Tightening torque for cable glands according to standard

_LTSR_2014.QXD_LTSR_062006(b).QXD 11/14/13 12:20 PM Page 43
Technical Annex
CHART III
International Protection (IP) Ratings to IEC 262
The standard EN 50 262 was issued on 01.04.1998 and published in April 1999 in Germany as DIN-EN 50 262/VDE 0619. The well-known standards for cable glands, such as DIN
VDE 0619 (VDE 0619): 1987-09, DIN 46 319: 1989-12, DIN 46 320-1: 1985-09 and DIN 46 320-2...-4: 1973-01 etc, are only applicable until 31.12.1999. Approved technical drawings
using these standards are valid until 01.03.2001.
1.) Fields of application for standard EN 50 262: This European standard contains the requirements and tests for the construction and design of metric cable glands. This standard
covers the cable gland as a complete part, but not the parts of cable glands.
2.) The screw-in thread of cable glands must be constructed according to chart 1 of EN 60 423. The dimensions of the thread are M6x0,75; M8x1; M10x1; M12x1.5; M16x1.5;
M20x1.5; M25x1.5; M32x1.5; M40x1.5; M50x1.5; M63x1.5 and M75x1.5.
3.) The mounting holes must be dimensioned according to Chart A.
4.) Cable glands must be able to guarantee the retaining power for cables and conduits for the complete sealing section. Cable glands with traction relief for cables and conduits must
free the conduits from the load of tension and twist. The tests are carried out, with in each case the smallest and largest mentioned value of the seal resp. tension relief section of the
according loads and torque values in Chart B.
These tests are performed with test pins reproducing the outer diameters of the cables and conduits. The test pins consist of a metal rod with an elastomere sheath.
5.) Cable glands must be impact resistant. A test pin according to the smallest value of the sealing section is fastened to the test probe and then the test is carried out a lowest
temperature according to the energy in accordance with category of Chart C. All specifications, charts and values are excerpts from standard DIN 50 262. Obviously further tests
(electric properties, IP-Code etc.), which are necessary to classify and mark cable glands are described in this standard. It would although go beyond the scope of this catalogue.
Chart A: Mounting holes for cable glands
Thread size
12
Diameter of
M12
Mounting hole
+ 0.2/- 0.4 mm
12.5
16
M16
20
M20
25
M25
32
M32
40
M40
50
M50
63
M63
16.5
20.5
25.5
32.5
40.5
50.5
63.5
Chart B: Tensile load for retaining power and tension relief, torque for turning tests
Cable and Conduit diameter
Retaining Power
Tensile relief Type A
[mm]
[N]
[N]
thru 4
5
> 4 thru 8
10
30
> 8 thru 11
15
42
> 11 thru 16
20
55
>16 thru 23
25
70
> 23 thru 31
30
80
> 31 thru 43
45
90
> 43 thru 55
55
100
> 55
70
115
Chart C: Value for impact test
Categorie
Load [N]
Weight [Kg]
Energy [J]
Height [m]
CHART IV
1
2
0.2
0.2
0.1
2
2
0.2
0.5
0.25
3
2
0.2
1.0
0.5
4
2
0.2
2.0
1.0
Tensile relief Type B
[N]
75
120
130
140
250
350
400
450
5
10
1.0
4.0
0.4
6
10
1.0
7.0
0.7
Torque Type A and B
[Nm]
0,10
0,15
0,35
0,60
0,80
0,90
1,00
1,20
7
10
1.0
10.0
1.0
8
20
2.0
20.0
1.0
Tightening torque for cable glands
In casing with female thread or hole
with lock nut.
Dome nuts may be tightened with max
half of the locknut tightening torque
according to the chart.
Note:
The values in the chart serve as a
general guideline, the exact procedure
depends upon the material.
Nominal size
Pg 7/M12
Pg 9/M16
Pg 11/NPT3/8
Pg 13.5/M20/NPT1/2
Pg 16
Pg 21/M25/NPT3/4
Pg 29/M32/NPT1
Pg 36/M40
Pg 42/M50
Pg 48/M63
Metal
Tightening torque [Nm]
6.25
6.25
6.25
6.25
7.5
10.0
10.0
10.0
10.0
10.0
Plastic moulded parts
Tightening torque [Nm]
2.5
3.75
3.75
3.75
5.0
7.5
7.5
7.5
7.5
7.5
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
43