10x38 10x38 10x38 10x38

Fuses
gL/gG - Line Protection
Cylinder Fuses are typically used in
industrial applications to protect electrical devices such as motors, drives, etc.
Standard: IEC 20269-4-1
and IEC60269-1
Rated Voltage: 500V
Rated Current/
Rated Voltate
Cat. No.
Std. Pk.
0.5A
1A
2A
4A
6A
8A
10A
12A
16A
20A
25A
32A*
2620017
2620000
2620001
2620003
2620005
2620006
2620007
2620008
2620009
2620011
2620013
2620015
10
10
10
10
10
10
10
10
10
10
10
10
Rated Current/
Rated Voltate
Cat. No.
Std. Pk.
0.5A
1A
2A
4A
6A
8A
10A
12A
16A
20A
25A
32A*
2621017
2621000
2621001
2621003
2621005
2621006
2621007
2621008
2621009
2621011
2621013
2621015
10
10
10
10
10
10
10
10
10
10
10
10
They are available in four sizes with a
current range from 1 to 125 Amps.
Cylinder Fuses have metal caps at both
ends, and a porcelain fuse body.
OPERATING CLASSES
gL/gG - Line Protection
Slow, typically used for distribution circuits or resistive loads.
10x38
Typical Markings: gL/gG
aM - Motor Protection
Fast acting short circuit protection,
but slow acting overload protection.
Typical Marking: aM
*400V
aM - Motor Protection
Standard: IEC 20269-4-1
and IEC60269-1
Rated Voltage: 500V
aR - Semiconductor Protection
Partial range, short circuit protection
for devices such as diodes, SCRs. etc.
Typical Markings: Ultra Rapid™,
Sitor™, Silcu™, Protister™, Recticur™,
Ultra Quick™, aR
gR - Semiconductor Protection
Full range, short circuit protection for
devices such as diodes, SCRs. etc.
Typical Markings: Ultra Rapid™,
Sitor™, Silcu™, Protister™, Recticur™,
Ultra Quick™, gR
10x38
*400V
aR - Semiconductor Protection
Standard: IEC 60269-4-1
Breaking Capacity: ~200 kA
Rated Voltage: ~600V**
Note:
Other fuse sizes and fuse holders
are available. Please refer to the
Altech European Fuse catalog for
more information.
In
(A)
Cat. No.
6
8
10
12
16
20
25
32
2625005
2625006
2625007
2625008
2625009
2625011
2625013
2625015
Operating
I2-value
(A’s)
Power
Dissipation Std. Pk.
(W)
30
50
70
120
150
260
290
600
1.5
2
2.5
3
3.5
4.8
6
7.5
10
10
10
10
10
10
10
10
** 6-25A (700V DC/ breaking capacity ––
--- 50kA)
10x38
32A (400V DC/ breaking capacity ––
--- 50kA)
gR - Semiconductor Protection
Standard: IEC 60269-4-1
Breaking Capacity: ~200 kA
Rated Voltage: ~690V
Ø10.3 mm
(0.4 in.)
10.5 mm
(0.4 in.)
6 mm
(0.24 in.)
38 mm
(1.5 in.)
10.5 mm
(0.4 in.)
6 mm
(0.24 in.)
10x38
Certified for 700V
In
(A)
Cat. No.
1
2
4
6
8
10
12
16
20
25
30
2645126
2645127
2645128
2645129
2645130
2645131
2645132
2645133
2645134
2645135
2645136
Operating
I2-value
(A’s)
1.6
8
8
25
39
66
87
166
280
580
1.010
Power
Dissipation Std. Pk.
(W)
1
1.8
1.1
1.6
1.8
2.1
3.1
4.4
5.8
6.8
8.2
10
10
10
10
10
10
10
10
10
10
10
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
25