Brochure “GEAFOL Basic”

siemens.com/transformers
Convincing technology creates
compact performance
The GEAFOL Basic: the optimum foundation for power distribution
Contents
The GEAFOL Basic:
A true GEAFOL and more
3
Construction and features
6
Selection of ordering data
7
Truck dimensions
10
Terminal dimensions (LV)
11
Accessories12
Temperature monitoring and additional ventilation
2
Standard housing
13
Selection of ordering data
15
The GEAFOL Basic:
A true GEAFOL and more
Maximum efficiency in use and economic, resource-saving production: the new GEAFOL Basic.
Tailored design
Let’s be clear right from the start: the GEAFOL Basic
­represents an evolution, not a revolution. It’s based on
nearly 50 years of proven GEAFOL technology and quality,
but it offers numerous innovations that have allowed
us to provide it with several very special characteristics.
Its design takes several requirements for special applications
into account which we wouldn’t have dared to dream of
when the original GEAFOL was being developed. As a result,
for example, the GEAFOL Basic distribution transformer
with a maximum rated power of 3.15 MVA is almost ten
percent lighter than a comparable model from the proven
GEAFOL series. And this “slimming down” also positively
affects the dimensions.
Universal use
The highest safety requirements must be met whenever
distribution transformers are operated in the direct vicinity
of humans. GEAFOL Basic distribution transformers are
the perfect solution in this case, because their proven
GEAFOL design is coupled with proven operational reli­
ability and a long service life. What’s more, they’ve got
the seal of approval because all GEAFOL Basic distribution
transformers meet the specifications of VDE 0532-76-11/
IEC 60076-11/DIN EN 60076-11, DIN EN 50541-1.
On request, other standards, such as GOST, SABS or
CSA/ANSI/ IEEE, can also be taken into account. Our GEAFOL
transformers are always also tested by UL/CSA/TÜV.
They meet the highest requirements for safe installation in
residential and work environments with Climatic Class C2,
Environmental Class E2 and Fire Classification F1.
Optimum compromise
Keeping the distance between the distribution transformer
and consumer as short as possible considerably reduces
both the complexity of the electrical network and losses
in the transmission and distribution of energy. Frequently,
however, there is often a shortage of space in the vicinity
of the consumer. The GEAFOL Basic distribution transformer
represents an optimum compromise between performance,
safety and small dimensions. In addition, the high degree
of standardization ensures the best possible cost-benefit
ratio. Thanks to their compact shape and comprehensive
safety certification, GEAFOL Basic distribution transformers
can be used in almost every environment.
Further development of proven technology
With approx. 100,000 transformers in use worldwide,
essential parts of the GEAFOL technology have already
proven themselves over the long term. These include
the strip winding and foil winding made from aluminum,
which we adopted without change for the new GEAFOL
Basic in order to ensure reliability and a long service life.
In return, the mechanical design and high-voltage wind­
ings underwent a re-design in order to make them lighter
and smaller as a truly clean solution. As a result, it was
possible to considerably improve heat dissipation. With
fewer horizontal surfaces, less dust is deposited, which
leads to a further reduction in the already minimal time
and effort needed for maintenance and also increases
operational reliability.
3
Thanks to its technical characteristics, the GEAFOL Basic
is well suited to a large number of applications. And you
don’t have to take the limitations of classic transformer
technology into account when planning. Use in a load
center allows optimum network designs to be realized –
with corresponding advantages in terms of cost and
efficiency.
In addition, the GEAFOL Basic makes it possible to dispense
with special safety precautions, such as coolant collecting
troughs. And with its small dimensions, the GEAFOL Basic
permits more power to be installed in the same space.
On request, GEAFOL Basic transformers can also be
designed for converter loads and particular mechanical
stresses (GEAFOL Basic+).
Everything that’s needed for the future
The GEAFOL Basic is also setting new standards when it
comes to being prepared for the future. Even though the
end of its service life is still a long way off, the GEAFOL
Basic already has the perfect answer to the question of
recycling. All metal parts as well as the cast resin can be
recycled in an environmentally friendly way.
EU guidelines: Ecodesign Directive of the European
Commission
Effective July 1, 2015, transformers that are installed
within the European Economic Area (EEA) must meet the
ecodesign requirements of the new directive, provided
that they fall within the scope of the directive. Since the
directive is a measure to implement Ecodesign Directive
209/125/EC, the CE mark is used as evidence of compliance.
GEAFOL Basic transformers are designed accordingly and
are particularly low-loss and economic.
GEAFOL Basic – the intelligent further development
of an excellent technology.
Regardless of the application, a low weight, small dimensions and
high operational reliability with the lowest possible maintenance
make the GEAFOL Basic the first choice.
4
The GEAFOL Basic – Overview of features and advantages
•• Innovative clean design
•• Power range up to 3.15 MVA and voltages up to 36 kV
(medium-voltage) or 1000 V (low-voltage)
•• Certified in accordance with VDE 0532/IEC 60076-11/
DIN EN 60076-11, DIN EN 50541-7
•• Variants available for converter operation
(GEAFOL Basic+ on request)
•• Loss-optimized designs taking into account Ecodesign
Directive 2009/125/EC for installation within the European
Economic Area
•• Mechanically reinforced designs available
(GEAFOL Basic+ on request)
•• Climatic Class C2, Environmental Class E2 and
Fire Classification F1
•• Up to approx. 10 % lower weight
•• Maintenance-free windings embedded in moisture-proof,
fire-resistant and self-extinguishing insulating material
that is suitable for the tropics
•• Up to approx. 30 % increase in power possible through
forced-air cooling
•• Proven GEAFOL technology and quality
•• Optimum compromise between size and power
Built-in safety
The coils of the high-voltage winding of the GEAFOL Basic
are manufactured from aluminum foil. This foil winding
combines simple winding techniques with high electrical
safety, as its insulation is subject to less electrical stress
than other types of windings. While in the case of a con­
ventional round-wire winding, the turn-to-turn voltages
amount to double the voltage between layers, in the case
of a foil winding no more than the simple turn-to-turn
voltage occurs, because in this case each layer consists
of one turn. This results in great power frequency voltage
strength and impulse strength. In addition, the epoxy-resin
vacuum casting of the high-voltage windings is performed at
a high temperature, which avoids hazardous entrapped gas
and allows for a high level of freedom from partial discharges
up to twice the rated voltage. A high level of process exper­
tise guarantees excellent product quality, which is reflected,
among other things, by an excellent MTBF Index.
•• High electrical safety thanks to foil winding
•• Freedom from partial discharges up to twice the rated voltage
•• Standardized accessories
Using vacuum switches with GEAFOL transformers
Transformers are the key operating elements at hubs in the
distribution system. Switches must control the switching of
distribution transformers reliably and safely, with no need
for overvoltage protection.
An important parameter in transformers is the magnetization
current, one of the “small inductive currents.” Interrupting
these currents naturally creates marked transients, but
no unacceptably high switching overvoltages that would
pose a threat to connected distribution transformers are
permitted.
Extensive trials using a combination of Siemens GEAFOL
transformers and vacuum switches have proven that the
GEAFOL medium-voltage windings can handle switching
overvoltages with no difficulty – providing further proof
of their high product quality and operational safety.
Reliable design
The conductive material for the low voltage strip winding
is also made of aluminum, with the width of the aluminum
strip practically equivalent to the length of the coil in order
to considerably reduce the axial short-circuit forces in the
transformer. It’s these characteristics that make the design
of the GEAFOL Basic possible. The conductive and insulating
materials are bonded to each other by heat treatment and
form a compact unit that also reliably handles radial forces.
The ends of the windings are encapsulated in resin.
5
Construction and features
1 Three-limb core made of grain-oriented, low-loss electric
9 High-voltage tappings ±2 x 2.5 % (on the high-voltage
terminal side) to adapt to the respective network conditions;
reconnectable off load
sheet steel insulated on both sides
2 Low-voltage winding made of aluminum strip; turns are
permanently bonded with insulating sheet
Temperature monitoring with PTC thermistor detector in limb V
of the low-voltage winding (in all three phases on request)
3 High-voltage winding made of individual aluminum coils
Painting of steel parts
High-build coating, RAL 5009 on request: special two-component
coating (for particularly aggressive environments)
using foil technology and vacuum casting
4 Low-voltage connectors (facing up)
5 Lifting eyes integrated into the upper core frame for
Structure made of individual components, for example,
windings can be individually assembled and replaced on site
simple transport
6 Delta connection tubes with HV terminals
Climatic Class C2
7 Clamping frame and truck
Environmental Class E2
Convertible rollers for longitudinal and transverse travel
Fire Classification F1
8 Insulation made of an epoxy resin/quartz powder mixture
makes the transformer extensively maintenance-free,
moisture-proof and suitable for the tropics, fire-resistant and
self-extinguishing
5
4
1
6
2
3
9
8
7
A new design for your success – the reliable, space-saving GEAFOL Basic
6
Selection of ordering data
315
400
500
630
800
1000
1250
1600
2000
2500
3150
Noise level
P0
Pk120
LWA
W
W
dB
280
280
400
400
520
520
650
650
750
750
950
950
1100
1100
1300
1300
1550
1550
1800
1800
2200
2200
2600
2600
3100
3100
3800
3800
2050
2050
2900
2900
3800
3800
4500
4500
5500
5500
6600
6600
7600
7600
8000
8000
9000
9000
11000
11000
13000
13000
16000
16000
19000
19000
22000
22000
51
51
54
54
57
57
59
59
60
60
61
61
62
62
64
64
65
65
67
67
68
68
70
70
71
71
74
74
Order No.
kg
mm
mm
mm
4GT5044-3FY
4GT5064-3FY
4GT5244-3FY
4GT5264-3FY
4GT5444-3FY
4GT5464-3FY
4GT5544-3FY
4GT5564-3FY
4GT5644-3FY
4GT5664-3FY
4GT5744-3FY
4GT5764-3FY
4GT5844-3EY
4GT5864-3EY
4GT5944-3EY
4GT5964-3EY
4GT6044-3EY
4GT6064-3EY
4GT6144-3EY
4GT6164-3EY
4GT6244 3EY
4GT6264 3EY
4GT6344-3EY
4GT6364-3EY
4GT6444-3EY
4GT6464-3EY
4GT6544-3EY
4GT6564-3EY
740
860
840
970
1170
1380
1280
1540
1360
1600
1540
1770
1820
1860
2190
2520
2520
2580
3030
2850
3520
3710
4270
4650
5430
5750
7080
7420
1220
1240
1240
1280
1340
1420
1390
1490
1370
1450
1430
1520
1500
1540
1600
1680
1640
1690
1740
1760
1695
1755
1870
1930
2000
2045
2140
2185
690
750
695
725
715
750
820
840
820
835
820
845
840
870
860
900
990
990
990
995
990
1005
1280
1280
1280
1280
1280
1280
970
1200
1100
1180
1125
1225
1115
1215
1270
1355
1270
1390
1485
1505
1505
1595
1575
1635
1695
1735
1845
1895
1885
1975
2125
2175
2435
2490
Height
Load losses
4
4
4
4
4
4
4
4
4
4
4
4
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
No-load losses
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
Impedance voltage
at rated current
%
28/75
50/95
28/75
50/95
28/75
50/95
28/75
50/95
28/75
50/95
28/75
50/95
28/75
50/95
28/75
50/95
28/75
50/95
28/75
50/95
28/75
50/95
28/75
50/95
28/75
50/95
28/75
50/95
Insulation level LV
(AC/LI)
kV
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
Insulation level HV
(AC/LI)
kV
10
20
10
20
10
20
10
20
10
20
10
20
10
20
10
20
10
20
10
20
10
20
10
20
10
20
10
20
uzr
Width
250
Ur
LV
kV
Length
160
Ur
HV
kV
Dimensions 1)
Total weight
kVA
100
Rated secondary
voltage (no-load)
Sr
Rated primary voltage
tapping ± 2 x 2.5 %
Rated power
GEAFOL Basic transformers according to Ecodesign Directive 2009/125/EG,
EU Regulation no. 548/2014
All GEAFOL Basic transformers comply with DIN VDE 0532-76-11/DIN EN 60076-11/IEC 60076-11/DIN EN 50541-1.
Power ratings >3150 kVA, different voltages and designs as well as special equipment on request.
1) Dimension drawing: page 10, indications are approximate values.
7
Selection of ordering data
315
400
500
%
W
28/75
28/75
28/75
28/75
50/95
50/95
50/95
50/95
28/75
28/75
28/75
28/75
50/95
50/95
50/95
50/95
28/75
28/75
28/75
28/75
50/95
50/95
50/95
50/95
28/75
28/75
28/75
28/75
50/95
50/95
50/95
50/95
28/75
28/75
28/75
28/75
50/95
50/95
50/95
50/95
28/75
28/75
28/75
28/75
50/95
50/95
50/95
50/95
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
4
4
6
6
4
4
6
6
4
4
6
6
4
4
6
6
4
4
6
6
4
4
6
6
4
4
6
6
4
4
6
6
4
4
6
6
4
4
6
6
4
4
6
6
4
4
6
6
440
320
360
290
600
400
460
340
610
440
500
400
700
580
650
480
820
600
700
560
880
800
880
650
980
730
850
670
1250
930
1000
780
1150
880
1000
800
1270
1100
1200
940
1300
1000
1200
950
1700
1300
1400
1100
No-load losses
Load losses
Noise level
P0
Pk120
LWA
W
dB
1850
1850
2000
2000
1750
1750
2050
2050
2600
2600
2750
2750
2500
2500
2700
2700
3200
3200
3300
3300
3200
3300
3400
3400
3500
3500
3900
3700
3500
3500
3800
3800
4400
4400
4900
4900
3800
3800
4300
4300
5900
5300
6400
6400
4900
4900
5100
5100
61
51
61
51
61
51
61
51
65
54
65
54
65
54
65
54
68
57
68
57
68
57
68
57
68
59
68
59
68
59
68
59
68
60
68
60
68
60
68
60
69
61
69
61
69
61
69
61
Order No.
kg
mm
mm
mm
4GT5044-3CY
4GT5044-3GY
4GT5044-3DY
4GT5044-3HY
4GT5064-3CY
4GT5064-3GY
4GT5064-3DY
4GT5064-3HY
4GT5244-3CY
4GT5244-3GY
4GT5244-3DY
4GT5244-3HY
4GT5264-3CY
4GT5264-3GY
4GT5264-3DY
4GT5264-3HY
4GT5444-3CY
4GT5444-3GY
4GT5444-3DY
4GT5444-3HY
4GT5464-3CY
4GT5464-3GY
4GT5464-3DY
4GT5464-3HY
4GT5544-3CY
4GT5544-3GY
4GT5544-3DY
4GT5544-3HY
4GT5564-3CY
4GT5564-3GY
4GT5564-3DY
4GT5564-3HY
4GT5644-3CY
4GT5644-3GY
4GT5644-3DY
4GT5644-3HY
4GT5664-3CY
4GT5664-3GY
4GT5664-3DY
4GT5664-3HY
4GT5744-3CY
4GT5744-3GY
4GT5744-3DY
4GT5744-3HY
4GT5764-3CY
4GT5764-3GY
4GT5764-3DY
4GT5764-3HY
600
780
580
710
690
880
700
780
840
940
790
860
910
1070
850
950
990
1140
940
1100
1100
1290
1040
1180
1150
1350
1080
1190
1310
1470
1250
1350
1320
1470
1250
1450
1460
1670
1370
1540
1480
1630
1390
1540
1650
1830
1530
1750
1190
1230
1200
1210
1230
1290
1270
1260
1270
1270
1280
1310
1330
1340
1330
1360
1320
1340
1350
1380
1360
1400
1400
1430
1370
1390
1370
1410
1440
1470
1450
1480
1400
1390
1410
1460
1460
1520
1480
1530
1450
1420
1450
1490
1510
1520
1520
1560
685
690
690
690
750
760
765
725
700
700
710
710
770
735
775
745
705
710
715
725
740
745
750
755
820
820
820
820
835
840
840
840
820
820
820
820
840
845
845
850
820
820
820
820
845
845
855
860
920
985
910
1040
1035
1085
1040
1120
1005
1105
980
990
1085
1130
1075
1095
1045
1125
1045
1070
1155
1210
1115
1135
1075
1155
1120
1125
1190
1210
1200
1190
1225
1325
1220
1240
1310
1310
1275
1320
1180
1345
1255
1250
1370
1385
1270
1355
All GEAFOL Basic transformers comply with DIN VDE 0532-76-11/DIN EN 60076-11/IEC 60076-11/DIN EN 50541-1.
Power ratings >2500 kVA, different voltages and designs as well as special equipment on request.
1) Dimension drawing: page 10, indications are approximate values.
8
Height
Impedance voltage
at rated current
Insulation level LV
(AC/LI)
kV
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
Insulation level HV
(AC/LI)
kV
10
10
10
10
20
20
20
20
10
10
10
10
20
20
20
20
10
10
10
10
20
20
20
20
10
10
10
10
20
20
20
20
10
10
10
10
20
20
20
20
10
10
10
10
20
20
20
20
uzr
Width
250
Ur
LV
kV
Length
160
Ur
HV
kV
Dimensions 1)
Total weight
kVA
100
Rated secondary
voltage (no-load)
Sr
Rated primary voltage
tapping ± 2 x 2.5 %
Rated power
GEAFOL Basic transformers
Selection of ordering data
1250
1600
2000
2500
Noise level
P0
Pk120
LWA
W
W
dB
1500
1150
1370
1100
2000
1600
1650
1250
1800
1400
1700
1300
2400
1900
1900
1500
2100
1600
2000
1500
2800
2300
2300
1800
2400
1800
2700
2100
2800
2100
3100
2400
3500
2600
3900
2900
4300
3000
4400
3500
7300
7300
7500
7500
6900
6900
6800
6800
7800
7800
8300
8300
8500
8500
8200
8200
10000
10000
9500
9500
9500
8700
9000
9000
11000
11000
11200
11200
13600
13600
13200
13200
15500
15500
15800
15800
20000
20000
19000
19000
70
62
70
62
70
62
70
62
72
64
72
64
72
64
72
64
73
65
73
65
73
65
73
65
78
68
78
68
76
68
76
68
78
70
78
70
81
71
81
71
Order No.
kg
mm
mm
mm
4GT5844-3CY
4GT5844-3GY
4GT5844-3DY
4GT5844-3HY
4GT5864-3CY
4GT5864-3GY
4GT5864-3DY
4GT5864-3HY
4GT5944-3CY
4GT5944-3GY
4GT5944-3DY
4GT5944-3HY
4GT5964-3CY
4GT5964-3GY
4GT5964-3DY
4GT5964-3HY
4GT6044-3CY
4GT6044-3GY
4GT6044-3DY
4GT6044-3HY
4GT6064-3CY
4GT6064-3GY
4GT6064-3DY
4GT6064-3HY
4GT6144-3DY
4GT6144-3HY
4GT6164-3DY
4GT6164-3HY
4GT6244-3DY
4GT6244-3HY
4GT6264-3DY
4GT6264-3HY
4GT6344-3DY
4GT6344-3HY
4GT6364-3DY
4GT6364-3HY
4GT6444-3DY
4GT6444-3HY
4GT6464-3DY
4GT6464-3HY
1660
1880
1760
1900
1900
2090
1800
2140
2020
2280
2000
2240
2140
2360
2120
2340
2560
2980
2390
2650
2580
2860
2460
2760
2710
3220
2850
3150
2970
3340
3200
3570
3640
4090
3700
4070
4380
5030
4590
5070
1460
1480
1550
1560
1550
1520
1590
1650
1520
1550
1610
1640
1550
1580
1650
1670
1600
1640
1620
1660
1590
1630
1660
1700
1720
1780
1780
1800
1705
1745
1765
1800
1805
1855
1785
1820
1895
1920
1900
1990
820
820
835
835
855
845
865
880
820
830
845
855
855
860
875
885
990
990
990
990
990
990
990
990
990
990
990
990
990
990
1010
1015
1280
1280
1280
1280
1280
1280
1280
1280
1335
1430
1350
1370
1405
1570
1370
1400
1520
1540
1345
1370
1615
1605
1445
1450
1635
1745
1580
1560
1790
1810
1645
1680
1655
1715
1695
1710
1710
1730
1810
1860
1815
1850
2025
2055
2045
2085
2150
2135
Height
Load losses
4
4
6
6
4
4
6
6
4
4
6
6
4
4
6
6
4
4
6
6
4
4
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
No-load losses
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
3/–
Impedance voltage
at rated current
%
28/75
28/75
28/75
28/75
50/95
50/95
50/95
50/95
28/75
28/75
28/75
28/75
50/95
50/95
50/95
50/95
28/75
28/75
28/75
28/75
50/95
50/95
50/95
50/95
28/75
28/75
50/95
50/95
28/75
28/75
50/95
50/95
28/75
28/75
50/95
50/95
28/75
28/75
50/95
50/95
Insulation level LV
(AC/LI)
kV
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
Insulation level HV
(AC/LI)
kV
10
10
10
10
20
20
20
20
10
10
10
10
20
20
20
20
10
10
10
10
20
20
20
20
10
10
20
20
10
10
20
20
10
10
20
20
10
10
20
20
uzr
Width
1000
Ur
LV
kV
Length
800
Ur
HV
kV
Dimensions 1)
Total weight
kVA
630
Rated secondary
voltage (no-load)
Sr
Rated primary voltage
tapping ± 2 x 2.5 %
Rated power
GEAFOL Basic transformers
All GEAFOL Basic transformers comply with DIN VDE 0532-76-11/DIN EN 60076-11/IEC 60076-11/DIN EN 50541-1.
Power ratings >2500 kVA, different voltages and designs as well as special equipment on request.
1) Dimension drawing: page 10, indications are approximate values.
9
Truck dimensions
Rated power
Dimensions in mm
e
f
g
k
630 to 800
Sr in kVA
670
125
40
45
1000 to 1600
820
160
50
55
2000 to 3150
1070
200
70
65
Dimension drawing of the transformer
A1
3
2N
2U, 2V, 2W
1
1U
1V
1W
2
H1
k
e
f
Dimension drawing
Dimensions A1, B1 and H1, see pages 7 to 9
Dimension e applies for longitudinal and transverse travel
10
g
B1
1 High-voltage terminal
2 High-voltage tappings on the HV terminal side
3 Low-voltage terminal
Terminal dimensions
(low-voltage)
Hole measurements for 400-V low-voltage terminals
Rated power
Fig.
Sr in kVA
Dimensions in mm
a
b
630
1
26
26
800 to 1250
2
60
40
1600
3
40
40
2000
3
50
40
2500
3
60
40
3150
4
60
40
Ø14
a
b
b
Fig. 1
Fig. 2
a
a
Ø14
b
Fig. 3
Ø14
a
a
a a
Ø14
b
Fig. 4
Dimensions in mm
Notes
Unless indicated otherwise on the individual pages of
this catalog, the specified values, dimensions and weights
in particular are subject to change without notice.
The illustrations are non-binding. All product designations
used are trademarks or product names of Siemens AG
or other suppliers. All dimensions in this catalog are given
in mm unless stated to the contrary.
11
Accessories*)
GEAFOL transformers can be equipped with fans to
increase the power rating by up to about 30 percent.
Ue = 250 V
Ie = 3 A
AC 15
With a 25 percent increase in power rating, for example,
the short-circuit losses given in the list are increased by
about 56 percent, and the short-circuit voltage increases
in linear fashion by 25 percent.
Alarm 2
PTC 1
Alarm 1
PTC 2
A2
~
Us
21
24
11
11
12
14
T0
T2
T1
PTC Alarm 1
DC+
AC~
A1
PTC Alarm 2
test
A1
Alarm 1
The fans are automatically switched on or off via
temperature sensors in the LV winding in connection
with a fan controller.
.com
MSF 220 K
PTC thermistor relay
T 2217 …
Alarm 2
Additional transformer ventilation
for more power
Terminal diagram: Standard trip relay for PTC sensors
Temperature monitoring
The temperature of GEAFOL transformers is monitored in the
low-voltage winding by means of PTC thermistor detectors
or by using PT 100 sensors (on request).
In the case of static converter transformers, the core tem­
perature is monitored additionally. The most cost-effective
solution is monitoring with PTC thermistor detectors and
trip relay without temperature indication.
Every GEAFOL transformer is equipped at least with
a PTC thermistor detector loop for tripping.
Function
Temperature monitoring with PTC thermistors: If two sensor
systems are used to monitor temperature, one is wired up
to give an alarm and the other to switch off the transformer.
The nominal operating temperatures of both systems differ
by 20 K. A third system can, for example, take over control­
ling of the fans.
The temperature sensors function as resistors. If the
response temperature of a sensor is reached, the resis­
tances rises sharply and the trip relay switches over
immediately.
If the winding cools down by about 6 K below the operating
temperature, the relay coil in the trip relay is fully energized
and the contact switches back.
The ambient temperature of the trip relay is limited to
55 °C. It is therefore suitable for installation in mediumor low-voltage distribution cabinets.
*) Accessories upon request
12
Standard housing
Installation
Protection class
Indoor
Indoor
IP00
IP20
IP23
IP23D
IP23DW
A
B
C
D
E
●
●
●
●
14th character of order no.
Indoor
Outdoor
Environmental influences
Enclosed electrical operating
areas
●
Electrical operating areas
–
●
●
●
●
Water up to 60° up to the l –
–
●
●
●
Snow
–
–
–
–
●
Direct sunlight
–
–
–
–
●
Salty air
●
●
●
●
● Special paint finish
Aggressive chem. atmosphere
●
●
●
●
● Special paint finish
Accidental contact
–
●
●
●
●
Foreign matter >12 mm Ø
–
●
●
●
●
Protection against access
with wire1)
–
–
on request
●
●
1) Test wire diameter 1 mm according to EN 60529.
Roof construction of protection class IP23
(indoor installation)
Graphic:
Cutaway section of the ventilation slots
with the roof strips.
Photo:
The roof strips are turned down at the
side walls and screwed firmly in place.
Labyrinth arrangement of ventilation
louvers provides additional security
against access with wire.
13
Standard housing
Variable connection technology: The cable can be fed in through
the floor, the roof or through one of the side walls.
A reduction in power is possible in case of
installation inside the protective housing.
Dimension drawing of the housing
Indoor (protection class IP20)
H
Housing
size
1
L
W
Outdoor (protection class IP23DW)
Housing
size
1
Max. housing dimensions
mm
L
W
H
1440
1070
1540
Max. housing dimensions
mm
L
W
H
1390
1010
1335
Housing weight
kg
121
2
1860
1280
1535
177
3
1860
1280
1885
211
4
2120
1500
2120
252
5
2360
1500
2340
290
Indoor (protection class IP23 and IP23D)
Housing weight
kg
153
Housing
size
1
Max. housing dimensions
mm
L
W
H
1390
1010
1395
Housing weight
kg
134
2
1880
1320
1845
233
2
1860
1280
1595
207
3
1880
1420
2245
267
3
1860
1280
1945
247
4
2240
1540
2480
325
4
2120
1500
2225
302
5
2380
1540
2950
392
5
2360
1500
2495
370
14
Selection of ordering data*) **)
Standard housing for GEAFOL Basic transformers
Rated
power Sr
(kVA)
100
160
250
315
315
400
500
Rated
voltage HV
Ur (kV)**)
Type
Housing
size
10
10
10
10
20
20
20
20
10
10
10
10
20
20
20
20
10
10
10
10
20
20
20
20
10
10
10
10
20
20
20
20
10
10
10
10
20
20
20
20
10
10
10
10
4GT5044-3CY
4GT5044-3GY
4GT5044-3DY
4GT5044-3HY
4GT5064-3CY
4GT5064-3GY
4GT5064-3DY
4GT5064-3HY
4GT5244-3CY
4GT5244-3GY
4GT5244-3DY
4GT5244-3HY
4GT5264-3CY
4GT5264-3GY
4GT5264-3DY
4GT5264-3HY
4GT5444-3CY
4GT5444-3GY
4GT5444-3DY
4GT5444-3HY
4GT5464-3CY
4GT5464-3GY
4GT5464-3DY
4GT5464-3HY
4GT5544-3CY
4GT5544-3GY
4GT5544-3DY
4GT5544-3HY
4GT5564-3CY
4GT5564-3GY
4GT5564-3DY
4GT5564-3HY
4GT5644-3CY
4GT5644-3GY
4GT5644-3DY
4GT5644-3HY
4GT5664-3CY
4GT5664-3GY
4GT5664-3DY
4GT5664-3HY
4GT5744-3CY
4GT5744-3GY
4GT5744-3DY
4GT5744-3HY
2
2
2
2
2
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Rated
power Sr
(kVA)
Rated
voltage HV
Ur (kV)**)
Type
Housing
size
20
20
20
20
10
10
10
10
20
20
20
20
10
10
10
10
20
20
20
20
10
10
10
10
20
20
20
20
10
10
20
20
10
10
20
20
10
10
20
20
10
10
20
20
4GT5764-3CY
4GT5764-3GY
4GT5764-3DY
4GT5764-3HY
4GT5844-3CY
4GT5844-3GY
4GT5844-3DY
4GT5844-3HY
4GT5864-3CY
4GT5864-3GY
4GT5864-3DY
4GT5864-3HY
4GT5944-3CY
4GT5944-3GY
4GT5944-3DY
4GT5944-3HY
4GT5964-3CY
4GT5964-3GY
4GT5964-3DY
4GT5964-3HY
4GT6044-3CY
4GT6044-3GY
4GT6044-3DY
4GT6044-3HY
4GT6064-3CY
4GT6064-3GY
4GT6064-3DY
4GT6064-3HY
4GT6144-3DY
4GT6144-3HY
4GT6164-3DY
4GT6164-3HY
4GT6244-3DY
4GT6244-3HY
4GT6264-3DY
4GT6264-3HY
4GT6344-3DY
4GT6344-3HY
4GT6364-3DY
4GT6364-3HY
4GT6444-3DY
4GT6444-3HY
4GT6464-3DY
4GT6464-3HY
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
4
4
3
3
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
5
5
5
5
5
5 1)
5
52)
Rated
voltage HV
Ur (kV)**)
Type
Housing
size
4GT5944-3EY
4GT5964-3EY
4GT6044-3EY
4GT6064-3EY
4GT6144-3EY
4GT6164-3EY
4GT6244-3EY
4GT6264-3EY
4GT6344-3EY
4GT6364-3EY
4GT6444-3EY
4GT6464-3EY
3
4
3
4
4
4
4
4
4
4
51)
52)
500
630
800
1000
1250
1600
2000
2500
Standard housing for GEAFOL Basic transformers per the Ecodesign Directive
Rated
power Sr
(kVA)
100
160
250
315
400
500
630
Rated
voltage HV
Ur (kV)**)
Type
Housing
size
10
20
10
20
10
20
10
20
10
20
10
20
10
20
4GT5044-3FY
4GT5064-3FY
4GT5244-3FY
4GT5264-3FY
4GT5444-3FY
4GT5464-3FY
4GT5544-3FY
4GT5564-3FY
4GT5644-3FY
4GT5664-3FY
4GT5744-3FY
4GT5764-3FY
4GT5844-3EY
4GT5864-3EY
1
2
2
2
2
2
2
2
3
3
3
3
3
3
Rated
power Sr
(kVA)
800
1000
1250
1600
2000
2500
> 2500
10
20
10
20
10
20
10
20
10
20
10
20
Housing on request
*) Different design and special equipment on request **) Design for 30 kV on request
1) IP20: Height + 100 mm 2) IP20/IP23/IP23D/IP23DW: Width and height + 100 mm
Apart from standard housings we can supply housings with frame construction and doors that can also be equipped with roof ventilators.
These housing types are also suitable for combined installation with low- and medium-voltage cabinets. Please ask us if you need them.
15
Published by
Siemens AG 2015
Energy Management Division
Freyeslebenstrasse 1
91058 Erlangen, Germany
Transformatorenwerk Kirchheim/Teck
Hegelstrasse 20
73230 Kirchheim/Teck, Germany
Phone: +49 (0) 7021 508-0
Fax: +49 (0) 7021 508-495
Siemens Transzformátor Kft.
1214 Budapest
II. Rákóczi Ferenc u.189., Hungary
Phone: +36 (1) 278 5300
Fax: +36 (1) 278 5335
For more information, please contact
our Customer Support Center.
Phone: +49 180/524 70 00
Fax:
+49 180/524 24 71
(Charges depending on provider)
E-mail:[email protected]
Article No. EMTR-B10005-01-4A00
Printed in Germany
Dispo 19201
TH 101-150766 WÜ WS 12151.0
Subject to changes and errors.
The information given in this document only contains general
descriptions and/or performance features which may not always
specifically reflect those described, or which may undergo
modification in the course of further development of the products.
The requested performance features are binding only when they
are expressly agreed upon in the concluded contract.