Littelfuse ProtectionRelays D0920 Manual

Arc-Detection Unit
D0920
D0920
ARC-DETECTION UNIT
REVISION 0-C-031115
2
4
6
8
1
3
5
7
LITTELFUSE SELCO
POWER
ACTIVE
D0920
MIN.
ARC DETECTION UNIT
MAX.
TEST
TRIP
SENSOR
ADJUST
9
11
13
15
10
12
14
16
Document Number: PM-1410-EN
www.littelfuse.com
• © 2015 Littelfuse •
• 1/18
D0920 Arc-Detection Unit
Rev. 0-C-031115
This page intentionally left blank.
www.littelfuse.com
• © 2015 Littelfuse •
• 2/18
D0920 Arc-Detection Unit
Rev. 0-C-031115
TABLE OF CONTENTS
1 INTRODUCTION ............................................................................................................. 5
1.1
General....................................................................................................................... 5
1.2
A0220 Point Sensor ................................................................................................... 5
2 OPERATION ................................................................................................................... 6
2.1
Front-Panel Controls .................................................................................................. 6
2.1.1 Sensor Adjust......................................................................................................... 6
2.1.2 ACTIVE and TEST Mode ....................................................................................... 6
2.2
Front-Panel Indication ................................................................................................ 6
2.2.1 Power ..................................................................................................................... 6
2.2.2 Trip ......................................................................................................................... 6
2.3
Auxiliary Relays ......................................................................................................... 6
2.3.1 Trip Indication ........................................................................................................ 6
2.3.2 Remote Signalling .................................................................................................. 6
3 INSTALLATION ............................................................................................................... 9
3.1
D0920 Arc-Detection Unit .......................................................................................... 9
3.2
A0220 Point Sensor ................................................................................................... 9
4 TECHNICAL SPECIFICATIONS ................................................................................... 12
4.1
D0920 ....................................................................................................................... 12
4.2
A0220 Point Sensor ................................................................................................. 14
5. ORDERING INFORMATION ......................................................................................... 15
6. WARRANTY .................................................................................................................. 15
7. PERFORMANCE TEST ................................................................................................ 15
APPENDIX A D0920 REVISION HISTORY ....................................................................... 17
LIST OF FIGURES
1
2
3
4
5
6
7
D0920 Arc Detection Unit .............................................................................................. 5
A0220 Point Sensor ....................................................................................................... 5
D0920 Outline and Mounting Details ............................................................................. 7
D0920 Typical Wiring Diagram ...................................................................................... 8
A0220 Outline and Connections .................................................................................. 10
A0220 Mounting Details ............................................................................................... 11
A0220 Detection Range for a 3 kA Fault ..................................................................... 11
LIST OF TABLES
1
Test Record .................................................................................................................. 16
www.littelfuse.com
• © 2015 Littelfuse •
• 3/18
D0920 Arc-Detection Unit
Rev. 0-C-031115
This page intentionally left blank.
www.littelfuse.com
• © 2015 Littelfuse •
• 4/18
D0920 Arc-Detection Unit
1
Rev. 0-C-031115
INTRODUCTION
1.1 General
The D0920 Arc Detection Unit is a high-speed arc-detection device for electrical power-distribution
systems. The D0920 requires a 230 Vac supply and supports up to three point sensors (A0220)
mounted in a switchboard.
On the occurrence of an arc fault, the D0920 detects the fault and pulses the trip output in less
than 1 ms. The fast trip time reduces the risk of personal injury and equipment damage.
The D0920 is typically supplied from the switchboard main power. The AC voltage may fail when
an arc fault develops. The D0920 uses energy stored in an internal capacitor to trip the circuit
breaker. The storage capacitor is an extremely long-life electrolytic capacitor with a specified life
time of more than 30 years at an ambient temperature of 50°C (121°F). The trip energy stored is
sufficient for circuit breakers with a 220/250 Vdc shunt trip coil.
The D0920 has one output indication relay with an isolated normally-open contact, and one output
indication relay with an isolated normally-closed contact. Additional features include power and
trip indication, test mode, and sensitivity adjustment.
NOTE: Dangerous voltage is present at the storage capacitor (terminals 4, 7, and 8) even after the
relay has been disconnected from the supply voltage. The capacitor has a self-discharge circuit
which will discharge it to a safe voltage level within two minutes after disconnection from the
supply voltage.
1.2 A0220 Point Sensor
The A0220 point sensor is a photoelectric sensor with a sensitivity range of 180 degrees. It has a
transparent polycarbonate enclosure that is IP65 rated. Each point sensor includes 10 m (33 ft) of
shielded 2-wire, 24 AWG (0.2 mm2) cable. The cable length can be extended to a maximum of
50 m (164 ft), however use shielded 2-wire, 20 AWG (0.5 mm2) cable.
FIGURE 1. D0920 Arc Detection Unit.
www.littelfuse.com
FIGURE 2. A0220 Point Sensor.
• © 2015 Littelfuse •
• 5/18
D0920 Arc-Detection Unit
2.
Rev. 0-C-031115
OPERATION
2.1 Front-Panel Controls
2.1.1 Sensor Adjust
The D0920 sensitivity default is 6 mA of sensor output current to cause a trip. This is equivalent to
a light intensity of 12,000 lux on a single sensor or 6,000 lux on each of two sensors. This means
that the total light intensity on all sensors installed has to exceed 12,000 lux to cause a trip.
The sensitivity is adjustable from 1 to 12 mA (2,000 to 24,000 lux) using the SENSOR ADJUST
dial.
2.1.2 ACTIVE and TEST Mode
The D0920 has a two-position key switch, marked ACTIVE and TEST.
In the ACTIVE mode, the D0920 is configured for normal operation and will trip the circuit breaker
if an arc flash occurs. In ACTIVE mode, the relay K2 contact (terminals 11 and 12) will be open
unless supply voltage is removed. Ensure that the D0920 is normally set to the ACTIVE mode.
The key can only be removed in this position.
In the TEST mode, the D0920 and any connected point sensors can be tested without tripping the
circuit breaker. In TEST mode, relay K2 will be closed. See Fig. 4.
2.2 Front-Panel Indication
2.2.1 Power
The green LED labelled POWER indicates the presence of supply voltage.
2.2.2 Trip
An electromagnetic circuit breaker with red TRIP indicator is used in the D0920. During normal
operation the red TRIP indicator is nearly flush with the front plate surface. After a trip, the red
TRIP indicator will extend to 6 mm, the D0920 will switch off (order option D0920.0010) and the
green POWER LED will be off. For order option D0920.0020, the D0920 will remain on after a trip.
Reset the D0920 by pushing the red TRIP indicator until it latches magnetically. The green
POWER LED should also light. External circuit breakers or other devices will have to be reset
manually.
2.3 Auxiliary Relays
2.3.1 Trip Indication
The D0920 has one normally-open contact (K1, terminals 9 and 10) that closes during a trip. It can
be used for trip indication.
2.3.2 Remote Signalling
The D0920 has one normally-closed contact (K2, terminals 11 and 12) that closes during loss of
supply, or when the D0920 is in the TEST mode. It can be used for remote signalling.
www.littelfuse.com
• © 2015 Littelfuse •
• 6/18
D0920 Arc-Detection Unit
59.8
(2.35)
58.3
(2.30)
105.0
(4.13)
2
90.0
(3.54)
1
4
6
8
3
5
7
LITTELFUSE SELCO
D0920
MIN.
ARC DETECTION UNIT
MAX.
Rev. 0-C-031115
POWER
ACTIVE
TEST
TRIP
SENSOR
ADJUST
9
11
13
15
10
12
14
16
FRONT
SIDE
NOTE:
62.0
(2.44)
1. DIMENSIONS IN MILLIMETRES (INCHES).
BOTTOM
FIGURE 3. D0920 Outline and Mounting Details.
www.littelfuse.com
• © 2015 Littelfuse •
• 7/18
D0920 Arc-Detection Unit
A
B
C
Rev. 0-C-031115
POINT
SENSORS
5
6
L1 L2/N
NOTE 1
NOTE 1
1
2
SENSOR
SHIELD
GREEN
RED
230 VAC
3
SHIELD
9
4 EXTERNAL
TRIP
7
K1
NOTE 2
TRIP COIL
(+)
11
K2
NOTE 3
TRIP
COIL
NOTE 1
8
10
12
TRIP
INDICATION
TEST AND
LOSS OF
SUPPLY
TRIP COIL/
NEUTRAL
D0920
NOTES:
1. CAUTION: DANGEROUS VOLTAGE IS PRESENT AT TERMINALS 4,7, AND 8, SOURCED FROM AN INTERNAL STORAGE CAPACITOR. A SELFDISCHARGE CIRCUIT WILL DISCHARGE THE STORAGE CAPACITOR TO A SAFE LEVEL WITHIN TWO MINUTES AFTER THE AC SUPPLY HAS
BEEN DISCONNECTED.
2. RELAY CONTACT IS SHOWN DE-ENERGIZED.
3. RELAY CONTACT IS CLOSED WHEN TEST MODE IS SELECTED, OR DURING LOSS OF SUPPLY.
FIGURE 4. D0920 Typical Wiring Diagram.
www.littelfuse.com
• © 2015 Littelfuse •
• 8/18
D0920 Arc-Detection Unit
3
Rev. 0-C-031115
INSTALLATION
3.1 D0920 Arc-Detection Unit
Outline and connection details are shown in Fig. 3. The D0920 can be DIN-rail mounted only. A
typical wiring diagram is shown in Fig. 4.
Connect supply voltage to terminals 5 (L1) and 6 (L2/N). The nominal supply voltage is 230 Vac.
Connect the 230/250 Vdc trip coil from a circuit breaker to terminals 7 (TRIP COIL +) and 8 (TRIP
COIL NEUTRAL). The trip coil output is not isolated from the 230 Vac supply input. To initiate an
external trip, install a normally-open momentary (250-Vac-rated) switch between terminals 4
(EXTERNAL TRIP) and 7 (TRIP COIL +). Limit the time the switch is closed to one second.
Do not install modules or sensors which have been damaged in transport.
NOTE: Dangerous voltage is present at the storage capacitor (terminals 4, 7, and 8) even after the
relay has been disconnected from the supply voltage. The capacitor has a self-discharge circuit
which will discharge it to a safe voltage level within two minutes after disconnection from the
supply voltage.
3.2 A0220 Point Sensor
Outline and connection details are shown in Fig. 5. Connect the red wire to terminal 1, the green
wire to terminal 2, and the shield to terminal 3. If more than one sensor is connected, do not mix
wire colors. Each sensor has an adhesive-backed drill template for surface-mount installation.
Place the drill template where the sensor is to be mounted. See Fig. 6.
www.littelfuse.com
• © 2015 Littelfuse •
• 9/18
D0920 Arc-Detection Unit
45.8
(1.80)
60.0
(2.36)
Rev. 0-C-031115
18.6
(0.73)
SHIELD
8.7
(0.34)
4.1 Ø6.0(0.24)
(0.16) MOUNTING HOLES
2 LOCATIONS
GREEN
14.6
(0.56)
Ø4.3(0.17)
MOUNTING HOLES
2 LOCATIONS
11.7
(0.46)
2
1
4
6
8
3
5
7
LITTELFUSE SELCO
POWER
ACTIVE
D0920
MIN.
ARC DETECTION UNIT
MAX.
TEST
TRIP
SENSOR
ADJUST
45.8
(1.80)
4.5
(0.18)
8.7
(0.34)
4.1
(0.16)
RED
SIDE VIEW
9
11
13
15
10
12
14
16
32.0
(1.26)
NOTE:
1. DIMENSIONS IN MILLIMETRES (INCHES).
FRONT VIEW
TERMINAL
FUNCTION
COLOR
1
SENSOR (+)
RED
2
SENSOR (-)
GREEN
3
SHIELD
COPPER / BLACK HEATSHRINK
FIGURE 5. A0220 Outline and Connections.
www.littelfuse.com
• © 2015 Littelfuse •
• 10/18
D0920 Arc-Detection Unit
Rev. 0-C-031115
A0220
DRILL TEMPLATE
M4 x 0.7 (8-32)
M4 x 0.7 (8-32)
M5 x 0.8 (10-32)
M5 x 0.8 (10-32)
Ø9(0.354)
DRILL TEMPLATE
NOTES AND INSTALLATION:
1. ALL DIMENSIONS IN MILLIMETERS (INCHES).
2. AFFIX THE DRILL TEMPLATE WHERE THE SENSOR IS TO BE
MOUNTED.
FIGURE 6. A0220 Mounting Details.
3 kA
3 kA
FIGURE 7. A0220 Detection Range for a 3 kA Fault.
www.littelfuse.com
• © 2015 Littelfuse •
• 11/18
D0920 Arc-Detection Unit
4
Rev. 0-C-031115
TECHNICAL SPECIFICATIONS
4.1 D0920
Supply:
230 Vac (+15, -30%), 50/60 Hz
Sensor Sensitivity:
1 to 12 mA (2 to 24 klux)
Maximum Number of Sensors:
2
Nominal Trip Energy:
3.5 Ws (Joule) at 325 Vdc, 68 µF capacitance
Trip Level Accuracy:
5%
Trip Time:
1 ms maximum
External Trip:
Active when Terminals 4 and 7 connected, limit to 1 s
(exceeding the 1 s time limit may damage the trip coil or
the D0920)
Output Relays:
Trip Coil:
Contact Configuration:
Normally Open
Voltage:
325 Vdc Peak at 230 Vac supply
Nominal Energy:
3.5 Ws (Joule) at 325 Vdc, 68 µF capacitance
Mode:
Close on Trip
Terminals:
7, 8
Relay K1:
Contact Configuration:
Form A, Normally Open
Mode:
Close on Trip
Rating:
120 Vac, 5 A
Terminals:
9, 10
Relay K2:
Contact Configuration:
Form B, Normally Closed
Mode:
Close on Loss of Supply or Test Mode
UL Rating:
150 Vac, 0.46 A, 65 Vdc, 0.46 A
Terminals:
11, 12
Unused Terminals:
13-16
Dimensions:
Height:
90 mm (3.5”)
Width:
105 mm (4.1”)
Depth:
Without Key:
60 mm (2.4”)
With Key:
77 mm (3.0”)
www.littelfuse.com
• © 2015 Littelfuse •
• 12/18
D0920 Arc-Detection Unit
Rev. 0-C-031115
Environment:
Operating Temperature:
-25 to 70°C (-13°F to 158°F)
Storage Temperature:
-25 to 70°C (-13°F to 158°F)
Humidity:
93% Non-Condensing
EMC Tests:
Verification tested in accordance with EN60255-26:2009.
1 MHz Burst:
IEC 60255-22-1
± 1 kV differential mode
(line-to-line)
± 2.5 kV common mode
Electrostatic Discharge:
IEC 60255-22-2
± 6 kV Contact Discharge
(direct and indirect)
± 8 kV Air Discharge
Radiated RF Immunity:
IEC 60255-22-3
10 V/m, 80-1,000 MHz,
80% AM (1 kHz)
10 V/m, 1.4 to 2.7 GHz,
80% AM (1 kHz)
Fast Transient:
IEC 60255-22-4
Class A: ± 4 kV
(on AC mains and I/O lines)
Surge Immunity:
IEC 60255-22-5
± 1 kV differential mode
(on AC lines)
± 2 kV common mode
(on AC lines)
± 1 kV differential mode
(on I/O ports)
Conducted RF Immunity:
IEC 60255-22-6
10 Vrms, 0.15-80 MHz,
80% AM (1 kHz)
Power Frequency:
IEC 60255-22-7
Class A – 150 V Differential
Class A – 300 V Common Mode
www.littelfuse.com
• © 2015 Littelfuse •
• 13/18
D0920 Arc-Detection Unit
Magnetic Field Immunity:
Rev. 0-C-031115
IEC 61000-4-8
50 Hz and 60 Hz
30 A/m and 300 A/m
Current Harmonics and Voltage
Fluctuations:
IEC 61000-3-2
and IEC 61000-3-3
Class A
Radiated and Conducted
Emissions:
CISPR 22:2008-09 / EN 55022:2010
Class B
Voltage Interruptions:
IEC 60255-11 and IEC 60255-29
Interrupts 30%, 25 Cycles x 3
Interrupts 60%, 10 Cycles x 3
Interrupts 100%, 250 Cycles x 3
Certification:
CE, European Union
EMC standards: EN60255-26
IEC 61010-1:2010 (3rd Edition)
Safety Requirements for Electrical Equipment
for Measurement, Control, and Laboratory
Use – Part I
4.2 A0220 Point Sensor
Sensor Type:
Photo electric
Sensitivity:
0.5 mA / klux
Sensitivity Range:
2 to 30 klux
Sensitivity Area:
180 degrees, see Fig. 7
Cable Type:
Shielded 2-wire, 24 AWG (0.2 mm2)
Cable Length:
10 m (33 ft) included, 50 m (164 ft) maximum, use
shielded 2-wire 20 AWG (0.5 mm2) when extending
length
IP Rating:
IP65
Operating Temperature:
-25 to 70°C (-13°F to 158°F)
Storage Temperature:
-25 to 70°C (-13°F to 158°F)
www.littelfuse.com
• © 2015 Littelfuse •
• 14/18
D0920 Arc-Detection Unit
5
Rev. 0-C-031115
ORDERING INFORMATION
D0920.
0010
0020
Arc-Detection Unit
Arc-Detection Unit, remains powered after trip
Accessories:
6
A0033.0010
Point Sensor Cable, shielded 2-wire, 24 AWG (0.2 mm2), 100 m (328 ft)
A0220.0010
Point Sensor, includes 10 m (33 ft) cable
A0220.0020
Point Sensor, includes 15 m (49 ft) cable
PGA-1100
Diode Logic Unit
WARRANTY
The D0920 Arc-Detection Unit is warranted to be free from defects in material and workmanship
for a period of 5 years from the date of purchase.
Littelfuse will (at Littelfuse’s option) repair, replace, or refund the original purchase price of a
D0920 that is determined by Littelfuse to be defective if it is returned to the factory, freight prepaid,
within the warranty period. This warranty does not apply to repairs required as a result of misuse,
negligence, an accident, improper installation, tampering, or insufficient care. Littelfuse does not
warrant products repaired or modified by non-Littelfuse personnel.
7
PERFORMANCE TEST
Testing of a completed installation can be done with a 100W light bulb or a photo flash. Use an
incandescent lamp as this has light and heat radiation (infrared) that closely matches the sensitivity
characteristic of the point sensor. The point sensor has its maximum sensitivity at a wave length of
850 nm which is in the infrared (invisible) range. In the middle of the visible region of 550 nm the
sensitivity is down to approximately 50%. This means that both light and heat radiation from an
arc contribute to the point sensor current that triggers the D0920.
If a photo flash unit is used it is essential that it is set to the ’MANUAL’ mode. If it is used in
’AUTO’ mode, the light emission will be dependent on random reflections and will change with the
position from which it is fired.
A test-record form is provided for recording the date and the final results of the performance tests.
The following system tests are to be conducted by qualified personnel:
a) Switch on the supply voltage to the D0920. Press the red TRIP indicator until it latches and the
green POWER LED remains on.
b) Turn the key switch to the TEST position. This will allow testing of the D0920 and point sensors
without tripping the circuit breaker. Relay K2 (terminals 11 and 12) will be closed when the D0920
is in test mode. The key cannot be removed in this mode.
c) Trip the D0920 by moving a light source close to a point sensor. When a trip occurs, the red
TRIP indicator will extend to 6 mm, the AC supply will be removed to the D0920, and the green
POWER LED will be off. Relay K1 (terminals 9 and 10) will be closed when the D0920 has
tripped.
www.littelfuse.com
• © 2015 Littelfuse •
• 15/18
D0920 Arc-Detection Unit
Rev. 0-C-031115
d) Press the red trip indicator until it latches and the green POWER LED remains on. Relay K1
(terminals 9 and 10) will open.
e) Repeat steps c) and d) for each installed point sensor.
f) Turn the key switch to the ACTIVE position and close the external circuit breaker.
g) Repeat step c). The circuit breaker will trip, and K1 (terminals 9 and 10) will be closed.
h) Repeat step d) and remove the key.
i) Record the date and the results of the test on the attached test-record form.
TABLE 1. TEST RECORD
DATE
TEST RESULTS
Retain this record for the authority having jurisdiction.
www.littelfuse.com
• © 2015 Littelfuse •
• 16/18
D0920 Arc-Detection Unit
Rev. 0-C-031115
APPENDIX A
D0920 REVISION HISTORY
MANUAL RELEASE
DATE
March 11, 2015
January 10, 2014
October 21, 2013
MANUAL REVISION
HARDWARE REVISION
(REVISION NUMBER ON PRODUCT LABEL)
0-C-031115
0-B-011014
0-A-102113
02
MANUAL REVISION HISTORY
Revision 0-C-031115
Section 4
K1 rating updated.
Appendix A
Revision history updated.
Revision 0-B-011014
Section 4
Supply voltage and output relay specifications updated.
Appendix A
Revision history updated.
Revision 0-A-102113
Initial release.
HARDWARE REVISION HISTORY
Hardware Revision 02
Changed transformer and transorb values.
www.littelfuse.com
• © 2015 Littelfuse •
• 17/18
D0920 Arc-Detection Unit
Rev. 0-C-031115
This page intentionally left blank.
www.littelfuse.com
• © 2015 Littelfuse •
• 18/18