JCH - Cooper Bussmann

Bussmann®
R-Rated Fuses
For Motor Circuit Protection
Medium Voltage
JCK, JCK-A, JCK-B, JCH,
JCL, JCL-A, JCL-B,
JCG, JCR-A, & JCR-B
• R-Rated medium voltage fuses are back-up current limiting
fuses used in conjunction with medium voltage motors and
motor controllers.
• The JCK-A, JCL-A, & JCR-A are supplied with CutlerHammer Ampgard Hookeye.
• This single hookeye is on one end of the fuse and aids in the
insertion and removal of the fuse.
• Current limiting fuses may be designated as R-Rated if they
meet the following requirements:
1. The fuse will safely interrupt all currents between its
minimum and maximum interrupting ratings.
2. The fuse will melt in a range of 15 to 35 seconds at a
value of 100 times the “R’ number (ANSI C37.46).
• Bussmann R-Rated current limiting fuses are designed for
use with medium voltage starters to provide short-circuit
protection for the motor and motor controller.
• These fuses offer a high level of fault current interruption in a
self-contained, non-venting package which can be mounted
indoors or in an enclosure.
• Open fuse indication on all fuses.
Catalog Symbol:
JCK, JCK-A, JCK-B, JCH, JCL, JCL-A,
JCL-B, JCG, JCR-A, & JCR-B
R-Rated
Medium Voltage
Current Limiting
2400V AC — JCK, JCK-A, JCK-B, JCH
4800V AC — JCL, JCL-A, JCL-B, JCG
7200V AC — JCR-A, JCR-B
Max. Design Voltage
2540V AC — JCK, JCK-A,
JCK-B, JCH
5080V AC — JCL, JCL-A
JCL-B, JCG
8300V AC — JCR-A, JCR-B
UL Recognized:
2540V AC — JCK, JCK-A
5080V AC — JCL, JCL-A
(2R-24R)
UL Recognized (GUIDE #MSSS2, FILE # E96676)
2-26-03
SB03044
Form No. JCK, JCK-A, JCK-B, JCH, JCL,
JCL-A, JCL-B, JCG, JCR-A, & JCR-B
Page 1 of 8
Data Sheet: 6001
Bussmann®
JCK, JCK-A, JCK-B, JCH,
JCL, JCL-A, JCL-B,
JCG, JCR-A, & JCR-B
R-Rated Fuses
For Motor Circuit Protection
Medium Voltage
Specifications
Buss
Catalog No.
Amperage
Maximum
Design Voltage
A
Dimensions (Inches)
B
C
Construction
Max. Int. Cap.
Amps (Asym.)
Amps (Sym.)
Min. Int. Cap.
Amps (Sym.)
2400V; R-Rated; Indoor/Enclosure (See Figure 1)
JCK-2R
70 2R
2540V
11.24
3.0
3.0
Single
80,000
50,000
165
JCK-3R
100 3R
2540V
11.24
3.0
3.0
Single
80,000
50,000
220
JCK-4R
130 4R
2540V
11.24
3.0
3.0
Single
80,000
50,000
320
JCK-5R
150 5R
2540V
11.24
3.0
3.0
Single
80,000
50,000
410
JCK-6R
170 6R
2540V
11.24
3.0
3.0
Single
80,000
50,000
480
JCK-9R
200 9R
2540V
11.24
3.0
3.0
Single
80,000
50,000
720
JCK-12R
230 12R
2540V
11.24
3.0
3.0
Single
80,000
50,000
970
JCK-18R
390 18R
2540V
11.24
3.0
3.0
Double
80,000
50,000
1,430
JCK-24R
450 24R
2540V
11.24
3.0
3.0
Double
80,000
50,000
1,880
2400V; R-Rated; Indoor/Enclosure; With Cutler-Hammer Ampgard Hookeye (See Figure 1)
JCK-A-2R
70 2R
2540V
11.24
3.0
3.0
Single
80,000
50,000
165
JCK-A-3R
100 3R
2540V
11.24
3.0
3.0
Single
80,000
50,000
220
JCK-A-4R
130 4R
2540V
11.24
3.0
3.0
Single
80,000
50,000
320
JCK-A-5R
150 5R
27540V
11.24
3.0
3.0
Single
80,000
50,000
410
JCK-A-6R
170 6R
2540V
11.24
3.0
3.0
Single
80,000
50,000
480
JCK-A-9R
200 9R
2540V
11.24
3.0
3.0
Single
80,000
50,000
720
JCK-A-12R
230 12R
2540V
11.24
3.0
3.0
Single
80,000
50,000
970
JCK-A-18R
390 18R
2540V
11.24
3.0
3.0
Double
80,000
50,000
1,430
JCK-A-24R
450 24R
2540V
11.24
3.0
3.0
Double
80,000
50,000
1,880
2400V; R-Rated; Indoor/Enclosure; Bolt-On (See Figure 2)
JCK-B-30
25
2540V
14.18
12.81
-
Single
80,000
50,000
100
JCK-B-2R
70 2R
2540V
14.18
12.81
-
Single
80,000
50,000
180
JCK-B-3R
100 3R
2540V
14.18
12.81
-
Single
80,000
50,000
270
JCK-B-4R
130 4R
2540V
14.18
12.81
-
Single
80,000
50,000
360
JCK-B-5R
150 5R
2540V
14.18
12.81
-
Single
80,000
50,000
450
JCK-B-6R
170 6R
2540V
14.18
12.81
-
Single
80,000
50,000
540
JCK-B-9R
200 9R
2540V
14.18
12.81
-
Single
80,000
50,000
740
JCK-B-12R
230 12R
2540V
14.18
12.81
-
Single
80,000
50,000
1,080
JCK-B-18R
390 18R
2540V
14.18
12.81
3.56
Double
80,000
50,000
1,500
JCK-B-24R
450 24R
2540V
14.18
12.81
3.56
Double
80,000
50,000
2,200
2400V; R-Rated; Indoor; Hermetically Sealed, Class 1, Group D, Div. 2, Hazardous Locations; For Use with Ampgard Motor Starters (See Figure 1)
JCH-30
25
2540V
11.56
3.0
4.12
Single
80,000
50,000
100
JCH-2R
70 2R
2540V
11.56
3.0
4.12
Single
80,000
50,000
180
JCH-3R
100 3R
2540V
11.56
3.0
4.12
Single
80,000
50,000
270
JCH-4R
130 4R
2540V
11.56
3.0
4.12
Single
80,000
50,000
360
JCH-5R
150 5R
2540V
11.56
3.0
4.12
Single
80,000
50,000
450
JCH-6R
170 6R
2540V
11.56
3.0
4.12
Single
80,000
50,000
540
JCH-9R
200 9R
2540V
11.56
3.0
4.12
Single
80,000
50,000
740
JCH-12R
230 12R
2540V
11.56
3.0
4.12
Single
80,000
50,000
1,080
JCH-18R
390 18R
2540V
11.56
3.0
7.68
Double
80,000
50,000
1,500
JCH-24R
450 24R
2540V
11.56
3.0
7.68
Double
80,000
50,000
2,200
4800V; R-Rated; Indoor/Enclosure (See Figure 1)
JCL-2R
70 2R
5080V
15.76
3.0
3.0
Single
80,000
50,000
165
JCL-3R
100 3R
5080V
15.76
3.0
3.0
Single
80,000
50,000
220
JCL-4R
130 4R
5080V
15.76
3.0
3.0
Single
80,000
50,000
320
JCL-5R
150 5R
5080V
15.76
3.0
3.0
Single
80,000
50,000
410
JCL-6R
170 6R
5080V
15.76
3.0
3.0
Single
80,000
50,000
480
JCL-9R
200 9R
5080V
15.76
3.0
3.0
Single
80,000
50,000
720
JCL-12R
230 12R
5080V
15.76
3.0
3.0
Single
80,000
50,000
970
JCL-18R
390 18R
5080V
15.76
3.0
3.0
Double
80,000
50,000
1,430
JCL-24R
450 24R
5080V
15.76
3.0
3.0
Double
80,000
50,000
1,880
2-26-03
SB03044
Form No. JCK, JCK-A, JCK-B, JCH, JCL,
JCL-A, JCL-B, JCG, JCR-A, & JCR-B
Page 2 of 8
Data Sheet: 6001
Bussmann®
JCK, JCK-A, JCK-B, JCH,
JCL, JCL-A, JCL-B,
JCG, JCR-A, & JCR-B
R-Rated Fuses
For Motor Circuit Protection
Medium Voltage
Specifications
Buss
Catalog No.
Amperage
Maximum
Design Voltage
A
Dimensions (Inches)
B
C
Construction
Max. Int. Cap.
Amps (Asym.)
Amps (Sym.)
Min. Int. Cap.
Amps (Sym.)
4800V; R-Rated; Indoor/Enclosure; With Cutler-Hammer Ampgard Hookeye (See Figure 1)
JCL-A-2R
70 2R
5080V
15.76
3.0
3.0
Single
80,000
50,000
165
JCL-A-3R
100 3R
5080V
15.76
3.0
3.0
Single
80,000
50,000
220
JCL-A-4R
130 4R
5080V
15.76
3.0
3.0
Single
80,000
50,000
320
JCL-A-5R
150 5R
5080V
15.76
3.0
3.0
Single
80,000
50,000
410
JCL-A-6R
170 6R
5080V
15.76
3.0
3.0
Single
80,000
50,000
480
JCL-A-9R
200 9R
5080V
15.76
3.0
3.0
Single
80,000
50,000
720
JCL-A-12R
230 12R
5080V
15.76
3.0
3.0
Single
80,000
50,000
970
JCL-A-18R
390 18R
5080V
15.76
3.0
3.0
Double
80,000
50,000
1,430
JCL-A-24R
450 24R
5080V
15.76
3.0
3.0
Double
80,000
50,000
1,880
JCL-A-36R
650 36R
5080V
16.0
4.0
-
Double
100,000
63,000
3,200
4800V; R-Rated; Indoor/Enclosure; Bolt-On (See Figure 2)
JCL-B-30
30
5080V
19.25
17.88
-
Single
80,000
50,000
100
JCL-B-2R
70 2R
5080V
19.25
17.88
-
Single
80,000
50,000
180
JCL-B-3R
100 3R
5080V
19.25
17.88
-
Single
80,000
50,000
270
JCL-B-4R
130 4R
5080V
19.25
17.88
-
Single
80,000
50,000
360
JCL-B-5R
150 5R
5080V
19.25
17.88
-
Single
80,000
50,000
450
JCL-B-6R
170 6R
5080V
19.25
17.88
-
Single
80,000
50,000
540
JCL-B-9R
200 9R
5080V
19.25
17.88
-
Single
80,000
50,000
740
JCL-B-12R
230 12R
5080V
19.25
17.88
-
Single
80,000
50,000
1,080
JCL-B-18R
390 18R
5080V
19.25
17.88
3.31
Double
80,000
50,000
1,500
JCL-B-24R
450 24R
5080V
19.25
17.88
3.31
Double
80,000
50,000
2,200
4800V; R-Rated; Indoor; Hermetically Sealed, Class 1, Group D, Div. 2, Hazardous Locations; For Use with Ampgard Motor Starters (See Figure 1)
JCG-30
30
5080V
16.6
3.0
4.12
Single
80,000
50,000
95
JCG-2R
70 2R
5080V
16.6
3.0
4.12
Single
80,000
50,000
180
JCG-3R
100 3R
5080V
16.6
3.0
4.12
Single
80,000
50,000
270
JCG-4R
130 4R
5080V
16.6
3.0
4.12
Single
80,000
50,000
350
JCG-5R
150 5R
5080V
16.6
3.0
4.12
Single
80,000
50,000
450
JCG-6R
170 6R
5080V
16.6
3.0
4.12
Single
80,000
50,000
540
JCG-9R
200 9R
5080V
16.6
3.0
4.12
Single
80,000
50,000
700
JCG-12R
230 12R
5080V
16.6
3.0
4.12
Single
80,000
50,000
1,000
JCG-18R
390 18R
5080V
15.85
3.0
6.31
Double
80,000
50,000
1,450
JCG-24R
450 24R
5080V
15.85
3.0
6.31
Double
80,000
50,000
2,000
7200V; R-Rated; Indoor/Enclosure; With Ampgard Hookeye (See Figure 1)
JCR-A-2R
70 2R
8300V
15.85
3.0
4.12
Single
80,000
50,000
200
JCR-A-3R
100 3R
8300V
15.85
3.0
4.12
Single
80,000
50,000
320
JCR-A-4R
130 4R
8300V
15.85
3.0
4.12
Single
80,000
50,000
405
JCR-A-5R
150 5R
8300V
15.85
3.0
4.12
Single
80,000
50,000
550
JCR-A-6R
170 6R
8300V
15.85
3.0
4.12
Single
80,000
50,000
670
JCR-A-9R
200 9R
7200V
15.85
3.0
4.12
Single
80,000
50,000
1,300
JCR-A-12R
230 12R
7200V
15.85
3.0
4.12
Single
80,000
50,000
1,500
JCR-A-18R
390 18R
7200V
15.85
3.0
7.43
Double
80,000
50,000
2,000
JCR-A-24R
450 24R
7200V
15.85
3.0
7.43
Double
80,000
50,000
2,600
7200V; R-Rated; Indoor/Enclosure; Bolt-On (See Figure 2)
JCR-B-2R
70 2R
8300V
19.25
17.88
-
Single
80,000
50,000
200
JCR-B-3R
100 3R
8300V
19.25
17.88
-
Single
80,000
50,000
320
JCR-B-4R
130 4R
8300V
19.25
17.88
-
Single
80,000
50,000
405
JCR-B-5R
150 5R
8300V
19.25
17.88
-
Single
80,000
50,000
550
JCR-B-6R
170 6R
8300V
19.25
17.88
-
Single
80,000
50,000
670
JCR-B-9R
200 9R
7200V
19.25
17.88
-
Single
80,000
50,000
1,300
JCR-B-12R
230 12R
7200V
19.25
17.88
-
Single
80,000
50,000
1,500
JCR-B-18R
390 18R
7200V
19.25
17.88
3.31
Double
80,000
50,000
2,000
JCR-B-24R
450 24R
7200V
19.25
17.88
3.31
Double
80,000
50,000
2,600
2-26-03
SB03044
Form No. JCK, JCK-A, JCK-B, JCH, JCL,
JCL-A, JCL-B, JCG, JCR-A, & JCR-B
Page 3 of 8
Data Sheet: 6001
Bussmann®
R-Rated Fuses
For Motor Circuit Protection
Medium Voltage
JCK, JCK-A, JCK-B, JCH,
JCL, JCL-A, JCL-B,
JCG, JCR-A, & JCR-B
Dimensional Data
INDICATOR
Showing Fuse is Open
0.38"
(9.5mm)
C
INDICATOR
Showing Fuse
is Open
A
B
Figure 1
Figure 2
2-26-03
SB03044
Form No. JCK, JCK-A, JCK-B, JCH, JCL,
JCL-A, JCL-B, JCG, JCR-A, & JCR-B
Page 4 of 8
Data Sheet: 6001
Bussmann®
R-Rated Fuses
For Motor Circuit Protection
Medium Voltage
JCK, JCK-A, JCK-B, JCH,
JCL, JCL-A, JCL-B,
JCG, JCR-A, & JCR-B
JCK, JCK-A, JCL, JCL-A
Time-Current Characteristic Curves–Minimum Melt
Total Clearing Curves
167-A
168-A
INSTANTANEOUS PEAK LET THRU
CURRENT AMPERES
Current Limitation Curves
184-A
PROSPECTIVE SHORT CIRCUIT CURRENT (X10)
RMS SYMMETRICAL AMPERES
2-26-03
SB03044
Form No. JCK, JCK-A, JCK-B, JCH, JCL,
JCL-A, JCL-B, JCG, JCR-A, & JCR-B
Page 5 of 8
Data Sheet: 6001
Bussmann®
R-Rated Fuses
For Motor Circuit Protection
Medium Voltage
JCK, JCK-A, JCK-B, JCH,
JCL, JCL-A, JCL-B,
JCG, JCR-A, & JCR-B
JCK-B, JCH
Time-Current Curve: Minimum Melt
50999-1
Time-Current Curve: Total Clearing
50999-2
Peak Let-Through Curves
INSTANTANEOUS PEAK LET THRU
CURRENT AMPERES
50999-3
PROSPECTIVE SHORT CIRCUIT CURRENT (X10)
RMS SYMMETRICAL AMPERES
2-26-03
SB03044
Form No. JCK, JCK-A, JCK-B, JCH, JCL,
JCL-A, JCL-B, JCG, JCR-A, & JCR-B
Page 6 of 8
Data Sheet: 6001
Bussmann®
R-Rated Fuses
For Motor Circuit Protection
Medium Voltage
JCK, JCK-A, JCK-B, JCH,
JCL, JCL-A, JCL-B,
JCG, JCR-A, & JCR-B
JCL-B, JCG
Time-Current Curve: Minimum Melt
Time-Current Curve: Total Clearing
51000-2
51000-1
Peak Let-Through Curves
INSTANTANEOUS PEAK LET THRU
CURRENT AMPERES
51000-3
PROSPECTIVE SHORT CIRCUIT CURRENT (X10)
RMS SYMMETRICAL AMPERES
2-26-03
SB03044
Form No. JCK, JCK-A, JCK-B, JCH, JCL,
JCL-A, JCL-B, JCG, JCR-A, & JCR-B
Page 7 of 8
Data Sheet: 6001
Bussmann®
R-Rated Fuses
For Motor Circuit Protection
Medium Voltage
JCK, JCK-A, JCK-B, JCH,
JCL, JCL-A, JCL-B,
JCG, JCR-A, & JCR-B
JCR, JCR-B
Time-Current Curve: Minimum Melt
Time-Current Curve: Total Clearing
51001-2
51001-1
Peak Let-Through Curves
INSTANTANEOUS PEAK LET THRU
CURRENT AMPERES
51001-3
PROSPECTIVE SHORT CIRCUIT CURRENT (X10)
RMS SYMMETRICAL AMPERES
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this Data Sheet are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected,
it should be tested by the user in all possible applications.
2-26-03
SB03044
Form No. JCK, JCK-A, JCK-B, JCH, JCL,
JCL-A, JCL-B, JCG, JCR-A, & JCR-B
Page 8 of 8
Data Sheet: 6001