Carling Thermal CB Catalog [pdf]

THERMAL
Circuit Protection
CATALOG
• Rocker
• Toggle
• Pushbutton
• Rotary
CIRCUIT
PROTECTION
• Hydraulic-Magnetic
• Thermal
• GFCI / ELCI
CUSTOM
SOLUTIONS
• PDU’s
• Keypads
• Control Modules
STRATEGIC MARKETS SERVED:
On/Off Highway
Marine
Telecom/Datacom
Military
Renewable Energy
GLOBAL LOCATIONS:
ISO9001:2008
ISO/TS16949:2009
ISO9001:2008
ISO/TS16949:2009
ISO9001:2008
ISO/TS16949:2009
ISO14001:2004
ISO9001:2008
ISO/TS16949:2009
ISO14001:2004
ISO9001:2008
ISO/TS16949:2009
ISO14001:2004
ISO9001:2008
ISO/TS16949:2009
COMPETITIVE ADVANTAGES +
Vertical
Integration
ii
Reliable &
On-Time Delivery
Excellent
Customer Service
MULTIPLEXED
POWER SYSTEMS
• HMI Devices & I/O Modules
• Programmable Displays
• Data Communication Interfaces
• Electrical Systems Monitoring
.....................................................................................................................
SWITCHES &
CONTROLS
...................
Since its founding, Carling
Technologies has continually
forged a tradition of leadership in
quality and product innovation.
...................
1920
There are few products that Carling Technologies hasn’t
turned “ON” and fewer industries that haven’t turned to
Carling for solutions. With ISO and TS registered
manufacturing facilities and technical sales offices
worldwide, Carling ranks among the world’s largest
manufacturers of circuit breakers, switches, power distribution
units, digital switching systems and electronic controls.
...................
FOUNDED IN
Innovative &
Eco-Friendly Products
OTHER SERVED
INDUSTRIES:
Medical
Industrial Control
Audio / Visual
Commercial Food
HVAC
Floor Care
Generators
Small Appliances
Security Systems
Test & Measurment
WORLDWIDE
NUMBERS:
2000+ 150+
EMPLOYEES
ENGINEERS
70 +
50+
DISTRIBUTORS
REP FIRMS
www.carlingtech.com
Table of Contents
2
C1005B–Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Selector Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Lighted Rocker Thermal Circuit Protection,
Ratings up to 16A AC/DC
CTB–Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Panel Mount Rocker Thermal Circuit Protection,
Ratings up to 15A AC/DC
CMB–Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pushbutton Thermal Circuit Protection,
Ratings up to 20A AC/DC
CLB–Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pushbutton Thermal Circuit Protection,
Ratings up to 60A AC/DC
CMBA/CLBA–Series. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Auto-Reset Thermal Circuit Protection,
Ratings up to 40A AC/DC
5
7
9
11
Thermal Circuit Protectors
This catalog features Carling Technologies’ current line of thermal circuit protectors, from 3 to 60
amps, which offer reliable, cost effective circuit protection. Thermal circuit protectors utilize a
bimetallic strip electrically in series with the circuit. The heat generated by the current during an
overload deforms the bimetallic strip and trips the breaker. Thermal protectors have a significant
advantage over fuses in that they can be reset after tripping. They can also be used as the main ON/
OFF switch for the equipment being protected.
Typical Applications Include:
• Household Appliances
• Transportation
• Marine
• Power Strips
• Medical Equipment
• Audio Visual Equipment
• Power Supplies
• Exercise Equipment
© 2016 Carling Technologies, Inc.
Carling Technologies is a registered trademark of Carling Technologies, Inc. in the U.S. and other countries.
www.carlingtech.com
1
Selector Guide
C1005B-Series
CTB-Series
CMB-Series
CLB-Series
CMBA/CLBA-Series
Number of Poles
1
1
1
1
1
Actuator Style
rocker,
lighted rocker
rocker
pushbutton
pushbutton
n/a
Max Current &
Voltage Ratings
7 to 16A,
125-250VAC,
32VDC
3 to 16A,
125-250VAC,
50VDC
3 to 20A,
125-250VAC,
32 VDC
3 to 60A,
125-250VAC,
32 VDC
3 to 40A,
125-250VAC,
32 VDC
Max Interrupting
Capacity
1000A
1000A
2500A@32VDC
2500A@32VDC
2500A@32VDC
Available Circuits
series trip
manual reset
series trip
manual reset
series trip
manual reset
series trip
manual reset
series trip
auto reset
Terminal Options
.250” tab,
solder lug
.250” tab
.250” tab,
.250” tab with 90° bend,
screw terminal,
screw terminal with 90°
bend
.250” tab,
.250” tab with 90° bend,
screw terminal,
screw terminal with 90°
bend
.250” tab,
.250” tab with 90° bend
Mounting Method front panel snap-in
front panel snap-in
threaded bushing,
front panel snap-in
threaded bushing,
front panel snap-in
plug-in
Operating
Temperature
-10°C to 65°C
-10°C to 60°C
-10°C to 60°C
-10°C to 60°C
-10°C to 60°C
Agency
Approvals
UL, CUL, TUV
UL, CUL, VDE, CE
UL, CUL, CSA, TUV, CE,
UL 1500 / ISO 8846 for
ignition protection / marine
UL, CUL, CSA, TUV, CE,
UL 1500 / ISO 8846 for
ignition protection /
marine
UL, CUL, TUV,
UL 1500 / ISO 8846 for
ignition protection /
marine
*Manufacturer reserves the right to change product information without prior notice
2
www.carlingtech.com
C1005B
C1005B-Series - Introduction
C1005B-Series
THERMAL CIRCUIT PROTECTORS
The C1005B-Series offers the functionality of a switch and circuit breaker in a single compact package, which
fits an industry standard .550 x 1.125 mounting hole. This combo device eliminates the need for both a switch
and thermal circuit protector on customer panels. By using only this multipurpose product, wiring and assembly
costs are greatly reduced, while at the same time, valuable panel real estate is saved.
The C1005B-Series is available lighted or unlighted, in a variety of colors, with solder lug or .250 tabs. Current
ratings range from 7-16 amps@125 and 250 VAC and up to 32 VDC.
Product Highlights:
.550 x 1.125 mounting hole (14mm x 28.6mm)
Ratings from 7-16A
ŠŠ Standard Reset/Off Legend
ŠŠ Curved Rocker & Angular Bezel
ŠŠ .250 Tabs or Solder Lug Terminations
ŠŠ 65°C Max Operating Temperature
ŠŠ 1000 AIC Interrupting Capacity
ŠŠ 1500 VAC Dielectric Strength
ŠŠ 100M ohms @500VDC Insulation Resistance
ŠŠ Compact Space-Saving Envelope
ŠŠ UL1077, UL1363, IEC 60934
Typical Applications:
Household Appliances
Commercial Appliances
ŠŠ Transportation
ŠŠ Marine
ŠŠ Telecommunications
ŠŠ Power Strips
ŠŠ Audio-visual Equipment
ŠŠ Medical equipment
ŠŠ Power supplies
ŠŠ Generators
ŠŠ
ŠŠ
ŠŠ
ŠŠ
www.carlingtech.com
3
C1005B-Series - Ordering Scheme, Time Delay, Dimensional Specifications
C1005B
3 B 15 1 B R 3
1
Series
2
3
4
Illumination Termination Current
Rating
5
Contact
Material
6
Bezel
Legend
7
Rocker
Color
8
Lamp
Voltage
1 SERIES
C1005B
5 CONTACT MATERIAL 1
1
Silver Cad Oxide (switch), Silver plated copper (breaker)
2 ILLUMINATION
2
Non-Lighted
3
Lighted
6 BEZEL LEGEND IMPRINT
B
Black Bezel with white legend
W White Bezel with black legend
C
Gray Bezel with black legend
3 TERMINATION
A
Solder Lug
B
.250 Tab
4 CURRENT RATING (AMPERES)
07
7 amps
08
8 amps
09
9 amps
10
10 amps
11
11 amps
12
13
14
15
16
7 ROCKER COLOR
R
Red
G
Green
U
Blue
T
Clear
Note: RESET OFF Legend is standard.
12 amps
13 amps
14 amps
15 amps
16 amps
8 LAMP VOLTAGE
3
Neon Lamp 125/250 VAC
9
Non-lighted
Notes:
1.
Silver cad oxide switch and breaker contacts are available as a special order.
Specify 3 for selection 5
Dimensional Specifications: in. [mm]
1.280 [32.5]
1.125 [28.6]
.669 [17]
.858 [21.8]
PANEL CUT OUT
.550 [14]
.07 [1.79]
.921 [23.4]
.236 [6]
.472 [12]
.0315 [.8]
.394 [10]
.394 [10]
.248 [6.17]
1.102 [28]
.532 [13.5]
Time Delay
Percentage of Rated Current
Overload
Trip Time
100%
No Trip
150%
Trip in 1 hr
200%
4.0 ~ 40 sec.
300%
0.9 ~ 8.0 sec.
400% 0.42 ~ 5.0 sec.
500% 0.25 ~ 3.0 sec.
600% 0.01 ~ 1.8 sec.
Trip Time in Seconds
Time Trip Factor 1
-10 °C x 1.70
-5 °C
x 1.60
0 °C
x 1.50
5 °C
x 1.40
10 °C x 1.30
15 °C x 1.20
20 °C x 1.10
25 °C x 1.00
Time Trip Factor 1
30 °C x 0.90
35 °C x 0.85
40 °C x 0.80
45 °C x 0.75
50 °C x 0.70
55 °C x 0.65
60 °C x 0.60
Notes:
1.
Trip Time factor
is a guideline that
indicates ambient
temperature effect on
trip times at various
overload values.
*Manufacturer reserves the right to change product specification without prior notice.
4
www.carlingtech.com
CTB-Series - Introduction
CTB
CTB-Series
THERMAL CIRCUIT PROTECTORS
The CTB-Series is a compact, single pole, rocker actuated family of thermal circuit breakers designed to
protect equipment. Utilizing simple, precision design with few moving parts, these breakers offer cost effective,
extremely reliable circuit protection with high resistance against shock and vibration. Electrical ratings range
from 3 to 16 amps at 125, 250VAC or 50VDC. This breaker resets with the push of a finger and features a snap
in mounting style, utilizing a 16mm dia. round Double D mounting hole.
Product Highlights:
Ratings from 3-16A, 125, 250VAC, 50VDC
.250 Tabs
ŠŠ 60°C Max Operating Temperature
ŠŠ 1000 AIC Interrupting Capacity
ŠŠ 100M ohms Insulation Resistance
ŠŠ UL, cUL, VDE, CE
Applications:
Household Appliances
Transportation
ŠŠ Marine
ŠŠ Power Strips
ŠŠ Medical Equipment
ŠŠ Audio Visual Equipment
ŠŠ Power Supplies
ŠŠ Exercise Equipment
ŠŠ ROHS Complaint
ŠŠ
ŠŠ
ŠŠ
ŠŠ
www.carlingtech.com
5
CTB-Series - Ordering Scheme, Dimensional Specifications, Time Delay
CTB
1
Series
B
2
Bezel Color
B
05
3
Rocker Color
4 RATING
03 3 amps
04 4 amps
05 5 amps
06 6 amps
07 7 amps
1 SERIES
CTB
2 BEZEL COLOR 1
B Black
3 ROCKER COLOR 1
B Black
B
5
Panel
Thickness
4
Rating
08
09
10
12
13
8 amps
9 amps
10 amps
12 amps
13 amps
14
15
16
14 amps
15 amps
16 amps
5 PANEL THICKNESS
blank fits standard thickness of .032 – .062
B
fits .070 – .110 panel thickness
Notes:
1.
Additional colors available. Consult factory.
Dimensional Specifications: in. [mm]
RECOMMENDED PANEL THICKNESS:
.032 - .062 [.81-1.57
Notes:
All dimensions are in inches [millimeters].Tolerance ±.005 [.127] unless otherwise specified. Breaker must
hold 100% of rated current and must trip at 150% and above, within the time limits shown in curve. Trip
times specified at 25° ambient with no preloading.
Time Delay
Percentage of Rated Current
Overload
Trip Time
100%
No Trip
135%
Trip in 1 hr
200%
2.2 ~ 15 sec.
300%
0.9 ~ 3.4 sec.
400% 0.57 ~ 1.6 sec.
500% 0.38 ~ 0.94 sec.
600% 0.27 ~ 0.76 sec.
Trip Time in Seconds
Correction Factor 1
0 °C
x 0.85
10 °C
x 0.90
15 °C
x 0.925
18 °C
x 0.952
25 °C
x 1.00
32 °C
x 1.05
40 °C
x 1.15
50 °C
x 1.39
60 °C
x 1.49
Notes:
1.
To adjust the breaker rating for ambient
temperature, multiply the breaker rating
by the factor. ex: 5A rating x .850 = 4.25A.
Select 4A rating.
*Manufacturer reserves the right to change product specification without prior notice.
6
www.carlingtech.com
CMB-Series - Introduction
CMB
CMB-Series
THERMAL CIRCUIT PROTECTORS
The CMB-Series is a compact, single pole, push-to-reset family of thermal circuit breakers designed to protect
equipment. Utilizing simple, precision design with few moving parts, these breakers offer cost effective,
extremely reliable circuit protection with high resistance against shock and vibration.
Product Highlights:
Ratings from 3-20A, 125, 250VAC, 32VDC
ŠŠ 2500 VAC/1 minute
ŠŠ 60°C Max Operating Temperature
ŠŠ 2500A @ 32VDC Interrupting Capacity
ŠŠ 100M ohms Insulation Resistance
ŠŠ Voltage drop <0.25 V
ŠŠ UL, CUL, CSA, TUV, CE
ŠŠ UL1500/ISO8846 for ignition protection/marine
ŠŠ
Applications:
Household Appliances
Transportation
ŠŠ Marine
ŠŠ Power Strips
ŠŠ Medical Equipment
ŠŠ Audio Visual Equipment
ŠŠ Power Supplies
ŠŠ ROHS Complaint
ŠŠ
ŠŠ
Dimensional Specifications: in. [mm]
www.carlingtech.com
7
CMB-Series Pushbutton Thermal Circuit Protector
CMB
10 3
1
Series
2
Rating
1 SERIES
CMB
2 RATING
03
3 amps
04
4 amps
05
5 amps
06
6 amps
07
7 amps
08
8 amps
11 C 3 N
3
Voltage
4
Mounting
Hole
5
Bushing
Type
6
Mounting
Nut
B
7
Indicator
Plate
8
Button
A /10
9
Terminal
10
Button Marking
3 VOLTAGE
3
125-250VAC/ 32 VDC
10
12
13
14
15
16
20
4 MOUNTING HOLE
11 1 M11
12 2 M12
00 3 Snap In Style
27 9 3/8” 27 UNS
28 12 3/8” 27 UNS
(double flatted)
10 amps
12 amps
13 amps
14 amps
15 amps
16 amps
20 amps
5 BUSHING
PLASTIC
C 4 Type C
D 4 Type D
E 5 Type E
G 8 Type G
H 6 Type H
K 13 Type K
METAL
Type J
J 8
6 MOUNTING NUT 7
N
None
1
Type 1
2
Type 2
3 11 Type 3
4
Type 4
5
Type 5
14
6 Type 6
9
7 Type 7
Type 8
8 9
NOTE: Type 5 is clear hex boot. Type 8 is black hex boot (available for bushings G, J & K only); Type 3 nut includes molded in “PRESS TO RESET” marking.
Embossed
(ALUMINUM)
7 INDICATOR PLATE 7
N
None
A
Embossed Legend
B
Silver Printing on Black
Silver Printing
On Black
.887
[22.5]
.887
[22.5]
.016
[.4]
Notes: All dimensions are in.[mm]. Tolerance ±.005 [.127] unless otherwise specified.
1 Used with bushing C or D only.
9 Available with G, J or K bushing only.
2 Used with H bushing only.
10 Amp rating must match button marking
3 Used with bushing E only.
(ex: 20 will be marked on the button of
4 Used with M11 mounting hole only. CMB-203-27G3N-W-A/20)
5 Used with mounting hole 00 only.
11 Includes molded in “PRESS TO RESET” 6 Used with M12 mounting hole only. marking.
7 All hardware available separately. 12 Available with K bushing only.
Consult factory.
13 Available with mounting hole 28 only.
8 Available with mounting hole 27 only. 14 Thickness is 3.0 mm, .118 in.
.016
[.4]
All indicator plates are marked
“Suppl. Prot. press to reset”.
8 BUTTON
B
Black
9 TERMINAL
A Type A
B Type B C Type C
D Type D E Type E
R
F
G
H
J
Red
W
White
Type F
Type G
Type H
Type J
F,G,H,J TERMINALS ARE 8-32 UNC
10 BUTTON MARKING (IF BLANK, NO MARKING.)10
03
04
3 amp
4 amp
05
06
5 amp
6 amp
07
08
Button Marking Orientation:
7 amp
8 amp
10
12
10 amp
12 amp
line
20
13
14
load
13 amp
14 amp
15
16
15 amp
16 amp
20
20 amp
Time Delay
Percentage of Rated Current
Overload
Trip Time
100%
No Trip
150%
Trip in 1 hr
200%
4.0 ~ 40 sec.
300%
0.9 ~ 8.0 sec.
400% 0.42 ~ 5.0 sec.
500% 0.25 ~ 3.0 sec.
600% 0.01 ~ 1.8 sec.
Trip Time in Seconds
Time Trip Factor 1
-10 °C x 1.70
-5 °C
x 1.60
0 °C
x 1.50
5 °C
x 1.40
10 °C x 1.30
15 °C x 1.20
20 °C x 1.10
25 °C x 1.00
Time Trip Factor 1
30 °C x 0.90
35 °C x 0.85
40 °C x 0.80
45 °C x 0.75
50 °C x 0.70
55 °C x 0.65
60 °C x 0.60
Notes:
1.
Trip Time factor
is a guideline that
indicates ambient
temperature effect on
trip times at various
overload values.
*Manufacturer reserves the right to change product specification without prior notice.
8
www.carlingtech.com
CLB-Series - Introduction
CLB
CLB-Series
THERMAL CIRCUIT PROTECTORS
The CLB-Series is a compact, single pole, push-to-reset family of thermal circuit breakers designed to protect
equipment. Utilizing simple, precision design with few moving parts, these breakers offer cost effective,
extremely reliable circuit protection with high resistance against shock and vibration.
Product Highlights:
Ratings from 3-60A, 125, 250VAC, 32VDC
2500 VAC/1 minute
ŠŠ 60°C Max Operating Temperature
ŠŠ 2500A @ 32VDC Interrupting Capacity
ŠŠ 100M ohms Insulation Resistance
ŠŠ Voltage drop <0.25 V
ŠŠ UL, CUL, CSA, TUV, CE
ŠŠ UL1500/ISO8846 for ignition protection/marine
Applications:
Household Appliances
Transportation
ŠŠ Marine
ŠŠ Power Strips
ŠŠ Medical Equipment
ŠŠ Audio Visual Equipment
ŠŠ Power Supplies
ŠŠ ROHS Complaint
ŠŠ
ŠŠ
ŠŠ
ŠŠ
Dimensional Specifications: in. [mm]
3-40A Construction
www.carlingtech.com
50 & 60A Construction
9
CLB-Series - Ordering Scheme, Time Delay
CLB
10 3
1
Series
2
Rating
1 SERIES
CLB
12 C 3 N
3
Voltage
4
Mounting
Hole
5
Bushing
Type
6
Mounting
Nut
B
7
Indicator
Plate
A / 10
8
Button
9
Terminal
10
Button
Marking
3 VOLTAGE
3
125-250VAC/ 32 VDC
2 RATING
03
3 amps
04
4 amps
05
5 amps
06
6 amps
07
7 amps
08
8 amps
10
10 amps
12
12 amps
13
13 amps
15
15 amps
18
18 amps
20
20 amps
25
25 amps
30
30 amps
35
35 amps
40
40 amps
50 12 50 amps
60 12 60 amps
4 MOUNTING HOLE
11 1 M11
12 2 M12
00 3 Snap In Style
27 4 3/8” 27 UNS
5 BUSHING
METAL
Type A
A 6
Type B
B 6
8
Type J
J PLASTIC
Type C
C 5
Type D
D 7
8
Type E
E 6 MOUNTING NUT 9
N
None
1
Type 1
2
Type 2
3
Type 3
4
Type 4
5
Type 5
6 4, 14 Type 6
4
7 Type 7
8 4
Type 8
NOTE: Type 5 is clear hex boot. Type 8 is black hex boot (available for bushings E & J only); Type 3 nut includes molded in “PRESS TO RESET” marking.
Embossed
(ALUMINUM)
7 INDICATOR PLATE 9
N
None
A
Embossed
B
Silver Printing on Black
.887
[22.5]
Silver Printing
On Black
.016
[.4]
.887
[22.5]
.016
[.4]
All indicator plates are marked
“Suppl. Prot. press to reset”.
8 BUTTON
B
Black
R
9 TERMINAL 10,11,15
A Type A
F
B Type B G
C Type C
H
D Type D J
E Type E
Red
W
Notes: All dimensions are in.[mm]. Tolerance ±.005 [.127] unless otherwise specified.
1 Used with bushing A or B only.
10 > 35 amp ratings must use solder joint to con
2 Used with bushing C only.
nect wire to non-screw type terminals.
3 Used with bushing D only.
11 Terminals are .040 [1.0] thickness for rating> 35, 4 Used with bushing E & J only.
& .315 [.8] thickness is for ratings < 35 amps.
5 Used with M12 mounting hole only. 12 Available only with 10-24 unc. screw terms. 6 Used with M11 mounting hole only. (select type F, G, H, J only.) UL, CUL only.
7 Used with mounting hole 00 only.
13 Amp rating must match button marking (ex: “20” 8 Used with 27 mounting hole only.
will be marked on the button of the breaker)
9 All hardware available separately. 14 Thickness is 3.0 mm, .118 in.
Consult factory.
15 Screw terminals are 8-32 UNC
White
Type F
Type G
Type H
Type J
10 BUTTON MARKING (IF BLANK, NO MARKING.)13 Button Marking Orientation:
03
04
05
3 amp
4 amp
5 amp
06
07
08
6 amp
7 amp
8 amp
10
12
13
10 amp
12 amp
13 amp
15
18
20
line
20
load
15 amp
18 amp
20 amp
25
30
35
25 amp
30 amp
35 amp
40
50
60
40 amp
50 amp
60 amp
Time Delay
Percentage of Rated Current
Overload
Trip Time
100%
No Trip
150%
Trip in 1 hr
200%
4.0 ~ 40 sec.
300%
0.9 ~ 8.0 sec.
400% 0.42 ~ 5.0 sec.
500% 0.25 ~ 3.0 sec.
600% 0.01 ~ 1.8 sec.
Trip Time in Seconds
Time Trip Factor 1
-10 °C x 1.70
-5 °C
x 1.60
0 °C
x 1.50
5 °C
x 1.40
10 °C x 1.30
15 °C x 1.20
20 °C x 1.10
25 °C x 1.00
Time Trip Factor 1
30 °C x 0.90
35 °C x 0.85
40 °C x 0.80
45 °C x 0.75
50 °C x 0.70
55 °C x 0.65
60 °C x 0.60
Notes:
1.
Trip Time factor
is a guideline that
indicates ambient
temperature effect on
trip times at various
overload values.
*Manufacturer reserves the right to change product specification without prior notice.
10
www.carlingtech.com
CMBA/CLBA-Series - Auto-Reset - Introduction
CMBA/CLBA
CMBA/CLBA-Series
THERMAL CIRCUIT PROTECTORS
The CMBA/CLBA-Series features automatic cycling and resetting thermal protection capabilities
with the same performance as its traditional push-to-reset counterparts.
Product Highlights:
CMBA: 3-20A, 125, 250VAC, 32VDC
ŠŠ CLBA: 3-40A, 125, 250VAC, 32VDC
ŠŠ 2500 VAC/1 minute
ŠŠ 60°C Max Operating Temperature
ŠŠ 2500A @ 32VDC Interrupting Capacity
ŠŠ 100M ohms Insulation Resistance
ŠŠ Voltage drop <0.25 V
ŠŠ UL, cUL, TUV
ŠŠ
Applications:
Household Appliances
ŠŠ Transportation
ŠŠ Power Strips
ŠŠ Medical Equipment
ŠŠ Audio Visual Equipment
ŠŠ Power Supplies
ŠŠ ROHS Complaint
ŠŠ
Dimensional Specifications: in. [mm]
CMBA Construction
www.carlingtech.com
CLBA Construction
11
CMBA/CLBA-Series - Auto-Reset Thermal Circuit Protector
CMBA
1
Series
10 3
2
Rating
NN F N N
3
Voltage
4
Mounting
5
Bushing
1 SERIES
CMBA
6
Mounting
Nut
B
7
Indicator
Plate
A
8
Button
Color
9
Terminal
10
Plug Marking
7 INDICATOR PLATE
N N/A
2 RATING
03 3 amps
04 4 amps
05 5 amps
06 6 amps
07 7 amps
08 8 amps
10
12
13
15
18
20
8 BUTTON COLOR
B Flush Black
10 amps
12 amps
13 amps
15 amps
18 amps
20 amps
9 TERMINAL
A Type A
3 VOLTAGE
3
125-250VAC/ 32 VDC
4 MOUNTING
NN Plug In
10 BUTTON MARKING 1 (IF BLANK, NO MARKING)
Plug Marking Orientation:
5 BUSHING
F
None
03
04
05
06
6 MOUNTING NUT
N N/A
CLBA
1
Series
10 3
2
Rating
3 amp 4 amp
5 amp
6 amp 07
08
10
12
7 amp
8 amp
10 amp
12 amp
NN F N N
3
Voltage
4
Mounting
5
Bushing
1 SERIES
CLBA
6
Mounting
Nut
line
20
load
13
15
18
20
13 amp
15 amp
18 amp
20 amp
B
7
Indicator
Plate
A
8
Button
Color
9
Terminal
10
Plug Marking
7 INDICATOR PLATE
N N/A
2 RATING
03 3 amps
04 4 amps
05 5 amps
06 6 amps
07 7 amps
08 8 amps
10 10 amps
12 12 amps
13
15
18
20
25
30
35
40
13 amps
15 amps
18 amps
20 amps
25 amps
30 amps
35 amps
40 amps
8 BUTTON COLOR
B Flush Black
9 TERMINAL
A Type A
3 VOLTAGE
3
125-250VAC/ 32 VDC
10 BUTTON MARKING 1 (IF BLANK, NO MARKING)
4 MOUNTING
NN Plug In
Plug Marking Orientation:
03
04
05
06
5 BUSHING
F
None
3 amp 4 amp
5 amp
6 amp 07
08
10
12
line
7 amp
8 amp
10 amp
12 amp
20
load
13
15
18
20
13 amp
15 amp
18 amp
20 amp 25
30
35
40
25 amp
30 amp
35 amp
40 amp
6 MOUNTING NUT
N N/A
Notes:
1 Amp rating must match plug marking. (ex: “20” will be marked on the plug of the breaker) No marking is standard.
Time Delay
Percentage of Rated Current
Overload
Trip Time
100%
No Trip
150%
Trip in 1 hr
200%
4.0 ~ 40 sec.
300%
0.9 ~ 8.0 sec.
400% 0.42 ~ 5.0 sec.
500% 0.25 ~ 3.0 sec.
600% 0.01 ~ 1.8 sec.
Trip Time in Seconds
Time Trip Factor 1
-10 °C x 1.70
-5 °C
x 1.60
0 °C
x 1.50
5 °C
x 1.40
10 °C x 1.30
15 °C x 1.20
20 °C x 1.10
25 °C x 1.00
Time Trip Factor 1
30 °C x 0.90
35 °C x 0.85
40 °C x 0.80
45 °C x 0.75
50 °C x 0.70
55 °C x 0.65
60 °C x 0.60
Notes:
1.
Trip Time factor
is a guideline that
indicates ambient
temperature effect on
trip times at various
overload values.
*Manufacturer reserves the right to change product specification without prior notice.
12
www.carlingtech.com
Carling Technologies Catalogs
There are several catalogs available featuring complete details on all Carling Technologies products.
Below is a list of useful information such as catalogs, brochures and videos. Please visit our website at
carlingtech.com or scan the QR codes below for complete details.
www.carlingtech.com
Watch Company Profile Video
Switches & Controls
Hydraulic-Magnetic
SWITCHES & CONTROLS
Rocker, Toggle, Pushbutton & Rotary
CATALOG
Circuit Protection
CATALOG
catalog
catalog
Complete line and ordering details for
Switches & Control products including
Rocker, Toggle, Pushbutton, and Rotary
style switches.
Complete line and ordering details for
all hydraulic-magnetic circuit breakers.
Thermal
GFCI / ELCI
GFCI / ELCI
THERMAL
Circuit Protection
Circuit Protection
CATALOG
catalog
Complete line and ordering details for
all thermal circuit breakers.
www.carlingtech.com
CATALOG
catalog
Complete line and ordering details for
all GFCIs/ELCIs.
13
Carling Technologies Catalogs
Marine
On-Off Highway
MARINE
ON/OFF HIGHWAY
Switches, Circuit Protection & ELCI/GFCIs
Switches & Controls
catalog
brochure
catalog
brochure
Complete line of ELCIs, thermal and hydraulic-magnetic
circuit breakers specific for marine applications.
Complete line of switches, controls and custom
solutions specific for on-off highway applications.
Renewable Energy
Military
MILITARY
RENEWABLE ENERGY
Circuit Breakers & Disconnects
COTS Switches & Circuit Breakers
catalog
brochure
catalog
brochure
Complete line of circuit breakers and disconnect
products specific for renewable energy applications.
Complete line of COTS (Commercial-Off-The-Shelf) switches
and circuit breakers specific for military applications.
Telecom/Datacom
Industrial Automation
TELECOM/DATACOM
INDUSTRIAL AUTOMATION
AND CONTROLS
Circuit Protection
Circuit Protection & Switches
catalog
brochure
Complete line of hydraulic-magnetic circuit breakers
specific for telecom/datacom applications.
14
brochure
Complete line of switches and circuit breakers specific
for industrial automation & controls applications.
www.carlingtech.com
Reps & Contact
Authorized Sales Representatives
Click on the group name on the map below to find your local representative or visit
www.carlingtech.com/findarep.
«
«
Matera
W. Canada
Matera
E. Canada
MIDWEST
DM
Michigan
TEMCO Northwest
Alaska, Hawaii
«
NORTHERN
Hanna Lind Ltd.
Melody
Emery
Sierra
Bridge Marketing
Omega Limited
Dy-tronix Inc.
LD. Allen
Norris
DM Assoc
East
Pacent
DM
Assoc
TSI North
TSI
WEST
Signal
Enterprises
Luscombe
Engineering
Pinnacle Marketing
Matrix
DM Mexico
South America
Mexico
«
«
Sunbelt Components
SOUTHEAST
ProRep
Solutions
LATIN AMERICA
Americas
Europe
Middle East
Africa
Asia-Pacific
Oceania
About Carling
Founded in 1920, Carling Technologies is a leading manufacturer of electrical and electronic switches
and assemblies, circuit breakers, electronic controls, power distribution units, and multiplexed power
distribution systems. With four ISO registered manufacturing facilities and technical sales offices worldwide,
Carling Technologies Sales, Service and Engineering teams do much more than manufacture electrical
components, they engineer powerful solutions! To learn more about Carling please visit
www.carlingtech.com/company-profile.
To view all of Carling’s environmental, quality, health & safety certifications please visit
www.carlingtech.com/environmental-certifications
www.carlingtech.com
15
Worldwide Headquarters
Carling Technologies, Inc.
60 Johnson Avenue, Plainville, CT 06062-1177
Phone: 860.793.9281 Fax: 860.793.9231
Email: sales@ carlingtech.com www.carlingtech.com
Northern Region Sales Office: nrsm@ carlingtech.com
Southeast Region Sales Office: sersm@ carlingtech.com
Midwest Region Sales Office: mrsm@ carlingtech.com
West Region Sales Office: wrsm@ carlingtech.com
Latin America Sales Office: larsm@ carlingtech.com
Asia-Pacific Headquarters
Carling Technologies, Asia-Pacific Ltd.,
Kowloon, Hong Kong
Phone: Int + 852-2737-2277 Fax: Int + 852-2736-9332
Email: sales@ carlingtech.com.hk
Shenzhen, China: shenzhen@ carlingtech.com
Shanghai, China: shanghai@ carlingtech.com
Pune, India: india@ carlingtech.com
Kaohsiung, Taiwan: taiwan@ carlingtech.com
Yokohama, Japan: japan@ carlingtech.com
Europe | Middle East | Africa Headquarters
Carling Technologies LTD
4 Airport Business Park, Exeter Airport,
Clyst Honiton, Exeter, Devon, EX5 2UL, UK
Phone: Int + 44 1392.364422 Fax: Int + 44 1392.364477
Email: ltd.sales@ carlingtech.com
Germany: gmbh@ carlingtech.com
France: sas@ carlingtech.com
THERMAL-C_06_2016