p085.

RA-V7SERIES
●RA-V7
The RA-V7 Series utilizes micro-gap discharge
technology, thus demonstrating extremely fast
response characteristics in dark ambient conditions
without the use of radioactive isotopes.
Applied as indirect lightning surge protection in the
power line of equipment, this model is used with a
series connected MOV between line and ground in the
power line.
It may also be used within electronic circuits to
protect from destructive impulse current while still
permitting “Voltage Withstand Testing”without
having to remove the RA-V7.
UL
UL
CSA
Safety Approvals
: UL-1449
: UL-1414
: C22.2 No. 1
: IEC 384-14
File No .
E143446
E47474
LR105073
J9551103
FEATURES:
● Fast response time(see V-T Chart)
● This Surge Absorber is Bi-polar and will fail open if
surge withstand capability is exceeded.
● Inter-terminal capacitance is extremely small,
resulting in little influence on electronic circuits.
● High Insulation Resistance(1×10 9 min.)
● Excellent Surge withstand capability (300 times at
100Amp, 8×20μs.)
● Small size for compact circuit design.
● Available taped for auto insertion. Add“Y”to
model number.(RA-242M-V7-Y)
L1
PROTECTED
EQUIPMENT
MOV
L2
RA-V7
RA-M-V7
RA-MS-V7
φ5min
270Vmin
A
19 Max
16 Max
Unit:mm
MOV
SAFETY STANDARD
CSA
UL
UL
C22.2
1449
1414
No.1
○
−
−
○
−
−
○
−
−
○
−
−
○
○
○
○
○
○
○
○
○
○
○
−
○
○
−
○
○
−
○
○
−
○
○
−
○
○
−
○
○
−
IEC
384-14
−
−
−
−
−
○
○
○
○
−
○
○
○
○
Type
RA-501M/MS-V7
RA-601M/MS-V7
RA-102M/MS-V7
RA-152M/MS-V7
RA-242M-V7
RA-302M-V7
RA-362M-V7
RA-402M-V7
RA-452M-V7
RA-242MS-V7
RA-302MS-V7
RA-362MS-V7
RA-402MS-V7
RA-452MS-V7
Consult factory for non-standerd products.
DC
spark-over
Voltage
(V)
500(400∼600)
600(480∼720)
1000(800∼1200)
1500(1200∼1800)
2400(1920∼2880)
3000(2400∼3600)
3600(2880∼4320)
4000(3200∼4800)
4500(3600∼5400)
2400(1920∼2880)
3000(2400∼3600)
3600(2880∼4320)
4000(3200∼4800)
4500(3600∼5400)
85
Capacitance
1kHz-1.5V(pF)
2.0Max.
Peak Surge
Current
8/20μs
(A)
3500
Impulse
life test
8/20μs
100A
300
Withstand
Voltage
Test
−
−
−
−
AC1250V 3sec.
AC1500V 60sec.
AC1800V 3sec.
AC2000V 60sec.
AC2000V 60sec.
AC1250V 3sec.
AC1500V 60sec.
AC1800V 3sec.
AC2000V 60sec.
AC2000V 60sec.
SURGE ABSORBERS
SURGE ABSORBER
RA-V7SERIES
POWER LINES
V - T CHARACTERISTICS
Vf
Transient Sparkover Voltage →
(V)
Response Time →(T)
LIGHTNING SURGE PROTECT FOR AC POWER LINES
RA-242M-V7
RA-302M-V7
SPECIFICATION
PLUS MOV
RATED VOLTAGE
DC BREAKDOWN VOLTAGE
RA-362M-V7
PLUS MOV
AC125V 50/60Hz
AC250V 50/60Hz
2400V±20%
3000V±20%
AC1000V, 50/60Hz, 60S Max.
AC1500V, 50/60Hz, 60S Max.
AC1250V, 50/60Hz, 3S Max.
VOLTAGE WITHSTANDING TEST
PLUS MOV
AC250V 50/60Hz
3600V±20%
AC1500V, 50/60Hz, 60S Max.
AC1800V, 50/60Hz, 3S Max.
L1
Z1
Z2
L2
CASE①
φ1
1 PHASE
PROTECTED
EQUIPMENT
E
RA
RA ; RA - 242M - V7
RA ; RA - 302M - V7
RA ; RA - 362M - V7
Z1 ; MOV φ10 Min., 270VMin. Z1 ; MOV φ10 Min., 400VMin. Z1 ; MOV φ10 Min., 400VMin.
Z2 ; MOV φ10 Min., 270VMin. Z2 ; MOV φ10 Min., 400VMin. Z2 ; MOV φ10 Min., 400VMin.
L1
PROTECTED
EQUIPMENT
Z1
METHOD OF USE
L2
Z2
E
CASE②
φ1
1 PHASE
RA ; RA - 242M - V7
RA ; RA - 302M - V7
RA ; RA - 362M - V7
Z1 ; MOV φ10 Min., 200VMin. Z1 ; MOV φ10 Min., 400VMin. Z1 ; MOV φ10 Min., 400VMin.
Z2 ; MOV φ5 Min., 270VMin. Z2 ; MOV φ5 Min., 400VMin. Z2 ; MOV φ5 Min., 400VMin.
RA
L1
L2 PROTECTED
EQUIPMENT
L3
E
CASE③
φ3
3 PHASE
Z1
Z2
Z3
RA ; RA - 302M - V7
Z1 ; MOV φ10 Min., 400VMin.
Z2 ; MOV φ10 Min., 400VMin.
Z3 ; MOV φ10 Min., 400VMin.
RA ; RA - 362M - V7
Z1 ; MOV φ10 Min., 400VMin.
Z2 ; MOV φ10 Min., 400VMin.
Z3 ; MOV φ10 Min., 400VMin.
RA ; RA - 302M - V7
Z1 ; MOV φ10 Min., 400VMin.
Z2 ; MOV φ10 Min., 400VMin.
Z3 ; MOV φ10 Min., 400VMin.
Z4 ; MOV φ5 Min., 400VMin.
RA ; RA - 362M - V7
Z1 ; MOV φ10 Min., 400VMin.
Z2 ; MOV φ10 Min., 400VMin.
Z3 ; MOV φ10 Min., 400VMin.
Z4 ; MOV φ5 Min., 400VMin.
RA
L1
Z1
Z2
CASE④
φ3
3 PHASE
Z3
L2 PROTECTED
EQUIPMENT
L3
Z4
E
RA
86