BE57-600-18 Eclipse705

™
705
software V3.x
Installation and Operating Manual
Guided Wave Radar
Level Transmitter
®
UNPACKING
Unpack the instrument carefully. Make sure all components
have been removed from the foam protection. Inspect all
components for damage. Report any concealed damage to
the carrier within 24 hours. Check the contents of the carton/crates against the packing slip and report any discrepancies to Magnetrol. Check the nameplate model number
to be sure it agrees with the packing slip and purchase
order. Check and record the serial number for future reference when ordering parts. To avoid moisture ingress in the
housing, covers should be fully tightened at all times. For
the same reason, plugs should remain properly installed in
the cable entries until replaced with a cable gland.
These units are in conformity with the
provisions of:
1. The EMC Directive: 2014/30/EU.
0038
The units have been tested to EN
0344
61326: 1997 + A1 + A2.
2. Directive 2014/34/EU for Equipment or protective system for use in potentially explosive atmospheres. ECtype examination certificate number KEMA99ATEX0518X
(intrinsic safe units) or BKI 12 ATEX 0017 (Ex d units) or
KEMA99ATEX5014 (Non sparking units).
3. The PED directive 2014/68/EU (pressure equipment
directive). Safety accessories per category IV module
H1.
SPECIAL CONDITIONS FOR ATEX INTRINSICALLY SAFE USE
Amplifier nameplate:
- partnumber
- amplifier
- serial n°
- temperature/pressure
- approval data
Probe nameplate
- partnumber
- serial number
Because the enclosure of the Guided Wave Radar Level Transmitter Eclipse Model 705-5xxx-x1x and 705-5xxx-x7x and/or
Probe Eclipse Model 7xx-xxx-xxx is made of aluminium, if it is mounted in an area where the use of category 1G apparatus is
required, it must be installed such, that, even in the event of rare incidents, ignition sources due to impact and friction sparks
are excluded.
For applications in explosive atmospheres caused by combustible dust, gases, vapours or mists and where category 1G or 1D
apparatus is required, electrostatic charges on the non-metallic parts of the Probe Eclipse Model 7M5-xxx-xxx, Model 7M7-xxxxxx and Model 7xF-xxx-xxx shall be avoided.
2
MOUNTING
IMPORTANT:
To avoid damaging during transportation, Eclipse® 7MD/7ML large coax probes are shipped with 3 transport screws, securing
the inner antenna. The 3 screws have to be removed prior to installation. They are located nearby the process connection. A
separate label is attached to draw the attention to remove the screws.
To avoid moisture ingress in the housing, covers should be fully tightened at all times. For the same reason, cable gland and
plugs should be properly installed in the cable entries.
The unit is preconfigured from factory, based on given application details (when available). Therefore transmitter and GWR
probe have the same serial n°.
Please make sure that corresponding serial numbers are mounted together.
Coaxial type GWR probes: Flushing connection
(7ML - 7MM - 7MN)
Coaxial type GWR probes
(7MD - 7MQ - 7MR - 7MS - 7MT)
Size: 38 mm
(1 1/2") or
adjustable
wrench
1/4" NPT
plugged
flushing
connection
Size: 38 mm
(1 1/2") or
adjustable
wrench
Not important
min 25 mm (1")
from tank bottom
Customer supplied brackets are recommended
per each 3 m length. (Required for WGH § 19
installations.)
1/4" NPT
plugged
flushing
connection
Not important
min 25 mm (1")
from tank bottom
Customer supplied brackets are recommended
per each 3 m length. (Required for WGH § 19
installations.)
Note: The flushing connection allows to purge the inside of
the coaxial probe without dismantling. Re-assure the use of
compatible purging liquid/gas to avoid unwanted chemical
reaction.
Overfill safe and Overfill proof
Eclipse 7MD/7ML, 7MR/7MM and 7MT/7MN coaxial GWR
probes are “Overfill safe” in use and “Overfill proof” certified.
Overfill safe means that the unit is capable to measure up
to the process connection.
Overfill proof protection (such as WHG or VLAREM) certifies reliable operation when the transmitter is used as
overfill alarm but assumes that the installation is designed
in such way that the vessel/ cage cannot overfill.
Eclipse 7MQ/7MS has a transitioning zone (zone in which
the unit does not measure accurately) at the top. Maximum
level should not be higher than 25 mm (1") up to 200 mm
(8") (depending dielectrics - see probe specifications) below
the process connection. This may include utilizing a nozzle
or spool piece.
Note: When using the 7MQ or 7MS probe, keep transmitter
and probe matched as a set.
Metallic (or any conductive) obstructions in the tanks
Metallic obstructions have no influence on the measuring
performance of coaxial GWR probes.
Turbulence
Customer supplied mounting brackets are recommended
per each 3 m (10’) length and have no influence on the measuring performance of coaxial GWR probes.
Stillwell /cages
Coaxial GWR probes are ideally suited for use in stillwells
or cages. There is no min. clearance allowance to be taken
into consideration.
Shortening of probe length
Coaxial GWR probes can be easily shortened on site when
a procedure for this is strictly followed. This procedure can
be separately obtained from factory.
3
MOUNTING
Twin rod (7MB) / Twin cable (7M5 - 7M7) GWR probes
Mounting considerations for 7MB
Nozzle should be DN80 (3") diameter or larger.
Mounting considerations for 7M5/7M7
For nozzles < DN80 (3") diameter, the bottom of the inactive section of the probe should be flush with the bottom of
the nozzle or extend into the vessel.
Size: 47 mm
(1 7/8") or
adjustable
wrench
min. 25 mm (1")
from any metal
object
min 25 mm (1")
from tank bottom
Use half open brackets
for twin rod probes.
Overfill safe and Overfill proof
Eclipse twin rod GWR probes use software to ignore level
readings in the transitioning zone at the top of the GWR
probe. The maximum level is a minimum of 150 mm (6")
below the process connection. This may include utilizing a
nozzle or spool piece to raise the probe. Twin rod probes
are overfill proof certified but not overfill safe in use.
Eclipse twin cable GWR probes, used in media with low
dielectrics (hydrocarbons, powders) may require the setting
of a blocking distance (zone in which the unit will not measure) of 300 mm up to 500 mm (12" to 20") depending probe
length. The longer the probe, the longer the blocking distance will be. Eclipse twin cable GWR probes are not overfill proof certified and not overfill safe in use.
Metallic (or any conductive) obstructions in the tanks
Objects in the proximity within 25 mm (1") or closer such as
pipes, support beams, metal ladders etc… may cause erroneous readings.
min 25
(1)
Off center rod
Tank or cage wall
4
For twin cable:
min 25 mm
(1") from any
metal object
Turbulence
7MB: Customer supplied brackets are recommended per
each 3 m (10') length and have no influence on the measuring performance of 7MB GWR probes. Use the “off center” rod to fasten the brackets (see above drawings).
7M5/7M7: It is recommended to secure the probe if significant turbulence exists. Optional weights are available to
keep the probe taught. The probe should not make any contact with the metal tank wall. The 7M7 (liquids) probe can be
attached to the bottom of the tank – it is not recommended
to attach the 7M5 (solids) probe at the bottom of the tank.
Stillwell/cages
Min. 3" / DN 80 size nozzles, stillwells or by-pass cages are
required for a good operation. Twin rod/cable probes should
be min 25 mm (1") away from any metal tank wall. 7M5/7M7
have a 76 mm (3") inactive section. For nozzles < 3"/
DN 80, this section should be flush with the bottom of the
nozzle or extend into the vessel.
IMPORTANT:
Twin rod/cable probes should be installed into a metal tank,
stillwell or by-pass cage to meet CE requirements
(EN 61326: 1997 + A1 + A2) electromagnetic compatibility.
MOUNTING
Twin rod (7MB) / Twin cable (7M5 - 7M7) GWR probes
Shortening of probe length
7MB probes can be shortened safely in the field. Make sure to re-install the bottom spacer for proper alignment and to adapt
the probe length/ 4-20 mA settings in the menu.
Twin cable probes can be safely shortened in the field using below procedure. Make sure to adapt the probe length / 4-20 mA
settings in the menu.
7M7/7M5 probe can be shortened
in field.
a. raise the weight (1) to expose the two
1
securing devices (2)
b. loosen the two #10-32 set screws (3)
on both securing devices using a
2.5 mm (3/32") hex wrench and slide
the securing devices off of the probe
c. slide the TFE weight off of the probe.
d. cut and remove the required cable (4)
length
e. remove 90 mm (3 1/2") of the rib
between the two cables
f. strip 16 mm (5/8") of coating from the
two cables.
2
g. slide the TFE weight back on to the
probe.
h. enter new probe length (cm or inches)
in software (See page 12, Item 9)
13 mm Ø
(0.50")
Note: Probe can be attached to the tank
bottom using the noose or the 13 mm Ø
(0.50") hole provided in the TFE weight.
7M7 GWR probes: cable tension should
not exceed 89 N
7M5 GWR probes: pull down force should
not exceed 1360 kg (3000 lbs)
3
4
Cage GWR probe (7MG)
For cage/still well:
2": Ø 13 mm
(0.50") rod
Vent
Venting
holes
For cage/still wells:
3": Ø 19 mm (0.75") tubing
4": Ø 25 mm (1.00") tubing
Bottom spacer
Bottom spacer
Customer or magnetrol
supplied cage/bridle or still well.
Drain
Overfill safe
All 7MG GWR probes are overfill safe. Overfill safe means
that the impedance match of the waveguide (probe) is
aligned from electronics down to the bottom of the GWR
probe. This allows the Eclipse 705 to measure up to the
process flange without any dead zone at the top of the GWR
probe.
Metallic (or any conductive) obstructions in the tanks
Metallic obstructions have no influence on the measuring
performance of cage GWR probes.
Stillwell/cages
The cage GWR probe is a single rod GWR probe which
uses an existing or new cage, bridle or schedule pipe stillwell to re-create the same propagation of signal of a coaxial GWR probe. Cage GWR probes are suited for 2", 3" or 4"
size diam. and use an impedance matching part that aligns
in the same way with the characteristic impedance of a
standard coaxial style GWR probe.
Shortening of probe length
Cage GWR probes can be easily shortened on site. Always
re-install the bottom spacer and adapt the new probe length
in the menu of the amplifier.
5
MOUNTING
Single rod (7MF - 7MH - 7MJ) / Single cable (7M1 - 7M2) GWR probes
Size: 38 mm
(1 1/2") or
adjustable
wrench
Size: 38 mm
(1 1/2") or
adjustable
wrench
High Level shutdown and Overfill protection
Special consideration is necessary in any high level shutdown / overfill protection application where single rod GWR
probes are used. To ensure proper measurement, the guided wave radar probe should be installed so the maximum
overfill level is at a minimum of 120 mm (4.8") up to
910 mm (36") – blocking distance depending application
below the process connection. Consult factory for further
information.
Metallic (or any conductive) obstructions in the tanks
Objects in the proximity of the probe may cause erroneous
readings.
Distance to probe
< 150 mm (6")
> 150 mm (6")
> 300 mm (12")
> 450 mm (18")
Acceptable objects
Continuous, smooth, parallel,
conductive surface (e.g. metal
tank wall); probe should not touch
tank wall
< 1"/DN25 diameter pipe and
beams, ladder rungs
< 3"/DN80 diameter pipe and
beams, concrete walls
All remaining objects
Turbulence
The bottom of the probe should be stabilized if turbulence
will cause a deflection of more than 75 mm at 3 m (3" at 10')
of length. Optional bottom spacers in TFE (for 7MF) or
PEEK (for 7MJ) should be used to stabilize the probe, in
case turbulence exists. It is recommended to secure the
probe (7M1/7M2) if significant turbulence exists (see above
drawing at right side). Optional weights are available to
keep the probe taught. The 7M1 (liquids) probe can be
attached to the bottom of the tank – it is not recommended
to attach the 7M2 (solids) probe at the bottom of the tank.
The probe should not make any contact with the metal tank
wall.
6
Stillwell/cages
Max. 6” / DN 150 size stillwells or by-pass cages or a metal
tank wall within 150 mm (6”) of the probe, will allow the unit
to measure accurately in media with dielectrics down to
εr 1,9.
Nozzles do not restrict the performance by ensuring the following:
1. Nozzle must be 50 mm (2") or larger diameter.
2. Nozzle inside diameter (A) should be ≥ to nozzle height
(B). If this is not the case, it is recommended to adjust
BLOCKING DISTANCE and/or SENSITIVITY settings.
A
B
Correct installation
Pipe reducers
should not be used
IMPORTANT:
Single rod/cable probes should be installed into a metal
tank, stillwell or by-pass cage to meet CE requirements
(EN 61326: 1997 + A1 + A2) electromagnetic compatibility.
When used in a non-metallic vessel flange (metal) mounting
is recommended for optimal performance.
MOUNTING
Single rod (7MF - 7MH - 7MJ) / Single cable GWR probes
Shortening of probe length
Single rod/cable probes can be shortened safely in the field. Make sure to adapt the probe length/ 4-20 mA settings in the menu
and the re-install of a bottom spacer when applicable.
Single cable probes can be safely shortened in the field using below procedure. Make sure to adapt the probe length/ 4-20 mA
settings in the menu.
7M1/7M2 probe can be shortened in
field.
a. raise TFE weight (1) exposing securing device (2)
b. loosen both #10-32 set screws (3)
using 2.5 mm (3/32") hex wrench
and remove securing device
c. cut and remove needed cable length
(4)
d. re-attach securing device (2) and
tighten screws
e. enter new probe length (cm or inches) in software (See page 12, Item 9)
1
2
13 mm
mm flØ
13
(0.50")
(0.50")
Note: Probe can be attached to the tank
bottom using the noose or the 13 mm Ø
(0.50") hole provided in the TFE weight.
7M1 GWR probes: cable tension should
not exceed 89 N (20 lbs).
7M2 GWR probes: pull down force
should not exceed 1360 kg (3000 lbs)
3
4
Top/Bottom GWR probes
(7EK)
1 1/2" or 2"
Flanged
1 1/2" or 2"
socket weld or
NPT
Overfill safe and Overfill proof
Eclipse 7EK GWR probes are “Overfill safe” in use and
“Overfill proof” certified.
Overfill safe means that the unit is capable to measure up
to the process connection. Units with “non overfill safe”
probes use software to ignore level readings in the blocking distance or transitioning zone. When level rises too high
in this zone, the unit may consider the end of probe reflection as the real level and may report an empty vessel
instead of an overfilling vessel.
Overfill proof protection (such as WHG or VLAREM) certifies reliable operation when the transmitter is used as
overfill alarm but assumes that the installation is designed
in such way that the vessel/cage cannot overfill.
The 7EK probe is designed to replace without modification
top/bottom mounted displacer transmitters. The unit will
measure over the entire probe length and indicate for
20.5 mA above the highest measurable point and 3.8 below
the lowest measurable point.
7
MOUNTING
Transmitter
Integral
(a)
(b)
Remote
Max. rotation 270°
360° rotatable: Position for
optimum wiring/viewing
Size: 38 mm (1 1/2") or
adjustable wrench
Recommended torque 60 Nm
(45 ft-lbs)
Remove
protection
Remove protection
CAUTION: be careful not to bend or dirty the gold, high frequency
male connector (a) and its female connector (b). Clean with isopropyl alcohol and cotton swabs, if necessary
Insulation
Do not insulate the
high frequency connector
in case of high temperature
applications
WRONG
8
Max +150 °C (+300 °F)
Max +100 °C (+212 °F) for Ex d unit
GOOD
On high or low temperature applications, install a vented
protection around the probe/housing.
WIRING
CAUTION: power must be switched OFF before wiring the unit.
Positive supply to (+) terminal
Negative supply to (-) terminal
Current loop test
point (HART® only)
–
–
LOOP
CURRENT
+
®
IS
IS
Shield wire to green grounding screw (resistance to
ground must be < 1 Ω).
Use certified flameproof cable
gland(s) and cable for Explosion
proof area.
Standard shielded twisted
pair cable (recommended
but not needed when wired
as per NAMUR NE 21 for
field strenghts up to
10 V/m).
100 %
0%
Ex
Ex
Non Ex
Ex
Non Ex
Galvanic Barrier (only needed for intrinsically safe units):
HART®: max. 28,4 V DC @ 124 mA
Foundation Fieldbus™ / Profibus PA™: max. 17,5 V DC
@ 380 mA
ANALOG I/O
or
DIGITAL I/O
(only for units with HART)
Customer supplied
local current meter
Non Ex
Do not connect shield
IMPORTANT:
The shield wire should only be grounded at ONE side only. It is recommended to connect the shield to ground in the field (at
the transmitter side - as shown above) but connecting in the control room is also allowed.
LOOP RESISTANCE
1200
20,5 mA
1000
800
Ω
630
600
400
200
0
0
10
11
20
24 Vdc
30
40 Vdc
9
CONFIGURATION
NOTE: When connected to an approved barrier, the intrinsically safe electronics of the Eclipse allow to remove the
covers with power switched on – even if the area is known to be hazardous
2 line – 8 characters LCD
Default display cycles every 5 s through Status «STATUS» / Level
«LEVEL» / % output «% OUTPUT» / Loop «LOOP».
Up/Down and Enter pushbuttons
IMPORTANT: The Eclipse amplifier can be bench configured without GWR
probe connected. Ignore the start up message «No Level Signal» / «STATUS» / «WeakSgnl» in this case.
Display
Units!
cm
Action
Press
Units!
cm
Press
Units
cm
Press
PASSWORD
DISPLAY
Ent Pass
0
Ent Pass!
1
New Pass
4096
:
Comment
The last character on the first line of the display changes to «!». This sign confirms that the values/choices of the second line can be modified via the and
push buttons.
* Scroll through the choices or increase/decrease the values on the second line
of the display by and pushbuttons.
pushbutton.
* Accept values/choices as selected by
Scroll through the menu.
ACTION
COMMENT
Display shows «0»
Factory default setting
Data is not protected
Press
and last character changes into «!»
Enter your personal password with and
(any value between 1 and 255)
Press
to confirm
Setting password
Display shows an encrypted value, enter your password
or call Magnetrol for assistance to recoop your password
if necessary
Data is protected by a valid
Password
Press
and enter old password
Press
and last character changes into «!»
Enter your new password with and
(any value between 1 and 255)
Press
to confirm
Changing password
NOTE: Password protection is activated when after 5 minutes no keystrokes are sensed.
10
CONFIGURATION
TERMINOLOGY
20 mA Level
(100%-point)
Probe Type
Offset
Blocking
distance
4 mA Level
Inch or cm
εr = 2.0: 150 mm (6") + Offset
εr = 80: 25 mm (1") + Offset
Safety
Zone
20 mA Level =
cm or inches
or 100 % level point, is measured from the reference point.
The unit has a transition zone at the top of the probe.
Transition zone varies depending on probe type and
media: see probe specifications page 34 and continuing.
cm or inches, record the exact probe length as
Probe length =
printed on the nameplate: 705-xxxx-xxx / 7Mx-xxx-xxx
Dielectric
Select the dielectric scale of the media to measure: 1.4–
1.7 or 1.7–3 or 3–10 or 10–100. When the dielectric is
known, it will enhance the overall accuracy of the unit but
select the dielectric scale ALWAYS to the lowest expected
dielectricum.
Probe
Length
Dielectric
of medium
4 mA Level
(0%-point)
Offset
Reference
point
Positive offset
No offset
(Offset at 0 cm) (Offset at 10 cm)
75 cm
15 cm
100 %
20 mA = 75 cm
0%
4 mA = 15 cm
10 cm
=
cm or inches
The offset is the distance between reference point (e.g.
bottom of tank) and end of probe. From the reference point
both 4 mA and 20 mA levels are calibrated. When offset is
set at zero, the end of the probe is the reference point.
=
cm or inches
or zero level point, is measured from the reference point.
The unit has a transition zone at the bottom of the probe.
Min. level to enter for media with:
Negative offset
(Offset at -15 cm)
20 mA = 85 cm
20 mA = 60 cm
4 mA = 25 cm
4 mA = 0 cm
Safety zone: In addition to the blocking distance,
the user can introduce a safety zone
to warn for liquid level entering this
zone beneath the blocking distance.
The loop signal will shift in this zone
to a selectable fault signal. The unit
will go to normal read out, when level
drops lower than the safety zone,
unless a latched fault signal is used.
The safety zone is disabled from factory. Safety zone related settings
include:
«SZ Fault»: to select the preferred
error signal
«SZ Height»: to define the safety
zone area
«SZ Alarm Reset»: to manually
reset a latched «SZ Fault»
BEFORE STARTING
Start from run mode:
1. Select the desired language for configuration: English, French, German or Spanish in the language screen (32)
«language». Scroll up for quickly reaching the language selection screen.
2. Define type of measurement:
a. Level only
(pages 12 & 13)
b. Level and Volume
(pages 14 & 15)
c. Interface only
(pages 16 & 17)
d. Interface and Volume
(pages 18 & 19)
Scroll down until the screen reads «MeasType». The unit will now show only the applicable screens for the selected type
of measurement.
3. Scroll one screen down and select the applicable engineering unit in «LvlUnits», all configuration values will be entered
in that engineering unit.
4. Move to the loop control screen «LoopCtrl», select the loop control in function of the type of measurement «MeasType»
selected.
5. Refer to the configuration procedure of the selected type of measurement.
6. Refer to page 20 for all hidden diagnostic screens and advanced configuration parameters. These screens allow the
advanced user to configure the unit for special applications or to troubleshoot the unit in the field. It is NOT recommended
to access this toolset without proper guidance or having followed proper training.
11
MENU: STEP BY STEP PROCEDURE – Eclipse 705: Level only
Screen
Run mode
1
Transmitter Display
Level
xx.x
Transmitter Display
4
Loop
xx.xx mA
Transmitter Display
6
PrbMount
(select)
8
LvlUnits
(select)
2
3
5
7
Configuration
*Status*
*Level*
*%Output*
*Loop*
Action
%Output
xx.x%
PrbModel
(select)
MeasType
(select)
Transmitter default values cycle every 5 seconds. Status «Status»,
Level «Level», % Output «% Output», and Loop «Loop».
Transmitter displays level value in selected engineering units.
Transmitter Display
Transmitter displays % Output measurement derived from 20 mA
span.
Select the type of probe
Select as per the 3 first digits of the probe partnumber. The partnumber
is shown on the nameplate: e.g. 705-510A-A11/7MT-A230-218, select
7xT-x from the list.
Transmitter displays Loop measurement (mA).
Select NPT «NPT», BSP «BSP» or Flange «Flange». (consult facto-
Select the type of probe
mounting.
ry when a «7xK» GWR probe is used)
Select units for level
cm «cm», m «m», inches «inches» or feet «feet».
Select the type of measurement
Select level «Levl Only».
9
Probe Ln
xxx.x
Enter the exact length of
probe.
10
Lvl Ofst
xxx.x
Enter the offset value.
11
Dielctrc
(Select)
Enter the dielectric range
value of the media
Select: «1.4–1.7»; «1.7–3»; «3–10» or «10–100»
«1.7–3» is recommended for dielectrics ≥ 1,7
13
Loop Ctrl
(Select)
Select primary variable (PV)
Primary variable is the loop controlling parameter. Select level
Set 4mA
xxx.x
Enter the level value
for the 4 mA point.
A transition zone may exist at the bottom of the probe. See Functional
Specifications Probe, see page 34 and continuing.
Damping
xx sec
Enter the damping factor.
12
14
15
16
17
Senstvty
xxx
Set 20mA
xxx.x
Fault
(Select)
Enter sensitivity value
Enter as per the 3 last digits of the probe partnumber on the nameplate:
- rigid probes, enter value cm or inches,
- flexible probes, enter value in meters or feet
e.g. 705-510A-A11/7MR-A230-218, enter «218» cm probe length.
When entering configuration values from the end of the probe is
cumbersome, an offset can be introduced to determine a new
reference point. This reference point can be either below the probe
(positive offset) or at the probe (negative offset). See page 11
“Terminology”.
Allows fine adjustment of internal gain.
«Lvl only»
Enter the level value
for the 20 mA point.
A transition zone / blocking distance may exist at the top of the probe.
See Functional Specifications Probe, see page 34 and continuing.
Enter the value for error.
Select «3.6 mA», «22 mA» or hold last value «HOLD». In case of
loop failure, error signal will follow the failing trend; meaning the unit
will show 3.6 mA when the reviewed loop current by the device is
found too low. The unit will show 22 mA in case the reviewed loop
current is found too high.
= Quick Start up
12
Comment
A Damping factor (1-10 seconds) may be added to smooth a noisy
display and/or output due to turbulence.
MENU: STEP BY STEP PROCEDURE – Eclipse 705: Level only
Screen
Comment
Enter distance in
selected level units
18
BlockDis
xx.x
19
SZ Fault
(select)
Select the safety zone fault.
20
SZHeight
xx.x
Select the safety zone value
21
SZ Alarm
Reset
Reset safety zone latch fault
Threshld
(select)
Select the type of threshold
23
Poll Adr
xx
Enter HART ID number.
Trim Lvl
xx.x
Enter value
to adjust level reading.
22
Diagnostics
Action
24
25
26
27
Loop Mode
Trim 4
xxxx
Trim 20
xxxx
Enable/Disable
Determines whether the loop is fixed at 4.0 mA or controlled by the
PV.
Allows to compensate for a fixed level deviation.
Set mA Output to any given value to perform loop test .
New Pass
xxx
Enter new password.
Mdl705HT
Ver xx.xx
None, do not adjust.
33
«Fixed» = the first reflection from the top will be considered as level
(default setting)
«CFD» = the strongest reflection from the top will be considered as
level.
Only change to «CFD», in case the unit is reading incorrect level.
Adjustment of trim level «Trim Lvl» may be necessary when
threshold is changed.
Select a HART poll address (0-15). Enter 0 for a single transmitter
installation.
Enter a mA output value.
Fine tune the 20 mA point.
30
32
Clear a latched safety zone alarm «SZFault».
Attach a mA meter to the output. If the output does not equal 4.0 mA,
adjust the value on the display to equal 4.00 mA.
Loop Tst
xx.x mA
31
Enter safety zone in cm or inches (see Terminology - page 11).
Fine tune the 4 mA point.
28
29
Allows to ignore level measurements near the top of the probe,
caused by e.g. condensation, crystalization. Make sure that the liquid
level does NOT enter this zone. Consult factory or the
‘Troubleshooting’ section before entering any value. Normaly to be
used with single rod probe.
Select «None» (None), «3.6mA», «22mA», «Latch 3.6mA» or
«Latch 22mA». When either «Latch 3.6 / 22mA» signals is
selected, the loop current remains in alarm until it is manually cleared
with the «SZAlarm» screen ( for safety zone explanation see
Terminology - page 11).
Attach a mA meter to the output. If the output does not equal
20.0 mA, adjust the value on the display to equal 20.00 mA.
LvlTicks
xxxxx
Diagnostic display.
Shows time of flight from fiducial pulse to reflected signal from level.
Language
Select language
Select «English», «Français», «Deutsch» or «Espagnol».
DispFact
(select)
Advanced diagnostics.
See page 20.
OFFSET
Use arrows to select desired value. Values between 0 and 255.
No offset
(Offset at 0 cm)
75 cm
15 cm
100 %
20 mA = 75 cm
0%
4 mA = 15 cm
Factory setting. «Ver» refers to software version.
Positive offset
(Offset at 10 cm)
Negative offset
(Offset at -15 cm)
20 mA = 85 cm
20 mA = 60 cm
4 mA = 25 cm
4 mA = 0 cm
10 cm
13
MENU: STEP BY STEP PROCEDURE – Eclipse 705: Level & Volume
Screen
Run mode
1
Transmitter Display
Volume
xxx
Transmitter Display
4
Loop
xx.xx mA
Transmitter Display
6
PrbModel
(select)
Select the type of probe
7
PrbMount
(select)
Select the type of probe
mounting.
9
LvlUnits
(select)
Select units for level
2
3
5
8
Configuration
*Status*
*Volume*
*%Output*
*Loop*
Action
Transmitter default values cycle every 5 seconds. Status «Status»,
Volume «Volume», % Output «% Output», and Loop «Loop».
Transmitter displays Volume Value in selected engineering units.
%Output
xx.x%
Transmitter Display
Transmitter displays % Output measurement derived from 20 mA
span.
Level
xxx
Transmitter Display
Transmitter displays level in selected volume units «LvlUnits».
MeasType
(select)
Select the type of measurement
Transmitter displays Loop measurement (mA).
Select as per the 3 first digits of the probe partnumber. The partnumber
is shown on the nameplate: e.g. 705-510A-A11/7MT-A230-218, select
7xT-x from the list.
Select NPT «NPT», BSP «BSP» or Flange «Flange». (consult factory when a «7xK» GWR probe is used)
Select level and volume «Lvl&Vol».
cm «cm», m «m», inches «inches» or feet «feet».
10
Probe Ln
xxx.x
Enter the exact length of
probe.
11
Lvl Ofst
xxx.x
Enter the offset value.
12
VolUnits
(select)
Select units for volume
Dielctrc
(Select)
Enter the dielectric range
value of the media
Select: «1.4–1.7»; «1.7–3»; «3–10» or «10–100»
«1.7–3» is recommended for dielectrics ≥ 1,7
Loop Ctrl
(Select)
Select primary variable (PV)
Primary variable is the loop controlling parameter. Select level
«Lvl only» or volume «volume»
13
14
15
16
17
18
19
20
StrapTbl
xx pnts
Senstvty
xxx
Enter level/volume
pairs in max 20 steps
Enter sensitivity value
Set 4mA
xxx.x
Enter the level value
for the 4 mA point.
Damping
xx sec
Enter the damping factor.
Set 20mA
xxx.x
Fault
(Select)
Enter as per the 3 last digits of the probe partnumber on the nameplate:
- rigid probes, enter value cm or inches,
- flexible probes, enter value in meters or feet
e.g. 705-510A-A11/7MR-A230-218, enter «218» cm probe length.
When entering configuration values from the end of the probe is
cumbersome, an offset can be introduced to determine a new
reference point. This reference point can be either below the probe
(positive offset) or at the probe (negative offset). See page 11
“Terminology”.
Liters «l» or gallons «g».
Liters «l» or gallons «g».
Allows fine adjustment of internal gain.
A transition zone may exist at the bottom of the probe. See Functional
Specifications Probe, see page 34 and continuing.
Enter the level value
for the 20 mA point.
A transition zone / blocking distance may exist at the top of the probe.
See Functional Specifications Probe, see page 34 and continuing.
Enter the value for error.
Select «3.6 mA», «22 mA» or hold last value «HOLD». In case of
loop failure, error signal will follow the failing trend; meaning the unit
will show 3.6 mA when the reviewed loop current by the device is
found too low. The unit will show 22 mA in case the reviewed loop
current is found too high.
= Quick Start up
14
Comment
A damping factor (1-10 seconds) may be added to smooth a noisy
display and/or output due to turbulence.
MENU: STEP BY STEP PROCEDURE – Eclipse 705: Level & Volume
Advanced configuration
Screen
Comment
Enter distance in
selected level units
21
BlockDis
x.x
22
SZ Fault
(select)
Select the safety zone fault.
23
SZHeight
xx.x
Select the safety zone value
24
SZ Alarm
Reset
Reset safety zone latch fault
Threshld
(select)
Select the type of threshold
26
Poll Adr
xx
Enter HART ID number.
Loop Mode
Enable/Disable
Trim Lvl
xx.x
Enter value
to adjust level reading.
25
27
28
29
30
Diagnostics
Action
Trim 4
xxxx
Trim 20
xxxx
31
Loop Tst
xx.x mA
33
New Pass
xxx
32
34
35
36
Allows to ignore level measurements near the top of the probe,
caused by e.g. condensation, crystalization. Make sure that the liquid
level does NOT enter this zone. Consult factory or the
‘Troubleshooting’ section before entering any value. Normaly to be
used with single rod probe.
Select «None» (None), «3.6mA», «22mA», «Latch 3.6mA» or
«Latch 22mA». When either «Latch 3.6 / 22mA» signals is
selected, the loop current remains in alarm until it is manually reset
with the «SZAlarm» reset screen ( for safety zone explanation see
Terminology - page 11).
Enter safety zone in cm or inches (see Terminology - page 11).
Select «Reset» «No» or «Yes» to reset alam when either «Latch
3.6mA» or «Latch 22mA» was selected in «SZFault».
«Fixed» = the first reflection from the top will be considered as level
(default setting)
«CFD» = the strongest reflection from the top will be considered as
level.
Only change to «CFD», in case the unit is reading incorrect level.
Adjustment of trim level «Trim Lvl» may be necessary when
threshold is changed.
Select a HART poll address (0-15). Enter 0 for a single transmitter
installation.
Determines whether the loop is fixed at 4.0 mA or controlled by the
PV.
Allows to compensate for a fixed level deviation.
Fine tune the 4 mA point.
Attach a mA meter to the output. If the output does not equal 4.0 mA,
adjust the value on the display to equal 4.00 mA.
Enter a mA output value.
Set mA Output to any given value to perform loop test.
Fine tune the 20 mA point.
Attach a mA meter to the output. If the output does not equal
20.0 mA, adjust the value on the display to equal 20.00 mA.
LvlTicks
xxxxx
Diagnostic display.
Shows time of flight from fiducial pulse to reflected signal from level.
Language
Select language
Select «English», «Français», «Deutsch» or «Espagnol».
Advanced diagnostics.
See page 20.
Mdl705HT
Ver xx.xx
DispFact
(select)
Enter new password.
Use arrows to select desired value. Values between 0 and 255.
None, do not adjust.
Factory setting. «Ver» refers to software version.
Strapping table
max. Pt 20 Vol = ...... l
Pt 4 Vol = 3000 l
Pt 3 Vol = 2000 l
Pt 2 Vol = 1000 l
Pt 1 Vol = 0 l
max. Pt 20 Lvl = ...... cm
Pt 4 Lvl = 200 cm
Pt 3 Lvl = 120 cm
Pt 2 Lvl = 50 cm
Pt 1 Lvl = 0 cm
NOTE: Consult page 13 for level offset «Lvl Ofst» details.
15
MENU: STEP BY STEP PROCEDURE – Eclipse 705: Interface
Screen
Run mode
1
Transmitter Display
Transmitter default values cycle every 5 seconds. Status «Status»,
Interface level «Ifclevel», % Output «% Output», and Loop
«Loop».
IfcLevel
xx.x
Transmitter Display
4
Loop
xx.xx mA
Transmitter Display
6
PrbModel
(select)
Select the type of probe
7
PrbMount
(select)
Select the type of probe
mounting.
ry when a «7xK» GWR probe is used)
9
Select units for level
Probe Ln
xxx.x
Enter the exact length of
probe.
cm «cm», m «m», inches «inches» or feet «feet».
10
LvlUnits
(select)
11
Lvl Ofst
xxx.x
Enter the offset value.
12
Upr Diel
(Select)
Enter the dielectric range
value of the upper media.
3
8
13
14
15
16
17
18
19
Transmitter displays interface level in selected engineering units.
%Output
xx.x%
Transmitter Display
Transmitter displays % Output measurement derived from 20 mA
span.
Level
xxx
Transmitter Display
Transmitter displays interface level in selected level units «LvlUnits».
MeasType
(select)
Select the type of measurement
Dielctrc
(Select)
Select the dielectric range
value of the lower media
Loop Ctrl
(Select)
Select primary variable (PV)
Senstvty
xxx
Enter sensitivity value
Set 4mA
xxx.x
Enter the level value
for the 4 mA point.
Damping
xx sec
Enter the damping factor.
Set 20mA
xxx.x
Fault
(Select)
Transmitter displays Loop measurement (mA).
Select as per the 3 first digits of the probe partnumber. The partnumber
is shown on the nameplate: e.g. 705-510A-A11/7MT-A230-218, select
7xT-x from the list.
Select NPT «NPT», BSP «BSP» or Flange «Flange». (consult factoSelect interface «Interface».
Enter as per the 3 last digits of the probe partnumber on the nameplate:
- rigid probes, enter value cm or inches,
- flexible probes, enter value in meters or feet
e.g. 705-510A-A11/7MR-A230-218, enter «218» cm probe length.
When entering configuration values from the end of the probe is
cumbersome, an offset can be introduced to determine a new
reference point. This reference point can be either below the probe
(positive offset) or at the probe (negative offset). See page 11
“Terminology”.
Enter the dielectrics of the upper layer liquid (between 1,4 and 5,0) –
only upper layer dielectrics need to be entered.
Select: «10–100»
Allows fine adjustment of internal gain.
Primary variable is the loop controlling parameter. Select interface level «Ifc Level» or top level «Lvl Only»
A transition zone may exist at the bottom of the probe. See Functional
Specifications Probe, see page 34 and continuing.
Enter the level value
for the 20 mA point.
A transition zone / blocking distance may exist at the top of the probe.
See Functional Specifications Probe, see page 34 and continuing.
Enter the value for error.
Select «3.6 mA», «22 mA» or hold last value «HOLD». In case of
loop failure, error signal will follow the failing trend; meaning the unit
will show 3.6 mA when the reviewed loop current by the device is
found too low. The unit will show 22 mA in case the reviewed loop
current is found too high.
= Quick Start up
16
Comment
2
5
Configuration
*Status*
*IfcLevel*
*%Output*
*Loop*
Action
A damping factor (1-10 seconds) may be added to smooth a noisy
display and/or output due to turbulence.
MENU: STEP BY STEP PROCEDURE – Eclipse 705: Interface
Advanced configuration
Screen
Comment
Enter distance in
selected level units
20
BlockDis
x.x
21
SZ Fault
(select)
Select the safety zone fault.
22
SZHeight
xx.x
Select the safety zone value
23
SZ Alarm
Reset
Reset safety zone latch fault
Threshld
Select top level threshold.
25
IfcThrs
(select)
Select interface threshold.
24
26
27
Poll Adr
xx
Loop Mode
28
Trim Lvl
xx.x
30
Trim 20
xxxx
29
Trim 4
xxxx
Fine tune the 4 mA point.
Attach a mA meter to the output. If the output does not equal 4.0 mA,
adjust the value on the display to equal 4.00 mA.
Set mA Output to any given value to perform loop test .
Allows to compensate for a fixed level deviation.
Fine tune the 20 mA point.
IfcTicks
xxxx
Diagnostic display.
35
New Pass
xxx
Enter new password.
Mdl705HT
Ver xx.xx
None, do not adjust.
38
Default selection for most common applications is «Fixed».
Select a HART poll address (0-15). Enter 0 for a single transmitter
installation.
Enter value
to adjust level reading.
33
37
Clear a latched safety zone alarm «SZFault».
Determines whether the loop is fixed at 4.0 mA or controlled by the
PV.
Enter a mA output value.
36
Enter safety zone in cm or inches (see Terminology - page 11).
Enable/Disable
Loop Tst
xx.x mA
34
Allows to ignore level measurements near the top of the probe,
caused by e.g. condensation, crystalization. Make sure that the liquid
level does NOT enter this zone. Consult factory or the
‘Troubleshooting’ section before entering any value. Normaly to be
used with single rod probe.
Select «None» (None), «3.6mA», «22mA», «Latch 3.6mA» or
«Latch 22mA». When either «Latch 3.6 / 22mA» signals is
selected, the loop current remains in alarm until it is manually reset
with the «SZAlarm» reset screen ( for safety zone explanation see
Terminology - page 11).
Default selection for all applications is «CFD». In case the unit does
not track the correct interface layer, select «Fixed».
Enter HART ID number.
31
32
Diagnostics
Action
LvlTicks
xxxxx
Diagnostic display.
Medium
Diagnostic display.
Attach a mA meter to the output. If the output does not equal
20.0 mA, adjust the value on the display to equal 20.00 mA.
Shows time of flight from fiducial pulse to reflected signal from level.
Shows time of flight through the upper liquid layer.
Shows type of detected upper liquid; unknown «Unknown» oil only
«Oil Only», thin oil layer «Thin Oil», thick oil layer «Thick
Oil», or no level «Dry Probe».
Use arrows to select desired value. Values between 0 and 255.
Language
Select language
Select «English», «Français», «Deutsch» or «Espagnol».
DispFact
(select)
Advanced diagnostics.
See page 20.
OFFSET
Factory setting. «Ver» refers to software version.
No offset
(Offset at 0 cm)
75 cm
15 cm
100 %
20 mA = 75 cm
0%
4 mA = 15 cm
Positive offset
(Offset at 10 cm)
Negative offset
(Offset at -15 cm)
20 mA = 85 cm
20 mA = 60 cm
4 mA = 25 cm
4 mA = 0 cm
10 cm
17
MENU: STEP BY STEP PROCEDURE – Eclipse 705: Interface & Volume
Screen
Run mode
1
Transmitter Display
2
IfcLevel
or Ifc Vol
Transmitter Display
4
Loop
xx.xx mA
Transmitter Display
3
5
6
7
Transmitter default values cycle every 5 seconds. Status «Status»,
Interface volume «IfcVolume», % Output «% Output», and Loop
«Loop».
Transmitter displays Interface volume or Interface level in selected
engineering units (depending selection in Loop control «Loop Ctrl»
Transmitter Display
Transmitter displays % Output measurement derived from 20 mA
span.
IfcLvl
xxxx
Transmitter Display
Transmitter displays interface level in selected level units
«LvlUnits».
Transmitter Display
Transmitter displays volume in selected volume units «VollUnits».
Select as per the 3 first digits of the probe partnumber. The partnumber
is shown on the nameplate: e.g. 705-510A-A11/7MT-A230-218, select
7xT-x from the list.
Volume
xx.x
Level
xxxx
Transmitter Display
PrbModel
(select)
Select the type of probe
9
PrbMount
(select)
Select the type of probe
mounting.
11
LvlUnits
(select)
Select units for level
MeasType
(select)
Select the type of measurement
Transmitter displays Loop measurement (mA).
Transmitter displays level in selected level units «LvlUnits».
Select NPT «NPT», BSP «BSP» or Flange «Flange». (consult factory when a «7xK» GWR probe is used)
Select interface - volume «IfcVol».
cm «cm», m «m», inches «inches» or feet «feet».
12
Probe Ln
xxx.x
Enter the exact length of
probe.
13
Lvl Ofst
xxx.x
Enter the offset value.
14
VolUnits
Select units for volume.
16
Upr Diel
(Select)
Enter the dielectric range
value of the upper media.
Enter the dielectrics of the upper layer liquid (between 1,4 and 5,0) –
only upper layer dielectrics need to be entered.
18
Senstvty
xxx
Enter sensitivity value
Allows fine adjustment of internal gain.
15
17
19
20
StrapTbl
xx pnts
Enter level/volume
pairs in max 20 steps
Dielctrc
(Select)
Select the dielectric range
value of the lower media
Loop Ctrl
(Select)
Select primary variable (PV)
Set 4mA
xxx.x
Enter the level value
for the 4 mA point.
Enter as per the 3 last digits of the probe partnumber on the nameplate:
- rigid probes, enter value cm or inches,
- flexible probes, enter value in meters or feet
e.g. 705-510A-A11/7MR-A230-218, enter «218» cm probe length.
When entering configuration values from the end of the probe is
cumbersome, an offset can be introduced to determine a new
reference point. This reference point can be either below the probe
(positive offset) or at the probe (negative offset). See page 11
“Terminology”.
Liters «l» or gallons «g».
Liters «l» or gallons «g».
Select: «10–100»
Primary variable is the loop controlling parameter. Select interface level «IfcLevel» or interface volume «Ifc Vol»
A transition zone may exist at the bottom of the probe. See Functional
Specifications Probe, see page 34 and continuing.
21
Set 20mA
xxx.x
Enter the level value
for the 20 mA point.
A transition zone / blocking distance may exist at the top of the probe.
See Functional Specifications Probe, page 34 and continuing.
23
Fault
(Select)
Enter the value for error.
Select «3.6 mA», «22 mA» or hold last value «HOLD». In case of
loop failure, error signal will follow the failing trend; meaning the unit
will show 3.6 mA when the reviewed loop current by the device is
found too low. The unit will show 22 mA in case the reviewed loop
current is found too high.
22
Damping
xx s
Enter the damping factor.
= Quick Start up
18
Comment
%Output
xx.x%
8
10
Configuration
*Status*
*IfcVol*
*%Output*
*Loop*
Action
A damping factor (1-10 seconds) may be added to smooth a noisy
display and/or output due to turbulence.
MENU: STEP BY STEP PROCEDURE – Eclipse 705: Interface & Volume
Advanced configuration
Screen
Comment
Enter distance in
selected level units
24
BlockDis
x.x
25
SZ Fault
(select)
Select the safety zone fault.
26
SZHeight
xx.x
Select the safety zone value
Threshld
Select top level threshold.
27
SZ Alarm
Reset
Reset safety zone latch fault
29
IfcThrsh
(select)
Select interface threshold.
28
Allows to ignore level measurements near the top of the probe,
caused by e.g. condensation, crystalization. Make sure that the liquid
level does NOT enter this zone. Consult factory or the
‘Troubleshooting’ section before entering any value. Normaly to be
used with single rod probe.
Select «None» (None), «3.6mA», «22mA», «Latch 3.6mA» or
«Latch 22mA». When either «Latch 3.6 / 22mA» signals is
selected, the loop current remains in alarm until it is manually reset
with the «SZAlarm» reset screen ( for safety zone explanation see
Terminology - page 11).
Enter safety zone in cm or inches (see Terminology - page 11).
Clear a latched safety zone alarm «SZFault».
Default selection for most common applications is «Fixed».
Default selection for all applications is «CFD». In case the unit does
not track the correct interface layer, select «Fixed».
Poll Adr
xx
Enter HART ID number.
32
Trim Lvl
xx.x
Enter value
to adjust level reading.
34
Trim 20
xxxx
Fine tune the 20 mA point.
LvlTicks
xxxxx
Diagnostic display.
Shows time of flight from fiducial pulse to reflected signal from level.
Medium
Diagnostic display.
Shows type of detected upper liquid; unknown «Unknown» oil only
«Oil Only», thin oil layer «Thin Oil», thick oil layer «Thick
Oil» or no level «Dry Probe».
30
31
33
Loop Mode
Trim 4
xxxx
Select a HART poll address (0-15). Enter 0 for a single transmitter
installation.
Enable/Disable
Determines whether the loop is fixed at 4.0 mA or controlled by the
PV.
Fine tune the 4 mA point.
Attach a mA meter to the output. If the output does not equal 4.0 mA,
adjust the value on the display to equal 4.00 mA.
Set mA Output to any given value to perform loop test .
Allows to compensate for a fixed level deviation.
Attach a mA meter to the output. If the output does not equal
20.0 mA, adjust the value on the display to equal 20.00 mA.
35
Loop Tst
xx.x mA
Enter a mA output value.
37
IfcTicks
xxxx
Diagnostic display.
39
New Pass
xxx
Enter new password.
40
Language
Select language
Select «English», «Français», «Deutsch» or «Espagnol».
DispFact
(select)
Advanced diagnostics.
See page 20.
36
Diagnostics
Action
38
41
42
Mdl705HT
Ver xx.xx
Shows time of flight through the upper liquid layer.
Use arrows to select desired value. Values between 0 and 255.
None, do not adjust.
Factory setting. «Ver» refers to software version.
Strapping table
max. Pt 20 Vol = ...... l
Pt 4 Vol = 3000 l
Pt 3 Vol = 2000 l
Pt 2 Vol = 1000 l
Pt 1 Vol = 0 l
max. Pt 20 Lvl = ...... cm
Pt 4 Lvl = 200 cm
Pt 3 Lvl = 120 cm
Pt 2 Lvl = 50 cm
Pt 1 Lvl = 0 cm
NOTE: Consult page 17 for level offset «Lvl Ofst» details.
19
MENU: STEP BY STEP PROCEDURE: ADVANCED CONFIGURATION
Hidden diagnostic screens. Do not acces without assistance or having followed advanced training.
Screen
1
2
Review Diagnostic messages.
Display mode.
5
HF cable
(select)
Superuser parameter
7
FidSprd
X
4
6
8
History
Reset
Diagnostic display.
FidTicks
xxxx
Diagnostic display.
Fid Type
(select)
Comment
Select «YES» to reveal Factory parameters; «NO» to hide.
A cumulative review of all diagnostic messages. Press the enter button twice to clear.
Shows time in hours that unit is in operation since last power on.
Select «YES» to clear «History».
Select from 1 m (3') or 3,6 m (12') remote.
Shows time of flight from electronics to fiducial pulse. Value should
remain stable within ± 10 ticks.
Diagnostic display.
Value represents the variation of fiducial ticks – a value indicates that
unit is OK, a problematic spread results into an error message.
Change gain.
Value represents the # of gain applied to the fiducial signal.
Select fiducial pulse type.
Requires superuser password.
«positive» or «negative» (selection only allowed for some
probes). Consult factory before changing status.
9
Fid Gain
xxx
11
Conv Fct
xxxx
13
Neg Ampl
xxx
Enter new value.
Requires superuser password.
15
Pos Ampl
xxx
Enter new value.
Requires superuser password.
17
Compensate
(select)
Access compensation screens.
Requires superuser password.
«None» default.
The selection of «Manual» or «Auto» activates the screens 16
through 20 for 7MS/7MQ probes.
19
Targ Ampl
Xxxx
None, do not adjust.
Diagnostic display if «Compsate» is on «Auto».
Shows amplitude of steam reference target.
20
Targ Tks
Xxxx
22
OperMode
(select)
10
12
Diagnostics
History
(current status)
Review factory parameters
Run time
xx h
3
14
16
18
21
23
Window
xxx
None, do not adjust.
Scl Ofst
xxx
None, do not adjust.
Ifc Ampl
xxx
Enter new value.
Requires superuser password.
Signal
xxx
DrateFct
Xxxx
Targ Cal
Xxxx
7xKCorr
xxx
None, do not adjust.
Diagnostic display.
None, do not adjust.
None, do not adjust.
Select operating mode.
Factory setting.
Factory setting.
Factory setting.
Negative amplitude threshold.
Interface amplitude threshold.
Positive amplitude threshold.
Indication of signal strength.
Diagnostic display if «Compsate» is on «Auto».
Shows velocity derating factor.
Diagnostic display if «Compsate» is on «Auto».
Shows # of ticks from fiducial to steam reference target.
Diagnostic display if «Compsate» is on «Auto».
Shows the calibrated # of ticks at ambient temperature.
Selection screen if «Compsate» is on «Auto».
Select run automatically «Run», calibrate «Cal», deactivate «Off».
Enter a value.
Requires additional password.
Distance in mm (regardless .«LvlUnits») from fiducial to user reference point. Only for 7EK (top/bottom) probe.
None, do not adjust.
Shows internal housing temperature.
24
ElecTemp
xxx C
25
Max Temp
xxx C
None, do not adjust.
Diagnostic display, shows maximum internal housing temperature
recorded.
27
SZ Hyst
xx.x
None, do not adjust.
Safety zone Hysterisis, diagnostic factory setting
26
20
DispFact
Select
Action
Min Temp
xxx C
None, do not adjust.
Diagnostic display, shows minimum internal housing temperature
recorded.
PACTware™ – Configuration and Troubleshooting
For more details about the use of PACTware™ and FDT technology, refer to instruction manual 59-601
WHAT IS FDT, PACTware AND DTM
• FDT (Field Device Tool) is a new interface code that
describes the standardization between frame programs
(e.g, PACTware) and DTMs (Device Type Manager).
• PACTware (Process Automation Configuration Tool)
is a frame program. It is a device-independent software
program that communicates with all approved DTMs.
• DTM (Device Type Manager) is a device-specific software driver designed to operate within a FDT compatible
frame program such as PACTware. It includes all special
information needed to communicate with a specific
device (e.g, Pulsar RX5). There are two basic categories
of DTM’s—Communication (HART, Fieldbus®, Profibus®,
etc.) and Field Device (e.g. Pulsar RX5 Radar transmitter).
CONNECTIONS
The following diagram shows a typical hardware configuration. Observe all safety codes when attaching to instrument
loops in hazardous areas or when measuring flammable
media. Computers are not intrinsically safe devices.
24 V DC
HART connections
Power
Transmitter
PC with
HART Serial
Interface
Magnetrol recommends the VIATOR®
USB HART® Interface
from MACTek®
Corporation.
QUICK START
1. Start a project
Open Pactware and add the Hart modem key and then
the Magnetrol instrument to your project.
Select: «Device» – «add device» – select device
(repeat for each device in your project)
Important: Make sure that the COM port settings for
your Hart modem key are correct;
2. Connect the devices
Select in the left window the Magnetrol instrument.
Select: «Device» – «connect» (both modem and
Magnetrol instrument are getting connected)
3. Configure the instrument
Select: «Device» – «parameter» – «Online parameterization»
Open «+ Main Menu» and select «+ Device set
up» – «Calibration»
Parameters can be changed in the window at right, via
the drop down boxes. ENTER confirms the change
online.
4. Troubleshoot / Monitior the instrument
Process trend:
Select: «Device» – «Additional functions» –
«Process Trend»
Process trend: all key data (level % Output, Loop, Signal
strength) can be trended and saved, time scales can be
adapted.
Echo Curve:
Select: «Device» – «Additional functions» –
«Echo Curve»
Echo Curve: shows the actual waveform. The echo
curve is an efficient tool for advanced calibration and
troubleshooting.
Present Status:
Open Main Menu and select «+ Device set up» –
«Diagnostics» – «Present status»
Present status: shows the entire overview of all
detectable faults and warnings. Blank boxes indicate the
healthy condition of the instrument. Ticked off boxes
indicate for a possible fault or warning.
21
PACTware™ – Configuration and Troubleshooting
Echo Curve patterns
Below screens are examples of the most typical echo curves that occur in normal operation / error condition.
Normal oil/water interface
Level with Blocking Distance correction
Normal signal pulses from oil over water
Signal pulse from level. Unit suffered from build up on top
of the probe. The introduced blocking distance (see area in
frame) solves the problem.
Dry Probe
EOP High or Low
Signal pulse from an empty vessel/ cage – displayed message on the unit is «DryProbe» Dry Probe
Signal pulse from an empty vessel or cage but with wrongly entered probe length – displayed message is «EOP
High» or «EOP Low» (as shown in graph). Correct the
probe length in either case.
Weak Signal
Threshold Fixed or CFD
Signal pulse of a weak signal. Displayed message is
«WeakSgnl». Solve this by either to:
- change dielectric setting to a lower range or
- increase the sensitivity
Signal pulse of oil over water level. Always select
«Threshld Fixed» (as shown in the graph). «Threshld
CFD» will track the stronger reflection pulse. In case of level
measurement, the unit will not compensate for the signal
velocity in the upper oil layer and show an erroneous level
reading.
22
CONFIGURATION USING HART®
-
Connection of your Hart communicator:
• at power terminals (+) and (-) in wiring compartment
• at first junction box between unit and control room.
+
Junction
250 Ω < RL < 450 Ω
+
Control
Room
Display
Power
Supply
Current
Meter
CONNECTIONS
IMPORTANT: The digital HART® communication is superimposed on the
4-20 mA loop and requires a min. load resistance of 250 Ω and a max load
resistance of 450 Ω.
CHECK HART®
Before starting the HART® configuration procedure – check if your HART® communicator is equipped with the proper Eclipse Device Descriptors (DD’s).
I/O
Select NO:
Select 4:
Select 5:
Check manufacturer:
HCF Release Date
September 2008
February 2013
start up the communicator
go offline
utility
simulation
Magnetrol
HART Version
Dev V1 DD V2
Dev V2 DD V2
Model
705 3.x
Compatible with software
Version 3.0A and later
Version 3.2A and later
When the proper software version is not found, consult your local HART® Service
Center to load the correct Eclipse DD’s.
HART MENU
I/O Start up the device
1 Enter Device Set Up «DEVICE SET UP»
Press one of the following alphanumeric keys (if no key is sensed after 5 s, the
unit will automatically jump to RUN mode and alternatively show Level/% Output
and Loop signal
1 for entering Calibration «CALIBRATION» (see page 24 for additional information)
2 for entering Basic Set Up «BASIC SET UP» – general HART
3 for Advanced Set Up «ADVANCED SET UP» (see page 24 for additional information)
4 for entering Diagnostics «DIAGNOSTICS» (see page 24 for additional information)
5 for entering Review «REVIEW» to review all settings.
23
CONFIGURATION USING HART®
1 Device Setup
2 Level
3 % Range
4 Loop
5 Device Variables
1
2
3
4
1 Calibration
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
Probe Model
Probe Mount
Measurement Type
Level Units
Probe Length
Level Offset
Volume Parameters
Dielectric Range
Sensitivity
PV is
Variable Selection
4 mA Set Point
20 mA Set Point
Damping
System Fault State
Blocking Distance
SZ Fault State
SZ Height
SZ Alarm Reset
Threshold
Interace Params
Trim Level
Date/Time/Initials
1 Upper Dielectric
2 Interface Threshold
3 Ifc Threshold Ampl
1 SV IS
2 TV IS
3 QV IS
1 Volume Units
2 Strapping Table
3 Table Length
24
2 Basic Setup
1
2
3
4
5
6
Tag
Descriptor
Date
Message
Poll Address
Final Asmbly Num
Level
Volume
IfcLvl
IfcVol
3 Advanced Setup
1
2
3
4
5
6
7
8
9
10
11
12
13
Trim Loop Current
Enter Password
Fiducial Type
Fiducial Gain
Neg Threshold Ampl
Pos Threshold Ampl
Compensation
Factory Settings
SZ Hystersis
Max Temperature
Min Temperature
Reset Temperatures
New User Password
1
2
3
4
Compensation Mode
Upper Dielectric
Target Calibration
7xK Correction
1 Target Oper Mode
2 Target Calib Value
3 Auto Target Calib
1
2
3
4
5
6
7
8
Magnetrol S/N
Device ID
HF Cable
Window
Conversion Factor
Scale Offset
Waveform Selection
Factory Param 2
5 Review
4 Diagnostics
1
2
3
4
5
6
7
8
9
10
11
12
13
Loop Test
Present Status
Status History
Level Ticks
Fiducial Ticks
Fiducial Spread
Signal Strength
Elec Temperature
Interface Ticks
Interface Medium
Derating Factor
Target Amplitude
Target Ticks
1 Faults
2 Warnings
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Seal Leak
Fiducial Spread
Hi Temperature
Lo Temperature
Calib Required
EOP Too Low
Trim Required
Initializing
May Be Flooded
Dry Probe
Weak Signal
System Warning
Warning 1
Warning 2
No Steam Target
Warning 4
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Software Failure
CPU Failure
EEPROM Failure
Default Params
No End of Ramp
Loop Failure
Fiducial Shift
Slope Error
No Probe
No Fiducial
Safety Zone Alrm
No Signal
EOP High
Hi Volume Alrm
Lvl < Probe Length
EOP < Probe Length
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
Model
Manufacturer
Magnetrol S/N
Firmware Version
Tag
Descriptor
Date
Message
Poll Address
Final asmbly num
Device ID
Probe Model
Probe Mount
Measurement Type
Level Units
Probe Length
Level Offset
Volume Units
Dielectric Range
Sensitivity
PV is
SV is
TV is
QV is
4mA Set Point
20mA Set Point
Damping
System Fault State
Blocking Distance
SZ Fault State
SZ Height
Trim Level
4 mA Trim Value
20 mA Trim Value
Threshold
Interface Threshold
Fiducial Type
Fiducial Gain
Neg Threshold Ampl
Pos Threshold Ampl
Ifc Threshold Ampl
Compensation Mode
Upper Dielectric
7xK Correction
SZ Hysteresis
Universal rev
Field dev rev
Software rev
Num req preams
MAINTENANCE
TROUBLESHOOTING
Symptom
LEVEL, % OUTPUT and LOOP values
are all inaccurate.
LEVEL readings are repeatable but
consistently high or low from actual
by a fixed amount.
Problem
Basic configuration data is
questionable.
Configuration data does not
accurately match probe length or tank
height.
Turbulence.
LEVEL, % OUTPUT and LOOP
values all reading low vs. actual
(level or volume applications).
Lower dielectric material over higher
dielectric material, e.g. oil over water.
HART device only: handheld will only
read Universal Commands.
Reconfigure the Probe Length «Prb Ln»
and Offset «Offset». Check also the
Probe Model «Prb Model» / Probe
Mount «Prb Mount»
1) Ensure the Level is accurate.
2) Reconfigure Loop values.
Interface level has significant emulsion. Examine process to reduce/eliminate
emulsion layer.
LEVEL, % OUTPUT and LOOP
values fluctuate.
LEVEL reading on Display is correct
but LOOP is stuck on 4 mA
Solution
High frequency connection.
Coating, clumping or buildup on probe.
Dense, water based foam.
Basic configuration data
is questionable.
Most current Device Descriptors
(DDs) are not installed in handheld.
(see page 20)
LEVEL reading on display is stuck
Software believes probe is flooded
at full scale, LOOP is stuck at 20,5 mA. (level near very top of probe).
Ensure proper probe length «Prb Ln» &
probe Model «Prb Model».
Adjust trim level value by the amount of
noted inaccuracy.
Increase the Damping «Damping» factor until the readings stabilize.
Check Fiducial Spread «FidSprd»
(should be stable within ± 10 counts.)
Select Fixed Threshold option «Fixed»
and/or select dielectric range from top layer.
Expected inaccuracies due to affect on
pulse propagation.
Expected inaccuracies due to affect on
pulse propagation.
Set Hart poll address «POLL ADR» to
«0». If not using HART® multi drop
Contact local HART service center for
the latest DD’s.
Check actual level. If probe is not flooded, check for build up or obstructions
near top of probe. Select higher dielectric range.
Check for condensation in probe connection. Add Blocking Distance.
LEVEL, % OUTPUT and LOOP
values all at maximum level.
Possible configuration issue with single
rod probe
1) Increase Blocking Distance
2) Increase Dielectric Range
LEVEL value reading high when
should be zero.
Transmitter loose or disconnected
from probe.
Ensure transmitter connected securely
to probe.
LEVEL, % OUTPUT and LOOP
values all reading high vs. actual.
HART ERROR MESSAGES
Error
Possible obstruction in tank affecting
single rod probe.
Screen
1) Increase Dielectric Range until
obstruction is ignored.
2) Relocate probe away from obstruction.
Displayed status
Faults
Enlists possible error messages.
OFF: safe status
ON: highlighted error is occurring – see
page 27
Warnings
Enlists warning messages.
History
Built in log of the last 26 error messages. See page 20.
OFF: safe status
ON: highlighted warning is occurring –
see page 26
PACTware™ PC Program
The Eclipse Model 705 offers the ability to do Trending and Echo Curve analysis using a PACTware DTM. This is a powerful troubleshooting tool that can aid in the resolution of some of the Error Messages shown above.
Refer to Bulletins 59-101 and 59-601 for more information.
25
MAINTENANCE
WARNING MESSAGES
A warning message identifies the status of the instrument. A warning message does not necessarily require immediate action but may
require close attention and/or follow up. The warning message will be displayed on the unit and/or selected on the Pactware screen while
the output signal will remain normal.
Display
Message
Action
Comment
None
Normal operating mode
None
Program is Initializing, level
reading held at 4 mA set point.
This is a transient condition.
None
Normal message for a dry
probe. End of probe signal is
being detected.
1) Set transmitter to lower dielectric range
2) Increase sensitivity
Signal amplitude is lower than
desired.
1) Decrease level in vessel
2) Set transmitter to lower dielectric range
3) Replace with Model 7MR Overfill probe
Loss of level signal possibly
due to flooding, twin rod
probes only
1) Check connection between probe and transmitter
2) Check for moisture on top of probe
3) Consult factory
Fiducial Ticks variation is
excessive.
1) Transmitter may need to be moved to ensure ambient temperature
is within specification
2) Change to remote mount transmitter
3) Use sunshade
Present temperature in
electronics compartment is
above +80° C
1) Transmitter may need to be moved to ensure ambient temperature
is within specification
2) Change to remote mount transmitter
Present temperature in
electronics compartment is
below -40° C.
Consult factory
TrimReqd
Unexpected but non-fatal
software event
Consult factory
Cal Reqd
Factory set Loop values are
defaults, loop output may be
inaccurate
Consult factory
Factory set default calibration
parameters are in use, level
reading may be inaccurate
OK
Initial
DryProbe
WeakSgnl
Flooded?
Fid Sprd*
Hi Temp
Lo Temp
Sys Warn
26
MAINTENANCE
ERROR MESSAGES
An error message identifies a possible instrument failure and requires an action. The error message will be displayed on the unit and/or
selected on the Pactware screen while the output signal will shift to the selected error output (3.6mA, 22mA or HOLD).
Display
Message
HiVolAlm
SlopeErr
LoopFail
No Ramp
DfltParm
EE Fail
CPU Fail
SfwrFail
Action
Comment
Verify strapping table is entered correctly.
Level more than 5% above
highest point in strapping table.
Consult factory
Ramp circuit generating
improper voltage
Consult factory
Note: In case of loop failure, error signal will follow the failing trend;
meaning the unit will show 3.6 mA when the reviewed loop current by
the device is found too low. The unit will show 22 mA in case the
reviewed loop current is found too high.
Loop current differs from
expected value
Consult factory
No End-of-Ramp signal detected
Consult factory
Internal non-volatile parameters
have been defaulted
Consult factory
EEPROM error allowing watchdog timer to expire
Consult factory
A-D converter time out allowing
watchdog timer to expire
Consult factory
A fatal software error allowing
watchdog timer to expire
EOP < Probe 1) Ensure probe length is entered correctly
Length
2) Set transmitter to a lower dielectric range
3) Set threshold to «fixed»
4) Consult factory
Lvl < Probe 1) Verify entered probe length
Length
2) Change threshold to «fixed»
EOP High
NoSignal
No Fid
FidShift
No Probe
SZ Alarm
End of Probe signal is out of
range
Apparent position of the upper
level pulse is lower than the
end of probe
1) Ensure probe length is entered correctly
2) Increase blocking distance (only for single or twin GWR probes)
3) Consult factory
End of Probe signal is out of
range
1)
2)
3)
4)
Ensure dielectric setting is correct for measured medium
Increase sensitivity
Confirm that the probe type is proper for the dielectric of the medium
Consult factory
No level signal being detected.
1)
2)
3)
4)
Check connection between probe and transmitter
Check for moisture on top of probe
Check for damaged gold pin on the high frequency connector
Consult factory
Fiducial signal is not being
detected
1)
2)
3)
4)
Check connection between probe and transmitter
Check for moisture on top of probe
Check for damaged gold pin on the high frequency connector
Consult factory
FidTicks shifted from expected
value
1) Ensure proper connection between probe and transmitter
2) Check for damaged gold pin on the high frequency connector
Decrease level in tank
When in «SZ Fault», «Latch 3.6 mA» or «Latch 22 mA» was
selected, reset with «SZ Alarm Reset»
Electronics does not sense that
a probe is attached
Safety Zone alarm has been
tripped, loop current fixed at
SZ Fault
27
MAINTENANCE
TROUBLESHOOTING APPLICATIONS: Level
Most frequent application problems that may occur, media
buildup on the probe and stratification, are covered here.
Media buildup on the probe is not a problem in most
cases–Eclipse circuitry typically works very effectively.
Media buildup should be viewed as two types – Film
Coating and Bridging.
Recommended guidelines to select the right GWR probe:
- Relatively clean liquids: use the standard coax GWR
probes
- Possible build up: use the enlarged coax or twin rod
GWR probe
- Extreme build up: use the single rod GWR probe
• Continuous Film Coating
The most typical of coating problems where the media
forms a continuous coating on the probe. Eclipse will
continue to measure effectively with some small degradation in performance. A problem can develop if the
product begins to buildup on the spacers that separate
the probe elements. High dielectric media (e.g, waterbased) will cause the greatest error.
• Bridging
Media that is viscous or solid enough to form a clog, or
bridge, between the elements causes the greatest
degradation in performance. High dielectric media (eg.
water-based) will show as level at the location of the
bridging.
• Stratification/Interface
The Eclipse transmitter is designed to measure the first
air/media interface it detects, when configured for level
measurement only. It will not measure further liquid/
liquid interfaces. However, a low dielectric over a high
dielectric application can cause a measurement problem
if the level of the low dielectric medium becomes small
enough (a few cm) to cause the electronics to trigger on
the high dielectric medium that lies beneath it. Select the
Fixed Threshold option to read the upper medium.
Example: oil over water.
Bridging
Bridging
Film
Coating
Film
Coating
Threshold
«Fixed»
GOOD
Air/gas
Threshold
«CFD»
WRONG
Outer tube
<
ε
>
ε
r
r
Inner rod
Continuous film coating / Bridging
Stratification/Interface
TROUBLESHOOTING APPLICATIONS: Interface
It is not uncommon for interface applications to have an
emulsion layer form between the two media. This emulsion
layer may pose problems for Guided Wave Radar as it may
decrease the strength of the reflected signal. Since the
properties of this emulsion layer are difficult to quantify,
applications with emulsion layer should be avoided with
Eclipse.
Oil
ε 2.0
r
Emulsion
Layer
Water
r 80
ε
28
MAINTENANCE
TROUBLESHOOTING APPLICATIONS: Single Rod type GWR probe
Most frequent application problems that may occur, media
buildup on the probe and stratification, are covered here.
Significant buildup on the probe is not a problem in most
cases–Eclipse circuitry typically works very effectively.
Nozzles
• 2" diameter minimum
• Nozzles (only for 7MF/7MH/7MJ/7M1/7M2)
Nozzles can create false echoes that can cause diagnostic messages and/or errors in measurement. If end
of probe high «Eop High» is displayed when first configuring the instrument:
1. Ensure the probe length «Prb Ln» as entered in the
software is equal to the actual probe length (see page
12, item 9). This value must be changed if the probe
is cut shorter from the original length.
2. Increase the blocking distance «BlockDis» value
until the message is eliminated; 20 mA point may
need to be lowered.
3. Increase the dielectric range a small amount or
decrease the sensitivity to aid in reducing echoes in
nozzle. Increasing the dielectric settings may cause
instrument to lose level of lower dielectric media; consult factory.
• Obstructions (only for 7MF/7MH/7MJ/7M1/7M2)
If the level reading repeatedly locks on to a specific level
higher than the current level, it may be caused by a
metallic obstruction. Obstructions in the vessel (e.g.
pipes, ladders) that are located close to the probe may
cause the instrument to show them as level.
1. Refer to the Probe Clearance Table
2. Increase the dielectric range a small amount or
decrease the sensitivity to aid in reducing disturbing
echoes in nozzle. Increasing the dielectric settings
may cause instrument to lose level of lower dielectric
media; consult factory.
• Coating/build-up (only for 7MF/7MH/7MJ/7M1/7M2)
The Eclipse® 705 wih Single Rod Probe was designed to
operate effectively in the presence of media building up.
Some expected error may be generated based upon the
following factors:
¨ Dielectric of the media that created the coating
≠ Thickness of the coating
Æ Length of the coating above the present level
In case build up is picked up as level, increase the
dielectric range a small amount or decrease the sensitivity.
• Coating/build-up (only for 7M5/7M7)
Continuous film coating is where the media forms a thin
continuous coating on the probe. Eclipse® will continue
to measure effectively with some degradation in performance. The degradation is proportional to the dielectric
of the media and the thickness of the coating up to a
degree that the unit will see coating as a level. Higher
dielectric media (eg. water based) will show sooner as a
level at the location of the build up.
• Ratio of diameter: length should be > 1:1
If not, set blocking distance at 2 x nozzle height
• Do not use pipe reducers (restriction)
Obstruction
Probe clearance table
Distance to probe
< 150 mm (6")
> 150 mm (6")
> 300 mm (12")
> 450 mm (18")
Acceptable objects
Continuous, smooth, parallel,
conductive surface (e.g. metal
tank wall); probe should not touch
tank wall
< 1"/DN25 diameter pipe and
beams, ladder rungs
< 3"/DN80 diameter pipe and
beams, concrete walls
All remaining objects
≠
Æ
Coating Build-up
¨
29
REPLACEMENT PARTS
4
5
3
5
2
3
3
1
Hygienic
Industrial
CAUTION: the electronic module connects to the antenna via the “High frequency connector”. This part is
extremely sensitive and brittle and requires to be handled very careful. It is recommended to exchange complete
amplifier heads instead of electronic modules in the field.
Partn°:
7 0 5
Digit in partn°:
5
1
2
3
5
1
30
2
or
3
Digits
6&7
X 1 2 3
00
0A
00 or 0A
Digits
8
all
4 5 6 7
8 9 10
Serial n°:
See nameplate, always provide complete partn° and
serial n° when ordering spares.
X = product with a specific customer requirement
Electronic Module (1)
Replacement part
9
Hart
00
0A
A0
AA
00 or 0A
A0 or AA
00
0A
00 or 0A
5
1, 2,
7 or
8
3 or
9
1, 2,
7 or 8
3 or 9
1, 2,
7 or 8
3 or 9
Z31-2835-002
Z31-2835-001
Z31-2835-004
Z31-2835-003
089-7254-001
089-7254-003
Several parts are available for quick shipment, within max.
1 week after factory receipt of purchase order, through the
Expedite Ship Plan (ESP).
Parts covered by ESP service are conveniently grey coded
in the selection tables.
Housing “O” ring (3)
Digit 9
Replacement part
1, 2, 7 or 8
3 or 9
FF
Z31-2841-002
Z31-2841-001
089-7254-002
Digit 9
Profibus PA
Z31-2846-002
Z31-2846-001
089-7254-004
Wiring board (2)
Replacement part
9
Hart
1, 2,
1, 2, A or B 7 or 8
3, 4, C, D, E,
or F
EXPEDITE SHIP PLAN (ESP)
1 or 7
2 or 8
7
0
Z30-9151-001
A
Z30-9151-003
0
A
FF - Profibus PA
Z30-9151-004
Digits
8
all
all
1, 2, A, B, E
or F
3 or 4
C or D
all
all
012-2201-237
012-2201-155
Housing cover (4)
Replacement part
004-9225-002
004-9225-003
Housing cover (5)
9
1 or 7
2 or 8
1 or
7
2 or 8
3 or
9
Replacement part
004-9225-002
004-9225-003
036-4413-005
036-4413-001
036-4410-003
036-4413-012
032-3934-001
036-5702-002
REPLACEMENT PARTS
6
7
11
Bottom spacer
- 7MF/7MJ single rod
GWR probe
- 7MG cage GWR probe
(2"/DN50)
10
9
8
6
Bottom spacer
- 7MG cage GWR probe
(other than 2"/DN50)
Description
6&7
7MF-B
6&7
N°
7MF-A
7MF-C
7MJ-A
7MJ-B
7MJ-C
9
8
9
089-9114-002
10
089-9114-001
089-9114-003
PEEK spacer & set pin
089-9114-005
089-9114-006
089-9114-007
Replacement part
7MG-C (2"/DN50)
089-9114-003
7MG (other than
2"/DN50)
Spacer 7MB
Twin rod
N°
TFE spacer & set pin
089-9114-001
10
Cable weight
7M5 dual flexible cable
for solids
13
Replacement part
Description
7MG-A (2"/DN50)
Cable weight
7M2 Single flexible cable
for solids
Cable weight
7M1 Single flexible cable
7M7 Dual flexible cable
Spacer and set pin - cage probes
6 & 7 7MG-B (2"/DN50)
6
9
8
Spacer and set pin - rigid probes
N°
12
8
9
11
12
N°
13
Cable weights - flexible probes
Description
Replacement part
7M1
7M7
7M2/7M5
cable rope clip
7M2-316 (1.4401)
7M5-316 (1.4401)
089-9120-001
089-9121-001
010-1731-001
(Qty 2 required)
004-8778-001
004-8778-002
Spacer - twin rod probe
Description
Replacement part
7MB probe spacer
consult factory
kit
089-9114-002
consult factory
31
TRANSMITTER SPECIFICATIONS
FUNCTIONAL/PHYSICAL
Description
Power (at terminals)
HART®:
- Weatherproof / ATEX flameproof enclosure / ATEX non sparking: 11 to 36 V DC
- ATEX Intrinsically Safe: 11 to 28,4 V DC
Foundation Fieldbus™ / Profibus PA™:
- Weatherproof / ATEX flameproof enclosure / ATEX FNICO: 9 to 32 V DC
- ATEX FISCO: 9 to 17,5 V DC
4-20 mA with HART®, 3,8 mA to 20,5 mA useable (meets NAMUR NE 43) – HART 6,
Foundation Fieldbus™ H1 or Profibus PA™ H1
15 cm to 22 m (6" to 72.18') depending on selected probe
Analog: 0,01 mA
Display: 0,1 (cm or inch)
Output
Span
Resolution
Loop Resistance
Damping
Diagnostic Alarm
User Interface
630 Ω @ 20,5 mA - 24 V DC
Adjustable 0-10 s
Adjustable 3,6 mA, 22 mA, HOLD last output
HART® communicator, AMS® or PACTware™, Foundation Fieldbus™, Profibus PA™
and/or 3-button keypad
Display
Menu Language
Housing Material
Approvals
SIL¬
(Safety Integrity Level)
Electrical Data
Standard
electronics
Enhanced
electronics
Equivalent Data
Shock/Vibration Class
Surge protection
Net weight
Overall Dimensions
Foundation Fieldbus™
specifications
Cast aluminium
Stainless steel
ITK Version
H1 Device Class
Function Blocks
Execution time
Profibus PA
specifications
Specification
Quiescent current draw
DD/CFF files
Device revision
Digital communication
protocols
Function Blocks
Execution time
Quiescent current draw
GSD files
2-line x 8-character LCD
English/Spanish/French/German (Foundation Fieldbus™, Profibus PA™: English)
IP 66/Aluminium A356T6 (< 0.20 % copper) or stainless steel
ATEX II 3 (1) G EEx nA [ia] IIC T6, non sparking (probe can be used in flammable liquids)
ATEX II 3 (1) G EEx nA [nL][ia] IIC T6, FNICO – non incendive¿ (probe can be used in
flammable liquids)
ATEX II 1 G Ex ia IIC T4 Ga, intrinsically safe
ATEX II 1 G Ex ia IIC T4 Ga, FISCO – intrinsically safe¿
ATEX II 1/2 G Ex d[ia Ga] IIC T6 Gb¡
ATEX II 1/2 D Ex t[ia Da] IIIC T85°C Db IP66¡
IEC Ex d[ia Ga] IIC T6 Gb
IEC Ex t[ia Da] IIIC T85°C Db IP66
IEC Ex ia IIC T4 Ga, intrinsically safe
IEC Ex ia IIC T4 Ga, FISCO – intrinsically safe¿
IEC Ex ic[ia Ga] IIC T4 Gc
EN 12952-11 and EN 12953-9 CE approved for steam drums as primary level safety
device
TÜV – WHG § 63, VLAREM II 5.17-7
LRS – Lloyds Register of Shipping (marine applications)
Other approvals are available, consult factory for more details
Functional safety to SIL 1 as 1oo1 / SIL 2 as 1oo2 in accordance to IEC 61508 – SFF of
84,5 %
Functional safety to SIL 2 as 1oo1 in accordance to IEC 61508 – SFF of 91 %
Certified for use in SIL 3 loops.
Ui = 28,4 V, li = 124 mA, Pi = 0,84 W (HART®)
Ui = 17,5 V, li = 380 mA, Pi = 5,32 W (Foundation Fieldbus™ / Profibus PA™)
Ci = 2,2 nF, Li = 3 µH (HART®)
Ci = 3 nF, Li = 3 µH (Foundation Fieldbus™ / Profibus PA™)
ANSI/ISA-S71.03 Class SA1 (Shock), ANSI/ISA-S71.03 Class VC2 (Vibration)
Meets CE EN 61326 (1000V)
2,7 kg (6.0 lbs) – transmitter head / electronics only
5,7 kg (12.6 lbs) – transmitter head / electronics only
H 214 mm (8.43") x W 111 mm (4.38") x D 188 mm (7.40")
5.0
Link Master (LAS) – selectable ON/OFF
1 x RB, 4 x AI, 1 x TB and 1 x PID
AI = 15 ms, PID = 40 ms
15 mA
Available at www.fieldbus.org
0x01
Version 3.0 MBP (31.25 kbits/sec)
1 x PB, 4 x Al blocks, 1 x TB
15 ms
15 mA
Available at www.profibus.com
¿ Foundation Fieldbus™ and Profibus PA™ units.
¡ For ATEX flameproof enclosure units use Ex d bushing material STYCAST 2057 FR.
¬ Not applicable for Foundation Fieldbus™ and Profibus PA™ units.
32
TRANSMITTER SPECIFICATIONS
PERFORMANCE
Description
Reference Conditions with a 1,8 m (72")
coaxial type GWR probe
Coaxial/twin lead probes
Linearity¡
Single lead probes
Coaxial/twin lead probes
Accuracy¡
Single lead probes
7MT/7ML interface
Resolution
Repeatability
Hysteresis
Response Time
Warm-up Time
Ambient Temp.
Process Dielectric Effect
Operating Temp. Effect
Humidity
Electromagnetic Compatibility
Specification
Reflection from liquid, with dielectric in center of selected range, at +20 °C (70 °F) with
CFD threshold¿
< 0,1 % of probe length or 2,5 mm (0.1"), whichever is greater
< 0,3 % of probe length or 8 mm (0.3"), whichever is greater
< 0,1 % of probe length or 2,5 mm (0.1"), whichever is greater
± 0,5 % of probe length or 13 mm (0.5"), whichever is greater
± 25 mm (1")
± 2,5 mm (0.1")
< 2,5 mm (0.1")
< 2,5 mm (0.1")
< 1 second
< 5 seconds
-40 °C to +80 °C (-40 °F to +175 °F)
– blind transmitter
-20 °C to +70 °C (-5 °F to +160 °F)
– with digital display
-40 °C to +70 °C (-40 °F to +160 °F)
– for Ex ia and Ex d[ia] with blind transmitter
-20 °C to +70 °C (-5 °F to +160 °F)
– for Ex ia and Ex d[ia] with digital display
< 7,5 mm (0.3") within selected range
Approx. +0,02 % of probe length/°C for probes ≥ 2,5 m (8')¬
0-99 %, non-condensing
Meets CE requirements (EN 61326: 1997 + A1 + A2) and NAMUR NE 21
(Single and Twin-Rod probe must be used in metallic vessel or stillwell)
¿ May degrade for 7MD/7ML probe or with fixed threshold.
¡ Top 600 mm (24") of twin rod probe: 30 mm (1.18").
Top 1220 mm (48") of single rod: application dependant.
Accuracy may degrade when using compensation.
¬ Accuracy may degrade slightly < 2,5 m (8')
33
PROBE SPECIFICATIONS
Description
Materials
Probe diameter
Mounting
Process Connection
Probe length
Transition Zone¿
Process Temp.¡
Max. Process Pressure¡
Max. Viscosity
Dielectric Range
Vacuum Service
Media coating
IntDescription
Probe
Process seal
Spacers
Small coax
Enlarged
Small coax
All
Top
Bottom
Max
Min
Materials
Probe
Process seal
Spacers
Probe diameter
Small coax
Mounting
Process Connection
Probe length
Transition Zone¿
Process Temp.¡
Max. Process Pressure¡
Max. Viscosity
Dielectric Range
Enlarged
Small coax
All
Top
Bottom
Max
Min
Small coax
Enlarged
Vacuum service
Media coating
7MR/7MM: overfill protection coaxial probe
316/316L (1.4401/1.4404), Hastelloy® C (2.4819) or Monel® (2.4360)
Teflon® with Viton® GFLT, Aegis PF 128 or Kalrez® 4079 (consult factory for alternatives)
Teflon®
Inside rod 8 mm (0.315") – outer tube 22,5 mm (0.88")
Stainless steel: inside rod 16 mm (0,63") – outer tube 45 mm (1.75")
Hast. C / Monel®: inside rod 16 mm (0,63") – outer tube 49 mm (1.93")
External cage and/or in-tank mounting
Threaded: 3/4" NPT or 1" BSP (G 1")
Flanged: various ANSI, EN (DIN) or torque tube mating flanges
From 60 cm to 610 cm (24" to 240")
0 mm (0")
εr: 1,4 = 150 mm (6")/εr: 80 = 25 mm (1")
+200 °C @ 18,6 bar (+400 °F @ 270 psi)
-40 °C @ 51,7 bar (-40 °F @ 750 psi)
70 bar @ +20 °C (1000 psi @ +70 °F)
Small coax: 500 mPa.s (cP); Enlarged coax: 2000 mPa.s (cP)
1,4 to 100
Negative pressure but not hermetic seal
In case of media coating, select 7MM probe
7MD/7ML: high pressure / high temperature GWR probe
316/316L (1.4401/1.4404), Hastelloy® C (2.4819) or Monel® (2.4360)
Borosilicate / Inconel® X-750
7Mx-A, B and C: Ceramic
7Mx-W: Teflon®
7Mx-V: High Temp PEEK
7Mx-N, P and R: PEEK
Inside rod 8 mm (0.315) – outer tube 22,5 mm (0,88")
Stainless steel: inside rod 16 mm (0,63") – outer tube 45 mm (1.75")
Hast. C / Monel®: inside rod 16 mm (0,63") – outer tube 49 mm (1.93")
External cage and/or in-tank mounting
Threaded: 3/4" NPT or 1" BSP (G 1")
Flanged: various ANSI, EN (DIN) or torque tube mating flanges
From 60 cm to 610 cm (24" to 240")
0 mm (0")
εr: 1,4 = 150 mm (6") / εr: 80 = 25 mm (1")
+425 °C @ 103 bar (+800 °F @ 1500 psi) for 7Mx-A, B and C
+345 °C @ 324 bar (+650 °F @ 4700 psi) for 7Mx-V, N, P and R
+200 °C @ 393 bar (+400 °F @ 5700 psi) for 7Mx-W
-196 °C @ 138 bar (-320 °F @ 2000 psi)
431 bar @ +20 °C (6250 psi @ +70 °F)
Small coax: 500 mPa.s (cP); Enlarged coax: 2000 mPa.s (cP)
1,4 to 100 for 7Mx-W
1,7 to 100 for 7Mx-V
2,0 to 100 for 7Mx-A, B and C
Level:
Interface:
Probes ≤ 2,5 m: εr ≥ 1,4 with single bottom spacer Probes > 2,5 m: εr ≥ 1,7
Upper liquid: εr ≥ 1,4 or 1,7 (see above) and ≤ 5 Lower liquid: εr ≥ 15
Full vacuum (Helium leak < 10-8 cc/s @ 1 atmosphere vacuum)
In case of media coating, select 7ML probe
¿ Transition Zone (zone with reduced accuracy) is dielectric dependent; εr = dielectric permitivity.
It is recommended to set 4-20 mA signal outside transition zone.
¡ See graphs at page 39 and 40.
34
PROBE SPECIFICATIONS
Description
Materials
Probe
Process seal
Spacers
Probe diameter
Mounting
Process Connection
Probe length
Transition Zone¿
Top
Process Temp.¡
Max. Process Pressure¡
Max. Viscosity
Bottom
Max
Min
Dielectric Range
Vacuum service
Media coating
Description
Materials
Probe diameter
7MQ: saturated steam GWR probe
High Temp PEEK
Silicon nitride
316/316L (1.4401/1.4404)
High Temp PEEK with Aegis PF 128
Inside rod 8 mm (0.315) –
outer tube 22,5 mm (0,88")
External cage and/or in-tank mounting
Threaded: 3/4" NPT or 1" BSP (G 1")
Flanged: various ANSI, EN (DIN) or torque
tube mating flanges
Probe
Process seal
Probe length
Blocking distance (top)
Transition Zone¿ (bottom)
Max
Min
Max Process Pressure¡
Max Viscosity
Dielectric Range
Vacuum service
Media coating
High Temp PEEK with Aegis PF 128
Alumina
Inside rod 8 mm (0.315) –
outer tube 32 mm (1,25")
Threaded: not available
Flanged: various ANSI, EN (DIN) or torque
tube mating flanges
From 60 cm to 450 cm (24" to 177")
200 mm (8"); consult factory for overfill applications
εr ≥ 10 = 25 mm (1")
+300 °C @ 88 bar (+575 °F @ 1275 psi)
-15 °C @ 207 bar (0 °F @ 3000 psi)
88 bar @ +300 °C (1275 psi @ +575 °F)
500 mPa.s (cP)
10 to 100
Negative pressure but not hermetic seal
Not applicable
Process Connection
Process Temp.¡
7MS: saturated steam GWR probe
7MF (industrial): standard single rod
316/316L (1.4401/1.4404), Hastelloy C (2.4819),
Monel® (2.4360), or PFA insulated 316/316L
(1.4401/1.4404)
®
TFE with Viton® GFLT, Aegis PF 128 or Kalrez®
4079 (consult factory for alternatives)
Bare: 13 mm (0.50") PFA coated: 16 mm (0.625")
Threaded: 2" NPT or 2" BSP (G 2")
Flanged: various ANSI or EN (DIN) flanges
+345 °C @ 155 bar (+650 °F @ 2250 psi)
155 bar @ +345 °C (2250 psi @ +650 °F)
7MJ: HTHP single rod
316/316L (1.4401/1.4404), Hastelloy® C (2.4819)
or Monel® (2.4360)
PEEK with Aegis PF 128
Bare: 13 mm (0.50")
From 60 cm to 610 cm (24" to 240")
120 mm up to 910 mm (4.8" up to 36") - depending probe length (adjustable)
εr ≥ 10: 25 mm (1")
+150 °C @ 27,6 bar (+300 °F @ 400 psi)
7MF-F: -40 °C @ 13,8 bar (-40 °F @ 200 psi)
Other 7MF-probes: -40 °C @ 51,7 bar (-40 °F @
750 psi)
70 bar @ +20 °C (1000 psi @ +70 °F)
+315 °C @ 155 bar (+600 °F @ 2250 psi)
-15 °C @ 245 bar (0 °F @ 3550 psi)
245 bar @ +20 °C (3550 psi @ +70 °F)
10.000 mPa.s (cP) – consult factory in case of agitation/turbulence
εr: 10-100 (depending installation conditions, down to εr ≥ 1,9)
Negative pressure but not hermetic seal
Max error of 10 % of coated length. % Error is related to dielectric of medium, thickness of coating and
coated probe length above level.
¿ Transition Zone (zone with reduced accuracy) is dielectric dependent; εr = dielectric permitivity.
It is recommended to set 4-20 mA signal outside transition zone / blocking distance.
¡ See graphs at page 39 and 40.
35
PROBE SPECIFICATIONS
Description
Materials
Probe diameter
Probe length
7MF-E/G/H & 7MH: hygienic single rod probe
316/316L (1.4401/1.4404), Hastelloy® C22 (2.4602) or AL-6XN stainless steel (UNS N08367); 7MH
Probe
also available in 316L (1.4435) stainless steel
7MF: PTFE (GRAS 21CFR177-1550 and USP <88> Class VI at 121 °C)
Process seal
7MH: PEEK & 'O'-ring in Viton or EPDM (GRAS 21CFR177-1550 and USP <88> Class VI at 121 °C)
Blocking distance (top)
Transition Zone➀ (bottom)
Process Temp.¡
Max
Min
Max Process Pressure¡
Max Viscosity
Dielectric Range
Materials
Probe diameter
0 mm up to 910 mm (0" up to 36") - depending probe length (adjustable)
εr ≥ 10: 25 mm (1")
+150 °C @ 13,8 bar (+300 °F @ 200 psi) for 7MH with Viton GF ‘O’-rings and 7MF
+120 °C @ 13,8 bar (+250 °F @ 200 psi) for 7MH with EPDM ‘O’-rings
-40 °C @ 13,8 bar (-40 °F @ 200 psi)
13,8 bar @ +150 °C (200 psi @ +300 °F) for 7MH with Viton GF ‘O’-rings and 7MF
13, 8 bar @ +120 °C (200 psi @ +250 °F) for 7MH with EPDM ‘O’-rings
10.000 mPa.s (cP) – consult factory in case of agitation/turbulence
Max error of 10 % of coated length. % Error is related to dielectric of medium, thickness of coating and
coated probe length above level.
Probe
7M1 (liquids) / 7M2 (solids): single flexible
Probe length
Blocking distance (top)
Transition Zone¿ (bottom)
Max
Min
Max Process Pressure¡
Max Viscosity
Dielectric Range
Mechanical load
Pull-down force
Vacuum service
Media coating
Threaded: 2" NPT or 2" BSP (G 2")
Flanged: various ANSI or EN (DIN) flanges
From 2 m (6.56') to max 22 m (72.18')
120 mm up to 910 mm (4.8" up to 36") - depending
300 mm to 500 mm (12" to 20")
probe length (adjustable)
305 mm (12")
7M1/7M7: +150 °C @ 27,6 bar (+300 °F @ 400 psi)
7M2/7M5: +65 °C @ 3,45 bar (+150 °F @ 50 psi)
7M1/7M7: -40 °C @ 51,7 bar (-40 °F @ 750 psi)
7M2/7M5: -40 °C @ 3,45 bar (-40 °F @ 50 psi)
7M1/7M7: 70 bar @ +20 °C (1000 psi @ +70 °F)
7M2/7M5: 3,45 bar @ +20 °C (50 psi @ +70 °F)
10.000 mPa.s (cP) – consult factory in case of
agitation/ turbulence
7M1: r: 10-100 (depending installation conditions,
down to r ≥ 1,9)
7M2: r: 4-100
ε
ε
ε
It is recommended to set 4-20 mA signal outside transition zone / blocking distance.
¡ See graphs at page 39 and 40.
1500 mPa.s (cP)
εr: 1,9-100
7M1: 9 kg (20 lbs)
7M2: 1360 kg (3000 lbs)
7M5: 1360 kg (3000 lbs)
Negative pressure but not hermetic seal
Max error of 10 % of coated length. % Error is related to dielectric of medium, thickness of coating and
coated probe length above level.
¿ Transition Zone (zone with reduced accuracy) is dielectric dependent; εr = dielectric permitivity.
36
7M5 (solids) /7M7 (liquids): twin flexible
316 SST (1.4401)
FEP coated 316 SST (1.4401)
7M1/7M7: Teflon® with Viton® GFLT, Aegis PF 128 or Kalrez® 4079 (consult factory for alternatives)
Process seal
7M2/7M5: Teflon® with Viton® GFLT
7M1: 5 mm (0.19")
6 mm (0.25")
7M2: 6 mm (0.25")
Process Connection
Process Temp.¡
From 30 cm to 610 cm (12" to 240") (selectable per 1 cm)
εr 10-100 (depending installation conditions, down to εr ≥ 1,9) – liquids
Media coating
Description
13 mm (0.50") or 6 mm (0.25")
PROBE SPECIFICATIONS
Description
Materials
Probe diameter
Mounting
Process Connection
Probe length
Transition Zone¿
Process Temp.¡
Max. Process Pressure¡
Max. Viscosity
Dielectric Range
Vacuum Service
Media coating
Description
Materials
Probe diameter
Mounting
Process Connection
Probe length
Transition Zone¿
Process Temp.¡
Max. Process Pressure¡
Max. Viscosity
Dielectric Range
Probe
Process seal
Bottom spacer
2" cage
3" cage
4" cage
Top
Bottom
Max
Min
Level
Interface
Probe
Process seal
Spacers
Small coax
Enlarged
Small coax
all
Top
Bottom
Max
Min
Vacuum service
Media coating
7MG: cage GWR probe
316/316L (1.4401/1.4404), Hastelloy® C (2.4819) or Monel® (2.4360)
Teflon® with Viton® GFLT, Aegis PF 128 or Kalrez® 4079 (consult factory for alternatives)
2" cage: Teflon®; 3" and 4" cage: PEEK
13 mm (0.50")
19 mm (0.75")
25 mm (1")
In a 2", 3" or 4" cage / schedule pipe stillwell or bridle
Flanged: various ANSI or EN (DIN) flanges
From 60 cm to 610 cm (24" to 240")
0 mm (0")
εr: 1,4 = 150 mm (6")/εr: 80 = 50 mm (2")
+200 °C @ 18,6 bar (+400 °F @ 270 psi)
-40 °C @ 51,7 bar (-40 °F @ 750 psi)
70 bar @ +20 °C (1000 psi @ +70 °F)
10.000 mPa.s (cP)
εr ≥ 1,4
Upper liquid: εr ≥ 1,4 and ≤ 5
Lower liquid: εr ≥ 15
Negative pressure but not hermetic seal
Max error of 10 % of coated length. % Error is related to dielectric of medium, thickness of
coating and coated probe length above level.
7MT/7MN: interface GWR probe
316/316L (1.4401/1.4404), Hastelloy® C (2.4819) or Monel® (2.4360)
Teflon® with Viton® GFLT, Aegis PF 128 or Kalrez® 4079 (consult factory for alternatives)
Teflon®
inside rod 8 mm (0.315") – outer tube 22,5 mm (0.88")
Stainless steel: inside rod 16 mm (0.63") – outer tube 45 mm (1.75")
Hast. C / Monel®: inside rod 16 mm (0.63") – outer tube 49 mm (1.93")
External cage and/or in-tank mounting
Threaded: 3/4" NPT or 1" BSP (G 1")
Flanged: various ANSI, EN (DIN) or torque tube mating flanges
From 60 cm to 610 cm (24" to 240")
0 mm (0")
εr: 1,4 = 150 mm (6")/εr: 80 = 50 mm (2")
+200 °C @ 18,6 bar (+400 °F @ 270 psi)
-40 °C @ 51,7 bar (-40 °F @ 750 psi)
70 bar @ +20 °C (1000 psi @ +70 °F)
Small coax: 500 mPa.s (cP); Enlarged coax: 2000 mPa.s (cP)
Upper liquid: εr ≥ 1,4 and ≤ 5
Lower liquid: εr ≥ 15
Negative pressure but not hermetic seal
In case of media coating, select 7MN probe
¿ Transition Zone (zone with reduced accuracy) is dielectric dependent; εr = dielectric permitivity.
It is recommended to set 4-20 mA signal outside transition zones.
¡ See graphs at page 39 and 40.
37
PROBE SPECIFICATIONS
Description
Materials
Probe diameter
Mounting
Probe
Process seal
Spacers
Process Connection
Probe length
Transition Zone¿
Process Temp.¡
Max. Process Pressure¡
Max. Viscosity
Dielectric Range
Vacuum service
Media coating
Description
Materials
Probe diameter
Cage
Top
Bottom
Max
Min
Probe
Process seal
Bottom spacer
Process Connection
Measuring range
Process Temp.¡
Max. Process Pressure¡
Max
Min
Max. Viscosity
Dielectric Range (level only)
Vacuum service
7MB: standard twin rod GWR probe
316/316L (1.4401/1.4404), Hastelloy® C (2.4819) or Monel® (2.4360)
Teflon® with Viton® GFLT, Aegis PF 128 or Kalrez® 4079 (consult factory for alternatives)
Teflon®
Two 13 mm (0.5") Ø rods – 22,2 mm (0.875") CL to CL
In-tank mounting only.
Twin rod probe must be used in metallic vessel or stillwell > 25 mm (1") from any surface or
obstruction.
Threaded: 2" NPT or 2" BSP (G 2")
Flanged: various ANSI, EN (DIN) or torque tube mating flanges
From 60 cm to 610 cm (24" to 240")
εr ≥ 1,9 = 150 mm (6")
εr: 1,9 = 150 mm (6")/εr: 80 = 25 mm (1")
+150 °C @ 27,6 bar (+300 °F @ 400 psi)
-40 °C @ 51,7 bar (-40 °F @ 750 psi)
70 bar @ +20 °C (1000 psi @ +70 °F)
1500 mPa.s (cP)
1,9 to 100
Negative pressure but not hermetic seal
Film: 3% error of coated length, bridging not recommendedÆ
7EK: Top/Bottom GWR probe
r ≥ 1,4 - max +260 °C
ε
7EK: Top/Bottom GWR probe
r ≥ 10 - max +315 °C
PEEK and TFE with Aegis PF 128
PEEK and Alumina with Aegis PF 128
316/316L (1.4401/1.4404)
TFE
Inside tube: max 22,5 mm (0.88")
2" - Sch 80 Top/Bottom cage
min 356 mm (14") Std. – max 6,1 m (240")
+260 °C @ 115 bar (+500 °F @ 1670 psi)
-15 °C @ 117 bar (0 °F @ 1700 psi)
117 bar @ -15 °C (1700 psi @ +0 °F)
10.000 mPa.s (cP)
1,4 to 100 - Non conductive and conductive
media
Negative pressure but not hermetic seal
εr = dielectric permitivity. It is recommended to set 4-20 mA signal out-
side transition zones.
38
PEEK
Threaded: 1 1/2" NPT or 2" NPT
Welded: 1 1/2" or 2" socket weld
Flanged: Various ANSI, EN (DIN) or torque tube mating flanges
¿ Transition Zone (zone with reduced accuracy) is dielectric dependent;
¡ See graphs at page 39 and 40.
ε
+315 °C @ 109 bar (+600 °F @ 1585 psi)
10 to 100 - Conductive media
Æ Bridging is defined as continuous accumulation of material between the
probe elements.
Process pressure (bar)
Process pressure (bar)
TEMPERATURE - PRESSURE RATING FOR ECLIPSE PROBE SEAL
Process temperature (°C)
Process temperature (°C)
7MR/7MM, 7MT/7MN, 7MG probes
Process pressure (bar)
Process pressure (bar)
7MS probes
7MJ probes
7MQ probes
Process temperature (°C)
Process temperature (°C)
7MD/7ML probes
small coax
Process pressure (bar)
Process pressure (bar)
7MD/7ML probes
enlarged coax
Process temperature (°C)
7M1/7M7, 7MB, 7MF probes
except 7MF-E, F, G, H
7MF-F probes
Process temperature (°C)
7MF-E, G, H probes
39
Process pressure (bar)
Process pressure (bar)
TEMPERATURE - PRESSURE RATING FOR ECLIPSE PROBE SEAL
Process temperature (°C)
Process temperature (°C)
7MH with Viton GF 'O'-rings
7MH with EPDM 'O'-rings
7EK probes for max +260 °C
7EK probes for max +315 °C and conductive
liquids only
“O” RING SPECIFICATIONS¿ – Not suited for Ammonia/Chlorine applications
“O”-ring material
Viton
GFLT
®
Neoprene®
EPDM
Kalrez® 4079
max process
temperature
200°C @ 16 bar
(400 °F @ 230 psi)
min process
temperature
-40 °C (-40 °F)
max process
pressure
70 bar @ 20 °C
(1000 psi @ 70 °F)
150 °C @ 20 bar
(300 °F @ 290 psi)
-55 °C (-65 °F)
70 bar @ 20 °C
(1000 psi @ 70 °F)
120 °C @14 bar
(250 °F @ 200 psi)
200 °C @ 16 bar
(400 °F @ 232 psi)
-50 °C (-60 °F)
-40 °C (-40 °F)
70 bar @ 20 °C
(1000 psi @ 70 °F)
70 bar @ 20 °C
(1000 psi @ 70 °F)
200 °C @ 14 bar
(400 °F @ 200 psi)
-30 °C (-20 °F)
Buna-N
135 °C @ 22 bar
(275 °F @ 320 psi)
-20 °C (-4 °F)
Polyurethane
95 °C @29 bar
(200 °F @ 420 psi)
-55 °C (-65 °F)
70 bar @ 20 °C
(1000 psi @ 70 °F)
200 °C @ 16 bar
(400 °F @ 232 psi)
-20 °C (-4 °F)
70 bar @ 20 °C
(1000 psi @ 70 °F)
Chemraz® 505
HSN
(Highly Saturated
Nitrile)
Aegis PF128 ¡
135 °C @ 22 bar
(275 °F @ 320 psi)
-20 °C (-4 °F)
70 bar @ 20 °C
(1000 psi @ 70 °F)
70 bar @ 20 °C
(1000 psi @ 70 °F)
70 bar @ 20 °C
(1000 psi @ 70 °F)
¿ Valid for all GWR probe types, except 7MD, 7ML, 7MS, 7MJ, 7EK
¡ Max +150 °C (+300 °F) for use on steam.
40
not recommended for
applications
ketones (MEK, acetone), skydrol fluids,
amines, anhydrous ammonia,
low molecular weight esters and ethers,
hot hydrofluoric or chlorosulfonic acids,
sour hydrocarbons
phosphate ester fluids,
ketones (MEK, acetone)
petroleum oils, di-ester base
lubricant, steam
hot water/steam, hot aliphatic
amines, ethylene oxide, propylene
oxide
acetaldehyde, ammonia + lithium
metal solution, butyraldehyde,
di-water, freon, ethylene oxide,
liquors, isobutyraldehyde
halogenated hydrocarbons, nitro
hydrocarbons, phosphate ester
hydraulic fluids, ketones (MEK,
acetone), strong acids, ozone,
automotive brake fluid
acids, ketones, chlorinated
hydrocarbons
halogenated hydrocarbons, nitro
hydrocarbons, phosphate ester
hydraulic fluids, ketones (MEK,
acetone), strong acids, ozone,
automotive brake fluid, steam
black liquor, freon 43, freon 75,
galden, KEL-F liquid, molten potassium,
molten sodium
recommended for applications
general purpose, ethylene
refrigerants, high anline point
petroleum oils,
silicate ester lubricants
acetone, MEK, skydrol fluids
inorganic and organic acids (including
hydro fluids and nitric), aldehydes,
ethylene, organic oils, glycols, silicone
oils, vinegar, sour hydrocarbons
inorganic and organic acids,
alkalines, ketones, esters, aldehydes,
fuels
general purpose sealing, petroleum
oils and fluids, cold water, silicone
greases and oils, di-ester base
lubricants, ethylene glycol base
fluids
hydraulic systems, petroleum
oils, hydrocarbon fuel, oxygen,
ozone
NACE applications
inorganic and organic acids (including
hydro fluids and nitric), aldehydes,
ethylene, organic oils, glycols, silicone
oils, vinegar, sour hydrocarbons, steam,
amines, ethylene oxide, propylene oxide,
NACE applications
DIMENSIONS in mm (inches) - Dual compartment housing
45° View
105
(4.12)
83
(3.28)
102
(4.00)
256
(10.08)
126
(4.94)
45°
2 cable
entries
102
(4.00)
214
(8.43)
70
(2.75)
19
(0.75)
89
(3.50)
111
(4.38)
Integral Electronics
83
(3.28)
Eclipse Housing,
(45° View)
2 cable
entries
102
(4.00)
95
(3.75)
105
(4.12)
45°
2 holes
Ø 9,5 (0.37)
840 or 3660
(33 or 144)
108
(4.25)
Remote Electronics
DIMENSIONS in mm (inches) - Twin Rod
83
(3.28)
83
(3.28)
105
(4.12)
102
(4.00)
83
(3.28)
105
(4.12)
102
(4.00)
102
(4.00)
256
(10.08)
2 cable
entries
45°
2 cable
entries
103 (4)
Probe
Insertion
Length
7MB
with threaded
2" BSP (G 2") connection
105
(4.12)
45°
256
(10.08)
256
(10.08)
2 cable
entries
45°
129 (5.08)
126 (4.96)
Probe
Insertion
Length
Probe
Insertion
Length
7MB
with threaded
2" NPT connection
7MB
with flanged
connection
22,2 (0.875)
Ø 13 (0.50)
Rods
Twin Rod GWR Probe,
End View
41
DIMENSIONS in mm (inches) - Coaxial GWR probes
83
(3.28)
105
(4.12)
83
(3.28)
102
(4.00)
102
(4.00)
45°
2 cable
entries
Probe Insertion
Length
NPT
256
(10.08)
45°
2 cable
entries
83
(3.28)
102
(4.00)
2 cable
entries
7MD:
218 (8.58)
7MS/7MQ: 177 (6.97)
Probe Insertion
Length
NPT
7MR / 7MT
with flanged connection
83
(3.28)
Probe Insertion
Length
BSP
7MD/7MS/7MQ
with threaded connection
Probe Insertion
Length
NPT
45°
162 (6.38)
Probe
Insertion
Length
7MD/7MS/7MQ
with flanged connection
1/4"
NPT
plugged
1/4"
NPT
plugged
256
(10.08)
206 (8.11)
Probe Insertion
Length
BSP
Probe
Insertion
Length
7MM / 7MN
with flanged connection
83
(3.28)
105
(4.12)
105
(4.12)
102
(4.00)
256
(10.08)
256
(10.08)
2 cable
entries
277 (10.90)
7MD:
7MS/7MQ: 240 (9.45)
45°
2 cable
entries
102
(4.00)
256
(10.08)
2 cable
entries
105
(4.12)
256
(10.08)
7MM / 7MN
with threaded connection
83
(3.28)
256
(10.08)
7MD:
199 (7.83)
7MS/7MQ: 156 (6.14)
NPT
plugged
1/4"
171
(6.73)
105
(4.12)
102
(4.00)
45°
45°
2 cable
entries
Probe
Insertion
Length
105
(4.12)
83
(3.28)
102
(4.00)
256
(10.08)
168 (6.61)
Probe Insertion
Length
BSP
7MR / 7MT
with threaded connection
105
(4.12)
102
(4.00)
137 (5.39)
144
(5.68)
42
83
(3.28)
105
(4.12)
45°
2 cable
entries
297 (11.69)
Probe
Insertion
Length
7ML
with threaded connection
1/4"
NPT
plugged
45°
375 (14.76)
Probe
Insertion
Length
7ML
with flanged connection
DIMENSIONS in mm (inches) - Coaxial GWR probes
50
(1.97)
20
(0.79)
Ø 229
(9.0)
B
A
45°
Venting holes
for level
Slots for 7MR-A, 7MD-A/V/W
(order per “x” description)
D
B
6
(.22)
Fisher 249B/259B (600 lbs), carbon steel
Ø 143
(5.625)
E
Ø 11
(.438)
B
E
C
Ø 191
(7.50)
D
E
F
305 (12)
305 (12)
22,5 (0.88)
45 (1.75) - SST
49 (1.29) - HC and Monel
Ø 22
(.875)
Ø 12,7 (0.5)
25,4 (1)
8 (0.31)
102
(4.00)
29
(1.125)
6
(.25)
Masoneilan (600 lbs), 316 carbon steel
16 (0.63)
32 (1.25)
Ø 149
(5.875)
45°
Large coax mm (inch)
19 (0.75)
5
(.188)
Fisher 249C (600 lbs), 316 stainless steel
7MQ End View
Ø 6,4 (0.25)
29
(1.125)
86
(3.375)
D
A
Ø 121
(4.750)
45°
F
Small coax mm (inch)
32
(1.125)
133
(5.23)
Coaxial GWR Probe,
End View
Venting holes
for interface
Dim.
Ø 184
(7.25)
Ø 22
(.875)
4 (0.16)
C
Proprietary flanges
DIMENSIONS in mm (inches) - Single Rod
83
(3.28)
105
(4.12)
102
(4.00)
Ø Rod
Bare 13 (0.50) /
PFA insulated
16 (0.62)
7MF: 60 (2.36)
7MJ: 150 (5.91)
60
(2.36)
Probe
Insertion
Length
7MF-F
with PFA
faced-flanged
connection
13 (0.50)
Ø Rod
Probe
Insertion
Length
Optional
Spacer
7MF/7MJ
with flanged
connection
2 cable
entries
7MF: 57 (2.24)
7MJ: 147 (5.79)
Ø Rod
Bare 13 (0.50) /
Probe Insertion PFA insulated
Length 16 (0.62)
NPT
Optional Spacer
45°
256
(10.08)
7MF: 36 (1.42)
7MJ: 126 (4.96)
Probe Insertion
Length
BSP
7MF/7MJ
with threaded connection
49
(1.90)
Spacer (end view)
43
DIMENSIONS in mm (inches) - Hygienic
58
(2.28)
52
(2.05)
60
(2.36)
175
(6.89)
Cable entry
43°
109
(4.28)
Integral Electronics
43° View
52
(2.05)
58
(2.28)
60
(2.36)
19
(0.75)
Cable entry
70
(2.75)
102
(4.00)
2 holes
Ø 9,5
(0.37)
89
(3.50)
43°
95
(3.75)
840 or 3660
(33 or 144)
108
(4.25)
Remote Electronics
Process
Connection
6 (0.25)
Ø Rod
60
(2.36)
Probe
Insertion
Length
3/4" Tri-Clamp® connection
44
Process
Connection
13 (0.50)
Ø Rod
7MF: 60 (2.36)
7MH: 70 (2.76)
Probe
Insertion
Length
all except 3/4" Tri-Clamp® connection
DIMENSIONS in mm (inches) - cable GWR probe
41 (1.61)
59 (2.32)
610 (24)
Probe Insertion
Length
BSP
62 (2.44)
62 (2.44)
76 (3)
610 (24)
Probe Insertion
Length
NPT
Probe Insertion
Length
Weight
Ø 51
(2)
99
(3.88)
99
(3.88)
7M1
with threaded connection
62 (2.44)
Ø 51
(2)
152
(6)
Ø 51
(2)
Probe Insertion
Length
152
(6)
Ø 51
(2)
7M2
with threaded connection
93 (3.66)
Probe Insertion
Length
Probe Insertion
Length
NPT
Weight
Weight
Weight
Ø 51
(2)
7M2
with flanged connection
83 (3.25)
76 (3)
Probe Insertion
Length
BSP
Probe Insertion
Length
NPT
152
(6)
7M1
with flanged connection
83 (3.25)
76 (3)
Probe Insertion
Length
BSP
Weight
80 (3.13)
76 (3)
80 (3.13)
152
(6)
Weight
111 (4.37)
76 (3)
76 (3)
Probe Insertion
Length
BSP
Probe Insertion
Length
NPT
Ø 51
(2)
Probe Insertion
Length
Weight
73
(2.88)
7M5
7M5
with threaded connection with flanged connection
114 (4.49)
Ø 51
(2)
73
(2.88)
Weight
Ø 51
(2)
7M7
7M7
with threaded connection with flanged connection
Additional weight
29 (1.13)
99
(3.88)
Ø 51
(2)
Ø 13,2
(0.52)
TFE Weight
450 g (1 lb.)
7M1
152
(6)
19 (0.75)
Ø 51
(2)
SST Weight
2,25 kg (5 lbs)
7M2
32 (1.25)
73
(2.88)
Ø 51
(2)
Ø 13,2
(0.52)
TFE Weight
284 g (10 oz.)
7M7
152
(6)
19 (0.75)
Ø 51
(2)
SST Weight
2,25 kg (5 lbs)
7M5
45
DIMENSIONS in mm (inches) - cage GWR probe
187
(7.37)
187
(7.37)
Ø 71 (2.80)
Ø 13 (0.50) rod
Probe
Insertion
Length
Ø 95 (3.77)
Ø 19 (0.75) rod
Probe
Insertion
Length
7MG - 2" cage
Ø 25 (1) rod
PEEK spacer
PEEK spacer
Teflon® spacer
187
(7.37)
7MG - 3" cage
7MG - 4" cage
49
(1.90)
71 (2.80)
Spacer (end view)
46
Spacer (end view)
94 (3.70)
Spacer (end view)
Probe
Insertion
Length
MODEL IDENTIFICATION
A complete measuring system consists of:
1. Eclipse transmitter head/electronics
2. Eclipse 705 GWR probe
3. Free of charge: Eclipse 705 DTM (PACTware™) can be downloaded from www.magnetrol.com.
4. Option: MACTek Viator USB HART® interface: order code: 070-3004-002
- TFE spacer for single rod metal GWR probes; order code: 089-9114-001 (7MF-A), 089-9114-002 (7MF-B),
5. Option:
- 089-9114-003 (7MF-C)
- PEEK spacer for single rod 7MJ GWR probe; order code: 089-9114-005 (7MJ-A), 089-9114-006 (7MJ-B),
- 089-9114-007 (7MJ-C)
- Additional weight for 7M1 GWR probe; order code: 089-9120-001
- Additional weight for 7M7 GWR probe; order code: 089-9121-001
- Additional weight for 7M2 GWR probe; order code: 004-8778-001
- Additional weight for 7M5 GWR probe; order code: 004-8778-002
1. Code for ECLIPSE 705 transmitter head/electronics
BASIC MODEL NUMBER
7 0 5
Eclipse 705 guided wave radar transmitter
POWER
5
24 V DC, two wire loop powered
OUTPUT AND ELECTRONICS
1
1
2
3
0
A
0
0
4-20 mA with HART® – standard electronics (SFF of 84.5%)
4-20 mA with HART® – SIL enhanced electronics (SFF of 91%)
Foundation Fieldbus™ communication
Profibus PA™ communication
ACCESSORIES
A
0
Digital display and keypad
- Blind transmitter (no display/keypad) for dual compartment housing
- Blind housing cover for hygienic housing
SEE NEXT PAGE
7 0 5
5
complete code for ECLIPSE 705 transmitter head/electronics
X = product with a specific customer requirement
47
MODEL IDENTIFICATION
1. Code for ECLIPSE 705 transmitter head/electronics
SEE PREVIOUS PAGE
MOUNTING / HOUSING MATERIAL / APPROVAL¿
Integral mount electronics
Cast aluminium - dual compartment
1
A
C
E
1
1
1
1
Weatherproof
ATEX intrinsically safe (digit 5 = 1) / ATEX FISCO (digit 5 = 2 or 3)
ATEX flameproof enclosure
ATEX non sparking (digit 5 =1) / ATEX FNICO (digit 5 = 2 or 3)
Cast SST - dual compartment
1 2
Weatherproof
A 2
ATEX intrinsically safe (digit 5 = 1) / ATEX FISCO (digit 5 = 2 or 3)
ATEX flameproof enclosure
C 2
E 2
ATEX non sparking (digit 5 =1) / ATEX FNICO (digit 5 = 2 or 3)
304 SST - IP 67 - hygienic
1 3
Weatherproof
A 3
ATEX intrinsically safe (digit 5 =1) / ATEX FISCO (digit 5 = 2 or 3)
84 cm (33") remote mount electronics
Cast aluminium - dual compartment
2
B
D
F
1
1
1
1
Weatherproof
ATEX intrinsically safe (digit 5 = 1) / ATEX FISCO (digit 5 = 2 or 3)
ATEX flameproof enclosure
ATEX non sparking (digit 5 =1) / ATEX FNICO (digit 5 = 2 or 3)
Cast SST - dual compartment
2 2
Weatherproof
B 2
ATEX intrinsically safe (digit 5 = 1) / ATEX FISCO (digit 5 = 2 or 3)
D 2
ATEX flameproof enclosure
F 2
ATEX non sparking (digit 5 =1) / ATEX FNICO (digit 5 = 2 or 3)
304 SST - IP 67 - hygienic
2 3
Weatherproof
B 3
ATEX intrinsically safe (digit 5 =1) / ATEX FISCO (digit 5 = 2 or 3)
3,66 m (144") remote mount electronics (consult factory for applications with r < 10)
Cast aluminium - dual compartment
2 7
Weatherproof
B 7
ATEX intrinsically safe (digit 5 = 1) / ATEX FISCO (digit 5 = 2 or 3)
D 7
ATEX flameproof enclosure
F 7
ATEX non sparking (digit 5 =1) / ATEX FNICO (digit 5 = 2 or 3)
ε
Cast SST - dual compartment
2 8
Weatherproof
B 8
ATEX intrinsically safe (digit 5 = 1) / ATEX FISCO (digit 5 = 2 or 3)
D 8
ATEX flameproof enclosure
F 8
ATEX non sparking (digit 5 =1) / ATEX FNICO (digit 5 = 2 or 3)
304 SST - IP 67 - hygienic
2 9
Weatherproof
B 9
ATEX intrinsically safe (digit 5 =1) / ATEX FISCO (digit 5 = 2 or 3)
¿
CABLE ENTRY
1
0
4
7 0 5
48
5
For IEC approval, use ATEX approval and clearly request IEC nameplate.
M20 x 1,5 (2 entries - 1 plugged)
3/4" NPT (2 entries - 1 plugged)
1/2" NPT (1 entry)
complete code for ECLIPSE 705 transmitter head/electronics
X = product with a specific customer requirement
MODEL IDENTIFICATION
2. Code for ECLIPSE 705 GWR probe
BASIC MODEL NUMBER
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
B
D
F
G
H
J
L
M
N
Q
R
S
T
1
2
5
7
Twin Rod GWR probe for liquid level – WHG approved
εr: ≥ 1,9
HTHP GWR probe for level/interface – WHG approved
εr: ≥ 2,0 if digit 4 = A, B or C
Single rod GWR probe
εr: ≥ 1,9/10
Cage GWR probe for level/interface
Hygienic single rod GWR probe
HTHP single rod GWR probe
εr: ≥ 1,9/10
HTHP GWR probe for level/interface with flushing connection εr: ≥ 2,0 if digit 4 = A, B or C
GWR probe for level with flushing connection
εr: ≥ 1,4
GWR probe for interface with flushing connection
upper liq: εr: ≥ 1,4 and ≤ 5 / lower liq: ≥ 15
Coaxial GWR probe for saturated steam applications, incl. steam compensation / reference target; 345 °C (650 °F) max.
GWR probe for level – WHG approved
εr: ≥ 1,4
Coaxial GWR probe for saturated steam applications, incl. steam compensation / reference target; 300 °C (575 °F) max.
GWR probe for interface
upper liq: εr: ≥ 1,4 and ≤ 5 / lower liq: ≥ 15
Single cable GWR probe in 316 stainless steel (1.4401)
εr: ≥ 1,9/10 – liquids
Single cable GWR probe in 316 stainless steel (1.4401)
εr: ≥ 4,0 – solids
Twin cable GWR probe in FEP coated 316 SST (1.4401)
εr: ≥ 1,9 – solids
Twin cable GWR probe in FEP coated 316 SST (1.4401)
εr: ≥ 1,9 – liquids
MATERIAL OF CONSTRUCTION - wetted parts (including process connection flange when applicable)
A
B
C
E
F
G
H
L
4
V
W
N
P
R
316/316L (1.4401/1.4404) stainless steel
Hastelloy C (2.4819)
Monel (2.4360)
316/316L (1.4401/1.4404) stainless steel 0,4 µm Ra (15 Ra) electropolished surface finish
PFA insulated 316/316L (1.4401/1.4404) stainless steel
AL-6XN stainless steel (UNS N08367) 0,4 µm Ra (15 Ra) electropolished surface finish
Hastelloy® C22 (2.4602) 0,4 µm Ra (15 Ra) electropolished surface finish
316L (1.4435) stainless steel 0,4 µm Ra (15 Ra) electropolished surface finish
PFA insulated 316/316L (1.4401/1.4404) stainless steel
316/316L (1.4401/1.4404) stainless steel with High Temp PEEK® spacers
εr: ≥ 1,7
316/316L (1.4401/1.4404) stainless steel with Teflon® spacers
εr: ≥ 1,4
Enlarged coax 316/316L (1.4401/1.4404) stainless steel
Enlarged coax Hastelloy C (2.4819)
Enlarged coax Monel (2.4360)
PROCESS CONNECTION - SIZE/TYPE (consult factory for other process connections)
Threaded
1 1
3/4" NPT
4 1
2" NPT
2 2
1" BSP (G 1")
4 2
2" BSP (G 2")
ANSI flanges
2 3
1"
150 lbs ANSI RF
2 4
1"
300 lbs ANSI RF
2 5
1"
600 lbs ANSI RF
2 K
1"
600 lbs ANSI RJ
2 L
1"
900 lbs ANSI RJ
3 3
1 1/2" 150 lbs ANSI RF
3 4
1 1/2" 300 lbs ANSI RF
3 5
1 1/2" 600 lbs ANSI RF
3 K
1 1/2" 600 lbs ANSI RJ
3 M
1 1/2" 900/1500 lbs ANSI RJ
3 N
1 1/2" 2500 lbs ANSI RJ
4 3
2"
150 lbs ANSI RF
4 4
2"
300 lbs ANSI RF
4 5
2"
600 lbs ANSI RF
4 K
2"
600 lbs ANSI RJ
4 M
2"
900/1500 lbs ANSI RJ
4
5
5
5
5
5
5
5
6
6
6
6
6
6
6
N
3
4
5
K
L
M
N
3
4
5
K
L
M
N
2"
3"
3"
3"
3"
3"
3"
3"
4"
4"
4"
4"
4"
4"
4"
2500
150
300
600
600
900
1500
2500
150
300
600
600
900
1500
2500
lbs
lbs
lbs
lbs
lbs
lbs
lbs
lbs
lbs
lbs
lbs
lbs
lbs
lbs
lbs
ANSI
ANSI
ANSI
ANSI
ANSI
ANSI
ANSI
ANSI
ANSI
ANSI
ANSI
ANSI
ANSI
ANSI
ANSI
RJ
RF
RF
RF
RJ
RJ
RJ
RJ
RF
RF
RF
RJ
RJ
RJ
RJ
SEE NEXT PAGE
7 M
complete code for ECLIPSE 705 GWR probe
X = product with a specific customer requirement
49
MODEL IDENTIFICATION
2. Code for ECLIPSE 705 GWR probe
SEE PREVIOUS PAGE
PROCESS CONNECTION - SIZE/TYPE
EN (DIN) flanges
B
B
B
C
C
C
C
C
C
D
D
D
D
D
D
D
B
C
F
B
C
F
G
H
J
A
B
D
E
F
G
H
2
3
4
9
5
6
C
D
V
D
V
E
D
S
T
P
P
P
P
P
P
S
S
V
N
N
N
R
Y
Y
DN
DN
DN
DN
DN
DN
DN
DN
DN
DN
DN
DN
DN
DN
DN
DN
Hygienic
25
25
25
40
40
40
40
40
40
50
50
50
50
50
50
50
PN
PN
PN
PN
PN
PN
PN
PN
PN
PN
PN
PN
PN
PN
PN
PN
16/25/40
63/100
160
16/25/40
63/100
160
250
320
400
16
25/40
63
100
160
250
320
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
1092-1
1092-1
1092-1
1092-1
1092-1
1092-1
1092-1
1092-1
1092-1
1092-1
1092-1
1092-1
1092-1
1092-1
1092-1
1092-1
Type
Type
Type
Type
Type
Type
Type
Type
Type
Type
Type
Type
Type
Type
Type
Type
A
B2
B2
A
B2
B2
B2
B2
B2
A
A
B2
B2
B2
B2
B2
3/4"
D
E
E
E
E
E
E
E
E
F
F
F
F
F
F
F
F
Tri-Clamp®
1" - 1 1/2" Tri-Clamp®
2" Tri-Clamp®
2 1/2" Tri-Clamp®
3" Tri-Clamp®
4" Tri-Clamp®
DN 40 DIN 11851
DN 50 DIN 11851
Varivent Type N (mounting diameter 68 mm)
D 50 NEUMO BioControl
D 65 NEUMO BioControl
D 80 NEUMO BioControl
DN 50 DIN 11864-1 Type A
DN 11/2" SMS
DN 2" SMS
J
A
B
D
E
F
G
H
J
A
B
D
E
F
G
H
J
DN
DN
DN
DN
DN
DN
DN
DN
DN
DN
DN
DN
DN
DN
DN
DN
DN
50 PN
80 PN
80 PN
80 PN
80 PN
80 PN
80 PN
80 PN
80 PN
100 PN
100 PN
100 PN
100 PN
100 PN
100 PN
100 PN
100 PN
400
16
25/40
63
100
160
250
320
400
16
25/40
63
100
160
250
320
400
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
1092-1
1092-1
1092-1
1092-1
1092-1
1092-1
1092-1
1092-1
1092-1
1092-1
1092-1
1092-1
1092-1
1092-1
1092-1
1092-1
1092-1
Type
Type
Type
Type
Type
Type
Type
Type
Type
Type
Type
Type
Type
Type
Type
Type
Type
B2
A
A
B2
B2
B2
B2
B2
B2
A
A
B2
B2
B2
B2
B2
B2
Torque tube mating flanges
T T
300/600 lbs Fisher (249B/259B) in carbon steel
T U
300/600 lbs Fisher (249C) in stainless steel
U T
300/600 lbs Masoneilan flange in carbon steel
U U
300/600 lbs Masoneilan flange in stainless steel
PROCESS SEAL - MATERIAL
0
1
2
3
4
5
Viton® GFLT
EPDM (Ethylene Propylene)
PEEK® & EPDM ‘O’-rings for 7MH
Kalrez® 4079
HSN (highly saturated nitrile)
Buna-N
Neoprene®
6
7
8
A
C
N
Chemraz® 505
Polyurethane
Aegis PF 128
Kalrez® 6375
PEEK® & Viton GF ‘O’-rings for 7MH
Borosilicate/Inconel® X-750 for 7MD/7ML
PTFE for 7MF-E/G/H
SEE NEXT PAGE
7 M
50
complete code for ECLIPSE 705 GWR probe
X = product with a specific customer requirement
MODEL IDENTIFICATION
2. Code for ECLIPSE 705 GWR probe
SEE PREVIOUS PAGE
INSERTION LENGTH
Rigid GWR probes: specify per cm (0.39") increment
0 6 0
min 60 cm (24")
6 1 0
max 610 cm (240") – max 450 cm (177") for 7MQ / 7MS
Flexible GWR probes: specify per m (3.28') increment
min 2 m (6.56')
0 0 2
0 2 2
max 22 m (72.18')
Hygienic GWR probes: specify per cm (0.39") increment
0 3 0
min 30 cm (12")
1 8 0
max 180 cm (72") for 3/4" Tri-Clamp® process connection
6 1 0
max 610 cm (240") for all other process connections
7 M
complete code for ECLIPSE 705 GWR probe
X = product with a specific customer requirement
51
MODEL IDENTIFICATION
2. Code for ECLIPSE® 705 Top/Bottom GWR probe and cage
Additional dimensions are provided (see drawings at bottom of this page):
- Dimension A: top of process connection up to 20 mA range
- Dimension B: bottom of process connection up to 4 mA range
- Level Range, if different from 356 mm (14")
BASIC MODEL NUMBER
GWR probe suited for in-line external cage mounting
7 E K
Top/Bottom GWR probe and cage - overfill safe
MATERIAL OF CONSTRUCTION - wetted parts (including process connection flange when applicable)
K
M
Cage and Flanges
316/316L (1.4401/1.4404) stainless steel
Carbon steel
PROCESS CONNECTION - SIZE/TYPE
Threaded
3 1
1 1/2" NPT
4 1
2" NPT
ANSI flanges
3 3
1 1/2"
3 4
1 1/2"
3 5
1 1/2"
4 3
2"
4 4
2"
4 5
2"
150
300
600
150
300
600
LEVEL RANGE
A
lbs
lbs
lbs
lbs
lbs
lbs
316/316L (1.4401/1.4404) stainless steel
Welded
3 9
1 1/2" socket weld
4 9
2" socket weld
RF
RF
RF
RF
RF
RF
356 mm (14")
OPTIONS
0
2
None
Sight glass connections (sight glass not included)
LIQUID TYPE / OPERATING TEMPERATURE
1 0
2 0
7 E K
ANSI
ANSI
ANSI
ANSI
ANSI
ANSI
GWR probe
A
Conductive liquids (εr ≥ 10)
All liquids (εr ≥ 1,4)
max +315 °C (+600 °F)
max +260 °C (+500 °F)
complete code for ECLIPSE 705 Top/Bottom GWR probe and cage
0
X = product with a specific customer requirement
DIMENSIONS in mm (inches)
A min 11/2": 64 (2.50)
2": 86 (3.37)
A min 11/2": 102 (4.03)
2": 110 (4.34)
100 %
100 %
mid
range
Max level range
in mm or inches
min 356 (14)
max 6,1 m (240)
0%
52
Flanged
7EK
B min 76 mm (3")
A min 94 (3.69)
mid
range
Max level range in
mm or inches
min 356 (14)
max 6,1 m (240)
0%
B min 76 mm (3")
Threaded
7EK
A min. 156 (6.12)
100 %
100 %
Max level range in
mm or inches
min 356 (14)
max 6,1 m (240)
mid
range
0%
B min 76 mm (3")
Welded
7EK
mid
range
3/4" NPT-F
0%
B min 76 mm (3")
Optional sight glass
connections
®
705 Eclipse Guided Wave Radar Transmitter
Configuration Data Sheet
Copy blank page and store calibration data for future reference and troubleshooting.
Item
Vessel Name
Vessel #
Process Medium
Tag #
Electronics Serial #
Probe Serial #
Level
Volume (optional)
Interface (optional)
Interface Volume (opt.)
Probe Model
Probe Mount
Measurement Type
Level Units
Probe Length
Level Offset
Volume Units (opt.)
Strapping Table (opt.)
(Make a separate list for each
level and its corresponding
volume
Dielectric
Sensitivity
Loop Control
4mA point
20mA point
Damping
Blocking Distance
Safety Zone Fault
Safety Zone Height
Safety Zone Alarm
Fault Choice
Threshold
Interface Threshold
HART Poll Address
Level Trim
Trim 4 mA
Trim 20 mA
Level Ticks
Interface Ticks (opt.)
HF cable
Screen
«Level»
«Volume»
«IfcLvl»
«IfcVol»
«PrbModel»
«PrbMount»
Value
Value
TROUBLESHOOTING
Working Value
Non-Working Value
«MeasType»
«LvlUnits»
«Probe Ln»
«Lvl Ofst»
«VolUnits»
«StrapTbl»
«Pt1..20»
«Dielectrc»
«Senstvty»
«LoopCtrl»
«Set 4mA»
«Set 20mA»
«Damping»
«BlockDis»
«Sz Fault»
«SzHeight»
«Sz Alarm Reset»
«Fault»
«Treshld»
«IfcThrs»
«Poll Adr»
«Trim Lvl»
«Trim 4»
«Trim 20»
«LvlTicks»
«IfcTicks»
«HF Cable»
53
®
705 Eclipse Guided Wave Radar Transmitter
Configuration Data Sheet – additional Advanced Diagnostic
Copy blank page and store calibration data for future reference and troubleshooting.
Item
# of Fiducial Ticks
Fiducial Spread
Sys Code
Fiducial Type
Fiducial Gain
Window
Conversion Factor
Scale Offset
Negative Amplitude
Positive Amplitude
Signal
Compensate
Screen
«FidTicks»
«Fid Sprd»
«Sys Code»
«Fid Type»
«Fid Gain»
«Window»
«Conv Fct»
«Scl Ofst»
«Neg Ampl»
«Pos Ampl»
«Signal»
«Compensate»
Derating Factor
«DrateFct»
Target Ticks (7MS)
«Targ Tks»
Operating Mode
«OperMode»
Target Amplitude (7MS) «TargAmpl»
Target Calibration (7MS) «Targ Cal»
7EK Correction
«7xK Corr»
Max temperature
«Max Temp»
Electronics temperature «ElecTemp»
Min temperature
Safety Zone Hysterisis
54
«Min Temp»
«SZ Hyst»
Value
Value
TROUBLESHOOTING
Correct Value
Incorrect Value
Notes
55
IMPORTANT
SERVICE POLICY
Owners of Magnetrol products may request the return of a control; or, any part of a control for complete rebuilding or
replacement. They will be rebuilt or replaced promptly. Magnetrol International will repair or replace the control, at no cost to
the purchaser, (or owner) other than transportation cost if:
a. Returned within the warranty period; and,
b. The factory inspection finds the cause of the malfunction to be defective material or workmanship.
If the trouble is the result of conditions beyond our control; or, is NOT covered by the warranty, there will be charges for labour
and the parts required to rebuild or replace the equipment.
In some cases, it may be expedient to ship replacement parts; or, in extreme cases a complete new control, to replace the
original equipment before it is returned. If this is desired, notify the factory of both the model and serial numbers of the
control to be replaced. In such cases, credit for the materials returned, will be determined on the basis of the applicability of
our warranty.
No claims for misapplication, labour, direct or consequential damage will be allowed.
RETURNED MATERIAL PROCEDURE
So that we may efficiently process any materials that are returned, it is essential that a “Return Material Authorisation” (RMA)
form will be obtained from the factory. It is mandatory that this form will be attached to each material returned. This form is
available through Magnetrol’s local representative or by contacting the factory. Please supply the following information:
1.
2.
3.
4.
5.
6.
Purchaser Name
Description of Material
Serial Number and Ref Number
Desired Action
Reason for Return
Process details
Any unit that was used in a process must be properly cleaned in accordance with the proper health and safety standards
applicable by the owner, before it is returned to the factory.
A material Safety Data Sheet (MSDS) must be attached at the outside of the transport crate or box.
All shipments returned to the factory must be by prepaid transportation. Magnetrol will not accept collect shipments.
All replacements will be shipped Ex Works.
BULLETIN N°:
EFFECTIVE:
SUPERSEDES:
UNDER RESERVE OF MODIFICATIONS
BE 57-600.18
APRIL 2016
September 2015
www.m a gne tr ol.c om
BENELUX
FRANCE
Heikensstraat 6, 9240 Zele, België -Belgique
Tel. +32 (0)52.45.11.11 • Fax. +32 (0)52.45.09.93 • E-Mail: [email protected]
DEUTSCHLAND
Alte Ziegelei 2-4, D-51491 Overath
Tel. +49 (0)2204 / 9536-0 • Fax. +49 (0)2204 / 9536-53 • E-Mail: [email protected]
INDIA
B-506, Sagar Tech Plaza, Saki Naka Junction, Andheri (E), Mumbai - 400072
Tel. +91 22 2850 7903 • Fax. +91 22 2850 7904 • E-Mail: [email protected]
ITALIA
Via Arese 12, I-20159 Milano
Tel. +39 02 607.22.98 • Fax. +39 02 668.66.52 • E-Mail: [email protected]
RUSSIA
198095 Saint-Petersburg, Marshala Govorova street, house 35A, office 427
Tel. +7 812 320 70 87 • E-Mail: [email protected]
U.A.E.
DAFZA Office 5EA 722 • PO Box 293671 • Dubai
Tel. +971-4-6091735 • Fax +971-4-6091736 • E-Mail: [email protected]
UNITED
KINGDOM
Unit 1 Regent Business Centre, Jubilee Road Burgess Hill West Sussex RH 15 9TL
Tel. +44 (0)1444 871313 • Fax +44 (0)1444 871317 • E-Mail: [email protected]