Configure ADAM-6100PN module in SIEMENS SIMATIC Manager Product: ADAM-6100PN Series Abstract: Introduction of ADAM-6100PN Series connected to SIEMENS PLC Description: In this document, we will demonstrate how to connect ADAM-6100PN module to SIEMENS PLC using SIMATIC Manager Contents Add CPU in SIMATIC Project Download to PLC Search and configure ADAM-6100PN module by SIMATIC Manager Install GSD File of ADAM-6100PN module Add ADAM-6100PN module under PLC Monitor and Modify I/O Programing in STEP7 Add CPU in SIMATIC Project 1. Click [New Project/Library] 1 2. Give a project [Name] and click [OK] 3. Right click [Project Name] (here, ADAM6100DVT), click [Insert New Object] \ [SIMATIC 300 Station] (We use this model as demo here) 2 4. [SIMATIC 300] model has been added 5. Right click [SIMATIC 300] label under project name, and click [Open module] 3 6. Now we start to configure model, drag a [Rail] under [SIMATIC 300] \ [RACK-300] to white workplace 4 7. Drag [SIMATIC 300] \ [CPU-300] \ [CPU 315F-2 PN/DP] \ [6ES7 315-2FH13-0AB0] \ [V2.6] CPU to slot 2 in the rack. 5 8. Here we add a subnet in pop-out windows, click [New…] 9. Click [OK] to add 6 10. Click [OK] to end 7 11. The CPU has been added 8 12. Click [Station] \ [Save and Compile] 9 Download to PLC 1. Back to [SIMATIC Manager], and connect PC and PLC thought [SIMATIC S7 PC Adapter USB] in MPI 2. Click [Options] \ [Set PG/PC Interface…] 10 3. Select [PC Adapter(Auto)] or [PC Adapter(MPI)], click [Properties…] 4. Select [Connection to USB] in [Local Connection] tab, click [OK] and back to SIMATIC Manager 11 5. Click [PLC] \ [Download] to start downloading 12 Search and configure ADAM-6100PN module by SIMATIC Manager 1. We need to switch interface to Ethernet, click [Option] \ [Set PG/PC Interface…] 13 2. Choose the connected interface and click [OK] 14 3. Click [PLC] \ [Edit Ethernet Node…] 15 4. Click [Browse…] 16 5. Browser will auto start search, the ADAM-6100PN module will show by the [Device type: adam-6100pn profinet]. Choose the module and click [OK] 17 6. IP parameter and device name can be configure in this window 18 Install GSD File of ADAM-6100PN module 1. Click [Option] \ [Install GSD File…] in HW Config 19 2. Click [Browse…] to import and select the GSD file, then click [Install] 3. Click [Yes] to continue, and wait for installing 20 4. The installed GSD is show under [PROFINET IO] \ [Additional Field Devices] \ [I/O] \ [Advantech PROFINET Devices] \ [ADAM-6100PN Compact I/O] 21 Add ADAM-6100PN module under PLC 1. Drag [ADAM-6100PN Compact I/O] node to [Ethernet: PROFINET-IO-System (100)] 22 2. Double click the ADAM node to configure 23 3. The [Device Name] can be assign here and the [IP address] can be configure be click [Ethernet…] buttom 24 4. Drag the ADAM-6100PN module to slot 1 of the [ADAM-6100PN Compact I/O] node 25 5. ADAM module is shown in slot 1, and the [I Address] and [Q address] are also shown in the slot 1. Double click slot 1 to configure 26 6. In [General] tab, the module name can be assigned 27 7. In the [Address] tab, the input address (I address) and output address (Q address) and be assigned. Here the ADAM-6150PN has one byte input and one byte output 28 8. For AI module, ADAM-6117PN, which has 8 channel with 1 word, 2 bytes, 16-bit, the input address from 256 to 271 is 16 words 29 Monitor and Modify I/O 1. Here use ADAM-6150PN and ADAM-6117PN as example. After download the logic to PLC, select slot 1 in the node first 30 2. Click [PLC] \ [Monitor/Modify] 31 3. Check [Monitor] to monitor the real-time status, here shows the input address 32 4. Input true/fulse value in [Modify value] column and check [Modify] 33 5. For AI module ADAM-6117PN, we can write 16-bit, word, value 34 Programing in STEP7 1. 2. Open [Start] \ [SIMATIC] \ [STEP 7] \ [LAD,STL, FBD – Programing S7 Blocks] Open object 3. Open the object [OB1] in the project as following figure, and click [OK] 35 4. Language can be change under [View] 36 5. After programing, click [Download] under [PLC] Written by Alan.Chien, ADAM Product AE, 2012/1/4 37