FlexView, DFO - Graphical display with ColourView indication Safety instructions The configurable FlexView, DFO grafical LCD display is used for read-out of a 4-20 mA signal. The process values, error indications, damping, engineering units, backlight, etc. can be configured by use of touch buttons on the front or by using the FlexProgrammer incl. FP-software. Some applications are working with a zoomed area e.g. 10...15 mA, which can be shown as a full 0...100% of the zoomed area. Custom engineering unit is selectable in the Flexprogramme by use of the 8×20 dot matrix field. Further a 30-point liniarization table can be entered for e.g. volume read-out. Electrical connection Terminal 1- 4-20 mA loop powered (Supply) Terminal 2- 4-20 mA loop powered (Supply) Terminal 3- Relay 1 - NO Terminal 4- Relay 1 - NO Terminal 5- Relay 2 - NO Terminal 6- Relay 2 - NO (When new instruments PFMx, LFPx, AFKx etc. are delivered with FlexView, DFO terminal 1 and 2 are not connected. Then FlexView, DFO will have power and data through a special flat cable. The connected instrument can also be programmed through the FlexView, DFO display, by selecting its DTM-file) Programming connect the FlexProgrammer to the FlexView, DFO. Com. 1-Red clip 1 it is not necessary to disconnect Com. 2-Black clip 2 the 4-20 mA loop to the FlexView, DFO display The electrical installation must always be according to national standards and regulations. Installation must be performed by trained staff only and always according to the wiring diagram. Shielded twisted pair cable is recommended. Correct and safe installation and operation of the FlexView, DFO is dependent on proper transport, storage, installation and operation. Before switching on or off the power, it must be ensured that no other equipment is affected and that the correct voltage is used. If in hazardous area (EX-area) installation must be according to the ATEX specifications and local standards and regulations – see separate instructions in “Operation Instructions FlexView, DFO”. Different ways of mounting are available. Mounted in the housing of an instrument as a pre-mounted display, the FlexView, DFO is selected without or with relay output. When new instruments PFMx, LFPx, AFKx etc. are delivered with FlexView, DFO, terminal 1 and 2 are not connected. In this case the FlexView, DFO will have power and data through a special digital communication cable. The instrument can then also be programmed directly through the FlexView, DFO display, by selecting its DTM-file. Alternatively the FlexView, DFO is delivered in a Ø80 mm housing for separate wall mounting. www.baumer.com Design and specifications subject to change without notice Installation Manual Page 1 Selectable views Value Small / Large Analog w. Bar graph / Value Bar graph Vertical / horizontal Tank illustration Tank / Bottle Programming by FlexProgrammer and/or touch screen The FlexProgrammer 9701 is a dedicated tool to configure all Baumer configurable products. FlexProgrammer, No. : 9701.0001 The FlexProgrammer interface unit will be delivered complete including - CD with FlexProgram software - Product drivers (DTM-files) - USB cable - Cable with 2 alligator clips - Cable with M12 connector For programming by the FlexProgrammer 9701 you will need to download tthe software from the Baumer homepage. Instructions for use can be found under « Help » If relays is to be activated in an instrument delivered with relays ”not activated”, please order an activation code from Baumer by informing of the serial number of the instrument (the code is unique for each instrument). The activation code must be entered under ”Identification” in the Flexprogramme (it cannot be entered using the touch screen). Order option: DFO-SW. www.baumer.com Design and specifications subject to change without notice Installation Manual Page 2 Programming Configuration see page 4 Screen layout Select between several display designs Colour Normal backlight colour (White/Red/Green) Intensity Backlight intensity (10 .. 140%) Password enable Enable / Disable New password Input new password Attached instrument Display name of attached instrument Attached instr. menu Access instrument specific menu Backlight MENU Display setup Password Attached instrument Diagnostics Menu timeout Select idle time before menu reset Statistics Min./max. value High/low errors Uptime since power-on/restart Demo setup www.baumer.com Design and specifications subject to change without notice Select demo mode Disabled/Static/Cyclic Static display value Input value used in static demo mode Factory settings Load Factory settings Service menu For service personnel Installation Manual Page 3 Programming Input Display output TAG No. / Serial No. / Date / Prod.date Input 100% Loop current at 100% (e.g. 20 mA) Input 0% Loop current at 0% (e.g. 4 mA) Damping 0 = off / 1…30 sec. Liniarization correction Enable / Disable Display 100% Displayed value at 100% input Display 0% Displayed value at 0% input Decimals Digits after point Units Pressure units 5850-036_EN/2012-04-02 This data sheet may only be reproduced in full. Identification Temperature units Electric units Configuration Other units MENU Abs./Rel. Select Absolute/Relative or none High error High error limit High error indication Error/warning setup Display setup (see page 3) Diagnostics Relay setup High error backlight High warning Same as for high error Low warning Same as for high error Low error Same as for high error Relay 1 mode AO / AC / NO / NC Relay 1 set point Point at which relay sets Relay 1 reset point Point at which relay resets Relay 2 mode AO / AC / NO / NC Relay 2 set point Point at which relay sets Relay 2 reset point Point at which relay resets This menu section is only accessible when the relays are activated www.baumer.com Design and specifications subject to change without notice Installation Manual Page 4