E-Rated Medium Voltage Fuses MV155

Bussmann®
E-Rated Medium Voltage Fuses
MV155
For Transformer and Feeder Protection
15.5 kV
Electrical Characteristics
Part Numbers†
Ampere
Rating
Min/
Melt I2t
Max.
Clear I2t
MV155F1CBX5E
5A
180
2900
MV155F1CBX7E
7A
850
8000
MV155F1CBX10E
10A
850
8000
MV155F1CBX15E
15A
2070
12000
MV155F1CBX20E
20A
2370
23000
MV155F1CBX25E
25A
4650
31000
MV155F1CBX30E
30A
9490
45000
MV155F1DBX10E
10A
850
8000
MV155F1DBX15E
15A
2070
12000
MV155F1DBX20E
20A
2370
23000
MV155F1DBX25E
25A
4650
31000
MV155F1DBX30E
30A
9490
45000
MV155F1DBX40E
40A
9490
45000
MV155F1DBX50E
50A
13600
90000
MV155F1DBX65E
65A
30700
181000
MV155F1DBX80E
80A
54600
270000
MV155F1DBX100E
100A
116200
600000
MV155F2DBX125E
125A
123000
677000
MV155F2DBX150E
150A
218700
1287000
MV155F2DBX175E
175A
314700
1689000
MV155F2DBX200E
200A
465100
2405000
MV155F1DCX65E
65A
30700
181000
MV155F1DCX80E
80A
54600
270000
MV155F1DCX100E
100A
116200
600000
MV155F2DCX125E
MV155F2DCX150E
125A
150A
123000
218700
677000
1287000
MV155F2DCX175E
175A
314700
1689000
MV155F2DCX200E
200A
465100
2405000
Physical Size (inches)
Length
Dia. Clip Center
Barrels
18.75
2
15
1
18.75
3
15
1
18.75
3
15
2
21.75
3
18
1
21.75
3
18
2
CATALOG SYMBOL: MV155
E-RATED MEDIUM VOLTAGE FUSES:
Meets E requirements per ANSI C37.46
Meets Full Range requirements per ANSI C37.40
FOR TRANSFORMER AND FEEDER PROTECTION
VOLTAGE RATING: 15.5 kV
INTERRUPTING RATING: 50 kA Maximum Sym.
CURRENT LIMITING
CONSTRUCTION: Silver ribbon element surrounded by
silica filler housed in a fiberglass tube and plated endcaps.
An epoxy paint protects the fuse tube from the surrounding environment.
FEATURES:
• Standard Clip Center Lengths and Barrel Diameters.
The new line of Bussmann 15.5 kV medium voltage fuses
have standard clip center distances of 15 or 18 inches
and barrel diameters of 2 or 3 inches which allow fuses to
retrofit exisiting hardware.
• Blown Fuse Indication with Indicator.
• 100% Tested for Reliability. All medium voltage fuses
are pulsed twice with 90% of their minimum melt I2t to
guarantee undamaged elements. This test does not affect
undamaged elements. A damaged element completely
opens when subjected to 90% of the minimum melt I2t,
allowing it to be detected by a resistance check.
• Full Range Fuses. Bussmann medium voltage fuses
provide full range protection and are capable of interrupting fault currents of 50,000A sym.
• Time Current Curves and Dimensional Data:
MV155F1CB series, see page 2;
MV155F1DB and MV155F1DC series, see page 3.
• Peak Arc Voltage Curves and Peak Let-Through
Data, see page 4.
• Fuse Clips, see page 4.
† To order with the optional striker pin, see Part Number Construction chart below.
Part Number Construction
Example
Medium Voltage
Voltage Rating
MV
155
F
055 = 5.5 kV
F = Full Range
155 = 15.5 kV
Number of Barrels
Barrel Diameter
Clip Center Distance
Indication Type
Ampere Rating
1
C
B
X
5E
1
C = 2 inches
A = 12 inches
X = Indicator only
2
D = 3 inches
B = 15 inches
S = Striker Pin
C = 18 inches
2-26-03
SB03044
Form No. MV155
Page 1 of 5
Data Sheet: 6701
Bussmann®
E-Rated Medium Voltage Fuses
MV155
For Transformer and Feeder Protection
15.5 kV - MV155F1CB Series
100
AMPERE
RATING
100
10
.01
100
10
10
.01
7,000
.1
1,000
.1
7,000
1
1,000
1
100
TIME IN SECONDS
10
TIME IN SECONDS
15A
20A
25A
30A
15A
20A
25A
30A
5A
7A
10A
AMPERE
RATING
5A
7A
10A
Time-Current Characteristics
Total Clearing
Time-Current Characteristics
Minimum Melt
CURRENT IN AMPERES
CURRENT IN AMPERES
MV155F1CBX
18.61"
17.77"
2.03"
.21"
BUSSMANN
.63"
Ø2.095"
INDICATOR
15.00"
CLIP CENTER
2-26-03
SB03044
POSITION OF BLOWN
INDICATOR AFTER
OPERATING.
Form No. MV155
Page 2 of 5
Data Sheet: 6701
Bussmann®
E-Rated Medium Voltage Fuses
MV155
For Transformer and Feeder Protection
15.5 kV - MV155F1DB & MV155F1DC Series
Time-Current Characteristics
Minimum Melt
Time-Current Characteristics
Total Clearing
1000
100
200A
125A
150A
175A
50A
65A
80A
100A
10A
15A
20A
25A
30A
40A
200A
125A
150A
175A
10A
15A
20A
25A
30A
40A
50A
65A
80A
100A
1000
100
10
TIME IN SECONDS
TIME IN SECONDS
10
1
1
.1
.1
DOUBLE BARREL
FUSE ASSY.
DOUBLE BARREL
FUSE ASSY.
SINGLE BARREL
FUSE ASSY.
SINGLE BARREL
FUSE ASSY.
MV155F1DBX
Double Barrel
Dimensions
18.61"
17.77"
.21"
2.40"
BUSSMANN
.63"
Ø2.96"
Ø1.30"
INDICATOR
Ø3.38"
15.00"
POSITION OF BLOWN
INDICATOR AFTER
OPERATING.
CLIP CENTER
3.50"
6.68"
MV155F1DCX
21.61"
20.77"
2.40"
.21"
Ø2.96"
BUSSMANN
.63"
INDICATOR
Ø3.38"
18.00"
Ø1.30"
POSITION OF BLOWN
INDICATOR AFTER
OPERATING.
CLIP CENTER
2-26-03
SB03044
Form No. MV155
Page 3 of 5
Data Sheet: 6701
20000
CURRENT IN AMPERES
10000
10
1000
CURRENT IN AMPERES
.01
100
20000
10000
1000
100
10
.01
Bussmann®
E-Rated Medium Voltage Fuses
MV155
For Transformer and Feeder Protection
15.5 kV - Peak Arc Voltage & Peak Let-Through Data
Max. Peak Let-Through Current Curves
MAXIMUM PEAK ARC VOLTAGE FOR
"E" RATED FULL RANGE POWER FUSE
(BUSSMANN)
B
100
50
200A
175A
150A
125A
100A
80A
65A
MAXIMUM PEAK ARC VOLTAGE (KV)
50A
30&40A
10
25A
20A
15A
07&10A
05A
1
30
20
10
A
20
0
15
0
AVAILABLE CURRENT IN KILOAMPERES (RMS Symmetrical)
10
10
1
.1
5
.1
100
MAXIMUM LET-THROUGH (Peak Kiloamperes)
40
CIRCUIT VOLTAGE (KV)
Recommended Fuse Clips for Medium Voltage Fuses
Part
No.
A3354710
A3354730
Fuse
Clip Dimensions
Diameter
A
B
2”
3”
3.74”
4.13”
1.97”
2.44”
C
2.00”
3.00”
D
E
F
G
1.18” 4.53” 1.50” .39”
1.18” 5.63” 1.50” .39”
Fuseclips are for single barrel applications up to 200E only.
C
A
G
F
D
E
B
2-26-03
SB03044
Form No. MV155
Page 4 of 5
Data Sheet: 6701
Bussmann®
E-Rated Medium Voltage Fuses
MV155
For Transformer and Feeder Protection
15.5 kV - Cross Reference Data
Catalog Number Cross Reference
Bussmann
Gould (New)
Gould (Old)
Westinghouse
MV155F1CBXxxxE
A155F1CORO-xxxE
A1550X-xxxE-1B
----
----
General Electric
----
MV155F1DBXxxxE
A155F1DORO-xxxE
A1550X-xxxE-1F
15HLE-xxxE
9F62DDDxxx
9F60FMHxxx
MV155F1DCXxxxE
A155F1DORO-xxxE
A1550X-xxxE-1D
----
----
----
MV155F2DCXxxxE
A155F2DORO-xxxE
A1550X-xxxE-1D
----
----
----
Bussmann Medium Voltage Cross Reference
Overall
Sym.
Length
kA
Manufacturer
18-3/4”
50
Bussmann
15.5 kV
17-3/100”
50
Gould†
18-3/4”
50
Bussmann
18-7/8”
40
Gould†
15.5 kV
3”
15”
18-7/8”
50
Westinghouse†
18-7/8”
40
General Electric†
3”
18”
21-3/4”
50
Bussmann
15.5 kV
21-3/4”
50
Gould†
† Gould, Westinghouse and General Electric are General Purpose Fuses.
kV
Dia.
2”
Clip
Center
15”
E Ratings Available
5
7
10 15
S S
S
S
S S
S
S
S
S
S
S
S = Single Barrel
20
S
S
S
S
S
S
25
S
S
S
S
S
S
30
S
S
S
S
S
S
D = Double Barrel
40
50
65
80
S
S
S
S
S
S
S
S
S
D
S
S
S
S
S
D
S
S
S
S
100 125 150 175
S
D
S
S
S
S
200 250 300 350 400 450
D
D
D
D
D
S
D
S
D
D
D
S
D
D
D
D
D
D
D
D
D
D
D
Current-limiting medium voltage fuses are classified into three categories:
Full Range - defined by ANSI as “a fuse capable of interrupting all currents from the maximum rated interrupting current down to
the minimum continuous current that causes melting of the fusible element(s), when the fuse is applied at the maximum ambient
temperature specified by the manufacturer.” It is able to interrupt any normal 60 cycle current that will melt its element.
General Purpose - defined by ANSI C37.40 as “a fuse capable of interrupting all currents from the maximum rated interrupting
current down to the current that causes melting of the fusible element in one hour.” Not all currents fall within this range. It is
possible to receive an overcurrent lower than the value given by the one hour criterion.
Back-up - defined by ANSI C37.40 as “a fuse capable of interrupting all currents from the maximum rated interrupting current
down to the rated minimum interrupting current.” The minimum rated interrupting current is the lowest current that the fuse will be
able to clear properly. This creates a need to place a low current interrupting device in series with the back-up rated fuse.
All Bussmann MV series medium voltage fuses are E-rated and offer Full Range Protection.
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this BIF document are by definition uncontrolled.This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected,
it should be tested by the user in all possible applications.
2-26-03
SB03044
Form No. MV155
Page 5 of 5
Data Sheet: 6701