drc 3

DIN Rail Mount
'DWDVKHHW
DRC Series
• 7.6 Amp AC Semiconductor Motor Controller
• Load voltage range up to 600VAC
• Fits standard 35mm DIN Rail
• LED input status indicator
• AC or DC control
• Zero Voltage (resistive loads) or instantaneous (inductive loads) turn-on output
• C-UL-US Listed, CCC Certified, IEC Rated, CE & RoHS Compliant, Horsepower Rated
• Built-in Overvoltage Protection
• Ultra-efficient thermal management design (Patented)
Start / Stop
Reversing
Solicon DRC3 Series are Solid State Contactors intended for
frequently switching on and off three phase loads up to 5 HP, 600
VAC 7.6 Amps. They are available in both contactor versions
DRC3P and reversing contactor versions DRC3R.
instantaneous change of direction is commanded, then it will
delay the direction change by 100msec in order to prevent
simultaneous forward and reverse operations.
All the models of Solicon DRC3 Series combine the benefits and
advantages of a solid state contactor with the functionality and
simplicity of use of an electromechanical contactor thanks to the
proprietary thermal management technology (Patented) and
complete electrical insulation (no grounding required); the
embedded auxiliary contacts, normally open and/or normally
closed, are intended to be used at 18-280VAC. Five different
control voltages are available in order to cover most applications.
All models include overvoltage protection.
The Solicon Contactor DRC3P is available in either instantaneous
turn-on (for Motor Control) or zero voltage turn-on (for Resistive
Loads). It is available in either 2 or 3 controlled leg versions. The
2 legs control version is particularly suitable for motor control
circuits where the neutral conductor is not utilized.
The Solicon Reversing Contactor DRC3R includes an interlock
control that allows only off, forward and reverse operation in a
safe mode while providing high space saving; it switches
instantaneously upon application of the control voltage unless an
PRODUCT SELECTION
Control Voltage
Without Auxiliary Contact
1 NO+NC Auxiliary Conctat
2 NO Auxiliary Contact
230 VAC
120 VAC
48 VAC/DC
24 VAC/DC, 24 VAC
24 VDC
DRC3P48A400, DRC3R48A400
DRC3P48B400, DRC3R48B400
DRC3P48C400, DRC3R48C400
DRC3P48D400, DRC3R48D400
DRC3R48E400
DRC3P48A411
DRC3P48B411
DRC3P48C411
DRC3P48D411
DRC3P48A420, DRC3R48A420
DRC3P48B420, DRC3R48B420
DRC3P48C420, DRC3R48C420
DRC3P48D420, DRC3R48D420
DRC3R48E420
AVAILABLE OPTIONS
Operating Voltage
40: 400 VAC
(3R function only)
48: 480 VAC
60: 600 VAC
(3P function only)
Series
DRC
3P
48
Function
3P: Contactor
3R: Reversing Contactor
D
Load Current per Phase
4: 7.6 Amp FLA
(x2 Controlled Legs
& 3R function);
4.8 Amp FLA
(x3 Controlled Legs only)
4
Control Voltage
A: 208-265 VAC
B: 90-140 VAC
C: 36-55 VAC/DC
D: 18-30 VAC/DC
(3P function only)
18-30 VAC
(3R function only)
Required for valid part number
E: 18-30 VDC
For options only and not required for valid part number
(3R function only)
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.
00
Switching Mode
(3P function only)
Blank: Zero Voltage Turn-On
R: Instantaneous Turn-On
R
2
Controlled Legs
Auxiliary Contacts,
(3P function only)
N.O. - N.C.
Blank: 3 Controlled Legs
00: Not included
2: 2 Controlled Legs
11: 1 Solid State Auxiliary
Contact, Normally Open;
1 Solid State Auxiliary
Contact, Normally Closed
(3P function only)
20: 2 Solid State Auxiliary
Contacts, Normally Open
DIN Rail Mount
'DWDVKHHW
OUTPUT SPECIFICATIONS (1)
DRC3P48x4x
DRC3P48x4x2
DRC3P60x4x
DRC3P60x4x2
DRC3R40x4x
DRC3R48x4x
Operating Voltage (47-63Hz) [Vrms]
48-530
Transient Overvoltage [Vpk] (2)
1200
Maximum Off-State Leakage Current @ Rated Voltage [mArms]
3.0
Maximum Off-State dv/dt @ Maximum Rated Voltage [V/μsec]
500
Load Current, General Use UL508 /AC51 @40°C [Arms] (3)
5
Load Current, Motor Controller UL508 /AC-53a @480VAC [Arms] (3)
4.8
Minimum Load Current [Arms]
0.15
Maximum Surge Current [Apk] 1 Cycle 60Hz
750
Maximum Surge Current [Apk] 1 Cycle 50Hz
716
2330
Maximum I2t for Fusing (8.33msec)[A2sec]
2560
Maximum I2t for Fusing (10msec)[A2sec]
Maximum On-State Voltage Drop @ Rated Current [Vpk]
1.35 per channel
Minimum Power Factor (with Maximum Load)
0.5
Ratings according to UL 508/IEC60947-4-2 [HP/kW]: 240 VAC
1/.75
Ratings according to UL 508/IEC60947-4-2 [HP/kW]: 400 VAC
2/1.5
Ratings according to UL 508/IEC60947-4-2 [HP/kW]: 480 VAC
3/2.2
Motor Ratings @ 600 VAC [HP/kW]
-
Description
48-530
1200
3.0
500
7.6
7.6
0.15
750
716
2330
2560
1.35 per channel
0.5
2/1.5
3/2.2
5/3.7
-
48-600
1200
1.0
500
5
4.8
0.15
750
716
2330
2560
1.35 per channel
0.7
1/.75
2/1.5
3/2.2
3/2.2
48-600
1200
1.0
500
7.6
7.6
0.15
750
716
2330
2560
1.35 per channel
0.7
2/1.5
3/2.2
5/3.7
5/3.7
48-415
1200
5.5
500
7.6
7.6
0.15
750
716
2330
2560
1.5 per channel
0.5
2/1.5
3/2.2
-
48-510
1600
5.5
500
7.6
7.6
0.15
625
597
1621
1779
1.5 per channel
0.5
2/1.5
3/2.2
5/3.7
-
INPUT SPECIFICATIONS (1)
Description
Option A
Option B
Option C
Option D
Option E
Control Voltage Range (4)
Minimum Turn-On Voltage (5)
Must Turn-Off Voltage
Minimum Input Current (for on-state) [mA]
Maximum Input Current [mA]
Nominal Input Impedance [Ohms]
Maximum Delay to Turn-On [msec] (6)(7)
Maximum Turn-Off Time [msec] (8)
208-265 VAC
208 VAC
40 VAC
6.1
8
33k
30
40
90-140 VAC
90 VAC
10 VAC
7.5
13
12.5k
30
40
36-55 VAC / VDC
36 VAC / VDC
4 VAC / VDC
12
20
3k
30
40
18-30 VAC / VDC
18 VAC / VDC
4 VAC / VDC
12.5
32
0.93k
20
30
18-30 VDC
18 VDC
4 VDC
12.5
32
0.93k
100 ± 30
20
SOLID STATE AUXILIARY CONTACTS (1)
Description
Normally Open Suffix 2x,1x
Normally Closed Suffix x1
18-280
600
1
5
40
38
6.7
7.2
0.1
500
30
40
18-280
600
1
5
40
38
6.7
7.2
5 mA
500
80
40
Operating Voltage Range (47-63Hz) [Vrms] (9)
Transient Overvoltage [Vpk]
Maximum Load Current [Arms]
Minimum Load Current [mA]
Maximum Surge Current [Apk] 1 Cycle 60Hz
Maximum Surge Current [Apk] 1 Cycle 50Hz
Maximum I2t for Fusing (8.33msec)[A2sec]
Maximum I2t for Fusing (10msec)[A2sec]
Maximum Off-State Leakage Current @ Rated Voltage [mArms]
Minimum Off-State dv/dt @ Maximum Rated Voltage [V/μsec]
Maximum Delay to Turn-On [msec] (6)
Maximum Turn-Off Time [msec] (7)
GENERAL SPECIFICATIONS (1)
Description
Dielectric Strength, Input/Output/Base (50/60Hz) (10)
Minimum Insulation Resistance (@ 500 VDC)
Maximum Capacitance, Input/Output
Ambient Operating Temperature Range (11)
Ambient Storage Temperature Range
Weight (typical)
Housing Material
Housing Color
LED Status Indicator (color) (12)
Short Circuit Current Rating (13)
MTBF (Mean Time Between Failures) at 40°C ambient temperature (14)
MTBF (Mean Time Between Failures) at 60°C ambient temperature (14)
Pollution Degree
Protection Degree (15)
Humidity
Control and Auxiliary Contact Terminal Screw Torque Range (in-lb/Nm)
Load Terminal Screw Torque Range (in-lb/Nm)
Input Terminal Wire Capacity
Output Terminal Wire Capacity
Parameters
3750 Vrms
109 Ohms
20 pF
-30 to 80 °C
-40 to 100 °C
2 Controlled Legs (6.9 oz [197 g]) / 3 Controlled Legs (8.0 oz [228 g])
UL94 V-0
Black and Light Gray
Forward (Green) / Reverse (Amber)
100kA
1,398,000 hours (159 years)
390,000 hours (44 years)
2
IP20
85% non-condensing
12 / 1.36
15 / 1.7
18-12 AWG (IEC 1-4 mm2) (stranded /solid)
18-10 AWG (IEC 1-6 mm2 ) (stranded /solid)
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.
DIN Rail Mount
'DWDVKHHW
MECHANICAL SPECIFICATIONS (1)
Tolerances: ±0.02 in / 0.5 mm
All dimensions are in: inches [millimeters]
3.51
[89]
2.91
[73.9]
0.23
[5.8]
A3
13
23
A1
DRC3
1.23
[31.3]
3.41
[86.7]
IND. CONT. EQ.
2.58
[65.5]
2.29
[58.3]
XXXX
1.68
[42.7]
INPUT
STATUS
14
24
A2
3.76
[95.6]
1.78
[45.3]
TERMINAL SCREW TYPE
Top/Bottom view (Fig. 1)
THERMAL DERATE INFORMATION (16)
DRC3P (2 controlled legs) & DRC3R
Single unit (17)
Multiple units
DRC3P (3 controlled legs)
Single unit (17)
Multiple units
8
6
7
Load Current (Amps)
Load Current (Amps)
5
4
3
2
1
6
5
4
3
2
1
0
0
0
10
20
30
40
50
60
70
80
Ambient Temperature (ºC)
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.
0
10
20
30
40
50
Ambient Temperature (ºC)
60
70
80
Fig. 1
DIN Rail Mount
'DWDVKHHW
SWITCHING FREQUENCY/LOAD CHARACTERISTIC FOR ALL DEVICES
IL : Load Operating Current
IR : Rated Full Load Current [FLA]
ID : Direct-On-Line Inrush Current
tL : Load Operating Current Time
tD : Direct-On-Line Inrush Current Time
tC : Cycle Time
tOn : On Time
tOff : Off Time
ID
IR
IL
tD
tL
tOn
tOff
tC
MAXIMUM ALLOWABLE NUMBER OF STARTS PER HOUR DEPENDING ON THE STARTING
TIME tD AND THE ON PERIOD tOn (as for standard IEC 60947-4-2) FOR ALL DEVICES
Without overload relay (limit given by the contactor itself)
Table 1
Table 2
Table 3
Table 4
• High inrush current (ID/IR = 4 to 7.2)
• Full load (IL/IR= 1)
• High inrush current (ID/IR = 4 to 7.2)
• 60% load (IL/IR= 0.6)
• Low inrush current (ID/IR < 4 )
• Full load (IL/IR= 1)
• Low inrush current (ID/IR < 4 )
• 60% load (IL/IR= 0.6)
tOn (sec)
tOn (sec)
tD (sec)
tOn (sec)
tD (sec)
tOn (sec)
tD (sec)
0.1
1
10
100
0.1
1
10
100
0.1
1
10
100
0.1
1
10
0.05
5000
2700
350
35
0.05
6000
3550
350
35
0.05
7450
3200
350
35
tD (sec)
0.05
9000
3550
350
100
35
0.1
3200
1950
350
35
0.1
4100
3000
350
35
0.1
4050
2100
350
35
0.1
5400
3550
350
35
0.2
-
950
320
35
0.2
-
1300
350
35
0.2
-
1200
350
35
0.2
-
1700
350
35
0.4
-
500
280
35
0.4
-
700
320
35
0.4
-
650
320
35
0.4
-
850
350
35
0.8
-
290
160
35
0.8
-
400
320
35
0.8
-
350
280
35
0.8
-
560
350
35
1.6
-
-
110
30
1.6
-
-
125
35
1.6
-
-
180
35
1.6
-
-
240
35
3.2
-
-
75
25
3.2
-
-
90
35
3.2
-
-
90
35
3.2
-
-
180
35
With overload relay (limit given by the overload relay itself)
Table 5
Table 6
Table 7
Table 8
• High inrush current (ID/IR = 4 to 7.2)
• Full load (IL/IR= 1)
• High inrush current (ID/IR = 4 to 7.2)
• 60% load (IL/IR= 0.6)
• Low inrush current (ID/IR < 4 )
• Full load (IL/IR= 1)
• Low inrush current (ID/IR < 4 )
• 60% load (IL/IR= 0.6)
tOn (sec)
tOn (sec)
tOn (sec)
tOn (sec)
tD (sec)
0.1
1
10
100
tD (sec)
0.1
1
10
100
tD (sec)
0.1
1
10
100
tD (sec)
0.1
1
10
100
0.05
2200
1650
330
30
0.05
2800
1800
320
35
0.05
5150
2800
260
35
0.05
5600
3200
350
35
0.1
1500
1000
280
28
0.1
1700
1300
310
32
0.1
2850
1920
250
34
0.1
3200
2700
350
35
0.2
-
550
255
26
0.2
-
650
290
30
0.2
-
1100
250
33
0.2
-
1400
350
35
0.4
-
250
150
24
0.4
-
300
200
26
0.4
-
600
200
32
0.4
-
700
350
35
0.8
-
80
60
20
0.8
-
200
90
25
0.8
-
320
200
30
0.8
-
350
280
35
1.6
-
-
40
16
1.6
-
-
65
25
1.6
-
-
120
25
1.6
-
-
170
35
3.2
-
-
3.2
-
-
-
-
3.2
-
-
75
20
3.2
-
-
80
25
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.
DIN Rail Mount
'DWDVKHHW
SHORT CIRCUIT AND OVERLOAD PROTECTION FOR ALL DEVICES
(Conforming to the IEC60947-4-2 and UL508)
IEC standard 60947-4-1 make a distinction between two different types of protection, (called “coordination”), which are designated types “1” and "2".
Any short-circuit that occurs is cleared safely by either type of coordination.
The only difference between the 2 categories concerns the extent of the SSR damage caused by the short-circuit.
Type "1" coordination requires that in the event of a short-circuit, the Solid State Contactor does not endanger personnel or installations,
but permanent damage to the SSC is permissible. In this case the SSC may need to be replaced. For this type of co-ordination,
the use of fusing or circuit breakers adequate to protect the system and wiring from short circuits, (but not specifically considering SSC protection), can be used.
Type "2" coordination requires that under a short-circuit condition, the circuit is interrupted, the SSC does not endanger persons or installations,
and in addition the SSR will be able to operate after the fault condition is repaired.
Type of coordination 1
Protection by Thermal Magnetic Circuit Breaker (18)
Nominal Motor
Current
Thermal Magnetic Circuit Breaker
(Schneider Electric)
Solid State Contactor
2 controlled legs
Solid State Contactor
3 controlled legs
Solid State Contactor
Reversing
0.40-0.63 A
GV2ME04 / GV2P04
DRC3Pxx4x2
DRC3Pxx4x
DRC3Rxx4x
0.63-1 A
GV2ME05 / GV2P05
DRC3Pxx4x2
DRC3Pxx4x
DRC3Rxx4x
1-1.6 A
GV2ME06 / GV2P06
DRC3Pxx4x2
DRC3Pxx4x
DRC3Rxx4x
1.6-2.5 A
GV2ME07 / GV2P07
DRC3Pxx4x2
DRC3Pxx4x
DRC3Rxx4x
2.5-4 A
GV2ME08 / GV2P08
DRC3Pxx4x2
DRC3Pxx4x
DRC3Rxx4x
4-6.3 A
GV2ME10 / GV2P10
DRC3Pxx4x2
DRC3Pxx4x (up to 4.8A)
DRC3Rxx4x
6.3-10 A
GV2ME14 / GV2P14
DRC3Pxx4x2 (up to 7.6A)
-
DRC3Rxx4x (up to 7.6A)
Protection by overload relays and fuses (18)
Nominal Motor
Current
Overload Relay
(Schneider Electric)
Class gG fuses
(example from Littlefuse)
Solid State Contactor
2 controlled legs
Solid State Contactor
3 controlled legs
Solid State Contactor
Reversing
0.40-0.63 A
LRD04
CY14X51G16
DRC3Pxx4x2
DRC3Pxx4x
DRC3Rxx4x
0.63-1 A
LRD05
CY14X51G16
DRC3Pxx4x2
DRC3Pxx4x
DRC3Rxx4x
1-1.6 A
LRD06
CY14X51G25
DRC3Pxx4x2
DRC3Pxx4x
DRC3Rxx4x
1.6-2.5 A
LRD07
CY14X51G25
DRC3Pxx4x2
DRC3Pxx4x
DRC3Rxx4x
2.5-4 A
LRD08
CY14X51G25
DRC3Pxx4x2
DRC3Pxx4x
DRC3Rxx4x
4-6.3 A
LRD10
CY14X51G40
DRC3Pxx4x2
DRC3Pxx4x(up to 4.8A)
DRC3Rxx4x
6.3-10 A
LRD14
CY14X51G40
DRC3Pxx4x2 (up to 7.6A)
-
DRC3Rxx4x (up to 7.6A)
Type of coordination 2
Protection by overload relays and fuses (18)
Nominal Motor Overload Relay
Semiconductor fuses with less than 1621A2S
Solid State Contactor
(Schneider Electric) Littlefuse SIBA (Cylindric) Ferraz (Cylindric) 2 controlled legs
Current
Solid State Contactor
3 controlled legs
Solid State Contactor
Reversing
DRC3Rxx4x
0.40-0.63 A
LRD04
LA50QS40-4
50.058.06.40
A093909
DRC3Pxx4x2
DRC3Pxx4x
0.63-1 A
LRD05
LA50QS40-4
50.058.06.40
A093909
DRC3Pxx4x2
DRC3Pxx4x
DRC3Rxx4x
1-1.6 A
LRD06
LA50QS40-4
50.058.06.40
A093909
DRC3Pxx4x2
DRC3Pxx4x
DRC3Rxx4x
1.6-2.5 A
LRD07
LA50QS40-4
50.058.06.40
A093909
DRC3Pxx4x2
DRC3Pxx4x
DRC3Rxx4x
2.5-4 A
LRD08
LA50QS40-4
50.058.06.40
A093909
DRC3Pxx4x2
DRC3Pxx4x
DRC3Rxx4x
4-6.3 A
LRD10
LA50QS40-4
50.058.06.40
A093909
DRC3Pxx4x2
DRC3Pxx4x (up to 4.8A)
DRC3Rxx4x
6.3-10 A
LRD14
LA50QS40-4
50.058.06.40
A093909
DRC3Pxx4x2 (up to 7.6A)
-
DRC3Rxx4x (up to 7.6A)
Note: All the Schneider Electric Thermal magnetic circuit breakers GV2 family (GV2ME and GV2P) is fully mechanical compatible with the DRC contactor using the GV2AF3 connection block.
All the Schneider Electric Overload relay LRD family is fully mechanical compatible with the DRC contactor without the need of any adapter.
The DRC Series can accept the LAD7C1 module (pre-wiring kit allowing direct connection of the NC contact of relay LRD to the contactor)
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.
DIN Rail Mount
'DWDVKHHW
WIRING AND BLOCK DIAGRAM
DRC3P CONTACTOR (19)
DRC3Pxx400
DRC3Pxx411
DRC3Pxx420
48-530 VAC, 50-60 Hz
48-600 VAC, 50-60 Hz
L1
L2
L3
L1
L2
L3
Short circuit and overload
current protection (see page 5)
L3
A1
DRC3PXXX400XX
IND. CONT. EQ.
CONTROL
INPUT
XXXX
INPUT
STATUS
A2
T1
T2
T1
T3
T2
T3
L1
T2
/>
L2
13
/>
L3
21
A1
DRC3PXXX411XX
IND. CONT. EQ.
CONTROL
INPUT
XXXX
INPUT
STATUS
14
T1
Motor Controller /
AC-53a Application
T1
/>
22
A2
T2
T1
T3
T2
T3
2nd Auxiliary Contact (18 - 280 VAC) Normally Open
L2
/>
1st Auxiliary Contact (18 - 280 VAC) Normally Open
/>
2nd Auxiliary Contact (18 - 280 VAC) Normally Closed
L1
/>
1st Auxiliary Contact (18 - 280 VAC) Normally Open
/>
General Use /
AC-51 Application
T1
T3
T2
L1
13
DRC3P
L1
L2
L3
A1
L1
L2
L3
A1
T1
T2
T3
A2
T1
T2
T3
A2
DRC3Pxx400
DRC3Pxx420
(2 Normally Open)
Auxiliary Contacts
13 23
14
24
XXXX
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.
22
INPUT
STATUS
14
T1
24
T2
DRC3Pxx411
(1 Normally Open - 1 Normally Closed)
Auxiliary Contacts
13 21
14
A1
CONTROL
INPUT
T1
Without Auxiliary Contacts
23
IND. CONT. EQ.
M
(2 controlled legs model)
Main Circuit
L3
DRC3PXXX420XX
3
DRC3P
/>
L2
T3
(3 controlled legs model)
Main Circuit
/>
A2
T3
T2
T3
DIN Rail Mount
'DWDVKHHW
DRC3R REVERSING CONTACTOR (20)
DRC3Rxx400
DRC3Rxx420
48-415 VAC, 50 - 60 Hz
48-510 VAC, 50 - 60 Hz
L1
L2
L3
L1
L2
L3
Short circuit and overload current
protection (see page 5)
/>
L2
L3
A3
CONTROL
INPUT
(Reverse)
/>
A1
CONTROL
INPUT
(Forward)
DRC3RXXX400XX
IND. CONT. EQ.
XXXX
INPUT
STATUS
A2
T1
T2
T1
CONTROL
INPUT
(Common)
T3
T2
2nd Auxiliary Contact (18 - 280 VAC) Normally Open
L1
/>
1st Auxiliary Contact (18 - 280 VAC) Normally Open
/>
L1
CONTROL
INPUT
(Reverse)
T1
T2
/>
L2
A3
L3
13
23
A1
CONTROL
INPUT
(Forward)
DRC3RXXX420XX
IND. CONT. EQ.
XXXX
INPUT
STATUS
14
T1
Motor Controller /
AC-53a Application
T3
/>
24
A2
T2
T1
CONTROL
INPUT
(Common)
T3
T2
T3
T3
M
3
Overload current
protection needs to
be considered
DRC3R
Reverse
Forward
L1
L2
L3
A1
T1
T2
T3
A2
Forward
13
14
Reverse
23
L1
L2
T1
T2
L3
A3
24
DRC3Rxx420
models only
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.
T3
A2
DIN Rail Mount
'DWDVKHHW
TIMING DIAGRAM
Input/Output
1
TIMING DIAGRAM FOR DRC3R
3
4
5
6
2
7
8
9
10
Input A1
Input A3
FWD Direction
100 msec
100 msec
100 msec
REV Direction
STEP
interlock
DESCRIPTION
1, 4, 10
Initial Condition. A1 & A3 open
2
A1 is activated, FWD Output waits for 100msec
3, 9
FWD direction is activated
4
A1 changes to off. FWD Output is disabled at the same time
5
A3 is activated. REV Outputs waits for 100msec
6
REV direction is On
7
Interlock fuction is activated. REV is disabled due to A1 & A3 both being active
8
A3 is open, A1 is closed, activation delayed 100msec
AGENCY APPROVALS
Certification in accordance with:
United States Standard for Industrial Control Equipment - UL 508 and
Canadian Standard Association for Industrial Control Equipment – C22.2 No. 14.
China Compulsory Certification for AC Semiconductor Motor Controller-GB14048.6-2008
DRC3 series conforms to the harmonized EN standard EN/IEC 60947-4-2
Electromagnetic Compatibility:
IEC 61000-4-2 : Electrostatic Discharge – Level 3
IEC 61000-4-4 : Electrically Fast Transients – Level 3
IEC 61000-4-5 : Electrical Surges – Level 3
Vibration Resistance:
IEC 60068-2-6 : Amplitude Range 10-55 Hz, Displacement 0.75mm
Shock Resistance:
IEC 60068-2-27 : Peak Acceleration 15g, Duration11msec.
E116949
s
(Only DRCx40x4x & DRCx48x4x)
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.
Input A1
Input A3
FWD
REV
Open
Open
Off
Off
Close
Open
On
Off
Open
Close
Off
On
Close
Close
Off
Off
DIN Rail Mount
'DWDVKHHW
ACCESSORIES FOR ALL DEVICES
Recommended Accessories
Motor Nominal
Current
Bimetal
Overload Relay
Electronic
Overload Relay
Thermal Magnetic Circuit
Breaker (Push Button)
Thermal Magnetic Circuit
Breaker (Selector)
0.40 - 0.63 A
LRD04
LR97 D015xx
GV2ME04
GV2P04
0.63 - 1 A
LRD05
LR97 D015xx
GV2ME05
GV2P05
1 - 1.6 A
LRD06
LR97 D07xx
GV2ME06
GV2P06
1.6 - 2.5 A
LRD07
LR97 D07xx
GV2ME07
GV2P07
2.5 - 4 A
LRD08
LR97 D07xx
GV2ME08
GV2P08
4 - 6.3 A
LRD10
LR97 D25xx
GV2ME10
GV2P10
6.3 - 10 A
LRD14
LR97 D25xx
GV2ME14
GV2P14
Fully compatible with
Schneider Electric
thermal overload
relays &
thermal magnetic
circuit breakers
Note: All the Schneider Electric Thermal magnetic circuit breakers GV2 family (GV2ME and GV2P) is fully mechanical compatible with the DRC contactor using the GV2AF3 connection block.
All the Schneider Electric Overload relay LRD family is fully mechanical compatible with the DRC contactor without the need of any adapter.
The DRC Series can accept the LAD7C1 module (pre-wiring kit allowing direct connection of the NC contact of relay LRD to the contactor)
When the LAD7C1 module is used, the common terminal for the control input is not anymore the ”A2” terminal of DRC but it is the “96” terminal of the overload relay.
ID Marker Strips
CNLB, CNLN, CNL2
Packages of 10 plastic strips comprising 10
individual markers which can be placed for easy
identification during the use of multiple units.
Numbered
N
b d 1 to 10 S
Strips
i
Part no.: CNLN
Blank Strips
Part no.: CNLB
Numbered 11 to 20 Strips
Part no.: CNL2
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.
DIN Rail Mount
'DWDVKHHW
GENERAL NOTES
(1) All parameters at 25°C unless otherwise specified.
(2) For DRC3P relay will self trigger between 900-1200V, Not suitable for capacitive loads.
(3) Mounted in the Vertical position.
(4) On DRC3R models the range for option D is 18-30 VAC.
(5) For low temperature operation consider nominal control voltage.
(6) For DRC3R the turn-on time is 100msec ± 30msec.
(7) For DRC3P Instantaneous Turn-on, Option D, turn-on time is 4 msec.
(8) When is complete removed the control signal. For DRC3R the turn-off time is 20msec.
(9) Operating voltage range 18-30 VDC is also valid when used to latch the DRC contactor control input.
(10) For input to auxiliary output the dielectric strength is 2.5kV.
(11) UL approval up to 40°C surrounding temperature.
(12) Reverse Amber Indicator is for DRC3R models only.
(13) 100kA, 480VAC, when protected with CC class fuses rated 600VAC, 20A or equivalent.
(14) All parameters at 50% power rating and 100% duty cycle (contact Crydom tech support for detailed report).
(15) IP20 rating is not associated with the UL approval.
(16) Derate information is valid when DCR contactors are used with or without accessories, installed on top and/or bottom.
(17) Minimum spacing to obtain max. current is 22mm between adjacent units.
(18) Combinations of these Protective Devices and Solid State Contactor have not been evaluated by UL.
(19) For DRC3P models external loads can be connected in parallel to the control input.
(20) DRC3R internal safety interlock circuit prevents the product to work if any leakage current is present in the control input currently not enabled.
Rev. 020916
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.
DIN Rail Mount
'DWDVKHHW
DANGER / PELIGRO / DANGER /GEFAHR / PERICOLO / ླ၃
HAZARD OF
ELECTRIC
SHOCK,
EXPLOSION,
OR ARC FLASH.
x Disconnect all
power before
installing or
working with
this equipment.
x Verify all
connections
and replace all
covers before
turning on
power.
Failure to follow
these
instructions will
result in death
or serious injury.
RIESGO DE
DESCARGA
ELECTRICA O
EXPLOSION.
x Desconectar
todos los
suministros de
energia a este
equipo antes
de trabajar
con este equipo.
x Verificar todas
las conexiones
y colocar todas
las tapas antes
de energizer
el equipo.
El
incumplimiento
de estas
instrucciones
puede provocar
la muerte o
lesiones serias.
RISQUE DE
DESCHARGE
ELECTRIQUE
OU EXPLOSION
x Eteindre
toutes les
sources
d'énergie de
cet appareil
avant de
travailler
dessus de cet
appareil
x Vérifier tous
connections, et
remettre tous
couverts en
olace avant de
mettre sous
De non-suivi de
ces instructions
provoquera la
mort ou des
lésions sérieuses
sérieuses.
GEFAHR EINES
ELEKTRISCHE
N SCHLAGES
ODER EINER
EXPLOSION.
x Stellen Sie
jeglichen
Strom ab, der
dieses Gerät
versorgt, bevor
Sie an dem
Gerät Arbeiten
durchführen
x Vor dem
Drehen auf
Energie alle
Anschlüsse
überprüfen
und alle
Abdeckungen
ersetzen.
Unterlassung
dieser
Anweisungen
können zum
Tode oder zu
schweren
Verletzungen
führen.
RISCHIO DI
SCOSSA
ELETTRICA O
DELL’ESPLOSIONE.
x Spenga tutta
l'alimentazione
che fornisce
questa
apparecchiatura
prima di lavorare
a questa
apparecchiatura
٪ሞ‫ۉ‬ऍĂ
Ԗቊई‫ࢷۉ‬
෻ຮླ၃
x
ሞ֡ፕُย
Ԣኮമ൩ံ
࠲Կ‫ۉ‬ᇸă
ැփፏ๰ኄၵຫ௽Lj
੗ీࣷ‫ڞ‬ዂჹዘ‫ڦ‬
ටวฅ࡞ฯ዁ຶྨă
x Verificare tutti
i collegamenti
e sostituire
tutte le coperture
prima
dell’accensione
L'omissione di
queste istruzioni
provocherà la
morte o
lesioni serie
WARNING / AVERTISSEMENT / WARNUNG /ADVERTENCIA / AVVERTENZA / 警告
RISK OF MATERIAL DAMAGE AND HOT
ENCLOSURE
RISQUE DE DOMMAGE MATERIEL ET DE
SURCHAUFFE DU BOITIER
GEFAHR VON MATERIALSCHÄDEN UND
GEHÄUSEERHITZUNG
• The product's side panels may be hot, allow
the product to cool before touching.
• Follow proper mounting instructions including
torque values.
• Do not allow liquids or foreign objects to enter
this product.
• Les panneaux latéraux du produit peuvent être
chauds. Laisser le produit refroidir avant de le
toucher.
• Respecter les consignes de montage, et
notamment les couples de serrage.
• Ne pas laisser pénétrer de liquide ni de corps
étrangers à l'intérieur du produit.
• Die Seitenwände können heiß sein. Lassen Sie
das Produkt abkühlen, bevor Sie es berühren.
• Beachten Sie die Montageanweisungen,
• Führen Sie keine Flüssigkeiten oder
Fremdkörper in das Produkt ein.
Le non-respect de cette directive peut entraîner,
Failure to follow these instructions can result in des lésions corporelles graves ou des
serious injury, or equipment damage.
dommages matériels.
Die Nichtbeachtung dieser Anweisung kann
Körperverletzung oder Materialschäden
zur Folge haben.
RIESGO DE DAÑOS MATERIALES Y DE
SOBRECALENTAMIENTO DE LA UNIDAD
RISCHIO DI DANNI MATERIALI E D'INVOLUCRO
CALDO
֌ଙ໦࣋ࢅߛ࿒ྔ੕‫ླڦ‬၃Ⴀ
• Los paneles laterales del producto pueden
estar calientes. Esperar que el producto se
enfríe antes de tocarlo.
• Respetar las instrucciones de montaje, y en
particular los pares de apretado.
• No dejar que penetren líquidos o cuerpos
extraños en el producto.
• I pannelli laterali dell'apparecchio possono
scottare; lasciar quindi raffreddare il prodotto
prima di toccarlo.
• Seguire le istruzioni di montaggio corrette.
• Non far entrare liquidi o oggetti estranei in questo
apparecchio.
Si no se respetan estas precauciones pueden
producirse graves lesiones, daños materiales.
La mancata osservanza di questa precauzione può
causare gravi rischi per l'incolumità personale o
danni alle apparecchiature.
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.
•!ׂ೗‫ڦ‬ᅃ֨௬ӱ੗ీ࢔ඤLjሞഄૐඐമ൩
!փᄲ‫ة‬ಸă
•!ፏቷኟඓ‫ڦ‬Ҿጎຫ௽LjԈઔ౦ਈኵă
•!൩ကඟᅂ༹तഄ໱ᅴ࿿৊෇Ԩׂ೗ă
සփీኟඓኴႜኄၵ֡ፕຫ௽Lj
टᆶ੗ీሰ‫ׯ‬ჹዘට༹ฅ࡞ईኁยԢ‫ڦ‬໦࣋ă
DIN Rail Mount
'DWDVKHHW
ANNEX - ENVIROMENTAL INFORMATION
The environmental information disclosed in this annex including the EIP Pollution logo are in compliance with People’s Republic of China
Electronic Industry Standard SJ/T11364 – 2006, Marking for Control of Pollution Caused by Electronic Information Products.
Part
Name
Toxic or hazardous Substance and Elements
Lead
(Pb)
Mercury
(Hg)
Cadmium
(Cd)
Hexavalent
Chromium
(Cr (VI))
Polybrominated
biphenyls
(PBB)
Polybrominated
diphenyl ethers
(PBDE)
Semiconductor die
Solder
䱴Ԧ⧟‫ؑ؍‬᚟
此附件所标示的包括电子信息产品污染图标的环保信息符合中华人民共和国电子行业标准 SJ/T11364 - 2006,
电子信息产品污染控制标识要求。
䜘Ԧ
਽〠
䫵
⊎
䭹
ᴹ∂ᴹᇣ⢙䍘ᡆ‫ݳ‬㍐
‫ޝ‬ԧ䬜
ཊⓤ㚄㤟
(Pb)
(Hg)
(Cd)
(Cr (VI))
ॺሬփ㣟⡷
✺᧕⛩
50
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.
(PBB)
ཊⓤҼ㤟䟊
(PBDE)