Altech Smart Relay Instruction Manual Introduction Altech Smart Relay provides the right solution for all your control needs! Providing excellent performance and functionality, Altech Smart Relay performs simple logic, timing, counting, and real time clock operations. It is an ideal programmable controller for simple control applications such as building construction equipments, HVAC, parking lot lighting and other applications in which cost is a primary design issue. All programming and data adjustments can be done via the on-board keypad and display or with the help of a software. Programming Altech Smart Relay with the help of ASR-Soft configuration software is quite simple, without particular programming knowledge. It facilitates program generation, project simulation and documentation which are accomplished simply using the pick and place functionality, allowing maximum ease of operation. Some of its features are: Ÿ Integrated, ready to use, wide range of programmable functions including 16 timers, 16 (retentive selectable) counters, 16 time switches, 16 compare counters, 16 soft text messages, 64 auxiliary relays and 12 analog comparators. Ÿ 8 digital inputs & 4 relay outputs . Two analog inputs (0 -10V) in 12 -24VDC, model which can be used as digital inputs. Ÿ Ability to add up to three(3) extension modules expanding I/O’s to 32 digital inputs, 16 relay outputs. Ÿ Communication module allows programmable relay to be connected to a Modbus network through RS 485 link Ÿ Backlit LCD screen for display and modification of pre-selected parameters of function blocks, viewing I/O status and programming on the device . Ÿ Ladder programming using software on PC as well on the device with the help of keypad & LCD Display Base Module Ÿ Memory back up allowing programs to be transferred or copied into another Altech Smart Relay with the help of a memory card. Ÿ Compact size –only 72mm (2-53/64") wide x 90mm(3-35/64”) high x 65 mm (2-9/16) deep, reducing panel area requirements for lower installed costs. Ÿ Soft keys for convenient creation and editing of programs on the device. Ÿ Available in both: AC(110 - 240 VAC) & DC(12 - 24 VDC) models. Ÿ Password & Parameter lock facility. Approvals RoHS Compliant EXTENSION MODULE Ÿ Extension Module can be used with base module to increase I/O capacity of Altech Smart Relay. Extension Module Ÿ Every extension module has 8 digital inputs & 4 digital outputs. Ÿ Connections are made in Daisy chain fashion. Ÿ Altech Smart Relay can be expanded by connecting 3 extension modules, to obtain a maximum configuration of 32 inputs and 16 outputs. COMMUNICATION MODULE RS 485 Ÿ RS 485 provides Modbus communication for Altech Smart Relay. Ÿ Possible to connect multiple Altech Smart Relay’s with a SCADA system or a HMI over RS 485. Ÿ Available in both AC (110 - 240 VAC ) & DC (12 - 24 VDC) models. Communication Module ACCESSORIES USB Cable Communication Cable Serial Cable 2 Memory Card Knowing The Product Power Supply Inputs Keypad Extension Selection switch Backlit LCD Display Communication Port Outputs FRONT VIEW OF KEYPAD & FUNCTIONS OF KEYS The 8 keys located on the front facia of Altech Smart Relay are used to configure, program and control the application. DEL This key is used to delete a program element or a blank line, if the cursor is located at the extreme column. ALT This key is used for selecting/exiting a parameter in the edit mode and to show either the Parameters or Program while the program is running. This feature is also useful for debugging. OK This key to is used to insert a program line, when cursor is blinking in the first column of first row. During the parameter entry while editing this key saves the changes and proceeds to next parameter. In RUN mode, this key can be used to select one of the 3 displays. This also selects/deselects links. ESC This key is used to exit the menu or a selection. During the parameter entry it proceeds to the next parameter without saving the changes. Z (ARROW) Keys On the program editor screen, the arrow keys are used to move up, left, down and right. The position on screen is shown by a cursor or blinking text. They are used as push buttons to get signals from user. If user goes into PAR (parameter mode), then these keys are not available as z-keys. At that time these keys are used as arrow keys. 3 Wiring Diagrams SUPPLY, INPUT & OUTPUT CONNECTIONS FUSE FUSE L L SUPPLY N N I1 I2 I3 I4 I5 I6 I7 I8 C1 C2 L N 110 - 230 V AC 50 / 60 Hz +SUPPLY + - I1 I2 I3 I4 I5 I6 I7 I8 C1 C2 L N 110 - 230 V AC 50 / 60 Hz INPUT 8XAC FUSE FUSE +SUPPLY - SUPPLY INPUT 8XAC INPUT 6XDC V1,V2=0-10 VDC 12 - 24V DC Z1 PROGRAM RUN PARAMETER UTILITIES Z3 ESC Z2 Q2 LOAD FUSE OUTPUT 4 X RELAY / 8A Q1 Q4 Q3 LOAD LOAD Z1 LOAD Q2 LOAD FUSE LOAD Q3 LOAD AC Base Module Z2 Q4 Q1 LOAD FUSE LOAD Q2 Q3 LOAD LOAD L N I1 I2 I3 I4 I5 I6 I7 I8 C1 C2 FUSE LOAD OP2 LOAD OP3 LOAD OP4 LOAD +SUPPLY - DC Base Module DC Extension Module Fig. 2 L N I1 I2 I3 I4 I5 I6 I7 I8 C1 C2 110 - 230 V AC 50 / 60 Hz INPUT 8XAC OP1 LOAD SUPPLY AC Extension Module OUTPUT 4 X RELAY / 8A Q4 Fig. 1 110 - 230 V AC 50 / 60 Hz OK OUTPUT 4 X RELAY / 8A +SUPPLY - SUPPLY INPUT 6XDC An1, An2 = 0-10 V DC 12 - 24V DC Z3 ESC OK OUTPUT 4 X RELAY / 8A Q1 I1 I2 I3 I4 I5 I6 ANAN C1 C2 DEL Z4 ALT DEL Z4 ALT PROGRAM RUN PARAMETER UTILITIES + - I1 I2 I3 I4 I5 I6 V1 V2 C1 C2 INPUT 8XAC DEL Z4 ALT PROGRAM RUN PARAMETER UTILITIES Z1 Z3 ESC Z2 OK 485DC OUTPUT 4 X RELAY / 8A ALTECH SAMRT RELAY OUTPUT 4 X RELAY / 8A ASR-SOFT Q1 Q2 Q3 Q1 Q4 Q2 Q3 Q4 Fig. 3 Connection Between Base Module & Extension Module Fig. 4 Connection Between Base Module & Communication Module Same for both AC & DC Power Supply Wiring 1. Although the Altech Smart Relay has been designed to withstand the negative effects of any electrical noise that might be present in the incoming power supply it may be necessary to insert an isolation transformer between the supply and the line terminals of the Altech Smart Relay. 2. While using the DC Altech Smart Relay, run the 24 VDC Input line away from the 100 V AC and 200 V AC lines. Wiring of Input/Ouput 1. Separate the Input lines and output. 2. When the output lines are running close to power supply lines or the Input lines use batch shielded and ground them. MOUNTING DIMENSIONS (mm) 485DC Dimensions for Base / Extension Module Dimensions for RS485 Communication Module 4 Programming the Altech Smart Relay at the Device: Menu & Functions PROGRAM RUN PARAMETER UTILITIES OK Screen 1 EDIT DELETE TRANSFER MODBUS CONF Z2 PROGRAM I 2 ------------ T1 Screen 2 EDIT DELETE TRANSFER MODBUS CONF Programming and other settings in Altech Smart Relay can be done using the software as well as on the device itself with the help of the keypad & display. When the connections are made and the device is powered ON, screen 1 is displayed on the device. By default the cursor will blink on the ‘PROGRAM’ option. Using the Up, Down keys, user can select between any of the options. When the cursor is on the PROGRAM option and OK key is pressed, then screen 2 is displayed. When screen 2 is being displayed, the cursor is on the ‘EDIT’ option. Press the OK key to enter this option & screen 6 will be displayed. Similarly by pressing down key and OK, one can enter the other functions viz. “DELETE”, “TRANSFER”, “MODBUS CONF” and screen 7,8 and 9 will be displayed respectively I 1 ------------ Q1 OK Screen 6 DELETE ! OK Screen 7 EDIT Z2 Z2 EDIT DELETE TRANSFER MODBUS CONF OK This function allows the user to enter a new program or edit an existing program. If Password is set, then this function is accessible only with the correct password. CARD > DEVICE DEVICE > CARD DELETE CARD DELETE This function will clear the entire program stored in the Altech Smart Relay. If password is set, then this function will work only with correct password. Screen 8 TRANSFER Z2 EDIT DELETE TRANSFER MODBUS CONF OK This function will transfer the program from device to memory card or vice versa. Program data on memory can also be deleted in this mode. SLV ID 000 BAUD 9600 PARITY NONE STOPBIT 1 MODBUS CONFIG This function will set Mod bus Slave configuration data. The user can set the following communication parameters: ŸSLAVE ID , BAUD RATE, PARITY , STOP BIT Screen 9 RUN When screen 1 is being displayed, press the down key to shift the cursor to the RUN option and press OK key to enter it. Screen 3 will be displayed. PROGRAM RUN PARAMETER UTILITIES OK PARAMETERS The RESET Mode resets all the previous states of Inputs/Outputs, clears timer and counter states, starts afresh. CONTINUE The CONTINUE Mode does not change the states of the Inputs/Outputs and special functions and continues with the execution of the program. Screen 3 Z2 When the cursor is on PARAMETERS option and OK is pressed then screen 4 will be displayed. PROGRAM RUN PARAMETER UTILITIES OK 9999 DIR RET CNT C1 Y RES Z2 PROGRAM RUN PARAMETER UTILITIES PARAMETERS This function displays and allows the user to change parameters of special functions like timer, counter, Time switch (clock), compare counters and analog functions used in the program. This may be password protected and may have additional individual lock for each parameter. Screen 4 OK SET CLOCK PASSWORD EXT MOD BACKLIT CONF Z2 UTILITIES RESET CONTINUE RESET OK Screen 10 Screen 5 SET CLOCK PASSWORD EXT MOD BACKLIT CONF When the cursor is on the UTILITIES option and OK key is pressed, then screen 5 is displayed. When screen 5 is being displayed, the cursor is on the ‘SET CLOCK’ option. Press the OK key to enter this option & screen 1 will be displayed. Similarly by pressing down key and OK, one can enter the other functions viz. “PASSWORD”, “EXT MOD”, “BACKLIT CONF” and screen 7,8 and 9 will be displayed respectively DD/MM/YY 01/01/2011 HH:MM 10:40 PASSWORD SET CLOCK OK This function is used to set the day and time: Day of the week, Date, HoursMinutes. This function is available only on Altech Smart Relay. 0000 PASSWORD Screen 11 This function allows setting of password. If password is set, certain functions like Program, Parameters are protected and are accessible only when correct password is entered. The Password can be set or removed; the status is indicated by the open or closed lock symbol. Z2 SET CLOCK PASSWORD EXT MOD BACKLIT CONF OK A B EXTENSION MODULE This function allows the selection of the Extension Modules (A/B/C). Maximum 3 Extension Modules can be connected to the Altech Smart Relay’s Main Unit. In the ASR-Soft on PC, extension modules have to be chosen using the "Configuration" menu. C Screen 12 Z2 SET CLOCK PASSWORD EXT MOD BACKLIT CONF EXTENSION MODULES OK BACKLIT CONF BACKLIT CONFIG This function allows the setting of backlight in either On, Off or Auto mode. In the Auto mode, the backlight comes up only when a key is pressed on the device and remains for 10 seconds. If the ON or OFF modes are selected the backlight will be permanently ON or OFF respectively. AUTO Screen 13 5 Ladder Programming Elements / Function Blocks In ladder programming, the ladder elements / Functional Blocks are connected to create a ladder for any application. The following section gives the description of each element that is used for ladder programming. INPUTS OUTPUTS Altech Smart Relay provides Digital Outputs: Base Module (4), Extension Module (4) The outputs can be configured as: I. State Change (Contactor), ii. Level Change (Remote Control), iii. Bi-stable (Set Reset) Q1, Q2, ..... Q4 Base Module U1, U2, ..... U4 Normally Open Extension Module 1 Contact V1, V2, ..... V4 Extension Module 2 (’NO’ Contact) W1, W2, ..... W4 Extension Module 3 Altech Smart Relay provides 2 types of Inputs viz. Digital & Analog AC Model: Digital Inputs (1 - 8) DC Model: Digital Inputs (1 - 6), Analog Inputs (V1, V2)8 I1, I2, ..... I8 J1, J2, ..... J8 K1, K2, ..... K8 Base Module Normally Open Extension Module 1 Contact Extension Module 2 (’NO’ Contact) Extension Module 3 L1, L2, ..... L8 i1, i2, ..... i8 j1, j2, ..... j8 k1, k2, ..... k8 q1, q2, ..... q4 u1, u2, ..... u4 v1, v2, ..... v4 Base Module Normally Closed Extension Module 1 Contact Extension Module 2 (’NC’ Contact) Extension Module 3 l1, l2, ..... l8 Base Module Normally Closed Extension Module 1 Contact Extension Module 2 (’NC’ Contact) Extension Module 3 w1, w2, ..... w4 TIMERS TIME SWITCHES Altech Smart Relay provides 16 Timers which can be configured as: I. ON Delay, ii. Off Delay, iii. Single Pulse iv. Symmetric/Asymmetric Altech Smart Relay provides 16 Time Switches which can be used for daily or weekly applications v. Equal/Unequal On/Off 2, vi. Equal/Unequal Off/On 2, vii. Leading Edge Impulse 1, viii. Leading Edge Impulse 2 ix. Trailing Edge Impulse 1, x. Trailing Edge Impulse 2 xi. Delayed Impulse, xii. Impulse On/Off, xiii. Signal Off/On. Normally Open (NO) Contact Normally Closed (NC) Contact 1, 2, ..... 16 1, 2, ..... 16 T1, T2, ..... T16 Timer Coil / Normally Open (NO) Contact Normally Closed (NC) Contact t1, t2, ..... t16 Trigger Input Timer Mode Reset Input Preset Time Unit Current Time Unit D TRG RES 000.0 006.0 S S T1 X OF OF From To Timer Number Make/Break Status of ‘NO’ Contact Locked/Unlocked State Preset Time Period Time Switch No Make/Break Status of ‘NO’ Contact Locked/Unlocked State COMPARE COUNTERS Altech Smart Relay provides 16 Compare Counters which can be used for comparison between values of two counters or between a counter and any absolute value I. Up Counter, ii. Down Counter Altech Smart Relay provides 12 Analog Comparators which can be used for comparison between values of two analog signals or between a an analog signal and any absolute value Compare Input Compare Function Absolute Value MO TRGSU T1 08 RES : 11 X 1 ON S 09 000.0 : 15 OF X OFF S 12 006.0 : 00 OF Current Time Period ANALOG COMPARATORS Normally Open (NO) Contact Normally Closed (NC) Contact A1, A2, ..... A12 a1, a2, ..... a12 D Current Time Start Time End Time D ANALOG TRG T1 V1 0000 X RES > P1 S 000.0 OF ABS 1023 OF X S 006.0 P1, P2, ..... P16 p1, p2, ..... p16 Analog Comparator No Locked/Unlocked State Compare Input Compare Function Absolute Value Normally Open (NO) Contact Normally Closed (NC) Contact D COMPARE TRG T1 C1 0000 X RES > P1 S 000.0 OF ABS 1023 OF X S 006.0 Compare Counter No Locked/Unlocked State Make/Break Status of ‘NO’ Contact Make/Break Status of ‘NO’ Contact COUNTERS AUXILIARY RELAYS Altech Smart Relay provides 64 Auxiliary relays which can be used to expand a rung from one line to another line. It can be configured as: I. State Change (Contactor), ii. Level Change (Remote Control), iii. Bi-stable (Set Reset) Altech Smart Relay provides 16 Counters which can be configured as: I. Up Counter, ii. Down Counter C1, C2, ..... C16 Counter Coil / Normally Open (NO) Contact c1, c2, ..... c16 Normally Closed (NC) Contact Preset Value Direction Input Counter Unit Reset Unit D S S TRG 0004 RES DIR 000.0 CNT 006.0 RES 0000 T1 RET X C1 OFN XOF M1, M2, ....M64 Auxiliary Coil / Normally Open (NO) Contact m1, m2, .....m64 Normally Closed (NC) Contact Current Value Retentive Selection (Y/N) Locked/Unlocked State Make/Break Status Counter Number of ‘NO’ Contact Z-KEYS Z-Keys are navigation keys provided on device front facia.They behave exactly like the physical inputs (Discrete inputs). The only difference is that they do not correspond to Altech smart relay connection terminals, but to the four gray buttons on the front panel. SOFT TEXT MESSAGES Z1, Z2, ..... Z4 z1, z2, ..... z4 Altech Smart Relay provides 16 Soft Text Message blocks which can be used to display text messages, the Preset Value and Current Value of any Special Function Block or the Current Date and time Normally Open (NO) Contact Normally Closed (NC) Contact ·Z-Keys can be used as navigation keys for current displayed menu. To use Z-Keys go to RUN Screen or RUN LADDER Screen and Press ALT which will display the Z-Key Screen. Then Press Z1 - Z4. X1, X2, ..... X16 Used for viewing Alarms, HMI Functionality 6 Functions Setting the Clock Extension Module Selection 1. Select the “UTILITIES” option from the Main Menu and press OK. 2. Select the “SET CLOCK” option from the Sub Menu and press OK. 3. The cursor will blink on the first digit of the date, press ALT to edit the digit 4. The digit will now start blinking 5. Using Up(Z4) and Down(Z2) keys select the appropriate digit. 6. Now press Z3 to edit the other digit and using Up & Down keys select the digit. 7. Now press OK to confirm the changes that have been made. 8. Repeat the same procedure to set the month, year, hour and minutes. Once all the parameters have been set, pres OK to save the changes and exit. 1. Select the “UTILITIES” option from the Main Menu and press OK. 2. Select the “EXT MOD” option from the Sub Menu and press OK. 3. The cursor will be blinking on ‘A’, press ALT to edit and the ‘A’ will start blinking. 4. Press Up(Z4) or Down(Z2) keys to select or deselect the extension module. 5. A dark square around ‘A’ indicates that the module has been selected. 6. Now press OK to confirm the changes that have been made. 7. Repeat the same procedure if the other modules are to be selected. 8. Press OK to save the changes and the ‘UTILITIES’ sub menu is displayed PROGRAM I RUN PARAMETERS UTILITIES DD/MM/YY I 11/01/11 HH:MM 09:30 OK Z3 SET I CLOCK PASSWORD EXT MOD BACKLIT CON DD/MM/YY I 11/01/11 HH:MM 09:30 OK Z4 DD/MM/YY I 01/01/11 HH:MM 09:30 ALT DD/MM/YY I 15/01/11 HH:MM 09:30 DD/MM/YY I 01/01/11 HH:MM 09:30 PROGRAM I RUN PARAMETERS UTILITIES Z4 A The password secures access to the following main menu options: "PROGRAM","PARAMETERS" and "UTILITIES". Password feature is disabled during Ladder Run Mode. User can view/edit SFB data during ladder Run mode if the "LOCK/UNLOCK" property is in unlock state. Edited at run time will not be saved permanently in the device. This functionality is provided only to test the system during run time. The password comprises four numeric digits from 0 to 9. Therefore the password can have any value between 0 and 9999. Setting the Password SET I CLOCK PASSWORD EXT MOD BACKLIT CON ALT PASSWORD I Z4 B OK PASSWORD 725 7 PASSWORD ENABLED A B ALT C EXTENSION I MODULES A B Z4 C SET I CLOCK PASSWORD EXT MOD BACKLIT CON C If only one extension module is being used and it has been assigned as ‘A’ on the extension module using the selection switch then make sure that ‘A’ is selected in the ‘EXT MOD’ option in the ‘UTILITIES’ menu. If more than one extension modules are being used then make sure that the modules have been assigned and selected appropriately because this in turn will affect the inputs and the outputs. Backlit Configuration PASSWORD 7 PROGRAM I RUN PARAMETERS UTILITIES OK I BACKLIT OK CONFIG OK EXTENSION I MODULES DATA ISAVING . . . WAIT SET I CLOCK PASSWORD EXT MOD BACKLIT CON I BACKLIT CONFIG ON PASSWORD 725 7 OK 1. Select the “UTILITIES” option from the Main Menu and press OK. 2. Select the “BACKLIT CONF” option from the Sub Menu and press OK. 3. The ‘Auto’ option will be displayed with the cursor blinking on it. 4. Press ALT to edit and the Auto option will start blinking. 5. Press Up(Z4) or Down(Z2) keys to select other options viz. ON, OFF. 6. Now press OK to confirm the changes that have been made. 7. Press OK to save the changes and the ‘UTILITIES’ sub menu is displayed. 1. Select the “UTILITIES” option from the Main Menu and press OK. 2. Select the “PASSWORD” option from the Sub Menu and press OK. 3. The unlock symbol means that the password is not yet set. 3. The cursor will blink on the first digit of the date, press ALT to edit the digit 4. The digit will now start blinking 5. Using Up(Z4) and Down(Z2) keys select the appropriate digit. 6. Now press Z3 to edit the other digit and using Up & Down keys select the digit. 7. Repeat the same procedure to set all the 4 digits. 8. Now press OK to confirm the changes that have been made. 9. Again on pressing OK the password is enabled and the Main Menu is displayed OK SET I CLOCK PASSWORD EXT MOD BACKLIT CON EXTENSION I MODULES DATA ISAVING . . . WAIT PASSWORD PROGRAM I RUN PARAMETERS UTILITIES OK OK I BACKLIT ALT CONFIG AUTO OK CONFIG Z4 AUTO DATA ISAVING . . . WAIT ON I BACKLIT SET I CLOCK PASSWORD EXT MOD BACKLIT CON AUTO: In AUTO mode, whenever a key is pressed the backlit will be switched ON and will switched OFF after 10 seconds. ON: In ON mode, the backlit will be permanently switched ON. OFF: In OFF mode, the backlit will be permanently switched ON. PROGRAM I RUN PARAMETERS UTILITIES Removing the Password Ladder Program Protection 1. Select the “UTILITIES” option from the Main Menu and press OK. 2. Select the “PASSWORD” option from the Sub Menu and press OK. 3. The lock symbol means that the password is set. 3. The cursor will be blink on the first digit, press ALT to edit the digit 4. The digit will now start blinking 5. Using Up(Z4) and Down(Z2) keys select the appropriate digit. 6. Now press Z3 to edit the other digit and using Up & Down keys select the digit. 7. Repeat the same procedure to set all the 4 digits. 8. Now press OK to confirm the changes that have been made. 9. Again on pressing OK the password is disabled and the Main Menu is displayed 1. If the password is already enabled and user attempts to gain access using wrong password, then an error message is displayed. 2. If four such consecutive attempts are made then user is presented with options to either delete the entire device data or else revert. 3. If the DELETE ALL option is selected , then all device data including Password and Ladder is erased. The user can then re program the Ladder using ASR-Soft and secure it with a new password. PASSWORD I OK INVALID I PASSWORD ... try later PROGRAM I RUN PARAMETERS UTILITIES OK SET I CLOCK PASSWORD EXT MOD BACKLIT CON ALT PASSWORD I Z4 PASSWORD 7 After four wrong attempts of entering the Password this Screen as shown below appears. Pressing OK here, will delete all device data. PASSWORD I PASSWORD 725 7 OK PASSWORD 725 7 OK PASSWORD ENABLED PROGRAM I RUN PARAMETERS UTILITIES OK DELETE ALL ? I OK INITIALIZING IDEVICE DATA . . . WAIT After four wrong attempts of entering the Password if user presses ESC ,the device will return to last menu mode from where it has entered in PASSWORD screen. 7 Functions Creating or Editing a Ladder TRANSFER To create a new ladder or edit an existing ladder, select the PROGRAM option from the Main Menu by pressing OK. Select the EDIT option to create or edit a ladder. The TRANSFER function allows data to be transferred from Memory Card to Altech Smart Relay or vice-versa. Transferring data to memory card is useful when user wants to load the same program in many Altech Smart Relay units. In this case instead of using PC user can make use of memory card, which is capable of storing one program. This feature is particularly useful on the production line where user is not required to edit and debug the program and a PC is not available. In this mode of transfer "PASSWORD"and "UTILITIES"such as Backlight configuration & Extension module state will also get transferred with the program ladder. Inserting a Contact 1. Place the blinking cursor in the required position. 2. Press ALT. 3. Choose the required element using the Up or Down keys. 4. Use the Right Arrow key to move to the number. 5. Choose the number using up or down keys. 6. Press ALT or Right Arrow to accept and to go to next position. I ALT II 1 Z3 I1 PROGRAM I RUN PARAMETERS UTILITIES Z4 OK EDIT I DELETE TRANSFER MODBUS CON OK CARD > DEVICE I DEVICE > CARD DELETE CARD Devie to Card I2 OK 1. Insert the Memory card in the connector of Altech Smart Relay. 2. Select the "TRANSFER" function from the "PROGRAM" menu. 3. Press the OK key to validate. 4. Select the Device > Card function. 5. Press the OK key to validate. I2 Inserting a Coil Card to Device 1. Place the blinking cursor in the required position. 2. Press ALT. 3. Choose the required element using the Up or Down keys. 4. Use the Right Arrow key to call-up the number. 5. Choose the number using Up or Down keys. 6. Use the Left Arrow key to move to the type of coil. 7. Choose the type of coil using Up or Down keys. 8. Press ALT or Right Arrow to accept and to go to next position. This transfer is used to reload an application into the Altech Smart Relay. It avoids the need to re-enter an existing application. 1. Insert the Memory card in the connector after removing the serial cable, if present. 2. Move cursor to the "TRANSFER" function from the "PROGRAM" menu. 3. Press the OK key to validate. 4. Select the Card > Device function. 5. Press the OK key to validate. II 1 ALT I1 Q1 Z3 I1 Q2 ALT I1 Q2 Editing Parameters of Special Function Blocks Parameters of special Function Blocks can be modified in two modes 1. Run Mode 2. Program Stop Mode Run Mode Entering a Link 1.User can enter into Run Time parameters. Press ESC to go on the PARAMETER RUN men as shown below. 2. Press ‘OK’. Enter the PASSWORD if it has been enabled and Press OK. Special function block with it's parameters set will get display. 3. Set parameters & press OK to save the parameters temporary. 4. Press ESC to return Run Mode Menu . 5. If user do not press OK and do press ESC previous settings retains & returns to Run Mode Menu. 1. Place the blinking cursor next to the desired location. 2. Press OK to start the link (" ","cursor") 3. Move the cursor to the desired location using the arrow keys. 4. As the cursor moves, the link is drawn. 5. Press OK to exit to normal mode. 6. Repeat this action as many times as necessary to link all the elements together as required II 1 Q1 Q2 OK I1 Q1 Q2 Z2 I1 Q1 Q2 OK I2 Q1 Q2 Deleting a Program Line Move the cursor to the first column of the line, if necessary delete the elements one by one to create a blank line. Press DEL. The line is deleted. It is also possible to delete the entire program stored in the Altech Smart Relay. To do this, call up the "DELETE" option in the Program menu and validate the deletion of all program lines. PAUSE I STOP PAR RUN PROG RUN OK PAUSE I STOP PAR RUN PROG RUN OK D TRG RES S 000.0 S 006.0 T1 X OF OF PAUSE I STOP PAR RUN PROG RUN ESC PASSWORD I D TRG RES S 000.0 S 006.0 OK T1 X OF OF ESC PAUSE I STOP PAR RUN PROG RUN Program Stop Mode 1.Place the cursor on PARAMETERS menu and Press OK. 2.Enter the PASSWORD if it has been enabled and press OK. 3.Set Parameters. Press OK.If user do press ESC key without pressing OK the screen as shown will appear, so that user can have three options as: EDIT: Again enter into parameter set mode. SAVE AND EXIT: Save the parameters & come out of mode. EXIT: Retain previous settings & come out of set mode. Replacing a Link with a Contact To replace a link with a contact, simply place cursor at the required location and press ALT to enter the contact PROGRAM I RUN PARAMETERS UTILITIES Changing an Element To change an element in an existing program, simply move to the element to change, press ALT and follow the same procedure as when entering a new element OK D TRG RES S 000.0 S 006.0 T1 X OF OF Deleting an Element To delete an element, simply place the cursor on the required element, then press DEL. Generally, the deleted element must be replaced by a link OK ESC Deleting Links between Elements To delete a link, simply move the cursor next to the desired position, press the OK key to change the cursor and press DEL key. This may delete some of the required connections, which may be restored by the same method as above PROGRAM I RUN PARAMETERS UTILITIES Inserting a Program Line To insert a program line, simply move cursor to the first column of the line immediately above the one to create and press OK. OK PASSWORD I OK PROGRAM I RUN PARAMETERS UTILITIES EDIT I SAVE & EXIT EXIT D TRG TRG D RES RES S 000.0 000.0 S S 006.0 006.0 S T1 T1 X X OF OF OF OF OK ESC 8 DATA ISAVING . . . WAIT EDIT I SAVE & EXIT EXIT Functions RUN MODE MODBUS SETTINGS Slave ID 1. Select the “PROGRAM” option from the Main Menu and press OK. 2. Select the “MODBUS CONF” option from the Sub Menu and press OK. 3. The cursor will blink on the first digit of the Salve ID (SLV ID). 4. Press ALT to edit the digit and the digit will now start blinking 5. Using Up(Z4) and Down(Z2) keys select the appropriate digit. 6. Now press Z3 to edit the other digit and using Up & Down keys select the digit. 7. Now press OK to confirm the changes that have been made. To enter into RUN mode select the "Run" option in the main menu and press 'OK'. PROGRAM I RUN PARAMETERS UTILITIES CONTINUE I RESET OK I 12345678 OK SA Q 1234 08:30 ESC If the CONTINUE option is selected then Ladder Program execution will proceed & the Run mode display screen will appear as shown If the RESET option is selected then all special function block parameters are initialized & the Run mode display screen will appear PROGRAM I RUN PARAMETERS UTILITIES Run Mode Functions During the Run mode the user can enter the Run Mode Functions by pressing the ESC key I 12345678 SA Q 1234 08:30 ESC ESC PAUSE I STOP PAR RUN PROG RUN CONTINUE I RESET OK OK SLV ID 101 I BAUD 9600 PARITY NONE STOPBIT 1 I 12345678 SA Q 1234 08:30 ESC OK PROGRAM I RUN PARAMETERS UTILITIES Z3 PAUSE I STOP PAR RUN PROG RUN OK D TRG RES S 000.0 S 006.0 SLV ID 111 I BAUD 9600 PARITY NONE STOPBIT 1 T1 X OF OF OK I I1---------Q1 I2---------- Q2 I3---------- Q3 SLV ID 111 I BAUD 0300 PARITY NONE STOPBIT 1 PAUSE If the PAUSE option is selected by pressing OK then program execution is paused. And user can have two options as Continue: Run with the parameters status it has or Reset: Reset the parameters and run the program. SLV ID 111 I BAUD 0300 PARITY ODD STOPBIT 1 PAR RUN ·If the PAR RUN option is selected then Parameter edit window of Special Function Block is displayed. The user can edit the parameters by using ALT, UP, DOWN & OK keys.* PROG RUN ·If the PROG RUN option is selected then the ladder program is displayed on the screen. The user cannot edit the program and can only go through the program by using UP, Down keys If Z-Keys are used in the program then pressing the ALT key will display the Z-Key screen. I I1---------Q1 I2---------- Q2 I3---------- Q3 Z4 SLV ID 001 I BAUD 9600 PARITY NONE STOPBIT 1 SLV ID 111 I BAUD 9600 PARITY NONE STOPBIT 1 SLV ID 001 I ALT BAUD 9600 PARITY NONE STOPBIT 1 OK SLV ID 111 I BAUD 9600 PARITY NONE STOPBIT 1 Z3 SLV ID 101 I BAUD 9600 PARITY NONE STOPBIT 1 Z4 SLV ID 111 I BAUD 0300 PARITY NONE STOPBIT 1 OK SLV ID 111 I BAUD 0300 PARITY NONE STOPBIT 1 Z3 SLV ID 101 I BAUD 9600 PARITY NONE STOPBIT 1 Z4 SLV ID 111 I BAUD 0300 PARITY ODD STOPBIT 1 OK SLV ID 111 I BAUD 0300 PARITY ODD STOPBIT 1 Stop Bits 14. Now press Z3 to select ‘STOPBIT’ and press ALT to edit.. 15. Using Up(Z4) and Down(Z2) keys select the number of stop bits. 16. Now press OK to confirm the changes that have been made. STOP If the STOP option is selected by then the program execution is stopped & Main Menu is displayed on the screen. PAUSE I STOP PAR RUN PROG RUN SLV ID 101 I BAUD 9600 PARITY NONE STOPBIT 1 OK Parity 11. Now press Z3 to select ‘PARITY’ and press ALT to edit.. 12. Using Up(Z4) and Down(Z2) keys select the appropriate parity. 13. Now press OK to confirm the changes that have been made. Z3 PAUSE I STOP PAR RUN PROG RUN Z3 EDIT I DELETE TRANSFER MODBUS CON Baud Rate 8. Now press Z3 to select Baud Rate (BAUD) and press ALT to edit.. 9. Using Up(Z4) and Down(Z2) keys select the appropriate Baud Rate. 10. Now press OK to confirm the changes that have been made. Z3 PAUSE I STOP PAR RUN PROG RUN OK SLV ID 111 I Z3 BAUD 0300 PARITY ODD STOPBIT 1 Z4 SLV ID 111 I BAUD 0300 PARITY ODD STOPBIT 2 OK SLV ID 111 I BAUD 0300 PARITY ODD STOPBIT 2 17. Once all the changes have been made press OK to save and exit. SLV ID 111 I BAUD 0300 PARITY ODD STOPBIT 2 DATA ISAVING . . . WAIT EDIT I DELETE TRANSFER MODBUS CON Parameter Lock When user edits parameter from text message and if parameter is locked then above screen appears. To change that parameter user has to edit that parameter in edit mode only. Z1 I Z2 Z3 Z4 PARAMETER I LOCKED * Embedded parameters when unlocked and edited at run time will not be saved permanently in the device. This functionality is provided only to test the system during run time. To save parameters permanently, user has to stop the program, move to edit mode & configure the system accordingly. Note: In Run Mode, extension module identities cannot be changed 9 Z4 ASR-Soft Installation This section provides Instructions for installing the ASR - Soft. The ASR – SOFT Installation Program creates directories as needed, creates files on your hard drive, and creates ASR-Soft icon on your desktop. Note: You must have Administrator privileges on your PC in order to install or uninstall the software. Installation on Windows XP: 1 Insert the ASR-soft CD into the CD-ROM drive of your computer/laptop. The 2 When prompted for the destination directory as shown below, user can either select the default directory (C:\Program Files\Altech Smart Relay\ASRSOFT) or enter another destination directory for the installation files. installation wizard starts automatically and a Welcome screen appears, as shown below. In case the Auto run feature is disabled in your Windows settings, use Windows explorer to access the 'setup.msi' file. Double-click the icon 'setup.msi' and the welcome screen appears. If you have downloaded the folder containing the ASR-Soft Setup then the installation process has to be done manually. For this, double-click the 'setup.msi' file in the folder and continue the installation process once the Welcome screen appears. In the Welcome screen, click the Next button to continue. 3 Click on "Next" to start installation. 4 A dialog box indicating the status of the progress of installation will display. 5 Then Driver Installation window will display. Click on "Install" to start 6 When the Installation is finished, select “Yes" to restart your PC. After this, the screen “ASR-Soft has been successfully installed ” will appear on your PC and it restarts. 7 After your PC has restarted, you can run the ASR –SOFT. installation. 10 ASR-Soft Installation Installation on Windows Vista and Windows 7: 1 Insert the ASR-soft CD into the CD-ROM drive of your computer/laptop. The 2 When prompted for the destination directory as shown below, user can either installation wizard starts automatically and a Welcome screen appears, as shown below. In case the Auto run feature is disabled in your Windows settings, use Windows explorer to access the 'setup.msi' file. Double-click the icon 'setup.msi' and the welcome screen appears. select the default directory (C:\Program Files\Altech Smart Relay\ASRSOFT) or enter another destination directory for the installation files. If you have downloaded the folder containing the ASR-Soft Setup then the installation process has to be done manually. For this, double-click the 'setup.msi' file in the folder and continue the installation process once the Welcome screen appears. In the Welcome screen, click the Next button to continue. 3 Click on "Next" to start installation. 4 A dialog box indicating the status of the progress of installation will display. 5 Then Driver Installation window will display. Click on "Install" to 6 When the Driver installation is finished, “Success” screen – Installation successful, will appear. Once we press OK, the screen “ASR-Soft has been successfully installed” will appear on your PC. start installation. 7 Restart your PC after installing the software, to complete the installation. After your PC has restarted, you can run the ASR –SOFT. 11 Programming using the ASR-Soft ASR-Soft is the exclusive Windows based programming software for the Altech Smart Relay . It facilitates: Entering the Program: Select & Place ASR-Soft provides a user-friendly interface wherein the user has to only select contact type and contact number and place it where it is required. Contacts get connected automatically if they are on the same line. User can enter comments for better readability and for future reference . Saving Programs ASR-Soft allows user to save individual programs on the PC. Debugging ASR-Soft is very powerful in error handling. It displays any possible errors as the program is being entered to make corrections simultaneously. Simulation on PC User can simulate the program on PC. User can use buttons provided on the screen to simulate the input connections. Scroll bar can be used to simulate Analog input. The actuation/ de-actuation of the relays can be monitored on the screen. Simulation on Altech Smart Relay User can connect the Altech Smart Relay unit to PC using a serial Communication cable / USB cable and perform on line program simulation. In this mode the PC acts as a master and the inputs are taken from Altech Smart Relay and outputs are sent to Altech Smart Relay unit (and the extension modules, if connected). This mode is useful in debugging the entire system since the actual I/Os are used. Printing User can take print outs of programs in two different formats, namely Short format and Detail format. Also, program Parameters and Comments can be printed. Transfering Programs Programs can be transferred from PC to Altech Smart Relay and vice versa using serial Communication cable / USB cable. This saves the program entering time on the Smart Transfering Clock With this utility user can set the clock (date and time) on the Altech Smart Relay. Program Editor Window I/O Function Selector Window Input/Output Window Error Window Select File -> New from the menu bar to create a new program. A blank screen will appear. Now you can start entering the program. Ensure that you have chosen proper Altech Smart Relay Configuration before starting the program entry. Choosing Contact Type Position the cursor at the place where you want to insert the contact by a left click with mouse. The position will get highlighted. Choose the required contact type and Contact Number from I/O function selector. Click on the required contact and contact number, which will be highlighted for a few seconds. The selected contact will appear at the position selected in the program. The selected contact number will be shown with a tick mark to indicate that it has been used in the program. You can right click on any of the contact to change its type and properties. Connecting Inputs & Outputs Each circuit connection runs from left to right. Please remember this when you interconnect contacts and relay coils. User can draw a circuit connection horizontally from left to right and vertically between adjacent circuit connections. An intersection of circuit connections represents an electrical connection. Horizontal connection To make a horizontal connection, click on the horizontal dotted line in the connection box of the circuit. Or to make connection in contact box, press right button and select "Joining link". Generally when an output coil is placed in the fourth column, it gets automatically connected. Vertical connection To make a vertical connection click on the vertical dotted line in the connection box of the circuit. Vertical connection represents OR connection. For deleting a connection just left click on the connection line. 12 Working with ASR-Soft To Set & Remove Password Ÿ Ÿ Ÿ Ÿ Ÿ Select the Configuration >Device Utilities menu command. Then Device Utilities window will pop up as shown in the Screen - 1 Click on set password. Enter four digits password in the two boxes “New password” and “Confirm New” Password then confirm with OK. You can delete your assigned password at any time. To do this, enter the existing password in “Old password” box. Then confirm with OK. To change the password, you must first enter the new password in the two boxes “New password” and “Confirm Password “ and the existing password in Current password text box. Then confirm with OK. To Set Backlight Mode Screen - 1 Select the Configuration >Device Utilities menu command. Then Device Utilities window will pop up as shown in the Screen - 1. Ÿ Select the mode Auto, On or Off then click on the set mode button. Ÿ Then “The requested operation will move the device out from the run mode. Do you want to continue?” message will pop up. Ÿ If pressed Yes, then backlight mode will get set in device and "Backlight mode has been set successfully" message will appear on the screen. Ÿ To Configure Communication Port Select the Options > Comm port menu command. Then COM Port setting window will pop up as shown in the Screen - 2 showing two option buttons to select the Port. Ÿ Select “Device is connected to USB port” when the device is connected with cable. Ÿ Select “Device is connected to Serial Communication port” when the device is connected with Serial Communication cable. Ÿ To Set Communication Parameters Select the Options > Comm port menu command. Then COM Port setting window will pop up as shown Screen - 2. Ÿ The user can set the following communication parameters: SLAVE ID: Selectable from 1 to 247. BAUD RATE: Selectable as 1200,2400,4800,9600 baud. PARITY: Selectable as NONE, EVEN and ODD. STOP BIT: Selectable as 1 and 2 stop bits. Ÿ Screen - 2 Clock Setting Select the Transfer > Device Clock menu command. Then Device Clock window will pop up as shown in the Screen - 3. Ÿ To view Date and time of device: Click Read button on the clock setting window. Then the Clock Setting window will show the Date and Time of the device. Ÿ To set Date and time in the device: User can select Date and Time to write into the device. Click Write button on the clock setting window. Ÿ DST (Daylight Saving Time) Setting Ÿ Ÿ Ÿ Ÿ Ÿ Select the Transfer > Device Clock menu command. Then Device Clock window will pop up as shown in the adjoining window. To set Enable DST, Follow the following steps: Click Daylight Saving Time check box then the DST setting section becomes visible. User can select the following parameters: Begin Week, Begin Day, Begin Month, Begin Time, End Week, End Day, End Month, End Time, Offset Time To set Disable DST, Follow the following steps: 1. Deselect Daylight Saving Time option then DST window will get disable. 2. Press Set DST. To read DST: Press Read DST, independent of the DST enable or disable. Transfer Options PC to Device Screen - 3 Select the Transfer > Program menu command. Then transfer window will pop up as shown in the Screen - 4. Ÿ Press "PC to Device" button on transfer dialog box. Current program on the screen will get transferred to device. Ÿ Transfer completion message "The Program is downloaded successfully" will appear on the screen. Ÿ Device to PC Select the Transfer > Program menu command. Then transfer window will pop up as shown in the Screen - 4. Ÿ Press "Device to PC" button on transfer dialog box. Current program on the screen will get transferred to device. Ÿ Transfer completion message "The Program is downloaded successfully" will appear on the screen. Ÿ Read program will be shown on main screen. Ÿ Screen - 4 Extension Module Selection Select the Configuration >PLC Model menu command. Then Model Selection window will pop up as shown Screen - 5. Ÿ Selection of Altech Smart Relay model and Extension modules. Maximum three extension modules can be connected to one Base Module. Ÿ Screen - 5 13 Sample Programs FACTORY/SCHOOL SCHEDULE Opening bell at 8am announces start of work or class (bell to last 10 sec and stop): Bell at 10:30am announces start of coffee break, Bell at 10:45am announces end of coffee break, Bell at 12noon announces lunch, Bell at 12:45 announces end of lunch, Bell at 5pm announces end of work day Programming For the 6 time periods 6 Time Switches are required. 1, 2, ..... 6 represent the 6 Time Switches. Timer T1 ensures that the duration of the output is 10 seconds only. Q1 represents the Output Coil (Alarm/Bell in this case) Double click on the ASR Soft icon the launch the ASR Soft Software application. Click on File New to launch a new Program window. Time Switch Selection & Parameter Editing 1. Click on the Time Switch symbol in the I/O selector window and select Time Switch 1 ( 1) 2. Move the cursor to the ‘Contact 1' column of the first row and left click on the block to place the Time Switch. 3. Right click on the Time Switch and select properties to open the properties window. 4. In the Weekday settings option select ‘From’ as Monday ans ‘To’ as Saturday. 5. In the Daily Duration option enter the start time as 10:30 and since we want the siren for 10 sec. enter end time as 10:31. 6. Similarly select the other 5 Time Switches and enter the times as described above and place them in the contact 1 column of lines 2, 3, 4, 5 & 6. Timer Selection & Parameter Editing 7. Select Timer T1 from the I/O selector window and place it in the coil column of line 1and contact column of line 7. 8. Open the Timer properties window and select the mode as Interval and enter the time duration i.e. SP as 10 sec. 9. Connect the lines from all the Time Switches to the Timer as shown in screen. Output Configuration 10. Select Output Q1 from the I/O selector window and place it in the coil column 11. Right click on output Q1 to and select the option ‘State Change: Contactor’ LADDER PROGRAM 14 Sample Programs CAR PARKING There are 5 parking spots available in a parking area. There are 2 sensors, one at the entry gate and one at the exit gate. When all the parking spots are occupied, there is a lamp outside the entry gate indicating parking is full. When any of the parking spots is available, other lamp is switched ON indicating parking is available. Programming Input I1is the sensor at the Entry gate and Input 2 is the sensor at the exit gate. Output Q1 indicates that Parking is available, Output 2 indicates that Parking is Full. Counter C1 is used to count the number of vehicles that have entered or exited the parking. Compare Counters P1 & P2 are used switch ON outputs Q1 & Q2 respectively by comparing the count of counter C1. Input Selection 1. 2. 3. 4. Click on the Input symbol in the I/O selector window and select I1. Move the cursor to the Contact 1 column of the first row and left click on the block to place the input. Again click on the Input symbol in the I/O selector window and select ‘I2’. Move the cursor to the Contact 1 column of the second t row and left click on the block to place the input. Also place it in the Contact 1 column of the third row. Counter Selection & Parameter Editing 5. Select Counter C1 from the I/O selector window and place it in the coil column of line 1. Right click on the counter and select the option counting input. 6. Again select the same counter C1 and place it in the coil column of line3 . Right click on the counter and select the option direction input. Compare Counter Selection & Parameter Editing 7. Select Compare Counter P1 from the I/O selector window and place it in the contact column of line 4. 8. Right click on the compare counter and select properties. 9. Under the compare selection option, select ‘F1’ as ‘C1’, ‘OP’ as ‘<’, ‘F2’ as ‘Abs Value’ and reference count as 5. 10. Select Compare Counter P2 from the I/O selector window and place it in the contact column of line 5. 11. Right click on the compare counter and select properties. 12. Under the compare selection option, select ‘F1’ as ‘C1’, ‘OP’ as ‘=’, ‘F2’ as ‘Abs Value’ and reference count as 5. Output Configuration 13. Select Output Q1 from the I/O selector window and place it in the coil column 14. Right click on output Q1 to and select the option ‘State Change: Contactor’ LADDER PROGRAM 15 Technical Specifications Supply Voltage 110 - 240 VAC 12 - 24 VDC Supply Variation -20% to +10% -20% to +10% 50/60 Hz ~5W ~5W Frequency Power Consumption N.A. Analog Inputs N.A. 2 (Can also be used as Digital) Analog Input Range N.A. 0 - 10 VDC Digital Inputs Digital Input Range 8 (0 - 50 VAC) OFF, (80 - 265 VAC) ON 4 6 (0 - 4 VDC) OFF, (8 - 26.4 VDC) ON 4 Outputs Contact Rating 8A @ 240 VAC / 5A @ 30 VDC 8A @ 240 VAC / 5A @ 30 VDC Input / Output Extension (Max) Yes (3) Yes (3) Power Reserve (For clock only) 150 h 150 h Timers 16 16 Time Switches (Daily/Weekly) 16 16 Counters (Up/Down, Retentive selectable) 16 16 Compare Counters 16 16 Soft Text Messages 16 (Priority Driven) 16 (Priority Driven) Analog Functions Auxiliary Relays N.A. 64 12 64 Lines for Ladder Programming 250 250 ORDERING INFORMATION ASR-B120AC 110 - 240 VAC, Altech Smart Relay, Base Module ASR-B24DC 12 - 24 VDC, Altech Smart Relay, Base Module ASR-E120AC 110 - 240 VAC, Altech Smart Relay, Extension Module ASR-E24DC ASR-C485-120AC ASR-C485-24DC ASR-MC ASR-RS232 12 - 24 VDC, Altech Smart Relay, Extension Module 110 - 240 VAC, Altech Smart Relay, RS 485 Communication Module 12 - 24 VDC, Altech Smart Relay, RS 485 Communication Module Memory Card RS 232 Serial Communication Cable ASR-USB USB Cable ASR-SOFT Software supplied on CD-ROM compatible with Windows 98, 2000, XP,Vista & 7. APPLICATIONS HVAC Controls • Energy management • Heating Control • Cooling systems • Ventilation systems • Air conditioning systems Transport facilities • Conveyor systems • Hoisting platforms • Elevators • Silo facilities • Livestock feed delivery Machine Controls • Motor, pump and valve controls • Air compressors • Exhaust and filtering systems • Water-treatment plants • Woodworking machinery • Etching and purification plants Operational Monitoring Systems • Access control • Vehicle control monitoring • Alarm systems • Level limit monitoring • Traffic light control systems • Baggage handling Residential and Commercial Building Services Other Applications • Solar-electric systems • Marine applications • Harsh environments • Display panels and traffic control signs • Interior and exterior lighting control • Door/gate control • Shutter, sun blind and awning control • Irrigation system control 16 Altech Corp. USA : 35 Royal Road, Flemington, NJ 08822 908.806.9400 USA www.altechcorp.com/smartrelay Altech Corp. Mexico : Adolfo López Mateos No. 1321-A Santa Cruz Buenavista Puebla, Pue 72154 Mexico 01 (222) 226 70 37 01 (222) 226 70 47 www.altechmexico.com