English User's Manual

User's Guide
3000A Current Probe Set
Model PQ34-30
Introduction
Congratulations on your purchase of this Extech Current Probe Set. A set of three 3000A flexible
current probes designed to be used with the Extech PQ3450 or PQ3470 Power Analyzers. These
probes are shipped fully tested and calibrated and, with proper use, will provide years of reliable
service.
Safety
This symbol, adjacent to another symbol or terminal, indicates the user must refer to the
manual for further information.
This symbol, adjacent to a terminal, indicates that, under normal use, hazardous voltages
may be present
Double insulation
Cautions

Read and understand this user manual before operating the meter.

Improper use of this meter can cause damage, shock, injury or death.

Inspect the condition of the leads and the meter itself for any damage before operating the
meter.

Use great care when making measurements if the voltages are greater than 25VAC rms or
35VDC. These voltages are considered a shock hazard.

Do not attempt to measure Current that exceeds specified limits

Do not operate this instrument in wet or dusty environments.

Do not operate this instrument in the presence of combustible or explosive gas

Do not touch exposed metal parts or unused terminals.

Use protective gloves near high current or voltage circuits.

If the equipment is used in a manner not specified by the manufacturer, the protection provided
by the equipment may be impaired.
2
PQ-12-EU-EN V1.0 01/12
Probe Description
1. Flexible current probe
1
2
2. Probe latch
3. Power LED
4. 3000A-300A-30A range switch
3
4
5. Signal output plug ( +, red )
6. Signal output plug ( -, black )
7. DCV power plug
5
6
7
Operation
1.
Connect the signal output cables from the first clamp to the “A1”
input sockets on the top of the analyzer.
2.
Connect the clamp’s power cable to the “A1” power socket on the
top of the analyzer.
3.
Set the "3000A-300A-30A” range switch to the range appropriate
for the application.
Note: Make sure the range set on the clamp matches the range
set in the analyzer.
4.
Connect the “A2” and “A3” clamps as above, if needed.
5.
Squeeze the latch release to open the loop and clamp around a
single conductor.
6.
Power on the power analyzer
3
PQ-12-EU-EN V1.0 01/12
Specifications
Measurement ranges
30A, 300A and 3000A, switch selectable
Output sensitivity
100mV/A on the 30A range
10mV/A on the 300A range
1mV/A on the 3000A range
Output coupling
Accuracy (50/60Hz)
Frequency range
Max conductor size
Phase error (50/60Hz)
AC coupled.
± 1% F.S. @ 23 ± 5°C (50/60Hz)
45 to 400 Hz.
Round: (177mm (7”), Oval: 216mm (8.5”)
< ± 1°
Minimum load
100 K ohm for specified accuracy
Linearity
±0.2% of reading from 10% to 100% of range
Phase error
<±1.5° (50/60Hz)
Conductor position sensitivity
± 2% F.S (conductor should be >25mm (1”) from the probe
latch.
Enclosure material
UL 94-V0 rated
Safety
IEC 1010, Category III 600V
Power Supply
8V± 1V (supplied from meter)
Operating Temperature
0°C to 50°C (32°F to 122°F)
Operating Humidity
Dimension
Circuit box:
Flexible probe:
Less than 80% RH
105 x 56.5 x 33 mm. (4.1 X 2.2 X 1.3”
600mm (23.6”) (length), 14.5mm 0.57” (diameter)
Cable length :
3.4 meters (11.2 feet)
DC plug size :
5.5 mm x 2.5 mm DIA.
Weight
480 g (1.06 LB)
www.extech.com
4