(IP) Ratings to IEC 262

International Protection (IP) Ratings to IEC 262
Technical Annex
CHART III
The standard EN 50 262 was issued on 01.04.1998 and published in April 1999 in Germany as DIN-EN 50 262/VDE 0619. The well-known standards for cable glands, such
as DIN VDE 0619 (VDE 0619): 1987-09, DIN 46 319: 1989-12, DIN 46 320-1: 1985-09 and DIN 46 320-2...-4: 1973-01 etc, are only applicable until 31.12.1999. Approved
technical drawings using these standards are valid until 01.03.2001.
1.) Fields of application for standard EN 50 262: This European standard contains the requirements and tests for the construction and design of metric cable glands. This
standard covers the cable gland as a complete part, but not the parts of cable glands.
2.) The screw-in thread of cable glands must be constructed according to chart 1 of EN 60 423. The dimensions of the thread are M6x0,75; M8x1; M10x1; M12x1.5;
M16x1.5; M20x1.5; M25x1.5; M32x1.5; M40x1.5; M50x1.5; M63x1.5 and M75x1.5.
3.) The mounting holes must be dimensioned according to Chart A.
4.) Cable glands must be able to guarantee the retaining power for cables and conduits for the complete sealing section. Cable glands with traction relief for cables and
conduits must free the conduits from the load of tension and twist. The tests are carried out, with in each case the smallest and largest mentioned value of the seal resp.
tension relief section of the according loads and torque values in Chart B.
These tests are performed with test pins reproducing the outer diameters of the cables and conduits. The test pins consist of a metal rod with an elastomere sheath.
5.) Cable glands must be impact resistant. A test pin according to the smallest value of the sealing section is fastened to the test probe and then the test is carried out a
lowest temperature according to the energy in accordance with category of Chart C. All specifications, charts and values are excerpts from standard DIN 50 262. Obviously
further tests (electric properties, IP-Code etc.), which are necessary to classify and mark cable glands are described in this standard. It would although go beyond the scope
of this catalogue.
Chart A: Mounting holes for cable glands
Thread size
12
Diameter of
M12
Mounting hole
+ 0,2/- 0,4 mm
12,5
16
M16
20
M20
25
M25
32
M32
40
M40
50
M50
63
M63
16,5
20,5
25,5
32,5
40,5
50,5
63,5
Chart B: Tensile load for retaining power and tension relief, torque for turning tests
Cable and Conduit diameter
Retaining Power
Tensile relief Type A
[mm]
[N]
[N]
bis 4
5
> 4 bis 8
10
30
> 8 bis 11
15
42
> 11 bis 16
20
55
>16 bis 23
25
70
> 23 bis 31
30
80
> 31 bis 43
45
90
> 43 bis 55
55
100
> 55
70
115
Chart C: Value for impact test
Categorie
Load [N]
Weight [Kg]
Energy [J]
Height [m]
CHART IV
1
2
0,2
0,2
0,1
2
2
0,2
0,5
0,25
3
2
0,2
1,0
0,5
4
2
0,2
2,0
1,0
Tensile relief Type B
[N]
75
120
130
140
250
350
400
450
5
10
1,0
4,0
0,4
6
10
1,0
7,0
0,7
Torque Type A and B
[Nm]
0,10
0,15
0,35
0,60
0,80
0,90
1,00
1,20
7
10
1,0
10,0
1,0
8
20
2,0
20,0
1,0
Tightening torque for cable glands according to standard DIN VDE 0619
In casing with female thread
respectively hole with lock nut.
Pressure screws may be tightened
with max 21/43 of the tightening
torque according to the chart.
Note:
The values in the chart serve as
a general guideline, the exact
procedure depends upon the
material.
Nominal size
Pg 7
Pg 9
Pg 11
Pg 13,5
Pg 16
Pg 21
Pg 29
Pg 36
Pg 42
Pg 48
Metal
Tightening torque [Nm]
6,25
6,25
6,25
6,25
7,5
10,0
10,0
10,0
10,0
10,0
Plastic moulded parts
Tightening torque [Nm]
2,5
3,75
3,75
3,75
5,0
7,5
7,5
7,5
7,5
7,5
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
55