LVD Series • Low Voltage Disconnect • Output Ratings from 40A to100A @ 3-75 VDC • Low On-State Resistance FET Output • Six DC control Ranges Available for 12 & 24VDC Battery Systems • Compact Encapsulated Panel Mount Package PRODUCT SELECTION Control Voltage 11.5-12 VDC 23-24 VDC 40A 60A 80A 100A LVD75B40 LVD75D40 LVD75B60 LVD75D60 LVD75B80 LVD75D80 LVD75B100 LVD75D100 AVAILABLE OPTIONS OUTPUT SPECIFICATIONS (1) Description 40A 60A 80A 100A Operating Voltage [Vdc] Maximum Load Current [Adc] (2) Minimum Load Current [mAdc] Maximum Surge Current (10msec) [Adc] Maximum On-State Voltage Drop @ Rated Current [Vdc] Thermal Resistance Junction to Case (Rjc) [°C/W] Max On-state Resistance @ rated current (Rds-on) [mOhms] Maximum Off-State Leakage Current @ Rated Voltage [mA] 3-75 40 5 120 0.6 1.2 15 0.5 3-75 60 5 180 0.6 1.0 10 0.5 3-75 80 5 220 0.64 0.5 8 0.5 3-75 100 5 250 0.5 0.4 5 0.5 INPUT SPECIFICATIONS (1) Description Must Turn-On Voltage [Vdc] (3) Must Turn-Off Voltage [Vdc] (3) Maximum Allowed input Voltage [Vdc] Maximum Input Current [mAdc] Maximum Turn-On Time [msec] Maximum Turn-Off Time [msec] LVD75Axx LVD75Bxx LVD75Cxx LVD75Dxx LVD75Exx LVD75Fxx 11.5 11 36 12 150 150 12 11.5 36 12 150 150 12.5 12 36 12 150 150 24 23 36 12 150 150 25 24 36 12 150 150 26.6 25.6 36 12 150 150 GENERAL SPECIFICATIONS Description Dielectric Strength, Input/Output to Baseplate (60Hz) (4) Minimum Insulation Resistance (@ 500 V DC) Maximum Capacitance, Input/Output Ambient Operating Temperature Range Ambient Storage Temperature Range Weight (typical) Terminals Input Terminal Screw Torque Range: Output Terminal Screw Torque Range: GENERAL NOTES 1) All parameters at 25°C unless otherwise specified. 2) Heat Sinking required, see derating curves. 3) Tolerance + 0.15Vdc 4) All four terminals shorted together during test. WIRING DIAGRAM MECHANICAL SPECIFICATIONS Parameters 2500 Vrms 109 Ohm 50 pF -30 to 80 °C -40 to 125 °C 3.5 oz (100g) Hardware Furnished, mounted 8-10 in lb (0.9-1.1Nm) 18-20 in lb (2-2.2Nm) THERMAL DERATE INFORMATION AGENCY APPROVALS Designed in accordance with the requirements of IEC 62314 Rev. 032712 ANNEX - ENVIROMENTAL INFORMATION