Operating Instructions

Vishay Electronic GmbH
Hofmark-Aich-Str.36
D-84030 Landshut
Telefon +49 871 86-0
www.vishay.com
Document number: 13172 - Rev. 01
_________________________________________________________________________________________________________
Unbalance protection relay
ESTAsym CPR
Operating instructions
_____________________________________________
QUALITY MANAGEMENT
Certified by VDE according to
DIN EN ISO 9001
Reg. No. 2556/QM/03.94
ESTAsym CPR
Doc No.: 13172 - Rev. 01
Operating instructions
Page 2 of 22
Revision history
Date
Name
Revision
Change
25.08.11
drt
00
initial document release
24.11.11
brm
01
update of content
ESTAsym CPR
Operating instructions
Doc No.: 13172 - Rev. 01
Page 3 of 22
Content
1
GENERAL ............................................................................................................................................. 4
2
APPLICATION ...................................................................................................................................... 6
2.1
Unbalance monitoring voltage .............................................................................................................. 6
2.2
Unbalance monitoring current ............................................................................................................... 6
3
OPERATION ......................................................................................................................................... 7
3.1
Power supply ........................................................................................................................................ 7
3.2
Inputs .................................................................................................................................................... 7
3.3
Outputs ................................................................................................................................................. 8
3.4
User Interface ....................................................................................................................................... 9
4
MENUS ............................................................................................................................................... 11
4.1
Info ...................................................................................................................................................... 11
4.2
Setup ................................................................................................................................................... 12
4.3
Alarm ................................................................................................................................................... 19
5
TECHNICAL DATA ESTASYM CPR .................................................................................................. 20
6
MENU OVERVIEW ............................................................................................................................. 21
7
SETTINGS .......................................................................................................................................... 22
ESTAsym CPR
Operating instructions
Doc No.: 13172 - Rev. 01
Page 4 of 22
1 General
The ESTAsym CPR is designed to monitor medium and high voltage capacitors. The ESTAsym CPR can be
set to monitor current or voltage, selectable from the menu. The device can monitor two threshold levels for
Alarm / Trip. All thresholds / readings can be either a current or voltage value or a % setting of the maximum
value. Once the Alarm or Trip level is reached the appropriate relay will operate, after the programmed delay
time has elapsed. Both relays can be programmed to be held in the Alarm/Trip position until reset by the
user if required, alternatively they can be set to automatically reset if the fault is cleared. A further relay can
be used to operate when the Alarm/Trip or both Alarm+Trip have operated. The ESTAsym CPR can record
details of the last 5 Alarm and Trip operations. An natural unbalance (out of balance or asymmetrical value)
can be programmed into the device if required. This natural unbalance is subtracted from the measured
value and allows a more exactly setting of the thresholds.
The ESTAsym CPR is working with unsigned absolute values. Due to this always a positive value is shown.
Independent of the direction of the changing (meas. value increase / decrease) always a exceeding of the
threshold is given.
Simplified diagram
Measured value
– Natural unbalance
= Value
No
Comparator
Adjusted threshold
Value > limit
Alarm / Trip
Yes
Adjusted delay time
Delay time
No
for Alarm / Trip
Alarm / Trip
Relay 1 TRIP
Yes
Relay 2 ALARM
Monitoring blocked
Yes
via DI1 & DI2
Switch output relay
No
Relay 3 progr.
ESTAsym CPR
Operating instructions
Doc No.: 13172 - Rev. 01
Page 5 of 22
Important Information!
If the above sign appears besides a text passage in the manual the reader is strongly
!
advised to read the corresponding information, as it is very important for the device
usage! It can contain safety advice or other information for the correct handling of the
device.
If the information is disregarded, the device may be inoperable or even damaged!
ESTAsym CPR
Operating instructions
Doc No.: 13172 - Rev. 01
Page 6 of 22
2 Application
High- and medium voltage capacitors taken into operation must be monitored all the time. Most of these
capacitors are manufactured by using insulating oil for the dielectricum, which could catch fire in any case of
fail. To avoid this, the capacitors must be monitored to detect failures. This monitoring can be done either by
monitoring the unbalance current or unbalance voltage of capacitor groups.
However, this voltage / current may change in case of any failure of one capacitor, for instance caused by
any flash over the inside winded foils.
2.1
Unbalance monitoring voltage
2.2
Unbalance monitoring current
ESTAsym CPR
Operating instructions
Doc No.: 13172 - Rev. 01
Page 7 of 22
3 Operation
3.1
Power supply
The ESTAsym CPR is equipped with an power supply capable
for 40-250VAC 45-65Hz and 40-300VDC.
3.2
Inputs
3.2.1 Measurement input
The ESTAsym CPR has one voltage and one current input. Possible range for voltage input is 0,1-20V. The
measurement range for the current input 10mA-5A. The ESTAsym CPR supervises current or voltage. It’s
not possible to use both inputs parallel!
3.2.2 Blocking input
All monitoring functions can be blocked via inputs DI1 and DI2. Please check the referring manual item for
further information’s.
ESTAsym CPR
Doc No.: 13172 - Rev. 01
Operating instructions
3.3
Page 8 of 22
Outputs
The ESTAsym CPR has 4 relay outputs.
See 3.3.1
See 3.3.2
See 3.3.3
See 3.3.4
3.3.1 Trip relay
The trip relay operates change over contacts 11-12/14. Contacts 11-12 are normally closed and 11-14
normally open ( no trip condition). However, if the trigger value (voltage or current) for trip is exceeded for a
longer period than
, contacts 11-14 will close and 11-12 will open.
3.3.2 Alarm relay
The alarm relay operates change over contacts 21-22/24. Contacts 21-22 are normally closed and 21-24
normally open (no alarm condition). However, if the trigger value (voltage or current) for alarm is exceeded
for a longer period than
, contacts 21-24 will close and 21-22 will open.
3.3.3 Relay 3
The programmable relay can be set to work with alarm, trip or both. Under normal conditions (no trip, no
alarm) the contacts 31-32 are closed and 31-34 open. In an alarm / trip situation, contacts 31-34 will close
and 31-32 will open.
3.3.4 “In order” relay
The ESTAsym CPR has an self-supervision that monitors internal modules and software. If an internal fault
is detected, the relay will open contact 41-44 and closes 41-42. Additional to the relay contact the fault is
shown in the display “SyS” or “Prog”. The “in order” relay is also a sign of life contact, in case of missing
power supply the contacts 41-42 closes and contact 41-44 opens.
ESTAsym CPR
Operating instructions
3.4
Doc No.: 13172 - Rev. 01
Page 9 of 22
User Interface
3.4.1 Keys
Increase values, select menu items
Escape menu,
Enter menu,
move cursor left,
move cursor right,
push 3 sec to clear
confirmation of settings
trips/alarm
Decrease values, select menu items
3.4.2 Display
The right side of the display shows the actually chosen main menu
items.
The top line of the display shows the codes for submenus and
abbreviation for measurement values.
The second line of the display indicates the values for settings and
measurement values.
The bottom line of the display indicates which output relays are in
active state.
ESTAsym CPR
Operating instructions
Doc No.: 13172 - Rev. 01
Page 10 of 22
3.4.3 Input of numerical values
Whenever the ESTAsym CPR prompts for the input of a value, the routine will be the same:
A preset-value will be displayed with the first (highest) digit blinking. This digit can now be changed by use of
the and keys. Use the button to change to the next smaller digit. After changing, the next digit will be
also blinking and can now be altered just like the first one. When arriving the last digit, press the key once
more. This position allows to set multipliers M (Mega) or k (kilo). To store the value, press the key once
more, and the new value will be saved and used.
For the case that a adjusted value cannot be stored respectively another value is shown after confirmation
with button, it’s possible that the adjusted value is outside of the allowed range. For further information’s
about possible ranges, please check the table on the last page.
At any time, one can go back to the menu he came from without changing the value by pressing the ⊳ key.
In this case the modified value will not be used!
ESTAsym CPR
Doc No.: 13172 - Rev. 01
Operating instructions
Page 11 of 22
4 Menus
4.1
Info
The main menu "INFO” contains all information’s about the adjusted thresholds,
delay times for trip/alarm and the stored natural unbalance. In the Info menu it’s not
possible to change any values. To enter this menu use the button to select “Info”
and enter the menu with . Submenus can be selected by .
Display’s the stored value for “Natural Unbalance” for current respectively voltage.
Display’s the adjusted threshold for trip.
Display’s the adjusted time delay for trip
Display’s the adjusted threshold for alarm.
Display’s the adjusted time delay for alarm.
Display’s the software version of the device.
Display’s the state of digital input. Possible readings are:
The function to block the monitoring system via DI1 and DI2 is switched off.
Terminals DI1 and DI2 are open.
Terminals DI1 and DI2 are closed.
The monitoring system can be blocked via the DI. Possible settings are explained in “Setup” menu item
and
.
ESTAsym CPR
Doc No.: 13172 - Rev. 01
Operating instructions
4.2
Page 12 of 22
Setup
The main menu “Setup” is split into two menu levels.
Level 1 is the “start menu”, this contains settings to commissioning the ESTAsym CPR.
Level 2 is the expert menu this menu contains all possible settings. Because of the possible settings this
menu is protected by an separate password.
4.2.1
Start menu
Password 242
To enter this menu, use the button to select “Setup” and confirm by pushing .
To enter the menu use password (242). The menus can be selected by and entered by .
This menu item allows store the natural unbalance for current or voltage of the monitored capacitors. To
store the natural unbalance push the button. The second line of the display
starts blinking and shows the actual measured value. To store the shown value
push the button again. To set a new value for natural unbalance, just push
the button again. The stored value for natural unbalance is shown in the
“Info” menu. The evaluation of the natural unbalance happens according to amount. If the measured value
drops below the stored value for natural unbalance, this causes a increased reading for display and
supervision.
Set the threshold for trip. The threshold can be set as real value (0,2 – 20 V for voltage / 20mA – 5A for
*
current ). Also it’s possible to set the threshold as percent value related to the nominal range for current or
voltage. In factory setting the real value has to be adjusted.
Attention: This value will be adapted by a later change of the transformer ratio automatically.
!
The input can changed to percent at menu item
*
in submenu
When using a VT / CT the given thresholds are multiplied by the adjusted transformer ratio.
.
ESTAsym CPR
Doc No.: 13172 - Rev. 01
Operating instructions
Page 13 of 22
Set the delay time for trip. If the trigger value (voltage or current) for trip is exceeded for a longer period than
, contacts 11-14 will close and 11-12 will open.
Set the threshold for alarm. The threshold can be set as real value (0,2 – 20 V for voltage / 20mA – 5A for
current*). Also it’s possible to set the threshold as percent value related to the nominal range for current or
voltage. In factory setting the real value has to be adjusted.
Attention: This value will be adapted by a later change of the transformer ratio automatically.
!
The input can changed to percent at menu item
in submenu
.
Sets the delay time for alarm. If the trigger value (voltage or current) for alarm is exceeded for a longer
period than
, contacts 21-24 will close and 21-22 will open.
The trip relay output can be configured as either latch able or non latch able output.
The trip relay goes back to inactive state as soon as the trip value falls below the adjusted
threshold.
The trip relay remains in active state even when the trip value falls below the adjusted
threshold. To reset push the "⊳" Button for 3 sec. After a power interruption the relay goes back to origin
state before the interruption.
The alarm relay output can be configured as either latch able or non latch able output.
The alarm relay goes back to inactive state as soon as the alarm value falls below the
adjusted threshold.
ESTAsym CPR
Doc No.: 13172 - Rev. 01
Operating instructions
Page 14 of 22
The alarm relay remains in active state even when the alarm value falls below the adjusted
threshold. To reset push the "⊳" Button for 3 sec. After a power interruption the relay goes back to origin
state before the interruption.
The relay 3 is free to program to become active state with trip, alarm or both. Following settings are possible:
relay 3 is always switched off
relay 3 becomes active only with alarm relay
relay 3 becomes active only with trip relay
relay 3 becomes active with trip and alarm relay
relay 3 becomes active with trip or alarm relay
The relay 3 output can be configured as either latch able or non latch able output.
The trip relay 3 goes back to inactive state as soon as the trip / alarm value fall below the
adjusted threshold.
The trip relay 3 remains in active state even when the trip / alarm value falls below the
adjusted threshold. To reset push the "⊳" Button for 3 sec. After a power interruption the relay goes
back to origin state before the interruption.
ESTAsym CPR
Operating instructions
4.2.2 Expert menu
Doc No.: 13172 - Rev. 01
Page 15 of 22
Password 511
To enter this menu select “Setup” and enter the expert password (511). Select submenus 100 – 400 by using
and . Enter the submenus by pushing .
4.2.2.1
Start menu
Contains the same settings as start menu above.
4.2.2.2
Measurement menu
Current measuring
The ESTAsym CPR is measuring the current at input K&L. Trip and alarm thresholds are
given in A respectively in % of nominal input range.
The ESTAsym CPR is measuring the voltage at input UM1 & UM2. Trip and alarm
thresholds are given in V respectively in % of nominal input range.
Values in percent
All values are shown in %. The thresholds for voltage or current are set in % related to
nominal value of the input.
All values are shown as real value. The thresholds for voltage or current are set as real
value.
Attention: A previous adjusted Transformerratio become set to 1 when altering this item.
!
Transformer factor
Voltage: adjustable VT ratio from 1-350.
Current: adjustable CT ratio from 1-4000.
Frequency
Here it’s possible to adjust the grid frequency. Possible settings are 50Hz and 60Hz. The setting for the
frequency should be correct otherwise the measurement does not work proper.
ESTAsym CPR
Operating instructions
4.2.2.3
Doc No.: 13172 - Rev. 01
Page 16 of 22
Alarm menu
Trip active
When exceeding the adjusted threshold for trip, the trip relays operates, the display is
blinking and shows
No event following the exceeding the trip threshold.
Store trip in “Alarm buffer”
Trips are stored with the trigger value in the “Alarm buffer”.
Trips are not stored.
Alarm active
When exceeding the adjusted threshold for alarm, the alarm relays operates, the display is
blinking and shows
No event following the exceeding the trip threshold.
Store alarm in “Alarm buffer”
Alarms are stored with the trigger value in the “Alarm buffer”.
Alarms are not stored.
Drop off ratio (hysteresis)
Possible setting from 50% - 100% of adjusted thresholds for current and voltage. The “drop off ratio”
defines the threshold when resetting a trip or an alarm when the monitored value falls below the adjusted
threshold.
i.e.
Case 1: Threshold for trip is 0.5A and “drop of ratio” is 100% = trip is reset when the current falls below 0.5A.
Case 2: Threshold for trip is 0.5A and “drop of ratio” is 50% = trip is reset when the current falls below 0.25A.
ESTAsym CPR
Doc No.: 13172 - Rev. 01
Operating instructions
Page 17 of 22
The ESTAsym CPR is working with unsigned absolute values. Due to this always a positive value is
!
shown. Independent of the direction of the changing (meas. value increase / decrease) always a
exceeding of the threshold is given.
Digital input active
the monitoring system can be blocked via the digital input.
the monitoring system cannot be blocked via the digital input.
Digital input open or closed
monitoring system is blocked when terminals DI1 & DI2 are closed.
monitoring system is blocked when terminals DI1 & DI2 are open.
Attention: The digital input is activated respectively deactivated by opening respectively closing the
!
contact DI1 and DI2. Connecting a voltage signal can destroy the ESTAsym CPR.
ESTAsym CPR
Doc No.: 13172 - Rev. 01
Operating instructions
4.2.2.4
Reset menu
reset trip
reset alarm
reset stored alarms and trips
reset natural unbalance
reset the device to factory settings.
change password “setup”. Possible adjustment 000-999. Master password 242.
change password “expert”. Possible adjustment 000-999. Master password 511.
To switch off the password protection, set
to 000.
Page 18 of 22
ESTAsym CPR
Operating instructions
4.3
Doc No.: 13172 - Rev. 01
Page 19 of 22
Alarm
The submenu “Alarm” contains the last 5 trips and the last 5 alarms. The alarms and trips are stored with the
value which has triggered the event. The alarm storage is an ring buffer, with upcoming a new trip/alarm, the
oldest event will be deleted. Also it’s possible to clear the “Alarm” menu in menu 400 “Reset menu”.
To enter this menu, use the button to select “Alarm”. Enter the menu by pushing
. Select the events by pushing the and buttons.
ESTAsym CPR
Doc No.: 13172 - Rev. 01
Operating instructions
Page 20 of 22
5 Technical Data ESTAsym CPR
Auxiliary voltage
40 – 250V AC, 45-65HZ / 40 – 300VDC, 5VA; max. fuse 6A
Voltage measuring
0,1 – 20V; burden 284kOhm; vt-ratio from 1 – 350, with low pass filter
Continuous overload: 120V
Short term overload: 500V for ten seconds
Accuracy: 0.5% from upper range value
Current measuring
10mA – 5A; burden 20mOhm; ct-ratio from 1-4000, with low pass filter
Continuous overload: 25A
Short term overload: 100A for one second
Accuracy: 0.5% from upper range value
Relay outputs
4 output relays, change over contact, voltfree, max fuse 6A
Function:
Relay 1: Trip,
Relay 2: Alarm,
Relay 3: adjustable Alarm, trip or both
Relay 4: in order
Max. output rating AC: 1250VA, max switching voltage: 440VAC
Max. output rating DC (ohmic): 30V / 5A; 60V / 1A; 110V / 0,5A; 220V / 0,3A
Digital input
Blocking Alarm / Trip via digital input.
Interface
TTL, rear (optional accessories TTL-USB converter)
Ambient temperature
Operation: -20°C – 70°C, storag e: -40°C – 85°C
Humidity
0% - 95%, without moisture condensation
Overvoltage class
II, pollution degree 3 (DIN VDE 0110, Teil 1 / IEC 60664-1)
Standards
DIN VDE 0110 part 1 (IEC 60664-1:1992)
VDE 0411 part 1 (DIN EN 61010-1 / IEC 61010-1:2001)
VDE 0843 part 20
(DIN EN 61326 / IEC 61326: 1997 + A1:1998 +A2: 2000)
Conformity and listing
CE
Terminals
screw-type, max. 2,5mm
Casing
front: instrument casing plastic (UL94-VO), rear: metal
Protection class
Front: IP50, (IP54 by using a gasket), Rear: IP20
Weight
ca. 0,65 kg
Dimensions
144 x 144 x 58mm (h x w x d), cutout 138
2
+0,5
+0,5
x 138
mm
ESTAsym CPR
Doc No.: 13172 - Rev. 01
Operating instructions
Page 21 of 22
6 Menu overview
MEAS U / I in % V/A
INFO
ALARM
SETUP
242
100 Natural unbalance U / I („NU“)
511
100 Natural unbalance U / I („NU“)
Trip value "trd"
Trip value "trd"
Trip time "trt"
Trip time "trt"
"tr1"
Alarm value "Ald"
"tr2"
Alarm time "Alt"
"tr3"
Software version "Fr"
Trip latchable "trL"
"tr4"
Di state "dl"
Alarm latchable "ALL“
"tr5"
Relay 3 "r3"
"AL1"
Relay 3 latchable "r3L"
"AL2"
Alarm value "Ald"
Alarm time "Alt"
"AL3"
200 Current / voltage metering "Cur“
"AL4"
Display real value or % "Per"
"AL5"
Transformer factor "trF"
Line frequency "Frq"
300 Trip active "tr"
Store trip in buffer "trs"
Alarm active "AL"
Store alarm in buffer "ALS"
Drop off ratio "dor"
Activate DI "dl"
DI open or closed "dIL"
400 Reset trip "rtr"
Reset alarm "rAL"
Reset stored alarms "rSE"
Reset natural unbalance "rNU"
Reset to factory settings "rFS"
Password setup "PS"
Password expertmenu "PE"
ESTAsym CPR
Doc No.: 13172 - Rev. 01
Operating instructions
Page 22 of 22
7 Settings
Parameter
Range
Factory settings
Natural unbalanced I “NU"
Trip value "trd"
Trip time“trt”
Alarm value“Ald”
Alarm time“Alt”
20mA-5A / 200mV-20V
*
2A
0,1-100 s
0,1 s
20mA-5A / 200mV-20V*
1A
0,1-100 s
5,0 s
Trip latchable“trL”
X
X
X
Alarm latchable“ALL”
Relays 3 „r3“
Relay 3 latchable “r3L”
X
X
Current / voltage metering „Cur“
Display real value“PEr”
Transformer factor “trF”
Line frequency „Frq“
X
CT 1-4000 / PT 1-350
6
50 / 60
50
Trip active“tr”
X
X
X
X
Store trip in buffer “trs”
Alarm active “AL”
Store alarm in buffer “ALS”
Drop off ratio “dor”
50% - 100%
90%
Activate DI “dI”
X
X
DI open or closed “dIL”
Password „Setup“
242
Password „Expert“
511
*
When using a VT / CT the given thresholds are multiplied by the adjusted transformer ratio.
Customer settings