Station and intermediate class surge arresters Product guide IEEE siemens.com/energy/arrester Definition of surge arresters Surge arresters are used to protect high-voltage equipment in substations, such as transformers, circuit breakers, and bushings, against the effects of overvoltages caused by incoming surges. Such overvoltages can be caused by a direct or nearby lightning strike, an electromagnetic pulse, electrostatic discharge, or switching operations in the power supply system as well as in devices. Some overvoltages are very high in energy. The current from the surge is diverted through the arrester, in most cases to earth. Effective overvoltage protection requires different surge arrester types to be used according to the particular application. 2 Contents Definition of surge arresters 02 Siemens surge arresters for any requirement 04 Always the best solution 05 History timeline 06 MOVs: the core of Siemens surge arresters 08 Silicone rubber 09 Porcelain 10 Station and intermediate class surge arresters 11 3EL silicone rubber surge arresters with Cage Design 12 3EQ silicone rubber surge arresters with composite hollow core design 14 3EP porcelain surge arresters 16 Standards and testing – reliability you can count on 17 Selection table and how to select a suitable surge arrester 18 Applications as line surge arresters 23 Early detection of relevant changes through efficient equipment monitoring 24 Product range 26 3EL5 Surge arrester with silicone rubber housing and Cage Design™ 28 3EL1 Surge arrester with silicone rubber housing and Cage Design™ 32 3EL2 Surge arrester with silicone rubber housing and Cage Design™ 36 3EL3 Surge arrester with silicone rubber housing and Cage Design™ 42 3EP5 Surge arrester with porcelain housing 48 3EP4 Surge arrester with porcelain housing 52 3EP6 Surge arrester with porcelain housing 58 3EQ1 Surge arrester with composite hollow core design 64 3EQ4 Surge arrester with composite hollow core design 68 Accessories for surge arresters 74 Monitoring devices for surge arresters 74 3 Siemens surge arresters for any requirement Experience is most essential when it comes to reliability in medium- and high-voltage applications. Siemens has been designing and manufacturing medium- and high-voltage surge arresters for standard and special applications since 1925. Continuous research and development, the wealth of Siemens know-how, and comprehensive worldwide experience give Siemens surge arresters a leading edge in overvoltage protection. Their uncompromising quality ensures a long service life and reliability in any application. Siemens surge arresters are an indispensable aid to insulation coordination in electrical power supply systems. Valu- able equipment such as transformers, circuit breakers, generators, motors, capacitors, traction vehicles, and bushings, as well as complete switchgear, is ideally protected against lightning and switching overvoltages. Siemens surge arresters have been designed to meet the requirements of a wide range of common installation environments, from arctic cold to the heat of the desert and the humidity of tropical climates. They are available for any application from 3 kV up to 1,200 kV including special applications such as high-voltage direct current (HVDC) and FACTS systems as well as all kinds of compensation systems for electric power networks. Substation Bidingen 400 kV Protection of transformer Solution with 3EQ4 4 Always the best solution Developments in technology and practical experience have led to three different surge arrester designs: • Surge arresters with porcelain housings • Surge arresters with silicone housings • Surge arresters with metal enclosures Siemens provides each of these types in several versions, making it possible to find the optimal surge arrester for every conceivable application and meet even specific demands, such as • High mechanical stability for outstanding seismic safety • E xtremely reliable pressure relief behavior for use in areas requiring special protection • E xcellent pollution layer characteristics for use in coastal and desert regions or in areas with extreme air pollution. All Siemens surge arresters feature a superior sealing system that reliably prevents moisture ingress to ensure the highest possible degree of overvoltage protection and decades of trouble-free service. Moreover, the choice of materials used in the making of Siemens surge arresters contributes to the protection of the environment. Substation Bidingen 400 kV Protection of switchgear Solution with 3EQ4 5 1925 1989 Siemens begins developing surge arresters. The first devices are of the so-called cathode drop type. The 3EQ2 surge arrester for systems of up to 550 kV is one of the first high-voltage surge arresters with composite polymer hollow core housing. 1847 1971 The ten-employee company Telegraphen-Bauanstalt von Siemens & Halske (Telegraph Construction Company of Siemens & Halske) begins operation on October 12, 1847, in a back building in Berlin. Development of the first gas-insulated and metalencapsulated surge arrester for gas-insulated switchgear (GIS). 1900 1866 Werner von Siemens discovers the dynamo-electric principle, which enables electricity to be put to practical use. The dynamo can convert mechanical energy into electrical energy in an economical way. Its invention lays the foundation for today’s world of electrical engineering. 1963 1992 The first surge arrester for systems of up to 550 kV is launched. The pulley wheel electrodes are replaced by ceramic-bonded shunt resistors and a series spark gap. The surge arrester comprises three columns in parallel and has a resistivecapacitive control. Continually pushing the envelope, Siemens develops a high-voltage surge arrester with a composite polymer housing for systems of up to 800 kV. It was originally developed as a suspended mounted HVDC valve arrester with several parallel metal oxide columns in a common housing. 1982 Siemens’ first gapless metal oxide arrester, a GIS surge arrester, is delivered for the 123 kV grid in Inchicore, a suburb of Dublin. History timeline Siemens is a pioneer in many fields of the electricity and digitization markets. Experience is most essential when it comes to reliability in medium- and high-voltage applications. Since 1925 Siemens has been manufacturing high-voltage surge arresters up to duty cycle voltages of 1,200 kV – for standard and specialized applications. Our permanent research and development and the concerted know-how in our factories give our surge arresters a leading edge in overvoltage protection. Our uncompromising quality ensures the long service life and reliability of each application. 6 1998 The polymer-housed medium-voltage/distribution class arresters of the 3EK family, which features Cage Design™, a unique solution with direct silicone molding on the metal oxide varistors, is introduced. 2003 Completion of the first line arrester project, an order from KELAG, one of the leading energy service providers in Austria. 2007 2011 3EL2, the first line arrester for 550 kV applications, is delivered to Sochi, a city in Russia. Siemens introduces its new range of long rod insulators. 2000 2010 2006 2008 2010 Development of the 3EQ5, a new surge arrester concept with composite housing (type A) for extra highvoltage applications in 800 kV DC and 1,200 kV AC transmission systems. The first externally gapped line arrester (EGLA), which increases the reliability of a 144 kV overhead line, is supplied to the South Korean power provider KEPCO. The world’s first 1,200 kV substation arrester with composite polymer hollow core technology is delivered to Power Grid Corporation of India. 2010 2000 Development of the first GIS arrester for systems of up to 800 kV. Siemens launches the arrester condition monitor, an innovative monitoring solution with unique features. As a pioneer in the field of silicone rubber insulation and one of the few suppliers with comprehensive in-house research and development capabilities in this technology, Siemens has been providing surge arresters with silicone rubber housing for more than 30 years and has gathered excellent service experience from even the most severe climatic and environmental conditions. Today, silicone rubber is among the most widely used materials for high-voltage outdoor equipment. 7 MOVs: the core of Siemens surge arresters The main task of an arrester is to protect equipment from the effects of over voltages. During normal operation, an arrester should have no negative effect on the power system. Moreover, the arrester must be able to withstand typical surges without incurring any damage. Nonlinear resistors fulfill these requirements thanks to the following properties: Nonlinear resistors made of metal oxide (MO) have proven especially suitable for this use. The nonlinearity of MO resistors is considerably high, which is why MO arresters do not need series gaps. Siemens has many years of experience with gapless MO arresters in low-voltage systems, distribution systems, and transmission systems. • L ow resistance during surges, so that overvoltages are limited Siemens metal oxide varistors (MOVs) provide a high switching surge energy rating and a very low protection level. This means they absorb a high amount of energy while avoiding thermal runaways. The MOVs are characterized by their high single impulse withstand rating. Siemens surge arresters are less prone to selfheating and consequent self-destruction, and they maintain their characteristics throughout their lifetime. igh resistance during normal opera• H tion to avoid negative effects on the power system ufficient energy absorption capability • S for stable operation With this kind of nonlinear resistor, there is only a small flow of current when continuous operating voltage is being applied. When there are surges, however, excess energy can quickly be removed from the power system by a high discharge current. p.u. Ur Power-frequency voltage vs. time (U-t) characteristic (TOV) 1.30 1.25 Preheating to 60°C prior duty 1.20 1.15 1.10 1.05 1.00 0.95 0.90 0.85 0.80 1 10 100 1,000 10,000 t/s 8 Silicone rubber As a pioneer in the field of silicone rubber insulation and one of the few suppliers with comprehensive in-house research and development capabilities in this technology, Siemens has been providing surge arresters with silicone rubber housing for more than 30 years and has gathered excellent service experience from even the most severe climatic and environmental conditions. Today, silicone rubber is among the most widely used materials for high-voltage outdoor equipment. Siemens silicone rubber-housed surge arresters are polymer-housed arresters that use silicone rubber as the only insulating material. The exclusive use of silicone has proven to be the best solution in several studies: Silicone rubber is highly hydrophobic. While there are many polymeric materials with similar initial hydrophobic properties, most of them, such as EPDM alloy rubber, lose their hydrophobicity after a relatively short period. Only genuine silicone rubber as used by Siemens is capable of maintaining its hydrophobicity throughout its entire lifetime. This ensures the long service life of Siemens surge arresters with silicone rubber housing. Even the most severe ambient conditions, such as salt fog in coastal regions or dust-laden air causing serious contamination in an industrial area, cannot impair the hydrophobicity of silicone rubber. This material property reliably prevents conductive moisture from forming on the arrester surface, thus averting surface currents and discharges. Moreover, genuine silicone is highly fire-retardant and selfextinguishing, and it is neither subject to erosion nor sensitive to UV radiation. This ensures the long-term stability of the housing material. There are several characteristics that set the silicone elastomers used by Siemens apart from other organic insulating materials. As a matter of principle, Siemens only uses HTV (high-temperature vulcanized) or LSR (liquid silicone rubber) silicone elastomers. These types of silicone help maintain the properties mentioned above. Characteristic damage on EPDM insulators due to natural UV radiation Chalking The –Si–O– backbone of silicone rubber has a higher bonding energy than the –C–C– backbone of EPDM. Silicone rubber has a lower carbon proportion than EPDM. Consequently, silicone rubber boasts inherently better chemical and physical resistance, better UV resistance, and lower flammability than EPDM. Consider these facts: • S ilicone rubber is highly stable under the influence of ultraviolet radiation (sunlight), ozone, and nitrogen oxide. Its stability beats that of EPDM-based alloy rubbers. he hydrophobic performance of a sili• T cone rubber surface remains excellent throughout the entire arrester service life, whereas EPDM-based alloy rubbers lack this critical requirement. Cracking he hydrophobicity of silicone rubber • T returns after a corona discharge, which assures reliable long-term performance. • T he arcing resistance of silicone rubber is higher as compared to EPDMbased alloy rubbers. he flame-retardant properties of • T silicone rubber comply with IEC 60707 and UL94 V-0 (i.e. self-extinguishing, no burning drips, probe does not burn). Moisture • S ilicone rubber is resistant to all common organic and nonorganic cleaning agents and solvents. ilicone rubber performs well in an • S ambient temperature range of –75 °F to +400 °F. No other polymeric material can beat silicone rubber. POWERSIL® Hydrophobic effect on Siemens 3EL surge arrester due to alignment of methyl groups in silicone polymers. 9 Porcelain Siemens porcelain surge arresters feature a directional pressure relief device that ensures maximum protection in the case of an overload. Thanks to the excellent sealing of its surge arresters, Siemens has recorded decades of trouble-free service life without failures or moisture ingress. Both ends of a porcelain surge arrester housing are equipped with aluminum flanges that are cemented to the housing. Sulfur cement is the first choice for this purpose. It has favorable mechanical properties and also proves advantageous over Portland cement, which is quite common in the insulator industry. The main advantage of sulfur cement is that it can be 10 brought into contact with aluminum during manufacturing without causing any corrosion, and it can be quickly processed, since it almost reaches its full mechanical strength directly after application. The design of the flanges and the end sections of the porcelain housings is key to the strength of the entire housing. This is why these parts of Siemens arresters are designed in a way that ensures that the cement joint is mechanically stronger than the porcelain itself. This enables making full use of the porcelain’s strength when specifying the permissible mechanical head loads of the arrester housing. Station and intermediate class surge arresters Siemens provides three surge arrester product families for standard and special AC applications from 3 kV up to 800 kV, which are described in this brochure: • 3EL surge arresters with silicone housing, Cage Design™ •3EQ surge arresters with silicone housing, composite hollow core design • 3EP surge arresters with porcelain housing 11 3EL silicone rubber surge arresters with Cage Design Design features Cage of FRP rods End fittings Metal oxide blocks Silicone rubber sheds directly molded on metal oxide blocks and on end fittings Siemens’ Cage Design ensures high mechanical strength and safe overload performance. It is characterized by the use of silicone and fiberglass-reinforced plastic (FRP) rods as housing materials. Reliability is guaranteed by the direct molding of the silicone rubber onto the MO blocks and the FRP rods. This ensures the total embedding of all components free of enclosures and gaps, thus preventing any partial discharge or moisture ingress. The MO blocks of 3EL surge arresters are enclosed by a cage made of FRP rods, which leads to a rigid, reinforced structure ensuring high mechanical strength. The high tensile strength of the FRP rods is used to hold the arrester’s MO blocks in place tightly. This is why Cage Design arresters are among the mechanically strongest polymer arresters available on the market and at the same time ensure minimal use of material and very low weight. As the MO blocks are neither enclosed in a sealed mechanical shell nor wrapped in hard material, no excess pressure will develop in the case of an 12 overload or the extremely rare event of an arrester short circuit. The arc can escape directly through the soft silicone housing, and the ejection of internal parts that could damage other equipment nearby is prevented almost completely. Long service life Mechanically strong enough to meet common mechanical requirements and with sheds that are resistant to damage resulting from transport, installation, storms, earthquakes, and vandalism, 3EL surge arresters are perfectly suited for installations that demand low weight and indestructibility of the arrester. Low weight: flexible and easy installation The use of FRP and silicone as housing materials also makes Siemens 3EL arresters extremely lightweight, allowing easy transport and flexible installation. The use of 3EL surge arresters helps reduce the required strength and weight of arrester supports and the need for heavy installation equipment. Applications The 3EL series of surge arresters covers a wide range of common installation requirements including station and line surge arresters for the protection of switchgear, transformers, and other equipment in high-voltage systems of up to 550 kV. 3EL surge arresters can be installed at all mounting angles (e.g. horizontally, vertically, or suspended from the transmission line as line surge arrester). Horizontal cut of a cage design arrester 13 3EQ silicone rubber surge arresters with composite hollow core design Design features Directional pressure relief device Cage of FRP rods End fittings with directional pressure relief device and sealing system Metal oxide blocks FRP tube Silicone rubber sheds directly molded on FRP tube Directional pressure relief device Siemens’ innovative composite hollow core design uses silicone and a fiberglass reinforced plastic (FRP) tube as housing materials. The advantages of this design are more than compelling, as it offers the perfect combination of cost savings and safety for substations. The direct molding of the silicone rubber onto the FRP tube ensures reliability, while an excellent special sealing of the flanges at both ends of the surge arrester effectively prevents partial discharges and moisture ingress. The combination of silicone rubber and FRP tube also allows 14 an enormous withstand capability against mechanical forces. Hence, 3EQ surge arresters are the perfect choice for the replacement of existing post insulators in substations of up to 800 kV. The composite hollow core design provides a very high degree of safety: In the case of an overload or the extremely rare case of an arrester short circuit, the arc escapes directly through directional pressure relief devices, internal parts are not ejected, and the housing does not break. A reliable, sturdy, and economic choice Siemens 3EQ composite hollow core design surge arresters are virtually indestructible. While the composite hollow core design provides the highest possible mechanical strength and enables the support of high bending moments, the silicone rubber insulation is ideal for outdoor applications in severe environmental conditions. No matter how tough environmental and operating conditions may be, 3EQ arresters assure 100% reliable pressure relief performance and provide the ultimate in protection. They are shatterproof and retain at least 75 percent of their mechanical strength even after pressure relief, and they provide the greatest stability, even during earthquakes. Reduced space requirements Whenever space is at a premium, 3EQ surge arresters can even be mounted directly over a transformer to support connectors without any danger to neighboring equipment. Their unique composite hollow core design ensures maximum stability, even if an arrester should »blow out« after overloading. Pressure relief is absolutely reliable – there is no danger to equipment in the direct vicinity, no parts will be ejected, and the emerging arc will safely burn between the ends of the pressure relief device. Longevity and reliability The silicone rubber housings of 3EQ surge arresters provide the best possible long life performance for high-voltage surge arresters. They make use of all the advantages of vulcanizing silicone rubber sheds onto an FRP tube, providing enhanced safety and meeting every requirement. Applications Horizontal cut of a composite hollow core design arrester Siemens 3EQ composite hollow core design surge arresters will go the extra mile. They meet highest mechanical demands and are ideally suited for challenging environments, such as areas with heavy seismic activity or extremely high wind loads. 3EQ surge arresters boast a prolonged service life, because they are absolutely shatterproof and feature reliable overload performance with no hazardous splinters being ejected even under maximum pressure. These arresters can be installed close to costly system components. 3EQ composite hollow core design arresters are virtually indestructible during transportation, installation, storms, and earthquakes, and they are immune to vandalism. 15 3EP porcelain surge arresters Design features Directional pressure relief device Cage of FRP rods End fittings with directional pressure relief device and sealing system Metal oxide blocks Porcelain housing Directional pressure relief device Siemens’ 3EP porcelain-housed surge arresters are the ideal choice for high mechanical performance requirements at voltage levels of up to 800 kV. With a seismic qualification of 0.5 g that is guaranteed up to 800 kV, they suit environments with even the most challenging mechanical requirements, such as heavy seismic activity and extremely high wind loads. 3EP surge arresters ensure maximum protection in an overload situation thanks to a specially designed directional pressure relief device. In the case of an overload or the extremely rare case of an arrester short circuit, the arc escapes easily through the pressure relief devices. No pressure is built up inside the arrester and no internal parts are ejected, which prevents damage to surrounding equipment. 16 The excellent sealing system of 3EP surge arresters prevents failures or moisture ingress and guarantees decades of troublefree service. The use of nonporous sulfur cement instead of corrosive Portland cement for bonding protects the MO blocks and prevents aging effects. The MO blocks of 3EP surge arresters are enclosed by a rigid, reinforced cage made of FRP rods. The high tensile strength of the FRP rods is used to hold the arrester’s MO blocks in place tightly. Applications Thanks to their high degree of safety and reliability, Siemens 3EP porcelain-housed surge arresters can be installed in close proximity to costly system components. 3EP composite hollow core design arresters are virtually indestructible during transportation, installation, storms, and earthquakes, and they are immune to vandalism. Standards and testing – reliability you can count on Tests Standardization Siemens surge arresters have been designed and tested in compliance with the latest IEC 60099-4, IEEE C62.11, and GB 11032 standards. All type tests are performed by independent, PEHLAcertified laboratories; reports are available on request. Please contact your Siemens representative for details. The aim of the IEEE’s Surge Protective Device Committee (SPDC) as well as the IEC’s Technical Committee 37 (TC 37) is the standardization of surge arrester testing and application. Moreover, every single surge arrester that leaves the Siemens factory undergoes a routine test and is delivered with a routine test certificate. Quality Assurance Siemens meets all requirements of ISO 9001:2008, ISO 14002:2004, and BS OHSAS 18001:2007. All Siemens suppliers need to be certified according to ISO standards or will be audited by Siemens. To maintain sustainable quality improvement, Siemens introduced corporate quality guidelines that contribute to each step of the quality process. The test field is certified by the »Deutsche Akkreditierungsstelle« (Germany’s national accreditation body) according to DIN EN ISO/IEC 17025 The SPDC develops the standard IEEE C62.11 and the application guide IEEE C62.22, while the TC 37 develops the standards IEC 60099-4, IEC 60099-8 (EGLA), IEC 60099-9 (HVDC), and the application guide IEC 60099-5. Both committees include representatives of manufacturers, utilities, test field labs, and universities. Siemens R&D experts are members of both bodies, thus playing an important role in the definition of the standards. They also share their expert knowledge in electrical power systems in CIGRE, the international council on large electric systems, which participates in the development of international standards. Test generator supplying both impulse voltages (1.2/50 µs and 250/250 µs) and impulse currents (8/20 µs and 30/60 µs) UHV arrester prepared for testing in the HV test laboratory 17 Selection table System Highest voltage of the system Us Neutral earthing electrical Temporary overvoltages (TOV) Arrester Environment Cont. operating voltage Uc,min –> Duty cycle voltage Ur1 Duty cycle voltage Ur Cont. operating voltage Uc Duty cycle voltage Ur2 Lightning current stress Lightning impulse classifying current In Insulation level, safety margin, distance (protective zone) LI protective level SI protective level Energy (single-impulse withstand rating, switching voltages) Energy class Ground flash density, magnitude of lightning strikes Active part specified Length of housing, number of units, flashover distance (withstand voltages) Altitude of erection Leakage distance, shape of sheds mechanical Short-circuit current Mechanical forces (short-circuit current, bending and tensile loads) Diameter, material, length of units (number of units) Seismic stress Rated short-circuit current Is, mechanical loads MDCL resp. UMS Housing Fig. 1: Configuration procedure for an MO surge arrester 18 Pollution How to select a suitable surge arrester This section describes the general approach to selecting typical arresters for overvoltage protection in high-voltage systems. For a detailed description of how to configure a surge arrester, please refer to the handbook Metal-Oxide Surge Arresters in High-Voltage Power Systems – Fundamentals.1 The requirements for a surge arrester emerge from two basic requirements: It should provide adequate protection with a sufficient safety margin, which means that overvoltages at the device to be protected must always remain below its withstand voltage. Furthermore, the surge arrester should be dimensioned for stable continuous operation, which means that the arrester must remain electrically and thermally stable under all conditions while handling all long-term, temporary, and transient stress resulting from network operation. These two requirements cannot be fulfilled independently. A reduction of the protective level automatically means a higher degree of specific electrical stress during continuous operation, and conversely, the continuous operating voltage of an arrester cannot be increased arbitrarily without raising its protective level as well. Both operating points are for a given type of MOV strictly associated with each other through the voltage-current (U-I-) characteristic curve. Step 1: Selection of the maximum continuous operating voltage and the duty cycle voltage. The first step is to define the minimally required continuous operating voltage Uc,min. This must be as high as the continuous phase-to-earth voltage of the system. Here, »continuously« applied voltage means every voltage that occurs within an uninterrupted period of more than 30 minutes. The type of neutral earthing of the system is decisive in determining the continuous operating voltage. In isolated or resonant earthed neutral systems, the voltage of a healthy phase against ground takes on the value of the phase-to-phase voltage in the case of a one-phase earth fault (earth fault factor k = 1.73). Since resonant earthed neutral systems are operated quite commonly for time periods of more than 30 minutes in this condition, the continuous operating voltage of the arrester must, in this case, have the value of the highest voltage of the system, Us. Solidly earthed neutral system: Uc,min ≥ Us/√3 Isolated or resonant earthed neutral system: Uc,min ≥ Us The definition of the minimally required continuous operating voltage, a factor which usually has a value of 1.25, helps achieve a duty cycle voltage Ur = 1.25 · Uc,min. This is the lowest necessary duty cycle voltage of the arrester. Table »Typical duty cycle voltages Ur for highest voltages of the system Us « on page 27 lists typically applied duty cycle voltages. Volker Hinrichsen: »Metal-Oxide Surge Arresters in High-Voltage Power Systems«, 3rd edition, September 2012, Order No. E50001-G630-H197-X-4A00 1 19 Step 2: Selection of the lighting impulse classifying current In The lighting impulse classifying current In serves to classify a surge arrester. From a technical point of view, it is calculated from a typical maximum lightning current amplitude that can be expected in the substation, for which the insulation coordination is performed via the arrester’s lightning protection level. This amplitude is calculated from the flashover voltage Ufo of the line insulators, the lightning protection level Upl of the arresters, and the surge impedance Z of the line for Imax: Imax = (2·Ufo – Upl)/Z Example for a 420 kV system: Ufo = 2.1 MV Upl = 806 kV Z = 350 Ω Imax = 9.7 kA A 10 kA arrester, for instance, can readily withstand lightning current impulses of higher amplitudes without severe damage. Step 3: Selection of protective levels The protective characteristics of an arrester are most frequently assessed by means of its lightning impulse protective level: It is assessed according to its discharge voltage while the lighting impulse classifying current is flowing. This usually means that a protective level equaling the standard lightning impulse withstand voltage of the device to be protected and divided by a factor of 1.4 is adequate for protection against lightning overvoltages. Upl, 10kA, 8/20µs < BIL / 1.4 The selection of the electrical characteristics of the arrester is finished when the requirements regarding the protective levels of all mentioned current impulse stresses are fulfilled. Example U-I-curve 550 kV network U / kV 1400 1000 600 50 Hz 200 0 0.001 0.1 10 I/A 20 Step 4: Selection of the energy class Step 5: Selection of the housing The application guide IEEE C62.22 to the standard IEEE C62.11 describes how the energy handling capability of a surge arrester can be determined. Dielectric and mechanical requirements are generally taken into account when selecting the housing. The length, the leakage distance, and the material must be determined. The arrester characteristics determined by the housing are the rated short-circuit current Is, the Maximum Design Cantilever Load-static (MDCL-static) for surge arresters with silicone housing and the Ultimate Mechanical Strength-static (UMS-static) for surge arresters with porcelain housing. Surge arresters dissipate switching surges by absorbing thermal energy. The amount of energy is related to the switching surge magnitude and wave shape, the system impedance, the arrester voltage-current characteristics, and the number of operations. The selected arrester should have an energy capability greater than the energy associated with the expected switching surges on the system. The application guide IEEE C62.22 offers equations to estimate the energy handling capability requirements of surge arresters.The energy discharged by an arrester J in kJ may be estimated by the equation: First of all, the clearance, which results from the withstand voltage requirements, must be determined. Siemens takes care of the parameters »demand by MOV column« and »clearance« by stating the minimum required housing length. J = 2DL EA IA / ν Where DL is the line length (in kilometers) EA is the arrester switching impulse discharge voltage (in kV) for IA IA is the switching impulse current (in kA) v is the speed of light, 300,000 km/s The equation assumes that the entire line is charged to a prospective switching surge voltage (which exists at the arrester location) and is discharged through the arrester during twice the travel time of the line. The single discharge voltage and current are related by the equation: IA = (ES − EA) / Z Where ES is the prospective switching surge voltage (in kV) Z is the single-phase surge impedance of line (in ohms) The table below shows the definition of the energy class according to standard IEEE C62.11. This energy is not a fixed value, but instead depends on the arrester’s protective level. The higher the discharge voltage, the less energy the arrester absorbs during the line discharge, since the line will discharge less intensely when the discharge voltage is higher. Energy Class A B C D E F G H J K L The minimal housing length first of all results from the demand that the MOV column (the active part) must fit. The length of this column is determined by the electrical data that were gathered during the selection steps taken up to that point. Generally speaking, further demands cause the housing lengths to be much greater than those of the active parts. M N Energy Rating (Two Shot) 3.0 4.5 6.0 7.5 9.0 11 13 15 18 21 24 27 30 kJ/kVMCOV Leakage distance requirements are, however, a much more frequent reason for longer housings. The shortest possible housing as a result of the length of the active part can normally be achieved only by designing for specific leakage distances of less than 1 inch per kV duty cycle voltage. However, specific creepage distances of 1.25 inch/kV duty cycle voltage and more play an important role. In addition, there are environmental conditions, such as maritime and desert climates as well as heavy industrial pollution, that require the use of even longer leakage distance. After the housing parameters have been determined in order to fulfill the electrical requirements, the next and last steps focus on mechanical criteria. They indirectly lead to the selection of housing material and housing diameter. There often is only a vague idea as to the mechanical stress of an arrester in service, and accordingly no requirements are made or – maybe even worse – values are estimated too high. If there is no information available about the actual requirements, the following values can serve as a guideline for the necessary dynamic head loads in high-voltage systems: Highest system voltage Us (kV) Dynamic load (lbf) < 121 200 121 … 420 225 550 340 800 450 21 Glossary Maximum Continuous Operating Voltage (MCOV, symbol Uc) indicates the designated permissible root mean square value of the power frequency voltage that is allowed to be applied continuously between the arrester terminals. Leakage (distance) defines the distance between the metal end fittings, measured along the housing surface. It is an important factor in the behavior of an insulator – or a device containing an insulator – in polluted conditions. Highest voltage of a system (symbol Us) indicates the root mean square value of the highest phase-to-phase operating voltage that occurs under normal operating conditions at any time and at any point in the system. Lightning impulse classifying current (symbol In) indicates the peak value of a lightning current impulse used to classify an arrester. Protective level is the maximum value of an arrester’s discharge voltage at a standard current impulse. In this case, there is a difference between the lightning impulse protective level (8/20 µs), the switching impulse protective level (30/60 µs), and the steep current impulse (1/2µs) protective level. Rated short-circuit current (symbol Is) indicates the root mean square value of the symmetrical highest short-circuit current that can flow after an arrester has been overloaded without causing violent shattering of the housing. Duty cycle voltage (symbol Ur) is the maximum permissible root mean square value of the power frequency voltage between the arrester terminals at which the arrester is designed to operate correctly 22 under temporary overvoltage conditions as established in the operating duty tests. Normally, the manufacturer specifies whether it can be applied to the arrester for a duration of 10 seconds (which corresponds to the value in the operating duty test) or 100 seconds. The duty cycle voltage is the reference parameter for determining the operating characteristics. Discharge voltage quantifies the voltage drop between the arrester’s terminals when a current impulse is injected. For current impulses in the shape and value of a standard test current impulse (lightning current impulse, switching current impulse, steep current impulse), the simultaneously occurring discharge voltages define the protective levels that are assigned to this current shape and value. Maximum Design Cantilever Load-static (MDCL-static) is a force perpendicular to the longitudinal axis of an arrester and allowed to be applied during service for long periods without causing any mechanical damage to the arrester. Ultimate Mechanical Strength-static (UMS-static) is a force perpendicular to the longitudinal axis of an arrester and allowed to be applied during service for long periods without causing any mechanical damage to the arrester. Temporary overvoltage (TOV) denominates the power frequency overvoltage that can occur for a duration of several tenths of a second to up to a few seconds, as a result of a switching operation or system failure. Its value depends on the type of neutral earthing in the system. Applications as line surge arresters The use of surge arresters on hazardous stretches of a power line helps improve network protection and increases the reliability of the entire transmission system. Offering a highly efficient combination of low weight, outstanding strength, and safety features, Siemens 3EL surge arresters are ideally suited for this purpose. Siemens provides two solutions for line surge arresters: 400 kV line in Bulgaria NGLA solution realized with 3EL2 Non-gapped line arresters (NGLA) Externally gapped line arresters (EGLA) Non-gapped line surge arresters offer a high degree of mounting flexibility and operational reliability. Depending on the tower design and the arrangement of insulators and lines, these arresters can either be installed directly on the insulators or on the tower. Thanks to their high energy absorption capacity, non-gapped line arresters ensure a very high level of protection against overvoltages caused by lightning and network-generated switching impulse currents. Siemens EGLA line surge arresters of the 3EV1, 3EV2, and 3EV5 series have an external spark gap placed in series that galvanically isolates the active part of the line surge arrester from the line voltage under normal conditions. In case of lightning, the spark gap is ignited and the dangerous overvoltage is safely discharged through the resulting arc. The active component limits the subsequent current to ensure that the arc is extinguished within the first half-cycle of the operating current frequency. Siemens 3EL1, 3EL2, 3EL3, 3EL5 surge arresters are available as NGLA types. 550 kV line in Colombia NGLA solution realized with 3EL2 The series varistor units (SVU) of the EGLA 3EV1, 3EV2, and 3EV5 product lines are based on the respective 3EL1, 3EL2, and 3EL5 product lines. Refer to the brochure »Line surge arresters for increased system reliability« for a detailed overview of Siemens’ solutions for line surge arresters. 23 Early detection of relevant changes through efficient equipment monitoring Due to continuously growing worldwide power demand, more and more power networks are required to transmit higher loads – sometimes up to the limits of their capacity. This makes reliable, responsible network operation an increasingly difficult challenge. In many of today’s markets, transmission and distribution system operators are also liable for compensation in the case of power failures. And natural events like lightning can cripple entire networks. As a result, many network operators are seeking solutions to increase the reliability of their transmission systems. Equipment monitoring is a proven method for the recording of operating states and remaining service life, providing the operator with important asset management data and enabling the immediate assessment of a network’s overall state. 24 Surge arresters are highly reliable components in power transmission and distribution systems. When operated in accordance with their specifications, their service life can reach up to 30 years without any maintenance. Nevertheless, overloads that can cause arrester failure and even endanger the safety of the network may sometimes occur. Equipment monitoring helps detect changes and faults at the earliest possible stage and supports security of supply on a whole new level. Siemens provides a complete line of monitoring devices with a variety of innovative functionalities that can be perfectly matched to customer requirements, ensuring that impending faults will be detected as early as possible and before security of supply is compromised. Order code system Data position 1 2 3 4 5 6 7 – 8 9 Order code n a a n n n n – n a Product line 3 E L 2 0 9 6 Rated voltage (kV) Long duration current impulse, energy absorption capability Application Housing size Line discharge class Number of units Form of sheds and color of housing 10 11 12 a n n – 13 14 15 16 – Z n – Z a a n 2 P J 3 1 4 High-voltage terminal X Nameplate H Mounting 5 Accessories a: alphabetical n: numerical Ordering example The order code can be obtained through the following steps: 1. Select the product line from table »Main technical data« on page 26. Example: product line 3EL2 2. Select the duty cycle voltage and required energy rating of the arrester using the »Ratings and specifications – Electrical characteristics« in the technical datasheet of the selected product line. Example: 3EL2 096-2P.3.-… 3. Select the required housing using the »Ratings and specifications – mechanical characteristics« in the technical datasheet of the selected product line. Example: for 3EL2 096-2P.3.-.… the minimum housing is »J«: + 3EL2 …-..J…, resulting in: 3EL2 096-2PJ31-… 4. Select the required terminal, nameplate, and mounting from the table »Order numbers« Example: 3EL2 096-2PJ31-4XH5. (4 = upright mounting, X = DIN/NEMA flat terminal, H = English ANSI nameplate, 5 = ø 10.0”, 3-hole grounded) 5. Select optional accessories from table »Optional accessories« on page 74 Example: D91 line clamp, resulting in 3EL2 096-2PJ31-4XH5-Z D91 D92 6. Select optional monitoring device from table »Monitoring devices« on page 75. Example: 3EX5 080-0 ACM basic 25 Product range Siemens offers multiple models of each surge arrester product family. The models mainly differ in diameter, length of the housings, and sizes of the MOV blocks to meet different customer requirements. The following selection table shows the main technical data of the different product lines. Detailed technical data is listed in the sections for each dedicated product line. For additional specifications, please contact your local Siemens representative. 3EL5 3EL1 3EL2 3EL3 3EP5 3EP4 3EP6 3EQ1 Highest nominal system voltage Maximum values kV 69 69 345 500 69 345 765 345 765 Maximum duty cycle voltage kV 60 72 288 444 72 276 588 288 588 kV 48 57 230 353 57 220 470 230 470 Maximum MCOV Lightning impulse classi fying current Energy class kA Switching surge energy rating Singleimpulse withstand rating kJ/kVMCOV C 4.5 0.6 10 B 10 C 6.0 1.2 10 E 9.0 2.0 15 F 11 2.4 15 G 13 2.8 20 J 18 3.6 20 K 21 6.0 Rated short-circuit current kA 20 65 65 65 40 65 65 40 651 High-current short-duration kA 65 65 65 100 65 65 100 65 100 3,098 7,435 24,782 58,238 n.a n.a n.a 37,173 130,106/ 235,4302 n.a n.a n.a n.a 21,242 47,794 191,175 n.a n.a Maximum design cantilever load (MDCL)inch-lbf Ultimate mechanical strength (UMS-static)inch-lbf Main technical data 26 3EQ4 1) Increased rated short-circuit current of 80 kA available on request. 2) Increased MDCL. The table below shows an overview of the typical minimum duty cycle voltage for the surge arrester, depending on the system voltage and grounding of the system. kV Four-wire multi-grounded neutral wye Ur kV Three-wire low impedance grounded neutral circuit Ur kV Three-wire high impedance grounded neutral circuit Ur kV 4.16 3 6 6 6 9 System L-L voltage Un 6.9 8.3 9 12 9 12 12.47 9 or 10 15 13.8 10 or 12 15 22.86 15 21 27 36 23 34.5 18 30 48.3 36 54 69 54 72 115 96 or 108 138 120 161 144 230 180 345 258 500 396 or 420 765 588 90 Typical duty cycle voltages Ur for system voltages Un according to IEEE C62.11. 27 3EL5 Surge arrester with silicone rubber housing and Cage Design™ Technical datasheet Protection of: • Transformers • Circuit breakers • Generators • Motors • Capacitors • Traction vehicles • Bushings • Switchgear • Transmission lines Maximum values 3EL5 Highest nominal system voltage kV 69 Maximum duty cycle voltage kV 60 Maximum MCOV kV 48 Lightning impulse classifying current kA 10 Energy class kJ/kVMCOV 4.5 Single-impulse withstand rating C 0.6 Rated short-circuit current kA 20 High-current short-duration kA 65 inch-lbf 3,098 Switching surge energy rating Maximum design cantilever load (MDCL) 28 3EL5 B 3EL5 – order numbers Data position 1 2 3 4 Order number 3 E L 5 3 E L 5 – 5 6 7 x x x x x x – 8 9 10 11 12 0 P H 1 1 – 13 14 15 16 4 X H 5 – Z – Z Product line Silicone rubber-housed surge arrester, cage design Duty cycle voltage in kV Energy class, single-impulse withstand rating, switching surge energy rating Energy class B, Qs = 0.6 C, W = 4.5 kJ/kVMCOV 0 1 Application Line surge arrester (For more details refer to catalog »Line surge arresters«) L Phase surge arrester P Housing size, number of units, leakage distance, height Housing »B«, 1 unit, leakage distance 15 inch, height 7 inch B 1 Housing »C«, 1 unit, leakage distance 19 inch, height 8 inch C 1 Housing »D«, 1 unit, leakage distance 24 inch, height 9 inch D 1 Housing »E«, 1 unit, leakage distance 31 inch, height 11 inch E 1 Housing »F«, 1 unit, leakage distance 35 inch, height 12 inch F 1 Housing »H«, 1 unit, leakage distance 48 inch, height 16 inch H 1 Housing »J«, 1 unit, leakage distance 56 inch, height 19 inch J 1 Housing »K«, 1 unit, leakage distance 63 inch, height 20 inch K 1 Form of sheds and color of silicone rubber Alternating sheds, gray silicone rubber, upright mounting 4 Alternating sheds, gray silicone rubber, suspended mounting 8 High-voltage terminal NEMA 4-hole pad, 1.75”x1.75”, hot dip galvanized steel X NEMA 4-hole pad, 1.75”x1.75”, stainless steel Y Nameplate English IEEE/ANSI H Mounting ø 10.0”, 3-hole insulated 1 ø 10.0”, 3-hole grounded 5 Customized solution 9 Accessories Refer to table »Accessories for surge arresters« on page 74 3EL5 29 Ratings and specifications Electrical characteristics Duty cycle voltage kV MCOV Energy class kV Switching Singlesurge impulse energy withstand rating rating kJ/kVmcov C Protective level Maximum discharge voltage 8/20µs 1.5 kA kV cr 8/20µs 3 kA kV cr 8/20µs 5 kA kV cr 8/20µs 10 kA kV cr 8/20µs 20 kA kV cr 8/20µs 40 kA kV cr Arrester order number 45/90µs 500 A kV cr 45/90µs 1 kA kV cr 3 2.55 B 4.5 0.6 6.8 7.1 7.4 8.0 9.1 10.6 6.1 6.4 3EL5 003 - 0PB11 - …. 6 5.10 B 4.5 0.6 13.5 14.2 14.8 15.9 18.3 21.1 12.2 12.7 3EL5 006 - 0PB11 - …. 9 7.65 B 4.5 0.6 20.3 21.2 22.2 23.9 27.4 31.7 18.4 19.1 3EL5 009 - 0PB11 - …. 10 8.4 B 4.5 0.6 22.5 23.6 24.6 26.5 30.5 35.2 20.4 21.2 3EL5 010 - 0PB11 - …. 12 10.2 B 4.5 0.6 27.0 28.3 29.6 31.8 36.6 42.3 24.5 25.4 3EL5 012 - 0PC11 - …. 15 12.7 B 4.5 0.6 33.8 35.4 37.0 39.8 45.7 52.9 30.6 31.8 3EL5 015 - 0PC11 - …. 18 15.3 B 4.5 0.6 40.5 42.5 44.4 47.7 54.9 63.4 36.7 38.2 3EL5 018 - 0PD11 - …. 21 17.0 B 4.5 0.6 47.3 49.5 51.8 55.7 64.0 74.0 42.9 44.5 3EL5 021 - 0PD11 - …. 24 19.5 B 4.5 0.6 54.1 56.6 59.1 63.6 73.1 84.6 49.0 50.9 3EL5 024 - 0PE11 - …. 27 22.0 B 4.5 0.6 60.8 63.7 66.5 71.6 82.3 95.2 55.1 57.2 3EL5 027 - 0PE11 - …. 30 24.4 B 4.5 0.6 67.6 70.8 73.9 79.5 91.4 106 61.2 63.6 3EL5 030 - 0PF11 - …. 36 29.0 B 4.5 0.6 81.1 84.9 88.7 95.4 110 127 73.5 76.3 3EL5 036 - 0PH11 - …. 39 31.5 B 4.5 0.6 87.8 92.0 96.1 103 119 137 79.6 82.7 3EL5 039 - 0PH11 - …. 45 36.5 B 4.5 0.6 101 106 111 119 137 159 91.8 95.4 3EL5 045 - 0PH11 - …. 48 39.0 B 4.5 0.6 108 113 118 127 146 169 97.9 102 3EL5 048 - 0PH11 - …. 54 42.0 B 4.5 0.6 122 127 133 143 165 190 110 114 3EL5 054 - 0PJ11 - …. 60 48.0 B 4.5 0.6 135 142 148 159 183 211 122 127 3EL5 060 - 0PK11 - …. Line terminals NEMA flat terminal 3EL5 …-…..-.X.. (hot dip galvanized) Figure A 30 3EL5 3EL5 …-…..-.Y.. (stainless steel) Mechanical characteristics Leakage distance Height [H] Recommended minimum clearances Between phases (ph-ph) inch Grading ring diameter [D] Cantilever strength MDCL Weight Figure inch inch To ground (ph-gnd) inch inch lbf lbs 15 7 1 2 - 463 6 A 15 7 1 2 - 463 6 A 15 7 1 2 - 463 6 A 15 7 2 3 - 463 7 A 19 8 2 3 - 393 7 A 19 8 3 4 - 393 7 A 24 9 4 5 - 328 8 A 24 9 4 5 - 328 8 A 31 11 5 6 - 291 9 A 31 11 6 7 - 291 9 A 35 12 7 9 - 262 10 A 48 16 8 10 - 197 11 A 48 16 9 11 - 197 12 A 48 16 12 13 - 197 13 A 48 16 12 13 - 197 13 A 56 19 16 18 - 167 14 A 63 20 16 18 - 154 15 A Mounting Insulated Grounded 3EL5 …-…..-…1 3EL5 …-…..-…5 3EL5 31 3EL1 Surge arrester with silicone rubber housing and Cage Design™ Technical datasheet Protection of: • Transformers • Circuit breakers • Generators • Motors • Capacitors • Traction vehicles • Bushings • Switchgear • Transmission lines Maximum values 3EL1 Highest nominal system voltage kV 69 Maximum duty cycle voltage kV 72 Maximum MCOV kV 57 Lightning impulse classifying current kA 10 Energy class kJ/kVMCOV 6.0 Single-impulse withstand rating C 1.2 Rated short-circuit current kA 65 High-current short-duration kA 65 inch-lbf 7,435 Switching surge energy rating Maximum design cantilever load (MDCL) 32 3EL1 C 3EL1 – order numbers Data position 1 2 3 4 Order number 3 E L 1 3 E L 1 – 5 6 7 x x x x x x – 8 9 10 11 12 1 P H 2 1 – 13 14 15 16 4 X H 5 – Z – Z Product line Silicone rubber-housed surge arrester, cage design Duty cycle voltage in kV Energy class, single-impulse withstand rating, switching surge energy rating Energy class C, Qs = 1.2 C, W = 6.0 kJ/kVMCOV 1 2 Application Line surge arrester (For more details refer to catalog »Line surge arresters«) L Phase surge arrester P Housing size, number of units, leakage distance, height Housing »C«, 1 unit, leakage distance 35 inch, height 12 inch C 1 Housing »E«, 1 unit, leakage distance 55 inch, height 18 inch E 1 Housing »H«, 1 unit, leakage distance 81 inch, height 24 inch H 1 Housing »K«, 1 unit, leakage distance 121 inch, height 35 inch K 1 Housing »E+H«, 2 units, leakage distance 136 inch, height 42 inch N 2 Housing »2xH«, 2 units, leakage distance 161 inch, height 49 inch H 2 Housing »E+K«, 2 units, leakage distance 176 inch, height 53 inch P 2 Housing »H+K«, 2 units, leakage distance 202 inch, height 60 inch Q 2 Housing »2xK«, 2 units, leakage distance 242 inch, height 71 inch K 2 Form of sheds and color of silicone rubber Alternating sheds, gray silicone rubber, upright mounting 4 Alternating sheds, gray silicone rubber, suspended mounting 8 High-voltage terminal NEMA 4-hole pad, 1.75”x1.75”, hot dip galvanized steel X NEMA 4-hole pad, 1.75”x1.75”, stainless steel Y Nameplate English IEEE/ANSI H Mounting ø 10.0”, 3-hole insulated 1 ø 10.0”, 3-hole grounded 5 Customized solution 9 Accessories Refer to table »Accessories for surge arresters« on page 74 3EL1 33 Ratings and specifications Electrical characteristics Duty cycle voltage kV MCOV Energy class kV Switching Singlesurge impulse energy withstand rating rating kJ/kVmcov C Protective level Maximum discharge voltage 8/20µs 1.5 kA kV cr 8/20µs 3 kA kV cr 8/20µs 5 kA kV cr 8/20µs 10 kA kV cr 8/20µs 20 kA kV cr 8/20µs 40 kA kV cr Arrester order number 45/90µs 500 A kV cr 45/90µs 1 kA kV cr 3 2.55 C 6.0 1.2 6.6 6.9 7.3 7.8 8.7 10.0 6.0 6.2 3EL1 003 - 1PC21 - …. 6 5.10 C 6.0 1.2 13.3 13.9 14.5 15.6 17.5 20.0 12.0 12.5 3EL1 006 - 1PC21 - …. 9 7.65 C 6.0 1.2 19.9 20.8 21.8 23.4 26.2 30.0 18.0 18.7 3EL1 009 - 1PC21 - …. 10 8.40 C 6.0 1.2 22.1 23.1 24.2 26.0 29.1 33.3 20.0 20.8 3EL1 010 - 1PC21 - …. 12 10.2 C 6.0 1.2 26.5 27.8 29.0 31.2 34.9 39.9 24.0 25.0 3EL1 012 - 1PC21 - …. 15 12.7 C 6.0 1.2 33.2 34.7 36.3 39.0 43.7 49.9 30.0 31.2 3EL1 015 - 1PC21 - …. 18 15.3 C 6.0 1.2 39.8 41.7 43.5 46.8 52.4 59.9 36.0 37.4 3EL1 018 - 1PC21 - …. 21 17.0 C 6.0 1.2 46.4 48.6 50.8 54.6 61.2 69.9 42.0 43.7 3EL1 021 - 1PC21 - …. 24 19.5 C 6.0 1.2 53.0 55.5 58.0 62.4 69.9 79.9 48.0 49.9 3EL1 024 - 1PC21 - …. 27 22.0 C 6.0 1.2 59.7 62.5 65.3 70.2 78.6 89.9 54.1 56.2 3EL1 027 - 1PE21 - …. 30 24.4 C 6.0 1.2 66.3 69.4 72.5 78.0 87.4 99.8 60.1 62.4 3EL1 030 - 1PE21 - …. 36 29.0 C 6.0 1.2 79.6 83.3 87.0 93.6 105 120 72.1 74.9 3EL1 036 - 1PE21 - …. 39 31.5 C 6.0 1.2 86.2 90.2 94.3 101 114 130 78.1 81.1 3EL1 039 - 1PH21 - …. 45 36.5 C 6.0 1.2 99.5 104 109 117 131 150 90.1 93.6 3EL1 045 - 1PH21 - …. 48 39.0 C 6.0 1.2 106 111 116 125 140 160 96.1 99.8 3EL1 048 - 1PH21 - …. 54 42.0 C 6.0 1.2 119 125 131 140 157 180 108 112 3EL1 054 - 1PH21 - …. 60 48.0 C 6.0 1.2 133 139 145 156 175 200 120 125 3EL1 060 - 1PH21 - …. 72 57.0 C 6.0 1.2 159 167 174 187 210 240 144 150 3EL1 072 - 1PK21 - …. Line terminals NEMA flat terminal 3EL1 …-…..-.X.. (hot dip galvanized) Figure A 34 3EL1 3EL1 …-…..-.Y.. (stainless steel) Mechanical characteristics Leakage distance Height [H] Recommended minimum clearances Between phases (ph-ph) inch Grading ring diameter [D] Cantilever strength MDCL Weight Figure inch inch To ground (ph-gnd) inch inch lbf lbs 35 12 1 2 - 619 13 A 35 12 1 2 - 619 13 A 35 12 1 2 - 619 14 A 35 12 2 3 - 619 14 A 35 12 2 3 - 619 14 A 35 12 2 3 - 619 15 A 35 12 3 4 - 619 15 A 35 12 4 5 - 619 15 A 35 12 5 6 - 619 15 A 55 18 6 7 - 424 19 A 55 18 6 7 - 424 19 A 55 18 8 10 - 424 19 A 81 24 9 11 - 305 23 A 81 24 10 12 - 305 23 A 81 24 12 13 - 305 23 A 81 24 16 18 - 305 24 A 81 24 16 18 - 305 25 A 121 35 21 24 - 210 29 A Mounting Insulated Grounded 3EL1 …-…..-…1 3EL1 …-…..-…5 3EL1 35 3EL2 Surge arrester with silicone rubber housing and Cage Design™ Technical datasheet Protection of: • Transformers • Circuit breakers • Generators • Motors • Capacitors • Traction vehicles • Bushings • Switchgear • Transmission lines Maximum values kV 345 345 Maximum duty cycle voltage kV 288 288 Maximum MCOV kV 230 230 Lightning impulse classifying current kA 10 15 E F kJ/kVMCOV 9.0 11 Single-impulse withstand rating C 2.0 2.4 Rated short-circuit current kA 65 65 High-current short-duration kA 65 65 inch-lbf 24,782 24,782 Switching surge energy rating Maximum design cantilever load (MDCL) 3EL2 3EL2 Highest nominal system voltage Energy class 36 3EL2 3EL2 – order numbers Data position 1 2 3 4 Order number 3 E L 2 3 E L 2 – 5 6 7 x x x x x x – 8 9 10 11 12 2 P M 3 1 – 13 14 15 16 4 X H 5 – Z – Z Product line Silicone rubber-housed surge arrester, cage design Duty cycle voltage in kV Energy class, single-impulse withstand rating, switching surge energy rating Energy class E, Qs = 2.0 C, W = 9.0 kJ/kVMCOV 2 3 Energy class F, Qs = 2.4 C, W = 11.0 kJ/kVMCOV 6 4 Application Line surge arrester (For more details refer to catalog »Line surge arresters«) L Phase surge arrester P Housing size, number of units, leakage distance, height Housing »C«, 1 unit, leakage distance 58 inch, height 19 inch C 1 Housing »F«, 1 unit, leakage distance 92 inch, height 28 inch F 1 Housing »J«, 1 unit, leakage distance 150 inch, height 42 inch J 1 Housing »M«, 1 unit, leakage distance 177 inch, height 49 inch M 1 Housing »C+J«, 2 units, leakage distance 208 inch, height 61 inch P 2 Housing »F+J«, 2 units, leakage distance 243 inch, height 70 inch Q 2 Housing »F+M«, 2 units, leakage distance 269 inch, height 77 inch R 2 Housing »2xJ«, 2 units, leakage distance 301 inch, height 84 inch J 2 Housing »J+M«, 2 units, leakage distance 327 inch, height 91 inch W 2 Housing »2xM«, 2 units, leakage distance 354 inch, height 98 inch M 2 Form of sheds and color of silicone rubber Alternating sheds, gray silicone rubber, upright mounting 4 Alternating sheds, gray silicone rubber, suspended mounting 8 High-voltage terminal NEMA 4-hole pad, 1.75”x1.75”, hot dip galvanized steel X NEMA 4-hole pad, 1.75”x1.75”, stainless steel Y Nameplate English IEEE/ANSI H Mounting ø 10.0”, 3-hole insulated 1 ø 10.0”, 3-hole grounded 5 Customized solution 9 Accessories Refer to table »Accessories for surge arresters« on page 74 3EL2 37 Ratings and specifications Electrical characteristics Duty cycle voltage kV 38 MCOV Energy class kV Switching Singlesurge impulse energy withstand rating rating kJ/kVmcov C Protective level Maximum discharge voltage 8/20µs 1.5 kA kV cr 8/20µs 3 kA kV cr 8/20µs 5 kA kV cr 8/20µs 10 kA kV cr 8/20µs 20 kA kV cr Arrester order number 8/20µs 40 kA kV cr 45/90µs 500 A kV cr 45/90µs 1 kA kV cr 3 2.55 E 9.0 2.0 6.2 6.5 6.8 7.2 8.0 9.1 5.8 5.9 3EL2 003 - 2PC31 - …. 6 5.10 E 9.0 2.0 12.4 13.0 13.5 14.4 16.0 18.1 11.5 11.8 3EL2 006 - 2PC31 - …. 9 7.65 E 9.0 2.0 18.6 19.4 20.3 21.6 24.0 27.2 17.3 17.7 3EL2 009 - 2PC31 - …. 10 8.4 E 9.0 2.0 20.6 21.6 22.6 24.0 26.6 30.2 19.2 19.7 3EL2 010 - 2PC31 - …. 12 10.2 E 9.0 2.0 24.8 25.9 27.1 28.8 32.0 36.3 23.0 23.6 3EL2 012 - 2PC31 - …. 15 12.7 E 9.0 2.0 31.0 32.4 33.8 36.0 40.0 45.4 28.8 29.5 3EL2 015 - 2PC31 - …. 18 15.3 E 9.0 2.0 37.2 38.9 40.6 43.2 48.0 54.4 34.6 35.4 3EL2 018 - 2PC31 - …. 21 17.0 E 9.0 2.0 43.3 45.4 47.4 50.4 55.9 63.5 40.3 41.3 3EL2 021 - 2PC31 - …. 24 19.5 E 9.0 2.0 49.5 51.8 54.1 57.6 63.9 72.6 46.1 47.2 3EL2 024 - 2PC31 - …. 27 22.0 E 9.0 2.0 55.7 58.3 60.9 64.8 71.9 81.6 51.8 53.1 3EL2 027 - 2PC31 - …. 30 24.4 E 9.0 2.0 61.9 64.8 67.7 72.0 79.9 90.7 57.6 59.0 3EL2 030 - 2PC31 - …. 36 29.0 E 9.0 2.0 74.3 77.8 81.2 86.4 95.9 109 69.1 70.8 3EL2 036 - 2PC31 - …. 39 31.5 E 9.0 2.0 80.5 84.2 88.0 93.6 104 118 74.9 76.8 3EL2 039 - 2PC31 - …. 45 36.5 E 9.0 2.0 92.9 97.2 102 108 120 136 86.4 88.6 3EL2 045 - 2PF31 - …. 48 39.0 E 9.0 2.0 99.1 104 108 115 128 145 92.2 94.5 3EL2 048 - 2PF31 - …. 54 42.0 E 9.0 2.0 111 117 122 130 144 163 104 106 3EL2 054 - 2PF31 - …. 60 48.0 E 9.0 2.0 124 130 135 144 160 181 115 118 3EL2 060 - 2PF31 - …. 72 57.0 E 9.0 2.0 149 156 162 173 192 218 138 142 3EL2 072 - 2PF31 - …. 90 70.0 E 9.0 2.0 186 194 203 216 240 272 173 177 3EL2 090 - 2PJ31 - …. 96 76.0 E 9.0 2.0 198 207 217 230 256 290 184 189 3EL2 096 - 2PJ31 - …. 96 76.0 F 11.0 2.4 192 199 208 221 243 265 179 183 3EL2 096 - 6PJ41 - …. 108 84.0 E 9.0 2.0 223 233 244 259 288 327 207 213 3EL2 108 - 2PJ31 - …. 111 88.0 E 9.0 2.0 229 240 250 266 296 336 213 218 3EL2 111 - 2PJ31 - …. 120 98.0 E 9.0 2.0 248 259 271 288 320 363 230 236 3EL2 120 - 2PJ31 - …. 132 106 E 9.0 2.0 272 285 298 317 352 399 253 260 3EL2 132 - 2PM31 - …. 144 115 E 9.0 2.0 297 311 325 346 384 435 276 283 3EL2 144 - 2PM31 - …. 168 131 E 9.0 2.0 347 363 379 403 448 508 323 331 3EL2 168 - 2PQ32 - …. 172 140 E 9.0 2.0 355 372 388 413 458 520 330 338 3EL2 172 - 2PQ32 - …. 180 144 E 9.0 2.0 372 389 406 432 480 544 346 354 3EL2 180 - 2PQ32 - …. 192 152 E 9.0 2.0 396 415 433 461 511 581 369 378 3EL2 192 - 2PQ32 - …. 192 152 E 9.0 2.0 396 415 433 461 511 581 369 378 3EL2 192 - 2PJ32 - …. 192 152 F 11.0 2.4 384 397 415 442 486 530 358 367 3EL2 192 - 6PQ42 - …. 192 152 F 11.0 2.4 384 397 415 442 486 530 358 367 3EL2 192 - 6PJ42 - …. 228 180 E 9.0 2.0 471 492 514 547 607 689 438 449 3EL2 228 - 2PJ32 - …. 240 190 E 9.0 2.0 495 518 541 576 639 726 461 472 3EL2 240 - 2PJ32 - …. 258 209 E 9.0 2.0 533 557 582 619 687 780 495 508 3EL2 258 - 2PW32 - …. 258 209 E 9.0 2.0 533 557 582 619 687 780 495 508 3EL2 258 - 2PM32 - …. 264 212 E 9.0 2.0 545 570 596 634 703 798 507 520 3EL2 264 - 2PM32 - …. 264 212 F 11.0 2.4 528 546 571 607 668 729 492 504 3EL2 264 - 6PW42 - …. 276 220 E 9.0 2.0 570 596 623 662 735 835 530 543 3EL2 276 - 2PM32 - …. 276 220 F 11.0 2.4 552 571 597 635 698 762 514 527 3EL2 276 - 6PM42 - …. 288 230 F 11.0 2.4 576 596 623 662 729 795 537 550 3EL2 288 - 6PM42 - …. 3EL2 Mechanical characteristics Leakage distance Height [H] Recommended minimum clearances Between phases (ph-ph) inch Grading ring diameter [D] Cantilever strength MDCL Weight Figure inch inch To ground (ph-gnd) inch inch lbf lbs 58 19 1 2 - 1,306 32 A 58 19 1 2 - 1,306 32 A 58 19 1 2 - 1,306 32 A 58 19 1 2 - 1,306 32 A 58 19 2 3 - 1,306 33 A 58 19 2 3 - 1,306 33 A 58 19 3 4 - 1,306 35 A 58 19 4 5 - 1,306 35 A 58 19 4 5 - 1,306 36 A 58 19 5 6 - 1,306 36 A 58 19 6 7 - 1,306 36 A 58 19 7 9 - 1,306 37 A 58 19 8 10 - 1,306 38 A 92 28 9 11 - 893 45 A 92 28 10 12 - 893 45 A 92 28 12 13 - 893 47 A 92 28 16 18 - 893 48 A 92 28 16 18 - 893 49 A 150 42 21 24 - 593 62 A 150 42 31 34 - 593 63 A 150 42 21 24 - 593 64 A 150 42 31 34 - 593 66 A 150 42 31 34 - 593 66 A 150 42 31 34 - 593 67 A 177 49 50 56 - 508 74 A 177 49 50 56 - 508 76 A 243 70 50 56 - 356 104 B 243 70 50 56 - 356 104 B 243 70 50 56 - 356 105 B 243 70 50 56 - 356 108 B 301 84 50 56 - 296 108 B 243 70 50 56 - 356 110 B 301 84 50 56 - 296 110 B 301 84 59 66 - 296 123 B 301 84 59 66 - 296 126 B 327 91 68 77 24 273 134 C 354 98 68 77 31 254 140 C 354 98 68 77 31 254 140 C 327 91 68 77 24 273 140 C 354 98 68 77 31 254 142 C 354 98 68 77 31 254 146 C 354 98 68 77 31 254 149 C 3EL2 39 Figure A 40 3EL2 Figure B Figure C Line terminals NEMA flat terminal 3EL2 …-…..-.X.. (hot dip galvanized) 3EL2 …-…..-.Y.. (stainless steel) Mounting Insulated Grounded 3EL2 …-…..-…1 3EL2 …-…..-…5 3EL2 41 3EL3 Surge arrester with silicone rubber housing and Cage Design™ Technical datasheet Protection of: • Transformers • Circuit breakers • Generators • Motors • Capacitors • Bushings • Switchgear • Transmission lines Maximum values kV 500 500 Maximum duty cycle voltage kV 444 444 Maximum MCOV kV 353 353 Lightning impulse classifying current kA 15 20 G J kJ/kVMCOV 13 18 Single-impulse withstand rating C 2.8 3.6 Rated short-circuit current kA 65 65 High-current short-duration kA 100 100 inch-lbf 58,238 58,238 Switching surge energy rating Maximum design cantilever load (MDCL) 3EL3 3EL3 Highest nominal system voltage Energy class 42 3EL3 3EL3 – order numbers Data position 1 2 3 4 Order number 3 E L 3 3 E L 3 – 5 6 7 x x x x x x – 8 9 4 P 10 11 12 J 4 1 – 13 14 15 16 4 X H 5 – Z – Z Product line Silicone rubber-housed surge arrester, cage design Duty cycle voltage in kV Energy class, single-impulse withstand rating, switching surge energy rating Energy class G, Qs = 2.8 C, W = 13.0 kJ/kVMCOV 4 4 Energy class J, Qs = 3.6 C, W = 18.0 kJ/kVMCOV 4 5 Application Line surge arrester (For more details refer to catalog »Line surge arresters«) L Phase surge arrester P Housing size, number of units, leakage distance, height Housing »F«, 1 unit, leakage distance 97 inch, height 29 inch F 1 Housing »G«, 1 unit, leakage distance 113 inch, height 33 inch G 1 Housing »H«, 1 unit, leakage distance 128 inch, height 36 inch H 1 Housing »J«, 1 unit, leakage distance 143 inch, height 40 inch J 1 Housing »K«, 1 unit, leakage distance 159 inch, height 43 inch K 1 Housing »L«, 1 unit, leakage distance 174 inch, height 47 inch L 1 Housing »M«, 1 unit, leakage distance 189 inch, height 50 inch M 1 Housing »2xG«, 2 units, leakage distance 226 inch, height 66 inch G 2 Housing »2xH«, 2 units, leakage distance 256 inch, height 73 inch H 2 Housing »2xJ«, 2 units, leakage distance 287 inch, height 80 inch J 2 Housing »2xK«, 2 units, leakage distance 317 inch, height 87 inch K 2 Housing »2xL«, 2 units, leakage distance 348 inch, height 94 inch L 2 Housing »2xM«, 2 units, leakage distance 378 inch, height 101 inch M 2 Housing »3xJ«, 3 units, leakage distance 430 inch, height 120 inch J 3 Housing »3xK«, 3 units, leakage distance 476 inch, height 130 inch K 3 Housing »3xL«, 3 units, leakage distance 522 inch, height 141 inch L 3 Housing »3xM«, 3 units, leakage distance 568 inch, height 151 inch M 3 Form of sheds and color of silicone rubber Alternating sheds, gray silicone rubber, upright mounting 4 Alternating sheds, gray silicone rubber, suspended mounting 8 High-voltage terminal NEMA 4-hole pad, 1.75”x1.75”, hot dip galvanized steel X NEMA 4-hole pad, 1.75”x1.75”, stainless steel Y Nameplate English IEEE/ANSI H Mounting ø 10.0”, 3-hole grounded 5 ø 10.0”, 3-hole insulated 7 Customized solution 9 Accessories Refer to table »Accessories for surge arresters« on page 74 3EL3 43 Ratings and specifications Electrical characteristics Duty cycle voltage kV 44 MCOV Energy class kV Switching Singlesurge impulse energy withstand rating rating Protective level Maximum discharge voltage kJ/kVmcov C 8/20µs 1.5 kA kV cr Arrester order number 8/20µs 3 kA kV cr 8/20µs 5 kA kV cr 8/20µs 10 kA kV cr 8/20µs 20 kA kV cr 8/20µs 40 kA kV cr 45/90µs 1 kA kV cr 45/90µs 2 kA kV cr 258 209 G 13.0 2.8 511 528 549 581 633 691 496 511 3EL3 258 - 4PK42 - …. 258 209 J 18.0 3.6 511 528 549 581 633 691 496 511 3EL3 258 - 4PK52 - …. 264 212 G 13.0 2.8 523 541 561 594 647 707 508 523 3EL3 264 - 4PK42 - …. 264 212 J 18.0 3.6 523 541 561 594 647 707 508 523 3EL3 264 - 4PL52 - …. 276 220 G 13.0 2.8 546 565 587 621 677 739 531 546 3EL3 276 - 4PL42 - …. 276 220 J 18.0 3.6 546 565 587 621 677 739 531 546 3EL3 276 - 4PL52 - …. 288 230 G 13.0 2.8 570 590 612 648 706 771 554 570 3EL3 288 - 4PL42 - …. 288 230 J 18.0 3.6 570 590 612 648 706 771 554 570 3EL3 288 - 4PL52 - …. 294 235 G 13.0 2.8 582 602 625 662 721 787 566 582 3EL3 294 - 4PL42 - …. 294 235 J 18.0 3.6 582 602 625 662 721 787 566 582 3EL3 294 - 4PM52 - …. 312 245 G 13.0 2.8 618 639 663 702 765 835 600 618 3EL3 312 - 4PJ43 - …. 312 245 J 18.0 3.6 618 639 663 702 765 835 600 618 3EL3 312 - 4PJ53 - …. 396 318 G 13.0 2.8 784 811 842 891 971 1,060 762 784 3EL3 396 - 4PL43 - …. 396 318 J 18.0 3.6 784 811 842 891 971 1,060 762 784 3EL3 396 - 4PL53 - …. 420 335 G 13.0 2.8 832 860 893 945 1,030 1,125 808 832 3EL3 420 - 4PK44 - …. 420 335 J 18.0 3.6 832 860 893 945 1,030 1,125 808 832 3EL3 420 - 4PK54 - …. 444 353 G 13.0 2.8 879 909 944 999 1,089 1,189 854 879 3EL3 444 - 4PK44 - …. 444 353 J 18.0 3.6 879 909 944 999 1,089 1,189 854 879 3EL3 444 - 4PK54 - …. 3EL3 Mechanical characteristics Leakage distance Height [H] Recommended minimum clearances Between phases (ph-ph) inch Grading ring diameter [D] Cantilever strength MDCL Weight Figure inch inch To ground (ph-gnd) inch inch lbf lbs 317 87 59 66 24 670 216 C 317 87 59 66 24 670 222 C 317 87 59 66 24 670 218 C 348 94 59 66 24 620 230 C 348 94 68 77 24 620 227 C 348 94 68 77 24 620 234 C 348 94 68 77 24 620 231 C 348 94 68 77 24 620 238 C 348 94 68 77 24 620 234 C 378 101 68 77 31 577 245 C 430 120 76 85 31 486 283 D 430 120 76 85 31 486 291 D 522 141 97 111 39 413 341 D 522 141 97 111 39 413 351 D 634 174 97 111 59 335 409 E 634 174 97 111 59 335 420 E 634 174 109 125 59 335 418 E 634 174 109 125 59 335 428 E 3EL3 45 Figure A 46 3EL3 Figure B Figure C Figure D Figure E Line terminals NEMA flat terminal 3EL3 …-…..-.X.. (hot dip galvanized) 3EL3 …-…..-.Y.. (stainless steel) Mounting Insulated Grounded 3EL3 …-…..-…7 3EL3 …-…..-…5 3EL3 47 3EP5 Surge arrester with porcelain housing Technical datasheet Protection of: • Transformers • Circuit breakers • Generators • Motors • Capacitors • Bushings • Switchgear Maximum values kV 69 69 Maximum duty cycle voltage kV 72 72 Maximum MCOV kV 57 57 Lightning impulse classifying current kA 10 10 C E kJ/kVMCOV 6.0 9.0 Single-impulse withstand rating C 1.2 2.0 Rated short-circuit current kA 40 40 High-current short-duration kA 65 65 inch-lbf 21,242 21,242 Switching surge energy rating Ultimate mechanical strength-static (UMS-static) 3EP5 3EP5 Highest nominal system voltage Energy class 48 3EP5 3EP5 – order numbers Data position 1 2 3 4 Order number 3 E P 5 3 E P 5 – 5 6 7 x x x x x x – 8 9 2 P 10 11 12 E 3 1 – 13 14 15 16 3 X H 5 – Z – Z Product line Porcelain-housed surge arrester Duty cycle voltage in kV Energy class, single-impulse withstand rating, switching surge energy rating Energy class C, Qs = 1.2 C, W = 6.0 kJ/kVMCOV 1 2 Energy class E, Qs = 2.0 C, W = 9.0 kJ/kVMCOV 2 3 Application Phase surge arrester P Housing size, number of units, leakage distance, height Housing »C«, 1 unit, leakage distance 26 inch, height 14 inch C 1 Housing »E«, 1 unit, leakage distance 50 inch, height 22 inch E 1 Housing »H«, 1 unit, leakage distance 74 inch, height 30 inch H 1 Housing »J«, 1 unit, leakage distance 90 inch, height 35 inch J 1 Form of sheds and color of porcelain Normal sheds, gray porcelain, upright mounting 3 Normal sheds, gray porcelain, suspended mounting 7 High-voltage terminal NEMA 4-hole pad, 1.75”x1.75”, hot dip galvanized steel X NEMA 4-hole pad, 1.75”x1.75”, stainless steel Y Nameplate English IEEE/ANSI H Mounting ø 10.0”, 3-hole insulated 1 ø 10.0”, 3-hole grounded 5 Customized solution 9 Accessories Refer to table »Accessories for surge arresters« on page 74 3EP5 49 Ratings and specifications Electrical characteristics Duty cycle voltage kV MCOV Energy class kV Switching Singlesurge impulse energy withstand rating rating kJ/kVmcov C Protective level Maximum discharge voltage 8/20µs 1.5 kA kV cr 8/20µs 3 kA kV cr 8/20µs 5 kA kV cr 8/20µs 10 kA kV cr 8/20µs 20 kA kV cr 8/20µs 40 kA kV cr Arrester order number 45/90µs 500 A kV cr 45/90µs 1 kA kV cr 10 8.4 C 6.0 1.2 22.1 23.1 24.2 26.0 29.1 33.3 20.0 20.8 3EP5 010 - 1PC21 - …. 18 15.3 C 6.0 1.2 39.8 41.7 43.5 46.8 52.4 59.9 36.0 37.4 3EP5 018 - 1PC21 - …. 27 22.0 C 6.0 1.2 59.7 62.5 65.3 70.2 78.6 89.9 54.1 56.2 3EP5 027 - 1PC21 - …. 27 22.0 C 6.0 1.2 59.7 62.5 65.3 70.2 78.6 89.9 54.1 56.2 3EP5 027 - 1PE21 - …. 30 24.4 C 6.0 1.2 66.3 69.4 72.5 78.0 87.4 99.8 60.1 62.4 3EP5 030 - 1PE21 - …. 36 29.0 C 6.0 1.2 79.6 83.3 87.0 93.6 105 120 72.1 74.9 3EP5 036 - 1PE21 - …. 39 31.5 C 6.0 1.2 86.2 90.2 94.3 101 114 130 78.1 81.1 3EP5 039 - 1PE21 - …. 45 36.5 E 9.0 2.0 92.9 97.2 102 108 120 136 86.4 88.6 3EP5 045 - 2PE31 - …. 48 39.0 E 9.0 2.0 99.1 104 108 115 128 145 92.2 94.5 3EP5 048 - 2PE31 - …. 54 42.0 E 9.0 2.0 111 117 122 130 144 163 104 106 3EP5 054 - 2PH31 - …. 60 48.0 E 9.0 2.0 124 130 135 144 160 181 115 118 3EP5 060 - 2PH31 - …. 72 57.0 E 9.0 2.0 149 156 162 173 192 218 138 142 3EP5 072 - 2PH31 - …. Line terminals NEMA flat terminal 3EP5 …-…..-.X.. (hot dip galvanized) Figure A 50 3EP5 3EP5 …-…..-.Y.. (stainless steel) Mechanical characteristics Leakage distance Height [H] Recommended minimum clearances Between phases (ph-ph) inch Grading ring diameter [D] Cantilever strength MDCL Weight Figure inch inch To ground (ph-gnd) inch inch lbf lbs 26 14 2 3 - 1,466 46 A 26 14 3 4 - 1,466 47 A 26 14 6 7 - 1,466 49 A 50 22 6 7 - 953 63 A 50 22 6 7 - 953 63 A 50 22 8 10 - 953 64 A 50 22 9 11 - 953 64 A 50 22 9 11 - 953 68 A 50 22 10 12 - 953 68 A 74 30 12 13 - 706 83 A 74 30 16 18 - 706 84 A 74 30 16 18 - 706 86 A Mounting Insulated Grounded 3EP5 …-…..-…1 3EP5 …-…..-…5 3EP5 51 3EP4 Surge arrester with porcelain housing Technical datasheet Protection of: • Transformers • Circuit breakers • Generators • Motors • Capacitors • Bushings • Switchgear Maximum values 3EP4 Highest nominal system voltage kV 345 Maximum duty cycle voltage kV 276 Maximum MCOV kV 220 Lightning impulse classifying current kA 10 Energy class kJ/kVMCOV 9.0 Single-impulse withstand rating C 2.0 Rated short-circuit current kA 65 High-current short-duration kA 65 inch-lbf 47,794 Switching surge energy rating Ultimate mechanical strength-static (UMS-static) 52 3EP4 E 3EP4 – order numbers Data position 1 2 3 4 Order number 3 E P 4 3 E P 4 – 5 6 7 x x x x x x – 8 9 2 P 10 11 12 E 3 1 – 13 14 15 16 3 X H 5 – Z – Z Product line Porcelain-housed surge arrester Duty cycle voltage in kV Energy class, single-impulse withstand rating, switching surge energy rating Energy class C, Qs = 1.2 C, W = 6.0 kJ/kVMCOV 1 2 Energy class E, Qs = 2.0 C, W = 9.0 kJ/kVMCOV 2 3 Application Phase surge arrester P Housing size, number of units, leakage distance, height Housing »B«, 1 unit, leakage distance 19 inch, height 15 inch B 1 Housing »C«, 1 unit, leakage distance 39 inch, height 22 inch C 1 Housing »D«, 1 unit, leakage distance 98 inch, height 41 inch D 1 Housing »E«, 1 unit, leakage distance 134 inch, height 52 inch E 1 Housing »F«, 1 unit, leakage distance 151 inch, height 57 inch F 1 Housing »2xD«, 2 units, leakage distance 196 inch, height 83 inch D 2 Housing »2xE«, 2 units, leakage distance 268 inch, height 104 inch E 2 Housing »2xF«, 2 units, leakage distance 302 inch, height 115 inch F 2 Form of sheds and color of porcelain Normal sheds, gray porcelain, upright mounting 3 Normal sheds, gray porcelain, suspended mounting 7 High-voltage terminal NEMA 4-hole pad, 1.75”x1.75”, hot dip galvanized steel X NEMA 4-hole pad, 1.75”x1.75”, stainless steel Y Nameplate English IEEE/ANSI H Mounting ø 10.0”, 3-hole grounded 5 ø 10.0”, 3-hole insulated 7 Customized solution 9 Accessories Refer to table »Accessories for surge arresters« on page 74 3EP4 53 Ratings and specifications Electrical characteristics Duty cycle voltage 54 MCOV Energy class Switching Singlesurge impulse energy withstand rating rating Protective level Maximum discharge voltage Arrester order number kJ/kVmcov C 8/20µs 1.5 kA kV cr E 9.0 2.0 111 117 122 130 144 163 104 106 3EP4 054 - 2PD31 - …. E 9.0 2.0 124 130 135 144 160 181 115 118 3EP4 060 - 2PD31 - …. 57.0 E 9.0 2.0 149 156 162 173 192 218 138 142 3EP4 072 - 2PD31 - …. 90 70.0 E 9.0 2.0 186 194 203 216 240 272 173 177 3EP4 090 - 2PD31 - …. 96 76.0 E 9.0 2.0 198 207 217 230 256 290 184 189 3EP4 096 - 2PD31 - …. 108 84.0 E 9.0 2.0 223 233 244 259 288 327 207 213 3EP4 108 - 2PE31 - …. 111 88.0 E 9.0 2.0 229 240 250 266 296 336 213 218 3EP4 111 - 2PE31 - …. 120 98.0 E 9.0 2.0 248 259 271 288 320 363 230 236 3EP4 120 - 2PE31 - …. 132 106 E 9.0 2.0 272 285 298 317 352 399 253 260 3EP4 132 - 2PE31 - …. 144 115 E 9.0 2.0 297 311 325 346 384 435 276 283 3EP4 144 - 2PF31 - …. 168 131 E 9.0 2.0 347 363 379 403 448 508 323 331 3EP4 168 - 2PD32 - …. 172 140 E 9.0 2.0 355 372 388 413 458 520 330 338 3EP4 172 - 2PD32 - …. 180 144 E 9.0 2.0 372 389 406 432 480 544 346 354 3EP4 180 - 2PD32 - …. 192 152 E 9.0 2.0 396 415 433 461 511 581 369 378 3EP4 192 - 2PD32 - …. 228 180 E 9.0 2.0 471 492 514 547 607 689 438 449 3EP4 228 - 2PE32 - …. 240 190 E 9.0 2.0 495 518 541 576 639 726 461 472 3EP4 240 - 2PF32 - …. 258 209 E 9.0 2.0 533 557 582 619 687 780 495 508 3EP4 258 - 2PF32 - …. 264 212 E 9.0 2.0 545 570 596 634 703 798 507 520 3EP4 264 - 2PF32 - …. kV kV 54 42.0 60 48.0 72 3EP4 8/20µs 3 kA kV cr 8/20µs 5 kA kV cr 8/20µs 10 kA kV cr 8/20µs 20 kA kV cr 8/20µs 40 kA kV cr 45/90µs 500 A kV cr 45/90µs 1 kA kV cr Mechanical characteristics Leakage distance Height [H] Recommended minimum clearances Between phases (ph-ph) inch Grading ring diameter [D] Cantilever strength MDCL Weight Figure inch inch To ground (ph-gnd) inch inch lbf lbs 98 41 12 13 - 1,156 101 A 98 41 16 18 - 1,156 102 A 98 41 16 18 - 1,156 105 A 98 41 21 24 - 1,156 108 A 98 41 31 34 - 1,156 109 A 134 52 31 34 - 923 138 A 134 52 31 34 - 923 138 A 134 52 31 34 - 923 139 A 134 52 50 56 - 923 142 A 151 57 50 56 - 831 155 A 196 83 50 56 - 578 227 B 196 83 50 56 - 578 227 B 196 83 50 56 - 578 228 B 196 83 50 56 - 578 231 B 268 104 59 66 31 462 291 C 302 115 59 66 31 416 320 C 302 115 68 77 31 416 324 C 302 115 68 77 31 416 325 C 3EP4 55 Figure A 56 3EP4 Figure B Figure C Line terminals NEMA flat terminal 3EP4 …-…..-.X.. (hot dip galvanized) 3EP4 …-…..-.Y.. (stainless steel) Mounting Insulated Grounded 3EP4 …-…..-…7 3EP4 …-…..-…5 3EP4 57 3EP6 Surge arrester with porcelain housing Technical datasheet Protection of: • Transformers • Circuit breakers • Generators • Motors • Capacitors • Bushings • Switchgear Maximum values 3EP6 kV 345 500 765 Maximum duty cycle voltage kV 288 444 588 Maximum MCOV kV 230 353 470 Lightning impulse classifying current kA 10 15 20 E G J kJ/kVMCOV 9.0 13 18 Single-impulse withstand rating C 2.0 2.8 3.6 Rated short-circuit current kA 65 65 65 High-current short-duration kA 65 65 100 inch-lbf 191,175 191,175 191,175 Switching surge energy rating Ultimate mechanical strength-static (UMS-static) 3EP6 3EP6 Highest nominal system voltage Energy class 58 3EP6 3EP6 – order numbers Data position 1 2 3 4 Order number 3 E P 6 3 E P 6 – 5 6 7 x x x x x x – 8 9 2 P 10 11 12 F 3 1 – 13 14 15 16 4 X H 5 – Z – Z Product line Porcelain-housed surge arrester Duty cycle voltage in kV Energy class, single-impulse withstand rating, switching surge energy rating Energy class E, Qs = 2.0 C, W = 9.0 kJ/kVMCOV 2 3 Energy class G, Qs = 2.8 C, W = 13.0 kJ/kVMCOV 3 4 Energy class J, Qs = 3.6 C, W = 18.0 kJ/kVMCOV 4 5 Application Phase surge arrester P Housing size, number of units, leakage distance, height Housing »C«, 1 unit, leakage distance 155 inch, height 51 inch C 1 Housing »D«, 1 unit, leakage distance 177 inch, height 57 inch D 1 Housing »F«, 1 unit, leakage distance 229 inch, height 69 inch F 1 Housing »G«, 1 unit, leakage distance 249 inch, height 74 inch G 1 Housing »J«, 1 unit, leakage distance 302 inch, height 86 inch J 1 Housing »2xD«, 2 units, leakage distance 355 inch, height 115 inch D 2 Housing »D+F«, 2 units, leakage distance 406 inch, height 127 inch N 2 Housing »D+G«, 2 units, leakage distance 427 inch, height 131 inch P 2 Housing »2xF«, 2 units, leakage distance 457 inch, height 138 inch F 2 Housing »2xG«, 2 units, leakage distance 499 inch, height 147 inch G 2 Housing »F+J«, 2 units, leakage distance 531 inch, height 155 inch R 2 Housing »G+J«, 2 units, leakage distance 551 inch, height 160 inch S 2 Housing »2xJ«, 2 units, leakage distance 604 inch, height 173 inch J 2 Housing »3xF«, 3 units, leakage distance 686 inch, height 207 inch F 3 Housing »3xG«, 3 units, leakage distance 748 inch, height 221 inch G 3 Housing »3xJ«, 3 units, leakage distance 906 inch, height 259 inch J 3 Form of sheds and color of porcelain Alternating sheds, gray porcelain, upright mounting 4 Alternating sheds, gray porcelain, suspended mounting 8 High-voltage terminal NEMA 4-hole pad, 1.75”x1.75”, hot dip galvanized steel X NEMA 4-hole pad, 1.75”x1.75”, stainless steel Y Nameplate English IEEE/ANSI H Mounting ø 10.0”, 3-hole grounded 5 ø 16.5”, 3-hole grounded 6 ø 10.0”, 3-hole insulated 7 ø 16.5”, 3-hole insulated 8 Customized solution 9 Accessories Refer to table »Accessories for surge arresters« on page 74 3EP6 59 Ratings and specifications Electrical characteristics Duty cycle voltage kV 60 MCOV Energy class kV Switching Singlesurge impulse energy withstand rating rating Protective level Maximum discharge voltage kJ/kVmcov C 8/20µs 1.5 kA kV cr Arrester order number 8/20µs 3 kA kV cr 8/20µs 5 kA kV cr 8/20µs 10 kA kV cr 8/20µs 20 kA kV cr 8/20µs 40 kA kV cr 45/90µs 1 kA kV cr 45/90µs 2 kA kV cr 108 84.0 E 9.0 2.0 223 233 244 259 288 327 213 223 3EP6 108 - 2PC31 - …. 111 88.0 E 9.0 2.0 229 240 250 266 296 336 218 229 3EP6 111 - 2PC31 - …. 120 98.0 E 9.0 2.0 248 259 271 288 320 363 236 248 3EP6 120 - 2PC31 - …. 132 106 E 9.0 2.0 272 285 298 317 352 399 260 272 3EP6 132 - 2PC31 - …. 144 115 E 9.0 2.0 297 311 325 346 384 435 283 297 3EP6 144 - 2PC31 - …. 168 131 E 9.0 2.0 347 363 379 403 448 508 331 347 3EP6 168 - 2PD31 - …. 172 140 E 9.0 2.0 355 372 388 413 458 520 338 355 3EP6 172 - 2PD31 - …. 180 144 E 9.0 2.0 372 389 406 432 480 544 354 372 3EP6 180 - 2PF31 - …. 192 152 E 9.0 2.0 396 415 433 461 511 581 378 396 3EP6 192 - 2PF31 - …. 228 180 E 9.0 2.0 471 492 514 547 607 689 449 471 3EP6 228 - 2PG31 - …. 240 190 E 9.0 2.0 495 518 541 576 639 726 472 495 3EP6 240 - 2PJ31 - …. 258 209 E 9.0 2.0 533 557 582 619 687 780 508 533 3EP6 258 - 2PJ31 - …. 258 209 G 13.0 2.8 527 546 570 606 667 728 503 527 3EP6 258 - 3PJ41 - …. 264 212 E 9.0 2.0 545 570 596 634 703 798 520 545 3EP6 264 - 2PJ31 - …. 264 212 G 13.0 2.8 540 558 583 620 682 744 515 540 3EP6 264 - 3PJ41 - …. 276 220 E 9.0 2.0 570 596 623 662 735 835 543 570 3EP6 276 - 2PD32 - …. 276 220 G 13.0 2.8 564 584 610 649 713 778 538 564 3EP6 276 - 3PD42 - …. 288 230 E 9.0 2.0 594 622 650 691 767 871 567 594 3EP6 288 - 2PN32 - …. 288 230 G 13.0 2.8 589 609 636 677 744 812 562 589 3EP6 288 - 3PN42 - …. 396 318 G 13.0 2.8 810 838 875 931 1,024 1,117 772 810 3EP6 396 - 3PJ42 - …. 396 318 J 18.0 3.6 784 811 842 891 971 1,060 762 784 3EP6 396 - 4PS52 - …. 420 335 G 13.0 2.8 859 888 928 987 1,086 1,184 819 859 3EP6 420 - 3PJ42 - …. 420 335 J 18.0 3.6 832 860 893 945 1,030 1,125 808 832 3EP6 420 - 4PJ52 - …. 444 353 G 13.0 2.8 908 939 981 1,043 1,148 1,252 866 908 3EP6 444 - 3PF43 - …. 444 353 J 18.0 3.6 879 909 944 999 1,089 1,189 854 879 3EP6 444 - 4PF53 - …. 468 372 G 13.0 2.8 957 990 1,034 1,100 1,210 1,320 913 957 3EP6 468 - 3PF43 - …. 468 372 J 18.0 3.6 927 958 995 1,053 1,148 1,253 900 927 3EP6 468 - 4PF53 - …. 576 462 J 18.0 3.6 1,140 1,179 1,225 1,296 1,413 1,542 1,108 1,140 3EP6 576 - 4PJ53 - …. 588 470 J 18.0 3.6 1,164 1,204 1,250 1,323 1,442 1,574 1,131 1,164 3EP6 588 - 4PJ53 - …. 3EP6 Mechanical characteristics Leakage distance Height [H] Recommended minimum clearances Between phases (ph-ph) inch Grading ring diameter [D] Cantilever strength MDCL Weight Figure inch inch To ground (ph-gnd) inch inch lbf lbs 155 51 31 34 - 3,738 338 A 155 51 31 34 - 3,738 338 A 155 51 31 34 - 3,738 339 A 155 51 50 56 - 3,738 341 A 155 51 50 56 - 3,738 344 A 177 57 50 56 - 3,328 378 A 177 57 50 56 - 3,328 378 A 229 69 50 56 - 2,776 440 A 229 69 50 56 - 2,776 442 A 249 74 59 66 - 2,598 475 A 302 86 59 66 - 2,218 542 A 302 86 68 77 31 2,218 553 B 302 86 68 77 31 2,218 593 B 302 86 68 77 31 2,218 554 B 302 86 68 77 31 2,218 595 B 355 115 68 77 31 1,661 698 C 355 115 68 77 31 1,661 741 C 406 127 76 85 39 1,511 766 C 406 127 68 77 39 1,511 810 C 604 173 97 111 47 1,108 1,093 C 551 160 97 111 47 1,195 1,058 C 604 173 109 125 47 1,108 1,101 C 604 173 97 111 47 1,108 1,133 C 686 207 109 125 59 923 974 D 686 207 109 125 59 923 1,006 D 686 207 109 125 59 923 983 D 686 207 109 125 59 923 1,017 D 906 259 109 125 83 738 1,322 D 906 259 109 125 83 738 1,322 D 3EP6 61 Figure A Figure B Line terminals NEMA flat terminal 3EP6 …-…..-.X.. (hot dip galvanized) 3EP6 …-…..-.Y.. (stainless steel) 62 3EP6 Figure C Figure D Mounting Grounded Insulated 3EP6 …-…..-…5 3EP6 …-…..-…7 Grounded Insulated 3EP6 …-…..-…6 3EP6 …-…..-…8 3EP6 63 3EQ1 Surge arrester with composite hollow core design Technical datasheet Protection of: • Transformers • Circuit breakers • Generators • Motors • Capacitors • Bushings • Switchgear Maximum values kV 115 230 Maximum duty cycle voltage kV 96 192 Maximum MCOV kV 76.8 152 Lightning impulse classifying current kA 10 10 C E kJ/kVMCOV 6.0 9.0 Single-impulse withstand rating C 1.2 2.0 Rated short-circuit current kA 40 40 High-current short-duration kA 65 65 inch-lbf 37,173 37,173 Switching surge energy rating Maximum design cantilever load (MDCL) 3EQ1 3EQ1 Highest nominal system voltage Energy class 64 3EQ1 3EQ1 – order numbers Data position 1 2 3 4 Order number 3 E Q 1 3 E Q 1 – 5 6 7 x x x x x x – 8 9 2 P 10 11 12 J 3 1 – 13 14 15 16 4 X H 5 – Z – Z Product line Silicone rubber-housed surge arrester, hollow core design Duty cycle voltage in kV Energy class, single-impulse withstand rating, switching surge energy rating Energy class C, Qs = 1.2 C, W = 6.0 kJ/kVMCOV 1 2 Energy class E, Qs = 2.0 C, W = 9.0 kJ/kVMCOV 2 3 Application Phase surge arrester P Housing size, number of units, leakage distance, height Housing »B«, 1 unit, leakage distance 82 inch, height 35 inch B 1 Housing »E«, 1 unit, leakage distance 104 inch, height 41 inch E 1 Housing »J«, 1 unit, leakage distance 133 inch, height 49 inch J 1 Housing »P«, 1 unit, leakage distance 170 inch, height 58 inch P 1 Housing »S«, 1 unit, leakage distance 193 inch, height 64 inch S 1 Housing »2xJ«, 2 units, leakage distance 267 inch, height 97 inch J 2 Housing »2xP«, 2 units, leakage distance 341 inch, height 117 inch P 2 Form of sheds and color of silicone rubber Alternating sheds, gray silicone rubber, upright mounting 4 Alternating sheds, gray silicone rubber, suspended mounting 8 High-voltage terminal NEMA 4-hole pad, 1.75”x1.75”, hot dip galvanized steel X NEMA 4-hole pad, 1.75”x1.75”, stainless steel Y Nameplate English IEEE/ANSI H Mounting ø 10.0”, 3-hole grounded 5 ø 10.0”, 3-hole insulated 7 Customized solution 9 Accessories Refer to table »Accessories for surge arresters« on page 74 3EQ1 65 Ratings and specifications Electrical characteristics Duty cycle voltage MCOV Energy class Switching Singlesurge impulse energy withstand rating rating Protective level Maximum discharge voltage Arrester order number kJ/kVmcov C 8/20µs 1.5 kA kV cr C 6.0 1.2 66.3 69.4 72.5 78.0 87.4 99.8 60.1 62.4 3EQ1 030 - 1PB21 - …. E 9.0 2.0 61.9 64.8 67.7 72.0 79.9 90.7 57.6 59.0 3EQ1 030 - 2PB31 - …. 29.0 C 6.0 1.2 79.6 83.3 87.0 93.6 105 120 72.1 74.9 3EQ1 036 - 1PB21 - …. 39 31.5 C 6.0 1.2 86.2 90.2 94.3 101 114 130 78.1 81.1 3EQ1 039 - 1PB21 - …. 45 36.5 E 9.0 2.0 92.9 97.2 102 108 120 136 86.4 88.6 3EQ1 045 - 2PB31 - …. 48 39.0 E 9.0 2.0 99.1 104 108 115 128 145 92.2 94.5 3EQ1 048 - 2PB31 - …. 54 42.0 E 9.0 2.0 111 117 122 130 144 163 104 106 3EQ1 054 - 2PB31 - …. 60 48.0 E 9.0 2.0 124 130 135 144 160 181 115 118 3EQ1 060 - 2PB31 - …. 72 57.0 E 9.0 2.0 149 156 162 173 192 218 138 142 3EQ1 072 - 2PB31 - …. 90 70.0 E 9.0 2.0 186 194 203 216 240 272 173 177 3EQ1 090 - 2PE31 - …. 96 76.0 E 9.0 2.0 198 207 217 230 256 290 184 189 3EQ1 096 - 2PE31 - …. 108 84.0 E 9.0 2.0 223 233 244 259 288 327 207 213 3EQ1 108 - 2PJ31 - …. 111 88.0 E 9.0 2.0 229 240 250 266 296 336 213 218 3EQ1 111 - 2PJ31 - …. 120 98.0 E 9.0 2.0 248 259 271 288 320 363 230 236 3EQ1 120 - 2PJ31 - …. 132 106 E 9.0 2.0 272 285 298 317 352 399 253 260 3EQ1 132 - 2PJ31 - …. 144 115 E 9.0 2.0 297 311 325 346 384 435 276 283 3EQ1 144 - 2PP31 - …. 168 131 E 9.0 2.0 347 363 379 403 448 508 323 331 3EQ1 168 - 2PP31 - …. 172 140 E 9.0 2.0 355 372 388 413 458 520 330 338 3EQ1 172 - 2PS31 - …. 180 144 E 9.0 2.0 372 389 406 432 480 544 346 354 3EQ1 180 - 2PS31 - …. 192 152 E 9.0 2.0 396 415 433 461 511 581 369 378 3EQ1 192 - 2PS31 - …. kV kV 30 24.4 30 24.4 36 8/20µs 3 kA kV cr 8/20µs 5 kA kV cr 8/20µs 10 kA kV cr 8/20µs 20 kA kV cr 8/20µs 40 kA kV cr 45/90µs 500 A kV cr 45/90µs 1 kA kV cr Line terminals NEMA flat terminal 3EQ1 …-…..-.X.. (hot dip galvanized) Figure A 66 3EQ1 3EQ1 …-…..-.Y.. (stainless steel) Mechanical characteristics Leakage distance Height [H] Recommended minimum clearances Between phases (ph-ph) inch Grading ring diameter [D] Cantilever strength MDCL Weight Figure inch inch To ground (ph-gnd) inch inch lbf lbs 82 35 6 7 - 1,067 53 A 82 35 6 7 - 1,067 54 A 82 35 8 10 - 1,067 54 A 82 35 9 11 - 1,067 54 A 82 35 9 11 - 1,067 58 A 82 35 10 12 - 1,067 58 A 82 35 12 13 - 1,067 59 A 82 35 16 18 - 1,067 60 A 82 35 16 18 - 1,067 61 A 104 41 21 24 - 912 70 A 104 41 31 34 - 912 71 A 133 49 31 34 - 765 78 A 133 49 31 34 - 765 78 A 133 49 31 34 - 765 79 A 133 49 50 56 - 765 82 A 170 58 50 56 - 636 87 A 170 58 50 56 - 636 94 A 193 64 50 56 - 577 98 A 193 64 50 56 - 577 99 A 193 64 50 56 - 577 102 A Mounting Grounded Insulated 3EQ1 …-…..-…5 3EQ1 …-…..-…7 3EQ1 67 3EQ4 Surge arrester with composite hollow core design Technical datasheet Protection of: • Transformers • Circuit breakers • Generators • Motors • Capacitors • Bushings • Switchgear Maximum values 3EQ4 3EQ4 3EQ4 3EQ4 Highest nominal system voltage kV 345 500 765 765 Maximum duty cycle voltage kV 288 444 588 588 Maximum MCOV kV 230 353 470 470 Lightning impulse classifying current kA 10 15 20 20 E G J K kJ/kVMCOV 9.0 13 18 21 Single-impulse withstand rating C 2.0 2.8 3.6 6.0 Rated short-circuit current kA 651) 651) 651) 65 High-current short-duration kA 65 65 100 100 inch-lbf 130,106 / 235,430 130,106 / 235,430 130,106 / 235,430 130,106 / 235,430 Energy class Switching surge energy rating Maximum design cantilever load (MDCL) 1) 68 Increased rated short-circuit current of 80 kA available on request 3EQ4 3EQ4 – order numbers Data position 1 2 3 4 Order number 3 E Q 4 3 E Q 4 – 5 6 7 x x x x x x – 8 9 10 11 12 4 P V 5 2 – 13 14 15 16 4 X H 5 – Z Product line Silicone rubber-housed surge arrester, hollow core design Duty cycle voltage in kV Energy class, single-impulse withstand rating, switching surge energy rating Energy class E, Qs = 2.0 C, W = 9.0 kJ/kVMCOV 2 3 Energy class G, Qs = 2.8 C, W = 13.0 kJ/kVMCOV 3 4 Energy class J, Qs = 3.6 C, W = 18.0 kJ/kVMCOV 4 5 Energy class K, Qs = 6.0 C, W = 21.0 kJ/kVMCOV 5 5 Application Phase surge arrester P Housing size, number of units, leakage distance, height Housing »D«, 1 unit, leakage distance 67 inch, height 34 inch D 1 Housing »E«, 1 unit, leakage distance 82 inch, height 38 inch E 1 Housing »H«, 1 unit, leakage distance 126 inch, height 50 inch H 1 Housing »J«, 1 unit, leakage distance 139 inch, height 54 inch J 1 Housing »K«, 1 unit, leakage distance 156 inch, height 57 inch K 1 Housing »N«, 1 unit, leakage distance 200 inch, height 69 inch N 1 Housing »P«, 1 unit, leakage distance 215 inch, height 73 inch P 1 Housing »R«, 1 unit, leakage distance 244 inch, height 81 inch R 1 Housing »R«, 1 unit, leakage distance 244 inch, height 81 inch, increased MDCL R 5 Housing »S«, 1 unit, leakage distance 259 inch, height 85 inch S 1 Housing »S«, 1 unit, leakage distance 259 inch, height 85 inch, increased MDCL S 5 Housing »V«, 1 unit, leakage distance 304 inch, height 97 inch V 1 Housing »V«, 1 unit, leakage distance 304 inch, height 97 inch, increased MDCL V 5 Housing »2xN«, 2 units, leakage distance 400 inch, height 139 inch N 2 Housing »2xN«, 2 units, leakage distance 400 inch, height 139 inch, increased MDCL N 6 Housing »2xP«, 2 units, leakage distance 430 inch, height 146 inch P 2 Housing »2xP«, 2 units, leakage distance 430 inch, height 146 inch, increased MDCL P 6 Housing »2xR«, 2 units, leakage distance 489 inch, height 162 inch R 2 Housing »2xS«, 2 units, leakage distance 519 inch, height 170 inch S 2 Housing »2xS«, 2 units, leakage distance 519 inch, height 170 inch, increased MDCL S 6 Housing »2xV«, 2 units, leakage distance 607 inch, height 194 inch V 2 Housing »2xV«, 2 units, leakage distance 607 inch, height 194 inch, increased MDCL V 6 Housing »3xP«, 3 units, leakage distance 645 inch, height 220 inch, increased MDCL P 7 Housing »3xS«, 3 units, leakage distance 778 inch, height 255 inch, increased MDCL S 7 Form of sheds and color of silicone rubber Alternating sheds, gray silicone rubber, upright mounting 4 Alternating sheds, gray silicone rubber, suspended mounting 8 High-voltage terminal NEMA 4-hole pad, 1.75”x1.75”, hot dip galvanized steel X NEMA 4-hole pad, 1.75”x1.75”, stainless steel Y Nameplate English IEEE/ANSI H Mounting ø 10.0”, 3-hole grounded (only with 12th position = 1, 2, 3) 5 ø 16.5”, 3-hole grounded (only with 12th position = 1, 2, 3) 6 ø 10.0”, 3-hole insulated (only with 12th position = 1, 2, 3) 7 ø 16.5”, 3-hole insulated (only with 12th position = 1, 2, 3) 8 ø 10.0”, 3-hole grounded, increased MDCL (only with 12th position = 5, 6, 7) 9 R4D ø 16.5”, 3-hole grounded, increased MDCL (only with 12th position = 5, 6, 7) 9 R4E ø 10.0”, 3-hole insulated, increased MDCL (only with 12th position = 5, 6, 7) 9 R4F Accessories Refer to table »Accessories for surge arresters« on page 74 – Z 3EQ4 69 Ratings and specifications Electrical characteristics Duty cycle voltage 70 MCOV kV kV 45 36.5 60 48.0 Energy class Switching Singlesurge impulse energy withstand rating rating Protective level Maximum discharge voltage 8/20µs 3 kA kV cr 8/20µs 5 kA kV cr 8/20µs 10 kA kV cr 8/20µs 20 kA kV cr Arrester order number kJ/kVmcov C 8/20µs 1.5 kA kV cr 8/20µs 40 kA kV cr 45/90µs 1 kA kV cr 45/90µs 2 kA kV cr E 9.0 2.0 92.9 97.2 102 108 120 136 88.6 92.9 3EQ4 045 - 2PD31 - …. E 9.0 2.0 124 130 135 144 160 181 118 124 3EQ4 060 - 2PE31 - …. 3EQ4 090 - 2PH31 - …. 90 70.0 E 9.0 2.0 186 194 203 216 240 272 177 186 96 76.0 E 9.0 2.0 198 207 217 230 256 290 189 198 3EQ4 096 - 2PJ31 - …. 108 84.0 E 9.0 2.0 223 233 244 259 288 327 213 223 3EQ4 108 - 2PK31 - …. 180 144 E 9.0 2.0 372 389 406 432 480 544 354 372 3EQ4 180 - 2PN31 - …. 180 144 E 9.0 2.0 372 389 406 432 480 544 354 372 3EQ4 180 - 2PV31 - …. 180 144 G 13.0 2.8 368 381 398 423 465 508 351 368 3EQ4 180 - 3PR41 - …. 228 180 E 9.0 2.0 471 492 514 547 607 689 449 471 3EQ4 228 - 2PV31 - …. 258 209 E 9.0 2.0 533 557 582 619 687 780 508 533 3EQ4 258 - 2PV31 - …. 258 209 G 13.0 2.8 527 546 570 606 667 728 503 527 3EQ4 258 - 3PV41 - …. 258 209 J 18.0 3.6 511 528 549 581 633 691 496 511 3EQ4 258 - 4PM52 - …. 276 220 E 9.0 2.0 570 596 623 662 735 835 543 570 3EQ4 276 - 2PV31 - …. 276 220 E 9.0 2.0 570 596 623 662 735 835 543 570 3EQ4 276 - 2PN32 - …. 276 220 G 13.0 2.8 564 584 610 649 713 778 538 564 3EQ4 276 - 3PN42 - …. 276 220 J 18.0 3.6 546 565 587 621 677 739 531 546 3EQ4 276 - 4PR52 - …. 288 230 E 9.0 2.0 594 622 650 691 767 871 567 594 3EQ4 288 - 2PN32 - …. 288 230 G 13.0 2.8 589 609 636 677 744 812 562 589 3EQ4 288 - 3PN42 - …. 288 230 J 18.0 3.6 570 590 612 648 706 771 554 570 3EQ4 288 - 4PV51 - …. 396 318 J 18.0 3.6 784 811 842 891 971 1,060 762 784 3EQ4 396 - 4PV52 - …. 396 318 J 18.0 3.6 784 811 842 891 971 1,060 762 784 3EQ4 396 - 4PV56 - …. 420 335 J 18.0 3.6 832 860 893 945 1,030 1,125 808 832 3EQ4 420 - 4PV52 - …. 420 335 J 18.0 3.6 832 860 893 945 1,030 1,125 808 832 3EQ4 420 - 4PV56 - …. 444 353 J 18.0 3.6 879 909 944 999 1,089 1,189 854 879 3EQ4 444 - 4PV52 - …. 444 353 J 18.0 3.6 879 909 944 999 1,089 1,189 854 879 3EQ4 444 - 4PV56 - …. 588 470 J 18.0 3.6 1,164 1,204 1,250 1,323 1,442 1,574 1,131 1,164 3EQ4 588 - 4PS57 - …. 3EQ4 Mechanical characteristics Leakage distance Height [H] Recommended minimum clearances Between phases (ph-ph) inch Grading ring diameter [D] Cantilever strength MDCL Weight Figure inch inch To ground (ph-gnd) inch inch lbf lbs 67 34 9 11 - 3,843 203 82 38 16 18 - 3,442 208 A 126 50 21 24 - 2,623 220 A 139 54 31 34 - 2,430 224 A 156 57 31 34 - 2,263 229 A 200 69 50 56 - 1,878 251 A 304 97 50 56 - 1,343 279 A 244 81 50 56 - 1,604 287 A 304 97 59 66 - 1,343 290 A 304 97 68 77 - 1,343 297 A 304 97 68 77 - 1,343 319 A 371 131 59 66 39 995 472 B 304 97 68 77 - 1,343 302 A 400 139 68 77 39 939 441 B 400 139 68 77 39 939 466 B 489 162 68 77 47 802 506 B 400 139 76 85 39 939 443 B 400 139 68 77 39 939 469 B 304 97 68 77 - 1,343 346 A 607 194 97 111 59 672 580 B 607 194 97 111 59 1,215 580 B 607 194 97 111 59 672 588 B 607 194 97 111 59 1,215 588 B 607 194 109 125 59 672 596 B 607 194 109 125 59 1,215 596 B 778 255 109 125 83 923 785 C A 3EQ4 71 Figure A Figure B Line terminals NEMA flat terminal 3EQ4 …-…..-.X.. (hot dip galvanized) 3EQ4 …-…..-.Y.. (stainless steel) 72 3EQ4 Figure C Mounting Grounded Insulated 3EQ4 …-…..-…5 3EQ4 …-…..-…7 Grounded Insulated 3EQ4 …-…..-…6 3EQ4 …-…..-…8 3EQ4 73 Accessories for surge arresters Siemens surge arresters can optionally be equipped with one or more accessories, listed in the table below. The selected code for the accessory should be added to the order number of the surge arrester. Example: 3EL2 096-2PJ31-4XH5-Z D91 D92. Accessories Code Earth terminal, copper tin-plated D51 DIN/NEMA earth terminal D71 Adapter DIN/NEMA to double DIN flat terminal, including 2 line clamps D81 Adapter DIN/NEMA to double NEMA flat terminal, including 2 line clamps D82 Line clamp D91 Eyebolt earth terminal D92 NEMA earth terminal, stainless steel D93 NEMA earth terminal, copper D94 Palm earth terminal, aluminum D95 Earth terminal, 2x D14, stainless steel D96 N2 filling K02 Yellow cover panels for gas diverter K14 Increased rated short-circuit current of 80 kA K80 3EL5 3EL1 3EL2 3EL3 3EP5 3EP4 3EP6 3EQ1 3EQ4 Optional accessories Monitoring devices for surge arresters Surge arresters are highly reliable components in power transmission and distribution systems. When operated in accordance with their specifications, their service life can span as much as 30 years without any maintenance. Nevertheless, overloads may sometimes occur that can cause arrester failure and even endanger the safety of the network. Monitors assist in the early detection of relevant changes and support security of supply on a whole new level. Siemens offers a complete line of monitoring devices with a variety of innovative functionalities that can be perfectly matched to the customer’s requirements, ensuring that impending faults will be detected as early as possible and before the security of supply is compromised. 74 Based on solid experience Siemens has over 90 years of experience with surge arresters – a solid foundation on which to build a comprehensive range of monitors that are precisely tailored to today’s surge arrester technology. Siemens’ line of surge arrester monitors ranges from simple counters and condition indicators to periodic analytic condition monitoring and a future live condition monitoring system. All monitors provide the requisite information on surge arrester responses and the arrester’s condition – perfectly matched to the respective voltage level, network situation, and customer requirements. Surge counter Order number: 3EX5 030-0 Surge counter with auxiliary contact Order number: 3EX5 030-1 Surge counter with leakage current meter (0–30 mA) Order number: 3EX5 050-0 Surge counter Surge counter with leakage current meter Surge counter with leakage current meter (0–30 mA) with auxiliary contact Order number: 3EX5 050-1 Surge counter with leakage current meter (0–50 mA) Order number: 3EX5 050-2 Arrester Condition Monitor (ACM) basic Order number: 3EX5 080-0 Arrester Condition Monitor (ACM) advanced Order number: 3EX5 080-1 Order number: 3EX5 086 (USB wireless module) ACM basic ACM advanced Upgrade from ACM basic to ACM advanced Order number: 3EX5 081 Sensor Order number: 3EX5 060-1 Display Order number: 3EX5 062-1 < 200m Sensor Display Connecting lead (required for operation) Length 3 m. Order number: 3EX5 963-0D Length 6 m. Order number: 3EX5 963-0G Length 10 m. Order number: 3EX5 963-1A Length 12 m. Order number: 3EX5 963-1C Length 14 m. Order number: 3EX5 963-1E Length 16 m. Order number: 3EX5 963-1G Length 18 m. Order number: 3EX5 963-1J Length 20 m. Order number: 3EX5 963-2A Length 22 m. Order number: 3EX5 963-2C Length 24 m. Order number: 3EX5 963-2E Length 26 m. Order number: 3EX5 963-2G Length 28 m. Order number: 3EX5 963-2J Length 30 m. Order number: 3EX5 963-3A Mounting bracket for surge counter Order number: 3EX5 930 Connection cable for monitors Order number: 3EX5 952 Earth lead Order number: 3EX5 955 Monitoring devices Please refer to our monitoring brochure for more information. 75 Published by Siemens AG 2015 Energy Management Freyeslebenstrasse 1 91058 Erlangen, Germany Please contact us at: Phone: +49 30 386 33 222 Fax: +49 30 386 26 721 E-mail: [email protected] Article No. E50001-F630-A254-X-4A00 Printed in Germany fb 6514 WÜ WS 01151.0 Subject to change without prior notice. The information in this document contains general descriptions of the technical options available, which may not apply in all cases. The required technical options should therefore be specified in the contract.