Medium Voltage Fuses Section Contents Page Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72 E-Rated Fues For transformers & feeders . . . . . . . . . . . . . . . . . . . . . . .75 CL-14 & bolt-in . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76 CL-14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77 For potential & small power transformers . . . . . . . . . . 78-79 British IEC fuses for motor circuit protection . . . 83 DIN IEC fuses for transformer protection . . . . . . 84 Potential transformer fuses . . . . . . . . . . . . . . . . . 85 British IEC fuses for oil-filled switchgear . . . . . . 86 Fast-acting fuses . . . . . . . . . . . . . . . . . . . . . . . . . 87 EEI-NEMA Type K & T and Type H & N fuses . . . 88 BBU Boric acid fuses . . . . . . . . . . . . . . . . . . . 89-90 Fuseclips for medium and high voltage fuses . . . 91 71 Medium Voltage Fuses R-Rated fuses for motor circuit protection . . . 80-82 Medium Voltage Fuses Medium Voltage Fuses Worldwide Circuit Protection Solutions Cooper Bussmann is a world-leading supplier of medium voltage fuses. Each product is backed by an efficient worldwide distribution network with unrivaled service and technical support. Cooper Bussmann circuit protection solutions comply with major international standards: ANSI, BS, DIN, IEC and UL. Fuse Types Medium voltage fuses generally fit into two categories – expulsion fuses and current limiting fuses. The definitions per ANSI C37.40 are: Expulsion Fuse: “A vented fuse in which the expulsion effect of the gases produced by internal arcing, either alone or aided by other mechanisms results in current interruption.” Expulsion fuses will limit the duration of an overcurrent event, but they will not limit the magnitude of fault current. Cooper Bussmann offers two types of expulsion fuses: replacement fuse links for fused cutouts and boric acid fuses. Current Limiting Fuse: “A fuse unit that, when in its currentresponsive element is melted by a current within the fuse’s specified current-limiting range, abruptly introduces a high resistance to reduce current magnitude and duration, resulting in subsequent current interruption.” A current limiting fuse will reduce the magnitude a fault current as well as limit the duration of the overcurrent event when operating in its current limiting range. Cooper Bussmann offers a broad range of current limiting fuses for protection of feeders, transformers and motor circuits designed to ANSI, BS, DIN and IEC standards. Medium Voltage Current Limiting Fuses Current limiting fuses are classified into three categories: 1. Full Range – defined by ANSI C37.40 as “a fuse capable of interrupting all currents from the maximum rated interrupting current down to the minimum continuous current that causes the melting of the fusible element(s), when the fuse is applied at the maximum ambient temperature specified by the manufacturer.” It is able to interrupt any current that will melt its element. 72 2. General Purpose – defined by ANSI C37.40 as “a fuse capable of interrupting all currents from the maximum rated interrupting current down to the current that causes melting of the fusible element(s) in one hour.” Not all currents fall within this range. It is possible for the fuse to be exposed to an overcurrent lower than the value given by the one hour criteria. In that case, a different overcurrent protection device would be required to interrupt the overcurrent. 3. Back-up – defined by ANSI C37.40 as “a fuse capable of interrupting all currents from the maximum interrupting rating current down to the minimum interrupting current.” The minimum interrupting current is the lowest current that the fuse will be able to clear properly. This creates a need to place a low current interrupting device, such as motor overloads, in series with the back-up rated fuse. E- and R-Rated Fuses In North America, current limiting fuses typically fall into the category of E-Rated fuses and R-Rated fuses. Cooper Bussmann also offers a wide range of current limiting fuses designed to BS, DIN and IEC standards. E-Rated fuses are used to protect feeder circuits, power transformers and potential transformers. E-Rated fuses have defined current response times specified by ANSI C37.46. E-Rated fuses 100A and below must melt in 300sec at an rms current within the range of 200% to 240% of the continuous current rating. E-Rated fuses above 100A must melt in 600sec at an rms current within the range of 240% to 264% of the continuous current rating of the fuse. Cooper Bussmann offers a wide variety of full range and general purpose E-Rated fuses from 2.4kV up to 38kV. R-Rated fuses are back-up fuses that provide short-circuit protection for motor circuits. They are applied with MV motor starters which provide the overload protection for the circuit. R-Rated fuses also have defined current response times specified by ANSI C37.46. R-Rated fuses will melt in a range of 15 – 35sec at a current equal to 100 times the “R” rating. Cooper Bussmann offers 2.4kV, 5.08kV, 7.2kV and 8.3kV R-Rated fuses for motor circuit protection. For detailed information, visit the Electrical IEC section at www.cooperbussmann.com Medium Voltage Fuses E-rated Fuses for Transformers and Feeders 5.5kV Catalog Numbers MV055 and MV155 Catalog Numbers MV055 Features and Benefits • Standard clip center distance of 12 inches with 2 and 3 inch barrel diameters for retrofitting in existing hardware • Open fuse indicator for ease in troubleshooting • Full range rating with 50,000 Interrupting Rating • Double pulsed at 90% of minimum I2t to establish manufacturing reliability • • • • MV055 Typical Applications 5.0kV Transformer Primary Protection 5.0kV Feeder Circuit Protection 5.0kV Voltage Switches 5.0kV Metal-enclosed Switchgear MV155 Features and Benefits • Standard clip center distance of 15 and 18 inches with 2 and 3 inch barrel diameters for retrofitting in existing hardware • Open fuse indicator for ease in troubleshooting • Full range rating with 50,000 Interrupting Rating • Double pulsed at 90% of minimum I2t to establish manufacturing reliability • • • • MV155 Typical Applications 15.0kV Transformer Primary Protection 15.0kV Feeder Circuit Protection 15.0kV Voltage Switches 15.0kV Metal-enclosed Switchgear Min Melt I2t MV055F1CAX5E 5 180 MV055F1CAX7E 7 850 MV055F1CAX10E 10 850 MV055F1CAX15E 15 2,070 MV055F1CAX20E 20 2,370 MV055F1CAX25E 25 4,650 MV055F1CAX30E 30 9,490 MV055F1CAX40E 40 9,490 MV055F1CAX50E 50 13,600 MV055F1CAX65E 65 30,700 MV055F1DAX10E 10 850 MV055F1DAX15E 15 2,070 MV055F1DAX20E 20 2,370 MV055F1DAX25E 25 4,650 MV055F1DAX30E 30 9,490 MV055F1DAX40E 40 9,490 MV055F1DAX50E 50 13,600 MV055F1DAX65E 65 30,700 MV055F1DAX80E 80 54,600 MV055F1DAX100E 100 116,200 MV055F1DAX125E 125 167,400 MV055F1DAX150E 150 218,700 MV055F1DAX175E 175 227,900 MV055F1DAX200E 200 297,600 MV055F2DAX250E 250 669,600 MV055F2DAX300E 300 874,800 MV055F2DAX350E 350 911,600 MV055F2DAX400E 400 1,190,400 MV055F2DAX450E 450 1,555,000 1” = 25.4mm Recommended Fuse Clips - see page 91 Max Clear I2t 2,400 8,000 8,000 11,000 23,000 31,000 45,000 45,000 90,000 181,000 8,000 12,000 23,000 31,000 45,000 45,000 90,000 181,000 270,000 580,000 600,000 786,000 1,100,000 1,520,000 2,400,000 3,149,000 4,376,000 6,071,000 9,796,000 Dimensions (in)* Clip Length Dia. Center Barrels 15.75 2 12 1 12 1 2 15.75 3 Medium Voltage Fuses Specifications Description: E-rated medium, voltage currentlimiting fuses: for transformer and feeder protection. Dimensions: See Catalog Numbers table. Construction: Silver ribbon element surrounded by silica filler housed in a fiberglass tube and plated endcaps. An epoxy paint protects the fuse tube from the surrounding environment. Ratings: Volts: — 5.5kV (5-450A) — 15.5kV (5-200A) Amps: — 5-450A (5.5kV) — 5-200A (15.5kV) IR: — 50kA Sym. Max Agency Information: Meets E requirements per ANSI C37.46, Meets full range requirements per ANSI C37.40. Amp Rating 1 12 15.75 3 15.75 3 12 1 15.75 3 12 2 2 Data Sheet: 6700 15.5kV Catalog Numbers Catalog Numbers MV155F1CBX5E MV155F1CBX7E MV155F1CBX10E MV155F1CBX15E MV155F1CBX20E MV155F1CBX25E MV155F1CBX30E MV155F1DBX10E MV155F1DBX15E MV155F1DBX20E MV155F1DBX25E MV155F1DBX30E MV155F1DBX40E MV155F1DBX50E MV155F1DBX65E MV155F1DBX80E MV155F1DBX100E MV155F2DBX125E MV155F2DBX150E MV155F2DBX175E MV155F2DBX200E MV155F1DCX65E MV155F1DCX80E MV155F1DCX100E MV155F2DCX125E MV155F2DCX150E MV155F2DCX175E MV155F2DCX200E *1” = 25.4mm. Amp Rating 5 7 10 15 20 25 30 10 15 20 25 30 40 50 65 80 100 125 150 175 200 65 80 100 125 150 175 200 Min Melt I2t Max Clear I2t 180 850 850 2,070 2,370 4,650 9,490 850 2,070 2,370 4,650 9,490 9,490 13,600 30,700 54,600 116,200 123,000 218,700 314,700 465,100 30,700 54,600 116,200 123,000 218,700 314,700 465,100 2,900 8,000 8,000 12,000 23,000 31,000 45,000 8,000 12,000 23,000 31,000 45,000 45,000 90,000 181,000 270,000 600,000 677,000 1,287,000 1,689,000 2,405,000 181,000 270,000 600,000 677,000 1,287,000 1,689,000 2,405,000 Dimensions* Clip Center Barrels Length Dia. 18.75 15 1 15 1 1 2 18.75 3 15 18.75 18.75 3 3 15 2 2 21.75 3 18 1 1 21.75 21.75 3 18 18 2 2 Recommended Fuse Clips - see page 91 Data Sheet: 6701 (MV155) For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa 73 Medium Voltage Fuses E-rated Fuses for Transformer & Feeders JCX, JCY, JCU, JCZ and JDZ Specifications Description: Indoor/enclosure E-rated medium voltage, currentlimiting fuses for feeders and power transformers with blown fuse indication. Dimensions: See Catalog Numbers table. Construction: plated ferrules. Ratings: Volts: — 2750-8300V (See Catalog Numbers table for details) Amps: — 1⁄2-750A IR: — 40-63kA Sym — 60-100kA ASYM — See Catalog Numbers table for details Features and Benefits • Physically dimensioned for retrofitting in existing hardware • Open fuse indicator for ease in troubleshooting • Full range ANSI classification • • • • Typical Medium Medium Medium Medium Applications Voltage Transformer Primary Protection Voltage Feeder Circuit Protection Voltage Switches Voltage Metal-enclosed Switchgear Catalog Numbers Catalog Amp Maximum Numbers Rating Design Voltage 2400V; E-Rated; Indoor/Enclosure JCX-1⁄2E 0.5 2750 JCX-1E 1 2750 JCX-2E 2 2750 JCX-3E 3 2750 JCX-5E 5 2750 JCX-7E 7 2750 JCX-10E 10 2750 JCX-15E 15 2750 JCX-20E 20 2750 JCX-25E 25 2750 JCX-30E 30 2750 JCX-40E 40 2750 JCX-50E 50 2750 JCX-65E 65 2750 JCX-80E 80 2750 JCX-100E 100 2750 JCX-125E 125 2750 JCX-150E 150 2750 JCX-200E 200 2750 JCX-225E 225 2750 JCX-250E/280X 250/280 2750 JCX-300E/325X 300/325 2750 JCX-350X 350 2750 JCX-400X 400 2750 JCX-450X 450 2750 5500V; E-Rated; Indoor/Enclosure JCY-1⁄2E 0.5 5500 JCY-1E 1 5500 JCY-2E 2 5500 JCY-3E 3 5500 JCY-5E 5 5500 JCY-7E 7 5500 JCY-10E 10 5500 JCY-15E 15 5500 JCY-20E 20 5500 JCY-25E 25 5500 Construction Maximum Interrupting Capacity Amps (Asym.) Amps (Sym.) Dimensions - in (mm) Length Diameter Single Single Single Single Single Single Single Single Single Single Single Single Single Single Single Single Single Single Single Single Double Double Double Double Double 60,000 60,000 60,000 60,000 60,000 60,000 60,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 40,000 40,000 40,000 40,000 40,000 40,000 40,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 40,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 9.19 (233.38) 9.19 (233.38) 9.19 (233.38) 9.19 (233.38) 9.19 (233.38) 9.19 (233.38) 9.19 (233.38) 9.5 (241.3) 9.5 (241.3) 9.5 (241.3) 10.81 (276.35) 10.81 (276.35) 10.81 (276.35) 10.81 (276.35) 10.81 (276.35) 10.81 (276.35) 10.81 (276.35) 10.81 (276.35) 10.81 (276.35) 10.81 (276.35) 10.81 (276.35) 10.81 (276.35) 10.81 (276.35) 10.81 (276.35) 10.81 (276.35) 2 (50.8) 2 (50.8) 2 (50.8) 2 (50.8) 2 (50.8) 2 (50.8) 2 (50.8) 2.1 (53.34) 2.1 (53.34) 2.1 (53.34) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) Single Single Single Single Single Single Single Single Single Single 60,000 60,000 60,000 60,000 60,000 60,000 60,000 60,000 60,000 60,000 40,000 40,000 40,000 40,000 40,000 40,000 40,000 40,000 40,000 40,000 11.19 11.19 11.19 11.19 11.19 11.19 11.19 11.19 11.19 11.19 2 2 2 2 2 2 2 2 2 2 (284.18) (284.18) (284.18) (284.18) (284.18) (284.18) (284.18) (284.18) (284.18) (284.18) Contact Cooper Bussmann for the latest product information on E-Rated fuses for transformer and feeder protection. Recommended fuseclips: see page 91 - 1A0065, 9078A67G04, A3354730 74 For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa (50.8) (50.8) (50.8) (50.8) (50.8) (50.8) (50.8) (50.8) (50.8) (50.8) Medium Voltage Fuses E-rated Fuses for Transformer & Feeders Catalog Numbers: E-Rated; Indoor/Enclosure Maximum Design Voltage Construction Maximum Interrupting Capacity Amps. (Asym.) Amps. (Sym.) Dimensions - in (mm) Length Diameter 5500 5500 5500 5500 5500 5500 5500 5500 5500 5500 5500 5500 5500 5500 5500 5500 5500 5500 5500 5500 5500 Single Single Single Single Single Single Single Single Single Single Single Single Single Single Single Double Double Double Double * * 80,000 80,000 80,000 80,000 100,000 100,000 100,000 100,000 100,000 100,000 100,000 100,000 100,000 100,000 100,000 100,000 100,000 100,000 100,000 80,000 80,000 50,000 50,000 50,000 50,000 63,000 63,000 63,000 63,000 63,000 63,000 63,000 63,000 63,000 63,000 63,000 63,000 63,000 63,000 63,000 50,000 50,000 17.81 12.88 12.88 12.88 17.88 17.88 17.88 17.88 17.88 17.88 17.88 17.88 17.88 17.88 17.88 17.88 17.88 17.88 17.88 28.81 28.81 (452.4) (327.0) (327.0) (327.0) (454.15) (454.15) (454.15) (454.15) (454.15) (454.15) (454.15) (454.15) (454.15) (454.15) (454.15) (454.15) (454.15) (454.15) (454.15) (731.77) (731.77) 3 (76.2) 2.1 (53.34) 2.1 (53.34) 2.1 (53.34) 3 (76.20) 3 (76.20) 3 (76.20) 3 (76.20) 3 (76.20) 3 (76.20) 3 (76.20) 3 (76.20) 3 (76.20) 3 (76.20) 3 (76.20) 3 (76.20) 3 (76.20) 3 (76.20) 3 (76.20) 4 (101.60) 4 (101.60) 8300 8300 8300 8300 8300 8300 8300 8300 8300 8300 8300 8300 8300 8300 8300 8300 8300 8300 8300 8300 8300 Single Single Single Single Single Single Single Single Single Single Single Double Single Single Single Single Single Single Double Double Double 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 15.51 15.51 15.51 17.88 17.88 17.88 17.88 17.88 17.88 17.88 17.88 17.88 15.88 15.88 15.88 15.88 15.88 15.88 15.88 15.88 15.88 (393.95) (393.95) (393.95) (454.15) (454.15) (454.15) (454.15) (454.15) (454.15) (454.15) (454.15) (454.15) (403.2) (403.2) (403.2) (403.2) (403.2) (403.2) (403.2) (403.2) (403.2) 2.1 (53.34) 2.1 (53.34) 2.1 (53.34) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) Medium Voltage Fuses Catalog Amp Numbers Rating 5500V; E-Rated; Indoor/Enclosure JCU-10E 10 JCU-15E 15 JCU-20E 20 JCU-25E 25 JCU-30E 30 JCU-40E 40 JCU-50E 50 JCU-65E 60 JCU-80E 80 JCU-100E 100 JCU-125E 125 JCU-150E 150 JCU-175E 175 JCU-200E 200 JCU-250E 250 JCU-300E 300 JCU-350E 350 JCU-400E 400 JCU-450E 450 JCU-600E 600 JCU-750E 750 8300V; E-Rated; Indoor/Enclosure JCZ-15E 15 JCZ-20E 20 JCZ-25E 25 JCZ-30E 30 JCZ-40E 40 JCZ-50E 50 JCZ-65E 65 JCZ-80E 80 JCZ-100E 100 JCZ-125E 125 JCZ-150E 150 JCZ-200E 200 JDZ-20E 20 JDZ-25E 25 JDZ-30E 30 JDZ-40E 40 JDZ-50E 50 JDZ-65E 65 JDZ-80E 80 JDZ-100E 100 JDZ-125E 125 Recommended fuseclips: see page 91 - 1A0065, 9078A67G04, A3354730 General Notes: 1. All fuses are fitted with a striker pin which can be used for indication or tripping purposes. 2. The fuses are suitable for use either indoors or outdoors. 3. These fuses are interchangeable with corresponding fuses produced by most other leading North American manufacturers. Contact Cooper Bussmann for the latest product information on E-Rated fuses for transformer and feeder protection. *Bolt on mounting For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa 75 Medium Voltage Fuses E-rated Fuses: CL-14 & Bolt-In ECL055 Specifications Description: E-rated medium voltage, current-limiting fuses for transformer and feeder protection. Construction: Filament wound, glass epoxy fuse tube, with silica filler, and silver-plated copper terminals and endcaps containing a silver element in a double concentric helical configuration. Ratings: Volts: — 5.5kV Amps: — 10-900A IR: — 63kA Sym. Max Agency Information: Meets E requirements per ANSI C37.46, Meets General Purpose requirements per ANSI C37.40. Features and Benefits • Clip-lock and bolt-in style available in double and triple barrel fuse designs for application flexibility • The filament wound, glass epoxy fuse tube provides UV and moisture protection, making these medium voltage fuses suitable for both indoor and outdoor applications • Open fuse indication (indicator travel distance is 16mm) easily integrates into automation schemes • 50/60Hz operating frequency make these fuses applicable world-wide • • • • Typical Applications 5.0kV Transformer Primary Protection 5.0kV Feeder Circuit Protection 5.0kV Voltage Switches 5.0kV Metal-enclosed Switchgear Catalog Numbers Catalog Numbers ECL055-10E ECL055-15E ECL055-20E ECL055-25E ECL055-30E ECL055-40E ECL055-50E ECL055-65E ECL055-80E ECL055-100E ECL055-125E ECL055-150E ECL055-200E ECL055-250E ECL055-300E ECL055-400E ECL055-450E ECL055-500E ECL055-600E ECL055-750E ECL055-900E Amp Rating 10 15 20 25 30 40 50 65 80 100 125 150 200 250 300 400 450 500 600 750 900 Voltage 5.5kV – – – – – – – – – – – – – – – – – – – – IR Max Sym. 63kA # of Barrels 1 Style Clip-Lock 1 Clip-Lock 2 Clip-Lock 3 Bolt-In Bolt-In 63kA 2 3 Catalog Number Construction (Example) Catalog Number ECL Voltage Rating 055 055 = 5.5 kV Amp Rating 500E Catalog Number Cross Reference Cooper Bussmann Catalog Numbers ECL055-10E ECL055-15E ECL055-20E ECL055-25E ECL055-30E ECL055-40E ECL055-50E ECL055-65E ECL055-80E ECL055-100E ECL055-125E ECL055-150E ECL055-200E ECL055-250E ECL055-300E ECL055-400E ECL055-450E ECL055-500E ECL055-600E ECL055-750E ECL055-900E Ferraz-Shawmut New Catalog # A055C1DORO-10E A055C1DORO-15E A055C1DORO-20E A055C1DORO-25E A055C1DORO-30E A055C1DORO-40E A055C1DORO-50E A055C1DORO-65E A055C1DORO-80E A055C1DORO-100E A055C1DORO-125E A055C1DORO-150E A055C1DORO-200E A055C1DORO-250E A055C1DORO-300E A055C1DORO-400E A055C2DORO-450E A055C2DORO-500E A055C2DORO-600E A055B3DORO-750E A055B3DORO-900E Data Sheet: 9002 76 For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa Ferraz-Shawmut Old Catalog # 225-007-937 225-007-938 225-007-939 225-007-940 225-007-941 225-007-942 225-007-943 225-007-944 225-007-945 225-007-946 225-007-947 225-007-948 225-007-949 225-007-950 225-007-951 225-007-952 225-007-953 225-007-954 225-007-955 A055X750E-4 A055X900E-4 Medium Voltage Fuses E-rated Fuses: CL-14 ECL155 Features and Benefits • Clip-lock double barrel fuse design assures positive installation • The filament wound, glass epoxy fuse tube provides UV and moisture protection, making these medium voltage fuses suitable for both indoor and outdoor applications • Open fuse indication (indicator travel distance is 16mm) easily integrates into automation schemes • 50/60 Hz operating frequency make these fuses applicable world-wide • • • • Typical Applications 15.0kV Transformer Primary Protection 15.0kV Feeder Circuit Protection 15.0kV Voltage Switches 15.0kV Metal-enclosed Switchgear Catalog Numbers Catalog Numbers ECL155-10E ECL155-15E ECL155-20E ECL155-25E ECL155-30E ECL155-40E ECL155-50E ECL155-65E ECL155-80E ECL155-100E ECL155-125E ECL155-150E ECL155-200E ECL155-250E ECL155-300E Amp Rating 10 15 20 25 30 40 50 65 80 100 125 150 200 250 300 Voltage 15.5kV IR Voltage Max Sym. 63KA # of Barrels 1 Style Clip-Lock 1 63kA 15.5kV Clip-Lock 2 50kA 50kA 2 Catalog Number Construction (Example) Catalog Number ECL Voltage Rating 155 155 = 15.5 kV Amp Rating 300E Catalog Number Cross Reference Cooper Bussmann Catalog Numbers ECL155-10E ECL155-15E ECL155-20E ECL155-25E ECL155-30E ECL155-40E ECL155-50E ECL155-65E ECL155-80E ECL155-100E ECL155-125E ECL155-150E ECL155-200E ECL155-250E ECL155-300E Ferraz-Shawmut New Catalog # A155C1DORO-10E A155C1DORO-15E A155C1DORO-20E A155C1DORO-25E A155C1DORO-30E A155C1DORO-40E A155C1DORO-50E A155C1DORO-65E A155C1DORO-80E A155C1DORO-100E A155C2DORO-125E A155C3DORO-150E A155C3DORO-200E A155C3DORO-250E A155C3DORO-300E Ferraz-Shawmut Old Catalog # 225-007-967 225-007-968 225-007-969 225-007-970 225-007-971 225-007-972 225-007-973 225-007-974 225-007-975 225-007-976 225-007-977 225-007-978 225-007-979 225-007-980 225-007-981 Data Sheet: 9004 For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa 77 Medium Voltage Fuses Specifications Description: E-rated medium voltage, current-limiting fuses for transformer and feeder protection. Construction: Filament wound, glass epoxy fuse tube, with silica filler, and silver-plated copper terminals and endcaps containing a silver element in a double concentric helical configuration. Ratings: Volts: — 15.5kV Amps: — 10-300A IR: — 63kA Sym. (10-200A) — 50kA Sym. (250-300A) Agency Information: Meets E requirements per ANSI C37.46, Meets General Purpose requirements per ANSI C37.40. Medium Voltage Fuses E-rated Fuses for Potential & Small Power Transformers Features and Benefits • Sized for retrofitting in existing hardware • Space saving size JCD, JCW, JCQ, JCI & JCT Specifications Description: Indicating and nonindicating E-rated medium voltage, current-limiting fuses for potential and small power transformers. Dimensions: See Catalog Numbers table. Construction: Plated ferrules. Ratings: Volts: — 2.4-15.5kV (See Catalog Numbers table for details) Amps: — 1⁄2-10A IR: — 25-80kA Sym — 40-130kA ASYM — See Catalog Numbers table for details Typical Applications • Primary protection of medium voltage potential transformers • Primary protection of small medium voltage service transformers • Primary protection of small medium voltage control transformers Catalog Numbers Catalog Numbers Amp Rating Maximum Design Voltage IR RMS Sym. Dimensions - in (mm) Length Diameter 2400V; E-Rated Fuse; Non-Indicating JCD-1⁄2E JCD-1E JCD-2E JCD-5E 0.5 1 2 5 2.75kV 2.75kV 2.75kV 2.75kV 63kA 40kA 40kA 25kA 4.50 4.50 4.50 4.50 (114) (114) (114) (114) 0.80 0.80 0.80 0.80 (20.32) (20.32) (20.32) (20.32) 2450/5500V; E-Rated Fuse; Non-Indicating JCW-1⁄2E JCW-1E JCW-2E JCW-3E JCW-5E 0.5 1 2 3 5 2.75/5.5kV 2.75/5.5kV 2.75/5.5kV 2.75/5.5kV 2.75/5.5kV 40kA 40kA 40kA 40kA 40kA 7.312 7.312 7.312 7.312 7.312 (185.72) (185.72) (185.72) (185.72) (185.72) 1.563 1.563 1.563 1.563 1.563 (39.70) (39.70) (39.70) (39.70) (39.70) 80kA 80kA 80kA 80kA 80kA 80kA 9.5 9.5 9.5 9.5 9.5 9.5 (241.3) (241.3) (241.3) (241.3) (241.3) (241.3) 1.6 1.6 1.6 1.6 1.6 1.6 (40.64) (40.64) (40.64) (40.64) (40.64) (40.64) 80kA 80kA 50kA 50kA 9.5 (241.3) 12.88 (327.15) 12.88 (327.15) 12.88 (327.15) 1.6 1.6 1.6 1.6 (40.64) (40.64) (40.64) (40.64) 80kA 80kA 80kA 80kA 80kA 80kA 12.93 (328.42) 12.93 (328.42) 12.93 (328.42) 17.5 (444.5) 17.5 (444.5) 17.5 (444.5) 1.6 1.6 1.6 1.6 1.6 1.6 (40.64) (40.64) (40.64) (40.64) (40.64) (40.64) 5500V; E-Rated Fuse; Indicating JCQ-1⁄2E JCQ-1E JCQ-11⁄2E JCQ-3E JCQ-5E JCQ-10E 0.5 1 1.5 3 5 10 5.5kV 5.5kV 5.5kV 5.5kV 5.5kV 5.5kV 8300V; E-Rated Fuse; Indicating JCI-1⁄2E JCI-3E JCI-5E JCI-10E 0.5 3 5 10 8.3kA 8.3kA 8.3kA 8.3kA 15,500V; E-Rated Fuse; Indicating JCT-1⁄2E JCT-1E JCT-1-1⁄2E JCT-3E JCT-5E JCT-10E 0.5 1 1.5 3 5 10 15.5kV 15.5kV 15.5kV 15.5kV 15.5kV 15.5kV Fuse clip for 1.56 and 1.6 inch diameter fuses - 1A0835. Fuse clip for 0.81 inch diameter fuses - 1A1837. Data Sheet: 6002 78 For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa Medium Voltage Fuses E-rated Fuses for Potential & Small Power Transformers Ratings: Volts: — 5.5-38kV Amps: — 0.5-15A IR: — 40kA-80kA Sym. — See Catalog Numbers table for details AB, AD, AM and CAV Typical Applications • Primary protection of medium voltage potential transformers • Primary protection of small medium voltage service transformers • Primary protection of small medium voltage control transformers Catalog Numbers Catalog Numbers Amp Rating 5.5ABWNA0.5E 5.5ABWNA1E 5.5ABWNA2E 5.5ABWNA3E 5.5ABWNA5E 5.5AMWNA0.5E 5.5AMWNA1.0E 5.5AMWNA2.0E 5.5AMWNA3.0E 5.5AMWNA4.0E 5.5AMWNA5.0E 5.5CAVH0.5E 5.5CAVH1E 5.5CAVH2E 5.5CAV15E 7.2AMWNA0.5E 7.2AMWNA1.0E 7.2AMWNA2.0E 7.2AMWNA3.0E 7.2AMWNA4.0E 7.2AMWNA5.0E 15.5CAV(H)0.5E* 15.5CAV(H)1E* 15.5CAV(H)2E* 15.5CAV3E 15.5CAV5E 15.5CAV7E 38ADMNA7E 38ADMNA10E 38CAV(H)0.5E* 38CAV(H)1E* 38CAV(H)2E* 38CAV4E 0.5 1 2 3 5 0.5 1.5 2.5 3.5 4.5 5.5 0.5 1 2 15 0.5 1 2 3 4 5 0.5 1 2 3 5 7 7 10 0.5 1 2 4 Maximum Design Voltage 5.5kV 5.5kV 5.5kV 5.5kV 5.5kV 5.5kV 5.5kV 5.5kV 5.5kV 5.5kV 5.5kV 5.5kV 5.5kV 5.5kV 5.5kV 7.2kV 7.2kV 7.2kV 7.2kV 7.2kV 7.2kV 15.5kV 15.5kV 15.5kV 15.5kV 15.5kV 15.5kV 38kV 38kV 38KV 38KV 38KV 38KV IR RMS Sym. 50kA 50kA 50kA 50kA 50kA 50kA 50kA 50kA 50kA 50kA 50kA 63kA 63kA 63kA 63kA 50kA 50kA 50kA 50kA 50kA 50kA 80kA 80kA 80kA 80kA 80kA 80kA 40kA 40kA 40kA 40kA 40kA 40kA Dimensions - in (mm) Length Diameter 5.6 (142.2) 5.6 (142.2) 5.6 (142.2) 5.6 (142.2) 5.6 (142.2) 5.6 (142.2) 5.6 (142.2) 5.6 (142.2) 5.6 (142.2) 5.6 (142.2) 5.6 (142.2) 7.375 (187.3) 7.375 (187.3) 7.375 (187.3) 7.375 (187.3) 5.6 (142.2) 5.6 (142.2) 5.6 (142.2) 5.6 (142.2) 5.6 (142.2) 5.6 (142.2) 12.87 (326.9) 12.87 (326.9) 12.87 (326.9) 12.87 (326.9) 12.87 (326.9) 12.87 (326.9) 17.4 (442) 17.4 (442) 17.32 (439.9) 17.32 (439.9) 17.32 (439.9) 17.32 (439.9) 1 (25.4) 1 (25.4) 1 (25.4) 1 (25.4) 1 (25.4) 0.81 (20.6) 0.81 (20.6) 0.81 (20.6) 0.81 (20.6) 0.81 (20.6) 0.81 (20.6) 1.63 (41.4) 1.63 (41.4) 1.63 (41.4) 1.63 (41.4) 0.81 (20.6) 0.81 (20.6) 0.81 (20.6) 0.81 (20.6) 0.81 (20.6) 0.81 (20.6) 1.63 (41.4) 1.63 (41.4) 1.63 (41.4) 1.63 (41.4) 1.63 (41.4) 1.63 (41.4) 2 (50.8) 2 (50.8) 1.63 (41.4) 1.63 (41.4) 1.63 (41.4) 1.63 (41.4) *Type CAVH fuses are fitted with a striker pin for indication. Omit ‘H’ for non-indicating fuses. Fuseclip for 0.8 inch diameter fuses - 1A1837. Fuseclip for 1 inch diameter fuses - A3354705. Fuseclip for 1.6 inch diameter fuses - 1A0835. For detailed information, visit the Electrical IEC section at www.cooperbussmann.com 79 Medium Voltage Fuses Specifications Description: Indicating and non-indicating E-rated medium voltage, current-limiting fuses for potential and small power transformers. Dimensions: See Catalog Numbers table. Features and Benefits • Sized for retrofitting in existing hardware • Space saving size Medium Voltage Fuses R-rated Fuses for Motor Circuit Protection JCG, JCH, JCK, JCK-A, JCK-B, JCL, JCL-A, JCL-B, JCR-A, & JCR-B Specifications Description: Indoor/enclosure R-rated medium voltage, current-limiting fuses for motor circuit protection. Dimensions: See Dimensions illustrations. Ratings: Volts: — 2.4-7.2kV (See Catalog Numbers table for details) Amps: — 25-450A (See Catalog Numbers table for details) IR: — 50kA Sym — 80kA ASYM — See Catalog Numbers table for details Agency Information: UL Recognized: 2540Vac — JCK, JCK-A, 5080Vac — JCL, JCL-A, UL Recognized (Guide #MSSS2, File #E96676). Features and Benefits • Physically dimensioned for retrofitting in existing hardware • Open fuse indicator for ease in troubleshooting • Available with optional Cutler Hammer® hookeye for ease of insertion and removal • Classified as back-up fuses for current-limited protection of medium voltage motor controllers Typical Applications • Medium Voltage Motor Controllers Dimensions - mm (in) Figure 1 INDICATOR Showing Fuse is Open 0.38" (9.5mm) C A INDICATOR Showing Fuse is Open B Figure 2 Figure 3 Data Sheet 6001 80 For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa Medium Voltage Fuses R-rated Fuses for Motor Circuit Protection Catalog Numbers: R-Rated; Indoor/Enclosure Catalog Numbers Amp Ratings Maximum Design Voltage A Dimensions - in (mm)* B Construction C Max Int. Cap. Amps (Asym.) Amps (Sym.) Min Int. Cap. Amps (Sym.) 2400V (See Figure 1) JCK-2R JCK-3R JCK-4R JCK-5R JCK-6R JCK-9R JCK-12R JCK-18R JCK-24R 70 100 130 150 170 200 230 390 450 2540 2540 2540 2540 2540 2540 2540 2540 2540 11.24 11.24 11.24 11.24 11.24 11.24 11.24 11.24 11.24 (285.5) (285.5) (285.5) (285.5) (285.5) (285.5) (285.5) (285.5) (285.5) 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 165 220 320 410 480 720 970 1,430 1,880 Single Single Single Single Single Single Single Double Double 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 165 220 320 410 480 720 970 1,430 1,880 Single Single Single Single Single Single Single Single Double Double 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 90 170 245 340 430 500 1,000 1,250 1,700 1,210 Medium Voltage Fuses Single Single Single Single Single Single Single Double Double 2400V — With Westinghouse Ampguard Hookeye (See Figure 1) JCK-A-2R JCK-A-3R JCK-A-4R JCK-A-5R JCK-A-6R JCK-A-9R JCK-A-12R JCK-A-18R JCK-A-24R 70 100 130 150 170 200 230 390 450 2540 2540 2540 2540 2540 2540 2540 2540 2540 11.24 11.24 11.24 11.24 11.24 11.24 11.24 11.24 11.24 (285.5) (285.5) (285.5) (285.5) (285.5) (285.5) (285.5) (285.5) (285.5) 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) 2400V — Bolt-On (See Figures 2 & 3) JCK-B-30 JCK-B-2R JCK-B-3R JCK-B-4R JCK-B-5R JCK-B-6R JCK-B-9R JCK-B-12R JCK-B-18R JCK-B-24R 25 70 100 130 150 170 200 230 390 450 2540 2540 2540 2540 2540 2540 2540 2540 2540 2540 14.18 14.18 14.18 14.18 14.18 14.18 14.18 14.18 14.18 14.18 (360.2) (360.2) (360.2) (360.2) (360.2) (360.2) (360.2) (360.2) (360.2) (360.2) 12.81 12.81 12.81 12.81 12.81 12.81 12.81 12.81 12.81 12.81 (325.4) (325.4) (325.4) (325.4) (325.4) (325.4) (325.4) (325.4) (325.4) (325.4) 3.56 (90.4) 3.56 (90.4) 2400V — Hermetically Sealed, For Use with Ampguard Motor Starters (See Figure 1) JCH-30 JCH-2R JCH-3R JCH-4R JCH-5R JCH-6R JCH-9R JCH-12R JCH-18R JCH-24R 25 70 100 130 150 170 200 230 390 450 2540 2540 2540 2540 2540 2540 2540 2540 2540 2540 10.81 10.81 10.81 10.81 10.81 10.81 10.81 10.81 10.81 10.81 (275.6) (275.6) (275.6) (275.6) (275.6) (275.6) (275.6) (275.6) (275.6) (275.6) 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) Single Single Single Single Single Single Single Single Double Double 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 90 170 245 340 430 500 1,000 1,250 1,700 2,100 15.76 15.76 15.76 15.76 15.76 15.76 15.76 15.76 15.76 (400.3) (400.3) (400.3) (400.3) (400.3) (400.3) (400.3) (400.3) (400.3) 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) Single Single Single Single Single Single Single Double Double 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 165 220 320 410 480 720 970 1,430 1,880 4800V (See Figure 1) JCL-2R JCL-3R JCL-4R JCL-5R JCL-6R JCL-9R JCL-12R JCL-18R JCL-24R 70 100 130 150 170 200 230 390 450 5080 5080 5080 5080 5080 5080 5080 5080 5080 • See previous page Figure 2 for single construction and Figure 3 for double construction information. Recommended fuseclips: see page 91 - 1A0065, A3354730, 9078A67G04. Data Sheet: 6001 For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa 81 Medium Voltage Fuses R-rated Fuses for Motor Circuit Protection Catalog Numbers: R-Rated; Indoor/Enclosure Catalog Numbers Amp Ratings Maximum Design Voltage A Dimensions - in (mm) B Max Int. Cap. Amps (Asym. Amps (Sym.) Single Single Single Single Single Single Single Double Double 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 165 220 320 410 480 720 970 1,430 1,880 Single Single Single Single Single Single Single Single Double Double 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 95 180 270 350 450 540 700 1,000 1,450 2,000 Construction C Min Int. Cap. Amps (Sym.) 4800V — With Westinghouse Ampguard Hookeye (See Figure 1) JCL-A-2R JCL-A-3R JCL-A-4R JCL-A-5R JCL-A-6R JCL-A-9R JCL-A-12R JCL-A-18R JCL-A-24R 70 100 130 150 170 200 230 390 450 5080 5080 5080 5080 5080 5080 5080 5080 5080 15.76 15.76 15.76 15.76 15.76 15.76 15.76 15.76 15.76 (400.3) (400.3) (400.3) (400.3) (400.3) (400.3) (400.3) (400.3) (400.3) 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) 4800V — Bolt-On (See Figures 2 & 3) JCL-B-30 JCL-B-2R JCL-B-3R JCL-B-4R JCL-B-5R JCL-B-6R JCL-B-9R JCL-B-12R JCL-B-18R JCL-B-24R 30 70 100 130 150 170 200 230 390 450 5080 5080 5080 5080 5080 5080 5080 5080 5080 5080 19.25 19.25 19.25 19.25 19.25 19.25 19.25 19.25 19.25 19.25 (488.9) (488.9) (488.9) (488.9) (488.9) (488.9) (488.9) (488.9) (488.9) (488.9) 17.88 17.88 17.88 17.88 17.88 17.88 17.88 17.88 17.88 17.88 (454.1) (454.1) (454.1) (454.1) (454.1) (454.1) (454.1) (454.1) (454.1) (454.1) 3.31 (84.1) 3.31 (84.1) 4800V — Hermetically Sealed, For Use with Ampguard Motor Starters (See Figure 1) JCG-30 JCG-2R JCG-3R JCG-4R JCG-5R JCG-6R JCG-9R JCG-12R JCG-A-18R JCG-A-24R 30 70 100 130 150 170 200 230 390 450 5080 5080 5080 5080 5080 5080 5080 5080 5080 5080 15.91 15.91 15.91 15.91 15.91 15.91 15.91 15.91 15.91 15.91 (404.1) (404.1) (404.1) (404.1) (404.1) (404.1) (404.1) (404.1) (404.1) (404.1) 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) Single Single Single Single Single Single Single Single Double Double 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 95 180 270 350 450 540 700 1,000 1,450 2,000 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) Single Single Single Single Single Single Single Double Double 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 160 250 325 390 500 750 1,000 1,450 2,500 Single Single Single Single Single Single Single Double Double 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 160 250 325 390 500 750 1,000 1,450 2,500 7200V — With Ampguard Hookeye (See Figure 1) JCR-A-2R JCR-A-3R JCR-A-4R JCR-A-5R JCR-A-6R JCR-A-9R JCR-A-12R JCR-A-18R JCR-A-24R 70 100 130 150 170 200 230 390 450 8300 8300 8300 8300 8300 7200 7200 7200 7200 15.85 15.85 15.85 15.85 15.85 15.85 15.85 15.85 15.85 (402.6) (402.6) (402.6) (402.6) (402.6) (402.6) (402.6) (402.6) (402.6) 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) 7200V — Bolt-On (See Figures 2 & 3) JCR-B-2R JCR-B-3R JCR-B-4R JCR-B-5R JCR-B-6R JCR-B-9R JCR-B-12R JCR-B-18R JCR-B-24R 70 100 130 150 170 200 230 390 450 8300 8300 8300 8300 8300 7200 7200 7200 7200 19.25 19.25 19.25 19.25 19.25 19.25 19.25 19.25 19.25 (488.9) (488.9) (488.9) (488.9) (488.9) (488.9) (488.9) (488.9) (488.9) 17.88 17.88 17.88 17.88 17.88 17.88 17.88 17.88 17.88 (454.1) (454.1) (454.1) (454.1) (454.1) (454.1) (454.1) (454.1) (454.1) 3.31 (84.1) 3.31 (84.1) Recommended fuseclips: see page 91 - 1A0065, A3354730, 9078A67G04. Data Sheet: 6001 82 For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa Medium Voltage Fuses British Standard Dimensioned IEC Fuses for Motor Circuit Protection The Cooper Bussmann range of motor fuses are designed to meet the specific requirements necessary for motor protection. During the starting cycle of direct on-line motors, the fuse elements will reach a considerably higher temperature than during normal operation; (this is due to the high amount of current the motor will draw as it starts, typically, six times its normal load current value). This results in expansion and contraction of the fuse elements and could cause premature operation of the fuse. Medium Voltage Fuses Cooper Bussmann motor fuses encompass an advanced design to minimize this effect. This therefore, negates the need to over specify the fuse rating due to high values of motor starting current. Cooper Bussmann motor fuses operate extremely quickly under heavy fault currents, resulting from the time / current characteristic. Low power dissipation ensures low temperature rise, important in multi-tier starters for example. Switching (arc), voltages are lower than permitted values, therefore, 5.5kV fuses are also suitable for 4.8kV and 2.4kV circuits. Table of Ratings Basic Cat. Number 3.6WJON6 3.6WDOH6 3.6WFOH6 3.6WDLSJ 3.6WFLSJ 3.6WDFHO 3.6WFFHO 3.6WKFHO 5.5VFNHA 5.5VKNHA 7.2WFNHO 7.2WKNHO 7.2WFMSJ 7.2WKMSJ Volts 3.6kV 3.6kV 3.6kV 3.6kV 3.6kV 3.6kV 3.6kV 3.6kV 5.5kV 5.5kV 7.2kV 7.2kV 7.2kV 7.2kV Breaking Capacity 50kA 50kA 50kA 50kA 50kA 50kA 50kA 50kA 60kA 60kA 40kA 40kA 63kA 63kA Amp Ratings 5, 6.3, 10, 16, 20, 25, 31.5, 40, 50 50, 63, 80, 100, 125 160, 200 50, 63, 80, 100, 125 160, 200 50, 63, 80, 100, 125 160, 200 250, 315, 355, 400 2R-6R 9R-24R 25, 31.5, 40, 50, 63, 80, 100, 125, 160 200, 224, 250, 315 25, 31.5, 40, 50, 63, 80, 125, 160 200, 224, 250, 315, 355 Catalog Number Build-A-Code kV Basic Catalog Number ___ _____ Dimensions - in (mm) Length Diameter 7.56 (192) 1.4 (35.6) 7.56 (192) 2 (50.8) 7.56 (192) 3 (76.2) 11.5 (292.1) 2 (50.8) 11.5 (292.1) 3 (76.2) 10 (254) 2 (51) 10 (254) 3 (76.2) 10 (254) 3 (76.2) 15.86 (402.8) 3 (76.2) 15.86 (402.8) 3 (76.2) 15.86 (402.8) 3 (76.2) 15.86 (402.8) 3 (76.2) 17.40 (442) 3 (76.2) 17.40 (442) 3 (76.2) Dimensional Standard BS 2692 (TA1) Interchangeable with GEC type K2 PA BS 2692 (TA1) or DIN 43625 BS 2692 (TA1) or DIN 43625 DIN 43625 DIN 43625 BS 2692 (TA2) BS 2692 (TA2) BS 2692 (TA2) ANSI R-rated ANSI R-rated BS 2692 (TA4) BS 2692 (TA4) DIN 43625 DIN 43625 Amps ___ For detailed information, visit the Electrical IEC section at www.cooperbussmann.com 83 Medium Voltage Fuses DIN Dimensioned IEC Fuses for Transformer Protection DIN Dimension Fuses To Spec. DIN 43625 Specifications Catalog Symbol: See Basic Catalog Numbers table. Description: DIN dimension fuses to Specification DIN 43625 covering current-limiting fuses with performance in compliance with IEC 60282-1. These are in accordance with the R10 and, in some cases, the R20 series of preferred numbers. Dimensions: See Catalog Numbers table. Catalog Number Build-A-Code kV Basic Catalog Number ___ _____ Amps ___ Volts: — See voltage associated with the Basic Catalog Numbers in the table. Amps: — See amp rating associated with the Basic Catalog Numbers in the table. IR: — See IR associated with the Basic Catalog Numbers in the table. Agency Information: Comply with DIN dimensional standard DIN 43625, VDE 0670 part 4, VDE 0670 part 40Z and with IEC 60282-1 (2005). Features and Benefits • DIN dimensioned for retrofitting in existing hardware • Open fuse indicator for ease in troubleshooting • Designed for use in IEC equipment Typical Applications • Medium Voltage IEC designed equipment Catalog Numbers kV 3.6 7.2 12 17.5 24 36 Catalog Numbers 3.6ADOSJ(amp) 3.6WDOSJ(amp) 3.6WFOSJ(amp) 3.6ADLSJ(amp) 3.6WDLSJ(amp) 3.6WFLSJ(amp) 3.6WKLSJ(amp) 7.2TDLSJ(amp) 7.2TFLSJ(amp) 7.2WKMSJ(amp) 12TDLEJ(amp) 12THLEJ(amp) 12TKLEJ(amp) 12TXLEJ(amp)* 17.5TDLSJ(amp)* 17.5TFLSJ(amp)* 17.5TDMEJ(amp) 17.5THMEJ(amp) 17.5TKMEJ(amp) 24TDMEJ(amp) 24THMEJ(amp) 24TFMEJ(amp) 24TXMEJ(amp)* 36TDQSJ(amp) 36TFQSJ(amp) 36TXQEJ(amp)* Amp Ratings 6.3, 10, 16, 20, 25, 31.5, 40 50, 63, 80, 100, 125 160, 200 25, 40 50, 63, 80, 100, 125 160, 200 250, 315, 400 6.3, 10, 16, 20, 25, 31.5, 40, 50, 63 80, 100, 125, 160 200, 225, 250, 315, 355 6.3, 10, 16, 20, 25, 31.5, 40, 50, 63 80, 100 125 160, 200 6.3, 10, 16, 20, 25, 31.5, 40 50 6.3, 10, 16, 20, 25, 31.5, 40, 50, 63 80, 100 125 6.3, 10, 16, 20, 25, 31.5, 40, 50 63 80, 100*1 1252, 160 3.153, 6.3, 10, 16, 20, 25 31.5, 40, 50 63 Dimensions - in (mm) Diameter x Length 2.00 x 7.56 (51 x 192) 2.00 x 7.56 (51 x 192) 3.00 x 7.56 (76 x 192 2.00 x 11.50 (51 x 292) 2.00 x 11.50 (51 x 292) 3.00 x 11.50 (76 X 292) 3.00 x 11.50 (76 X 292) 2.00 x 11.50 (51 x 292) 3.00 x 11.50 (76 x 292) 3.00 x 17.41 (76 x 442) 2.00 x 11.50 (51 x 292) 2.52 x 11.50 (64 x 292) 3.00 x 11.50 (76 x 292) 3.50 x 11.50 (88 x 292) 2.00 x 11.50 (51 x 292) 3.00 x 11.50 (76 x 292) 2.00 x 17.41 (51 x 442) 2.52 x 17.41 (64 x 442) 3.00 x 17.41 (76 x 442) 2.00 x 17.41 (51 x 442) 2.52 x 17.41 (64 x 442) 3.00 x 17.41 (76 x 442) 3.46 x 17.41 (88 x 442) 2.00 x 21.16 (51 x 537) 3.00 x 21.16 (76 x 537) 3.46 x 21.16 (88 x 537) IR RMS Sym 40kA 50kA 40kA 63kA 35.5kA 50kA 50kA 31.5kA 35.5kA 20kA Recommended fuseclips for DIN style fuses – 270303, A3354745 see page 91. *Not compliant with VDE 0670, part 402. 1 -IR RMS Sym is 63kA 2 -IR RMS Sym is 40kA 3 -IR RMS Sym is 20kA Dimensions - In (mm) Diameter Striker In Operated Position 0.59" 15.0mm 1.77" 45.0mm Length For Diameter and Length Dimensions See Table Above 84 1.02" 1.34" 34.0mm 26.0mm For detailed information, visit the Electrical IEC section at www.cooperbussmann.com Medium Voltage Fuses Potential Transformer Fuses Ratings: E-Rated: — See single asterisk in Basic Catalog Numbers table Volts: — 3.6-38kV (See Basic Catalog Numbers table) Amps: — 2-15A (See Basic Catalog Numbers table) IR: — 25-80kA (See Basic Catalog Numbers table) Agency Information: BS2692-1 and IEC60282-1 AB, AM and CAV Features and Benefits • Physically dimensioned for retrofitting in existing hardware. • Space saving size. Medium Voltage Fuses Specifications Description: British Standard VT fuses with low current ratings for use in voltage transformers or operating transformers to provide isolation of the associated system in the event of faults in the transformer circuit. Dimensions: See Basic Catalog Numbers table. Typical Applications • Medium Voltage Potential Transformers • Small Medium Voltage Service Transformers Basic Catalog Numbers for “AB” & “AM” Series Basic Cat. Numbers 3.6ABWNA 3.6ABCNA 5.5ABWNA* 5.5AMWNA* 7.2ABWNA 7.2ABCNA 12ABCNA 15.5ABFNA 17.5ABGNA 24ABGNA 36ABGNA** Volts 3.6kV 3.6kV 5.5kV 5.5kV 7.2kV 7.2kV 12.0kV 15.5kV 17.5kV 24.0kV 36.0kV Amp Ratings 3.15, 6.3 3.15, 6.3, 10 0.5, 1, 2, 3, 5 0.5, 1.0, 2.0, 3.0, 4.0, 5.0 3.15, 6.3 3.15, 6.3 3.15 3.15 3.15 3.15 3.15 Dimensions - in (mm) Length Diameter 5.6 (142.2) 1 (25.4) 7.69 (195.3) 1 (25.4) 5.6 (142.2) 1 (25.4) 5.6 (142.2) 0.81 (20.6) 5.6 (142.2) 1 (25.4) 7.69 (195.3) 1 (25.4) 7.69 (195.3) 1 (25.4) 10.00 (254) 1 (25.4) 14.13 (358.9) 1 (25.4) 14.13 (358.9) 1 (25.4) 14.13 (358.9) 1 (25.4) Type AB AB AB AM AB AB AB AB AB AB AB IR 50KA 50KA 50KA 50KA 45KA 45KA 45KA 32KA 35KA 25KA 31.5KA Recommended fuse clip for 1 diameter fuses – A3354705. Basic Catalog Numbers for “CAV” Series Basic Cat. Number 3.6CAV 5.5CAV* 5.5CAVH* 7.2CAV 12CAV 15.5CAV* 15.5CAVH* 17.5CAV 24CAV 36CAV 36CAVH 38CAV* 38CAVH* Volts 3.6kV 5.5kV 5.5kV 7.2kV 12kV 15.5kV 15.5kV 17.5kV 24kV 36kV 36kV 38kV 38kV Amp Ratings 2 15 0.5, 1, 2 2, 4, 6, 10 2 0.5, 1, 2, 3, 5, 7 0.5, 1, 2 2, 4, 6, 10 2, 3, 4 2, 4 2 4 0.5, 1, 2 Dimensions - in (mm) Length Diameter 8.66 (220) 1.63 (41.4) 7.375 (187.3) 1.63 (41.4) 7.375 (187.3) 1.63 (41.4) 8.66 (220) 1.63 (41.4) 8.66 (220) 1.63 (41.4) 12.87 (326.9) 1.63 (41.4) 12.87 (326.9) 1.63 (41.4) 8.66 (220) 1.63 (41.4) 13.39 (340.1) 1.63 (41.4) 17.32 (439.9) 1.63 (41.4) 17.32 (439.9) 1.63 (41.4) 17.32 (439.9) 1.63 (41.4) 17.32 (439.9) 1.63 (41.4) IR 50KA 63KA 63KA 63KA 40KA 80KA 80KA 40KA 40KA 40KA 40KA 40KA 40KA Type CAVH are fitted with a striker pin for indication. * E-Rated fuses **For clean indoor applications only. Catalog Number Build-A-Code kV Basic Catalog Number ___ _____ Amps ___ Recommended Fuse Clips: 1” dia. - A3354705, 1.63” dia. - 1A0835, .819 dia. - 1A1837 Contact Cooper Bussmann for complete specifications on potential transformer fuses For detailed information, visit the Electrical IEC section at www.cooperbussmann.com 85 Medium Voltage Fuses British Standard IEC Fuses for Use in Oil Filled Distribution Switchgear OEFMA Code Number Reference Specifications Description: BS 2692-1 medium voltage fuses for use on the primary circuit of three-phase 50Hz transformers in oil field switchgear. Fitted with powerful pyrotechnic striker pin. Ratings: Volts: — 3.6-24kV Amps: — 6.3-200A IR: — 25-50kA (See Catalog Number table below) Agency Information: Fuses comply with IEC 60282-1, BS2692-1 and ESI Standard 12-8. 7.2 and 12kV fuses tested at highest system voltage and approved by the UK Electricity Association approvals panel. O _ _ M A Type O = Oil tight Diameter E = 63.5mm H = 63.5mm L = 63.5mm Length F = 254mm G = 359mm Striker M = As specified in BS 2692 table 11 Tags A = None (plain caps) Dimensions: Current-limiting fuse for use in oil switchgear Featues and Benefits • Physically sized for replacement of British Standard fuse links Fuse types: OEF, OEG, OHF, OHG, OLG 254mm (10 in) or 359mm (14 in) 68 Max 63.5 44 Typical Applications • Medium Voltage BS Designed Equipment 10 Min — 16 Max striker travel after operation, if fitted. Catalog Numbers Transformer kVA 200 250 300/315 400 500 630 750/800 1000 1250 1600 Catalog Numbers/Transformer Primar y Voltage 3.3kV 3.6OEFMA63 3.6OEFMA80 3.6OEFMA100 3.6OEFMA125 3.6OEFMA160 3.6OEFMA200 3.6OLGMA250 3.6OLGMA250* — — 6.6kV 12OEFMA31.5 12OEFMA40 12OEFMA50 12OEFMA63 12OHFMA71 7.2OEFMA100 7.2OHGMA125 7.2OHGMA140 7.2OHGMA160* — 11kV/ESI 12-8 Ref. 12OEFMA25/01 12OEFMA25/— 12OEFMA31.5/02 12OEFMA40/— 12OEFMA50/03 12OEFMA63/— 12OHFMA80/04 12OHGMA90**/05 12OHGMA100/— 12OLGMA125*/— 13.8kV 15.5OEFMA16 15.5OEFMA20 15.5OEFMA25 15.5OEFMA31.5 15.5OEFMA40 15.5OEFMA50 15.5OEFMA63 15.5OHGMA71 15.5OHGMA90 15.5OLGMA100* This Catalog Number selection table is based upon the following criteria: 1. Withstand against magnetizing inrush current taken as 12 times full-load current for 0.1 second. 2. Withstand against 150% permissible overload current. Recommendations marked with asterisks have the following significance:*Limited to permissible overloads of 130%. **Permits use of a 12kV OHFMA 80A fuse with a 100kVA transformer where permissible overload does not exceed 130%. 3. For 6.6kV systems, 12kV fuses are recommended where possible in the interests of standardization. 4. Wherever possible, 10 inch long FO1 fuses are offered rather than equivalent 14 inch FO2 types. 5. The above recommendations are not generally applicable to transformers feeding motor circuits with starting currents in excess of the transformer full load current. In this event, please consult Cooper Bussmann. Catalog Numbers Basic Cat. Number 3.6OEFMA 3.6OEGMA 3.6OLGMA 7.2OEFMA 7.2OHGMA 12OEFMA 12OHFMA 12OHGMA 12OLGMA 15.5OEFMA 15.5OHGMA 15.5OLGMA 17.5OHGMA 24OEGMA Voltage 3.6kV 3.6kV 3.6kV 7.2kV 7.2kV 12.0kV 12.0kV 12.0kV 12.0kV 15.5kV 15.5kV 15.5kV 17.5kV 24.0kV Dimensional Ref. BS 2692 FO1 FO2 FO2 FO1 FO2 FO1 FO1 FO2 FO2 FO1 FO2 FO2 FO2 FO2 Amp Ratings 6.3, 10, 16, 20, 25, 100, 125, 160, 200 250 80, 100, 112 125, 140, 160 6.3, 10, 16, 20, 25, 71, 80 6.3, 10, 16, 20, 25, 125 6.3, 10, 16, 20, 25, 71, 80, 90 100 6.3, 10, 16, 20, 25, 6.3, 10, 16, 20, 25, Breaking Capacity (kA) 31.5, 40, 50, 63, 80, 100, 125, 160, 200 50 50 50 45 45 31.5, 40, 50, 63 40 40 31.5, 40, 50, 63, 71, 80, 90, 100 40 40 31.5, 40, 50, 63 40 40 40 31.5, 40, 50, 63, 80 35 31.5, 40, 50 25 Catalog Number Build-A-Code kV Basic Amps Catalog Number ___ _____ Contact Cooper Bussmann for complete specifications on medium voltage fuses. 86 For detailed information, visit the Electrical IEC section at www.cooperbussmann.com ___ Medium Voltage Fuses Fast-acting Fuses HVA, HVB, HVJ, HVL, HVR, HVT, HVU, HVW & HVX Test Specifications Basic Catalog Numbers HVA, HVB, HVJ, HVL HVR, HVT, HVU, HVW, HVX Load / Opening Time 110% / 4 Hours (min) 135% / 1 Hour (max) 100% / 4 Hours (min) 150% / 1 Hour (max) Features and Benefits • Physical size varies with electrical rating of fuse to prevent over-fusing. • Space saving size. Typical Applications • Medium Voltage Instrument Protection • Medium Voltage Circuit Protection Medium Voltage Fuses Specifications Description: Medium voltage, non-time delay, fast-acting fuses. Dimensions: See Basic Catalog Numbers table. Ratings: Volts: — 1-10kV (See Basic Catalog Numbers table) Amps: — 1⁄16-10A (See Basic Catalog Numbers table) Fuse blocks: 4528, 4529, 4530 & 2960 Voltage Rating: 1000 to 10,000V Basic Catalog Numbers HVA, HVR HVB, HVT HVJ, HVU HVL, HVX Fuse Block Catalog Number 4528 4529 4530 2960 Fuse Clip Catalog Number 5960 5960 4180 4180 Use #8 screws on blocks 4528 and 4529. Use #10 screws on blocks 4530 and 2960. Basic Catalog Number HVA kV 1 HVB HVJ HVL HVR HVW HVT HVU HVX 2.5 5 10 1 1.2 2.5 5 10 Amp Ratings 1 ⁄16, 1⁄10, 1⁄8, 2⁄10, 1⁄4, 3⁄10, 3⁄8, 1⁄2, 3 ⁄4, 1, 1 1⁄2, 2, 3, 4, 6, 10 1 ⁄2, 3⁄4, 1, 1 1⁄2, 2, 3 1 ⁄16, 1⁄8, 1⁄4, 1⁄2, 3⁄4, 1 1⁄2, 2, 4, 6, 10 1 ⁄16, 1⁄8, 1⁄4, 1⁄2, 1, 1 1⁄2, 2, 3 1 ⁄2, 1, 2, 3, 4, 5 1, 2, 3, 4, 5, 8 1 ⁄2, 1, 2, 3, 5 1 ⁄2, 1, 2, 3, 4, 5 1 ⁄2, 1, 3, 5 Maximum S.C. 20kW dc/30kVA ac Dimensions - in (mm) Diameter Length 0.41 (10.4) 3 (76.1) 20kW dc/30kVA ac 20kW dc/30kVA ac 20kW dc/30kVA ac kVA-500 ac only kVA-12,000 ac only kVA-1250 ac only kVA-2500 ac only kVA-5,000 ac only 0.41 0.81 0.81 0.41 0.41 0.41 0.81 0.41 (10.4) (20.6) (20.6) (10.4) (10.4) (10.4) (20.6) (10.4) 4.5 (114.2) 5 (126.9) 10 (254) 3 (76.2) 2.25 (57.1) 4.5 (114.2) 5 (126.9) 10.0 (253.8) Catalog Number Build-A-Code Basic Catalog Number Amps _____ ___ Data Sheet: 6003 For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa 87 Medium Voltage Fuses EEI-NEMA Type K & T and Type H & N FL: Type H and EEI-NEMA Type K & T Fuses Catalog Numbers EEI-NEMA and High-Surge Universal Tin Element Fuses for Cutouts — Rated to 27kV Non-Removable Button-Head For Standard Open or Enclosed Cutouts Specifications Description: Medium voltage fuses: Type H (high surge), EEI-NEMA Type K (fast-acting), EEI-NEMA Type T (slow-acting). Ratings: Amps: — 1-200A (See Catalog Numbers tables) Features and Benefits • Wide range of EEI-NEMA type fuse links for use in open fuse cutouts • Voltage ratings up to 27kV. • Can be coordinated with other overcurrent protective devices for sectionalizing to isolate feeder branches. Typical Applications • Medium Voltage Fused Cutouts High-Surge Type H Fuses High-surge, Type H fuses are manufactured in ratings of 1, 2, 3, 5, and 8A. They have been developed principally for primary fusing of small-sized transformers. Type H links are manufactured in the universal buttonhead design. Type N Fuses Type N fuses conform to previous NEMA standards and have been superseded by Type K and T links. Type N fuses are manufactured in the universal button design in ratings of 5 through 200A for use in NEMA standard dimensioned cutouts rated through 27kV. Catalog Numbers Type H EEI-NEMA (High Type K Surge) (Fast) FL11H1 FL11K1 FL11H2 FL11K2 FL11H3 FL11K3 FL11H5 FL11K5 — FL11K6 FL11H8 FL11K8 — FL11K10 — FL11K12 — FL11K15 — FL11K20 — FL11K25 — FL11K30 — FL11K40 — FL11K50 — FL11K65 — FL11K80 — FL11K100 — FL11K140 — FL11K200 EEI-NEMA Type T (Slow) FL11T1 FL11T2 FL11T3 FL11T5 FL11T6 FL11T8 FL11T10 FL11T12 FL11T15 FL11T20 FL11T25 FL11T30 FL11T40 FL11T50 FL11T65 FL11T80 FL11T100 FL11T140 FL11T200 Amps 1 2 3 5 6 8 10 12 15 20 25 30 40 50 65 80 100 140 200 Removable Button-Head For Cutouts Requiring Removable-Button Links Catalog Numbers EEI-NEMA EEI-NEMA Type K Type T (Fast) (Slow) FL3K1 FL3T1 FL3K2 FL3T2 FL3K3 FL3T3 FL3K5 FL3T5 FL3K6 FL3T6 FL3K8 FL3T8 FL3K10 FL3T10 FL3K12 FL3T12 FL3K15 FL3T15 FL3K20 FL3T20 FL3K25 FL3T25 FL3K30 FL3T30 FL3K40 FL3T40 FL3K50 FL3T50 FL3K65 FL3T65 FL3K80 FL3T80 FL3K100 FL3T100 FL3K140 FL3T140 FL3K200 FL3T200 Amps 1 2 3 5 6 8 10 12 15 20 25 30 40 50 65 80 100 140 200 Adapter-type removable-button links with ferrule adapter to convert to double-leader links are available in K and T types. Order by description. EEI-NEMA Type K Universal Silver-Element Fuses for Cutouts — Rated through 27kV Non-Removable Button-Head For Standard Open or Enclosed Cutouts Catalog Numbers EEI-NEMA Type K Amps FL12K8 8 FL12K10 10 FL12K12 12 FL12K15 15 FL12K25 25 FL12K50 50 88 For detailed information, visit the Electrical IEC section at www.cooperbussmann.com Medium Voltage Fuses BBU Boric Acid Fuses BBU is designed to operate. Its dielectric withstand level corresponds to insulation levels of power class equipment, thus the name “power fuse.” Maximum voltage ratings for BBU fuses are: 17kV, 27kV and 38kV. Amps:— The continuous amp rating of a BBU fuse should equal or exceed the maximum load current where the fuse is applied. They are designed to carry their rated continuous current without exceeding the temperature rise outlined in NEMA and ANSI standards. The BBU is available with continuous current ratings up to 200 amps The current ratings carry an “E” designation as defined by ANSI and NEMA. For example, the current responsive element rated 100E amps or below will melt in 300 seconds at an RMS current within the range of 200 to 240 percent of the continuous current ratings. Above 100E amps, melting takes place in 600 seconds at an RMS current within the range of 220 to 264 percent of the continuous current rating. IR:— BBU fuses have interrupting capabilities from 10kA to 14kA symmetrical. Features and Benefits • Voltage ratings of up to 38kV coupled with ratings to 200A provide a wide range of circuit protection. • Time-current characteristics allow for easier coordination with downstream devices. • Provides replacement of a variety of existing systems. Typical Applications • Power and Distribution Transformer Protection • Medium Voltage Feeder Circuit Protection • Distribution Transformers • Medium Voltage Metal-enclosed Switchgear • Medium Voltage Pad-mounted Switches For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa 89 Medium Voltage Fuses that elongate the arc through a boric acid chamber upon release by the fuse Specifications element to interrupt short circuits within Description: Boric one-half cycle and prevent the arc from acid fuses for power re-striking after a current zero. transformers, feeder BBU End Fittings: BBU end fittings circuits, distribution complete the electrical connection transformers, metalbetween the fuse unit and the fuse enclosed and padmounting. Positioned on the top and mounted switchgear bottom of the fuse, unit end fittings can Construction: be used over again if they remain Principle parts of the undamaged. They are completely replaceable BBU fuse interchangeable with other unit are shown in the manufacturers’ equivalent fuse units and cross section views. A mountings. glass epoxy tube Indoor Fittings: The indoor end fittings encloses the assembly are made of high-impact plastic and containing the silver high-conducting copper alloy. The blown fuse element, arcing fuse indicator, located on the top end rod, boric acid cylinder fitting, provides visual indication of a and spring. Using a faulted fuse unit. When engaged into the pure silver element and nichrome wire mounting, the spring-loaded plastic strain element makes the BBU less mounting handle actuates the latch susceptible to failure caused by vibration, mechanism and readily accepts a corona corrosion and fuse element hookstick to install or remove the aging. The components are housed in a assembled fuse unit. fiberglass reinforced resin tube with The bottom indoor fitting is threaded to plated copper contacts. BBU fuses can accept a muffler constructed of a plated directly replace competitive equivalent steel housing, containing copper mesh units. screening, that absorbs and contains the noise and exhaust materials during a fault condition, and prevents contamination of indoor components and mechanisms located within the switchgear. Containment also prevents accidental flash-over from phase-tophase or phase-to-ground by limiting airborne particles and gases. BBU Melt Curve Constructions: The BBU fuse is offered in three constructions to meet specific melt curves for an application. The construction is designated in the Catalog Number suffix as follows; • E (Standard) • K (Fast), and • SE (Slow) Element Vapor Rod withdraws, The curves for the SE construction are Melts elongating arc quenches less inverse and allow for more of a and vaporizing arc at first Boric Acid current zero time-delay at high currents. Consult Cooper Bussmann for application Operation: The BBU fuse uses boric assistance. acid to create the de-ionizing action to Ratings: interrupt the arc. At high temperatures, Volts: — The maximum voltage rating of boric acid decomposes to produce a the BBU fuse is the highest blast of water vapor and inert boric RMS voltage at which the fuse anhydride. Fault interruption is achieved by an arcing rod and a charged spring Medium Voltage Fuses BBU Boric Acid Fuses for Indoor Use Catalog Numbers* BBU17-3K BBU17-6K BBU17-8K BBU17-10K BBU17-12K BBU17-15K BBU17-20K BBU17-25K BBU17-30K BBU17-40K BBU17-50K BBU17-65K BBU17-80K BBU17-100K BBU17-140K BBU17-200K BBU17-5E BBU17-7E BBU17-10E BBU17-13E BBU17-15E BBU17-20E BBU17-25E BBU17-30E BBU17-40E BBU17-50E BBU17-65E BBU17-80E BBU17-100E BBU17-125E BBU17-150E BBU17-175E BBU17-200E BBU17-15SE BBU17-20SE BBU17-25SE BBU17-30SE BBU17-40SE BBU17-50SE BBU17-65SE BBU17-80SE BBU17-100SE BBU17-125SE BBU17-150SE BBU17-175SE BBU17-200SE Amps 3 6 8 10 12 15 20 25 30 40 50 65 80 100 140 200 5 7 10 13 15 20 25 30 40 50 65 80 100 125 150 175 200 15 20 25 30 40 50 65 80 100 125 150 175 200 Fuse Type K K E E SE SE Voltage kV 17 Max Int. kA Sym 14 17 14 17 14 17 17 14 14 17 14 Catalog Numbers* BBU27-3K BBU27-6K BBU27-8K BBU27-10K BBU27-12K BBU27-15K BBU27-20K BBU27-25K BBU27-30K BBU27-40K BBU27-50K BBU27-65K BBU27-80K BBU27-100K BBU27-140K BBU27-200K BBU27-5E BBU27-7E BBU27-10E BBU27-13E BBU27-15E BBU27-20E BBU27-25E BBU27-30E BBU27-40E BBU27-50E BBU27-65E BBU27-80E BBU27-100E BBU27-125E BBU27-150E BBU27-175E BBU27-200E BBU27-15SE BBU27-20SE BBU27-25SE BBU27-30SE BBU27-40SE BBU27-50SE BBU27-65SE BBU27-80SE BBU27-100SE BBU27-125SE BBU27-150SE BBU27-175SE BBU27-200SE Amps 3 6 8 10 12 15 20 25 30 40 50 65 80 100 140 200 5 7 10 13 15 20 25 30 40 50 65 80 100 125 150 175 200 15 20 25 30 40 50 65 80 100 125 150 175 200 * BBU Melt Curve Constructions: The BBU fuse is offered in three constructions to meet specific melt curves for an application. The construction is designated in the Catalog Number suffix: E (Standard), K (Fast) and SE (Slow). Contact Cooper Bussmann for application details. Fuse Type K Voltage kV 27 Max Int. kA Sym. 12.5 K 27 12.5 E 27 E SE SE 12.5 27 27 12.5 12.5 27 12.5 Catalog Numbers BBU38-3K BBU38-6K BBU38-8K BBU38-10K BBU38-12K BBU38-15K BBU38-20K BBU38-30K BBU38-40K BBU38-50K BBU38-65K BBU38-80K BBU38-100K BBU38-140K BBU38-200K BBU38-5E BBU38-7E BBU38-10E BBU38-13E BBU38-15E BBU38-20E BBU38-25E BBU38-30E BBU38-40E BBU38-50E BBU38-65E BBU38-80E BBU38-100E BBU38-125E BBU38-150E BBU38-175E BBU38-200E BBU38-15SE BBU38-20SE BBU38-25SE BBU38-30SE BBU38-40SE BBU38-50SE BBU38-65SE BBU38-80SE BBU38-100SE BBU38-125SE BBU38-150SE BBU38-175SE BBU38-200SE Amps 3 6 8 10 12 15 20 30 40 50 65 80 100 140 200 5 7 10 13 15 20 25 30 40 50 65 80 100 125 150 175 200 15 20 25 30 40 50 65 80 100 125 150 175 200 Fuse Type K K E Voltage kV 38 38 38 E SE SE 90 38 38 Note: Muffler can be ordered separately. Order Catalog number BBU-MFLR. For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa 10 38 End Fitting Detail Data Sheet: 1123 10 10 Application Notes Low currents, usually referred to as overload currents, must be considered as BBU fuses have a rather low thermal capacity. They cannot carry overloads of the same magnitude/duration as motors and transformers of equal continuous currents. For this reason, the BBU fuse must be sized with the full load current in mind so the fuse does not open on otherwise acceptable overloads and inrush conditions. Coordination should be considered to help determine what type of fuse is applied. The BBU fuse interrupts at a natural current zero in the current wave and allows a minimum of a half-cycle of fault current to flow before the fault is cleared. The time-current characteristics associated with a BBU fuse has a rather gradual slope making it easier to coordinate with downstream equipment. In addition, the BBU is ideal for higher voltage (up to 38kV) and high current applications (up to 200A). It is important to examine the minimum melting and total clearing time-current characteristics of this fuse. Max Int. kA Sym. 10 10 10 Medium Voltage Fuses Fuseclips for Medium & High Voltage Fuses Recommended Fuseclips for Medium Voltage Fuses Catalog Numbers A3354710 A3354730 A3354745 Fuse Diameter in (mm) 2 (50.8) 3 (76) 1.77 (45) A 3.749 4.139 3.50 B 1.979 2.449 2.50 Clip Dimensions (in) C D E 2.009 1.189 4.539 3.009 1.189 5.639 1.77 1.19 4.50 F 1.509 1.509 1.50 G 0.399 0.399 0.38 C A G Fuseclips are for single barrel applications only. Are not sold in pairs. F E D B 270303 DIN Fuseclip A Medium Voltage Fuses 1A0065 3” Diameter Clip 0.99" 25.0mm 4.06" 103mm A 0.43" 10.8mm 9078A67G04 3” Diameter Clip 2 Cup assemblies per package. Dimensions shown are for reference only. For detailed information, visit the Electrical IEC section at www.cooperbussmann.com 91 92