system. It shall be complete with disposable canister, all
supply and drain valves, 1" (25.4mm) air gap on fill line, inlet strainer, steam distributor and
electronic controls. The need to change canister shall be annunciated on the microprocessor wall box
control panel. The humidifier shall have a capacity of 4.3 lb/hr (2.0 kg/h). An LED light on the
humidifier assembly shall indicate cylinder full, overcurrent detection, fill system fault and end of
cylinder life conditions.
2.4.2
Electric Reheat
The electric reheat shall be low-watt density, 304/304 stainless steel, finned-tubular and shall be
capable of maintaining room dry bulb temperature conditions when the system is calling for
dehumidification. The reheat section shall include a UL-approved safety switch to protect the system
from overheating. The capacity of the reheat coils shall be ______ BTU/HR (kW), with unit input
voltage of _____ V, controlled in one stage.
2.4.3
Hot Water Reheat
The hot water reheat coil shall have copper tubes and aluminum fins with a capacity of ______ BTU/
HR (kW) when supplied with ______°F (°C) entering water temperature at _______ GPM (l/s) flow
rate. Maximum pressure drop shall be ______ PSI (kPa). The control system shall be factory prepiped
with a 2-way solenoid valve and cleanable Y-strainer. The hot water reheat coil shall only be available
on chilled water units.
2.4.4
SCR Electric Reheat
The electric reheat shall be low-watt density, 304/304 stainless steel, finned-tubular and shall be
capable of maintaining room dry bulb conditions when the system is calling for dehumidification. The
reheat section shall include a UL-approved safety switch to protect the system from overheating.
The SCR (Silicon Controlled Rectifier) controller shall proportionally control the reheat elements to
maintain the selected room temperature. The rapid cycling made possible by the SCR controller
provides precise temperature control, and the more constant element temperature improves heater
life. The unit microprocessor control shall operate the SCR controller, while cooling is locked on. The
capacity of the reheat coils shall be ______ BTU/HR (kW), with input voltage of ______ V. Not
available on chilled water or free-cooling units.
2.4.5
Disconnect Switch, Non-Locking
The non-automatic, non-locking, molded case circuit interrupter shall be factory mounted in the
high-voltage section of the electrical panel. The switch handle shall be accessible from the front of the
indoor unit.
2.4.6
High-Temperature Sensor
The high-temperature sensor shall immediately shut down the system when high temperatures are
detected. The high-temperature sensor shall be mounted with the sensing element in the return air.
2.4.7
Smoke Sensor
The smoke detector shall immediately shut down the environmental control system and activate the
alarm system when activated. The sensing element shall be located in the return air compartment.
This smoke sensor shall not function or replace any room smoke detection system that may be
required by local or national codes.
2.4.8
Filter Clog Switch
The filter clog switch senses pressure drop across the filters and shall annunciate the wall box display
upon exceeding the adjustable setpoint.
47
Liebert® Mini-Mate2™
Guide Specifications for Liebert Mini-Mate2—2- and 3-Ton Systems
2.4.9
Free-Cooling/Dual Cooling Coil
A free-cooling coil shall be integral to the evaporator cabinet, and shall be constructed of copper tubes
and aluminum fins. The coil shall be rated at ______ BTU/HR (kW) sensible cooling capacity with a
45°F (22°C), ___% glycol solution. The coil shall require ______ GPM (l/s) and the total unit pressure
drop shall not exceed ______ feet of water (kPa) when in the free cooling mode. Free-cooling shall be
activated by a temperature stat and shall include factory-piped three-way valve and separate supply
and return piping.
Coil is designed for closed-loop applications using properly treated and circulated fluid. Not available
with SCR reheat. An optional Cu-Ni coil is required to prevent premature corrosion if applied to open
water tower loop.
A heat exchanger and pump shall be field-supplied to isolate the open water tower loop from the
freecooling loop.
2.5
Ship-Loose Accessories
2.5.1
Remote Sensors
The unit shall be supplied with remote temperature and humidity sensors. The sensors shall be
connected to the unit by a ______ ft. (m) shielded cable.
2.5.2
Air Filter Box
The evaporator section shall be supplied with an air filter box for use with ducted installations. The
filter shall be 4" x 20" x 20" (102mm x 508mm x 508mm), deep-pleated type, with a MERV 8 rating
based on ASHRAE 52.2-2007.
2.5.3
Air Distribution Plenum
The evaporator section shall be supplied with an air distribution plenum with integral filter. The
plenum shall be 24" x 48" (610mm x 1219mm) in size and shall provide 4-way air distribution, for
installation into a standard 24" x 48" (610mm x 1219mm) ceiling grid. Filter size shall be
4"-x-16"-x 25" (102 mm x 406mm x 535 mm), deep pleated type with MERV 8 rating, based on
ASHRAE 52.2-2007.
2.5.4
High Static Blower Assembly
A blower box shall be field attached to the evaporator to provide up to 2.0" (51mm) of external static
pressure on the discharge side of the evaporator. The blower box shall contain a centrifugal type,
double inlet blower, with belt drive and single speed motor, mounted to an adjustable motor base.
2.5.5
Condensate Pump
The condensate pump shall have the capacity of _____ GPH (___ l/h) at ___ ft. head (___ kPa). It shall
be complete with integral float switch, pump, motor assembly and reservoir.
2.5.6
Refrigerant Line Sets
Pre-charged refrigerant line sets shall be provided by Emerson in proper lengths for application. Line
set length shall be [(15 ft. (4.5m)) (30 ft. (9m))].
2.5.7
Refrigerant Line Sweat Adapter Kit
Provide a sweat adapter kit to permit field brazing of refrigerant line connections.
2.5.8
Single Point Power Kit
A Single Point Power Kit shall be provided for a close-coupled system to allow a single electrical feed
to supply power to both the evaporator and condensing unit.
2.5.9
Step-Down Transformer
A step-down transformer shall be provided for Outdoor Condensing Unit needing 277V input power
voltage. The transformer shall be coated with epoxy and contained in an enclosed, non-ventilated
electrical box with adaptable mounting brackets, suitable for outdoor mounting.
Liebert® Mini-Mate2™
48
Guide Specifications for Liebert Mini-Mate2—2- and 3-Ton Systems
2.5.10 Liebert SiteScan® Site Monitoring System
A Liebert SiteScan Site Monitoring System Model __________________ shall be provided for remote
monitoring of the Mini-Mate2 unit and monitoring of other Liebert support equipment. The Liebert
SiteScan shall have the capability to monitor and change (at the user direction) the temperature and
humidity setpoints and sensitivities of each unit. The printer shall provide the user with
chronological alarm information. It shall also be capable of being programmed to print out
environmental conditions or operating modes at each unit.
2.5.11 Drycooler
The Liebert drycooler shall be a low-profile, direct-drive propeller fan-type air-cooled unit. The
drycooler shall be constructed with an aluminum cabinet and a copper-tube aluminum fin coil and
multiple direct drive fans. All electrical connections and controls shall be enclosed in an integral
weather resistant electric control panel section of the drycooler. The unit is quiet and
corrosion-resistant.
The drycooler shall be designed for _____°F (°C) ambient.
2.5.12 Glycol Pump Package
The system shall include a centrifugal pump mounted in a weatherproof and vented enclosure. The
pump shall be rated for ____ gpm (l/s) at ____ ft. (kPa) of head, and shall operate on ____ volt,
_____ phase, ____ Hz.
3.0
EXECUTION
3.1
Installation of Air Conditioning Unit
3.1.1
General
Install air conditioning unit in accordance with manufacturer's installation instructions. Install unit
plumb and level, firmly anchored in location indicated, and maintain manufacturer's recommended
clearances.
3.1.2
Electrical Wiring
Install and connect electrical devices furnished by manufacturer but not specified to be
factory-mounted. Furnish copy of manufacturer’s electrical connection diagram submittal to electrical
contractor.
3.1.3
Piping Connections
Install and connect devices furnished by manufacturer but not specified to be factory-mounted.
Furnish copy of manufacturer’s piping connection diagram submittal to piping contractor.
3.1.4
Supply and Drain Water Piping
Connect water supply and drains to air conditioning unit. Unit drain shall be trapped internally.
3.1.5
Field-Supplied Pan
A field-supplied pan with drain shall be installed beneath cooling units installed without air
distribution plenum and beneath water/glycol condensing units.
3.1.6
Field Quality Control
Startup air conditioning unit in accordance with manufacturer's start up instructions. Test controls
and demonstrate compliance with requirements.
49
Liebert® Mini-Mate2™
Technical Support / Service
Web Site
www.liebert.com
Monitoring
[email protected]
800-222-5877
Outside North America: +00800 1155 4499
Single-Phase UPS & Server Cabinets
[email protected]
800-222-5877
Outside North America: +00800 1155 4499
Three-Phase UPS & Power Systems
800-543-2378
Outside North America: 614-841-6598
Environmental Systems
800-543-2778
Outside the United States: 614-888-0246
Locations
While every precaution has been taken to ensure the accuracy
and completeness of this literature, Liebert Corporation assumes no
responsibility and disclaims all liability for damages resulting from use of
this information or for any errors or omissions.
© 2013 Liebert Corporation
All rights reserved throughout the world. Specifications subject to change
without notice.
® Liebert is a registered trademark of Liebert Corporation.
All names referred to are trademarks
or registered trademarks of their respective owners.
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
29/F, The Orient Square Building
F. Ortigas Jr. Road, Ortigas Center
Pasig City 1605
Philippines
+63 2 687 6615
Fax: +63 2 730 9572
SL-10535_REV8_10-13
Emerson Network Power
Division: Liebert
Web: www.emerson.com
www.EmersonNetworkPower.com