OMRON K8AB-PW1

Three-phase Voltage Relay
K8AB-PW
CSM_K8AB-PW_DS_E_2_1
Ideal for monitoring 3-phase power supplies
for industrial facilities and equipment.
• Monitor overvoltages and undervoltages for three-phase 3-wire
or 4-wire power supplies.
DIP switch setting for 3-phase 3-wire or 3-phase 4-wire power
supply.
• Two SPDT output relays, 6 A at 250 VAC (resistive load).
Separate outputs possible for overvoltages and undervoltages.
• World-wide power specifications supported by one Unit
(switchable using DIP switch).
• Relay status can be monitored using LED indicator.
Refer to Safety Precautions for the K8AB
Series. Refer to page 9 for the Q&A section.
Model Number Structure
■ Model Number Legend
K8AB-@@
1
2 3
1. Basic Model
K8AB: Measuring and Monitoring Relays
2. Functions
PW: Three-phase Voltage Relay (Simultaneous upper and lower monitoring)
3. Rated Input Voltage
1:
115, 127, 133, 138, 200, 220, 230, 240 VAC
2:
220, 230, 240, 277, 380, 400, 415, 480 VAC
1
K8AB-PW
Ordering Information
■ List of Models
Three-phase Voltage Relay
Rated input (See note 2.)
3-phase 3-wire mode
200, 220, 230, 240 VAC
3-phase 4-wire mode
115, 127, 133, 138 VAC
3-phase 3-wire mode
380, 400, 415, 480 VAC
3-phase 4-wire mode
220, 230, 240, 277 VAC
Model
K8AB-PW1
K8AB-PW2
Note: 1. Three-phase, three-wire or four-wire and the input range are switched using a DIP switch.
2. The power supply voltage is the same as the rated input voltage.
2
K8AB-PW
Ratings and Specifications
■ Ratings
Rated input
voltage
K8AB-PW1
Three-phase, three-wire Mode: 200, 220, 230 and 240 VAC
Three-phase, four-wire Mode: 115, 127, 133 and 138 VAC
K8AB-PW2
Three-phase, three-wire Mode: 380, 400, 415 and 480 VAC
Three-phase, four-wire Mode: 220, 230, 240 and 277 VAC
Input load
K8AB-PW1: 25 VA max.
K8AB-PW2: 45 VA max.
Operating value setting range (OVER, UNDER)
Overvoltage
−30% to 25% of rated input voltage
Undervoltage
−30% to 25% of rated input voltage
Note: The rated input voltage can be switched using the DIP switch.
Operating value
100% operation at set value
Reset value
5% of operating value (fixed)
Reset method
Automatic reset
Operating time setting range (T)
Overvoltage and undervoltage: 0.1 to 30 s
Startup lock time (LOCK)
1 s or 5 s (Switched using DIP switch.)
Indicators
Power (PWR): Green, Relay output (RY): Yellow, OVER/UNDER: Red
Output relays
Two SPDT relays (NC operation)
Output relay ratings
Rated load
Resistive load
6 A at 250 VAC (cosφ = 1)
6 A at 30 VDC (L/R = 0 ms)
Inductive load
1 A at 250 VAC (cosφ = 0.4)
1 A at 30 VDC (L/R = 7 ms)
Maximum contact voltage:
250 VAC
Maximum contact current:
6 A AC
Maximum switching capacity: 1,500 VA
Minimum load:
10 mA at 5 VDC
Mechanical life:
10,000,000 operations
Electrical life:
Make: 50,000 times, Break: 30,000 times
Ambient operating temperature
−20 to 60°C (with no condensation or icing)
Storage temperature
−40 to 70°C (with no condensation or icing)
Ambient operating humidity
25% to 85% (with no condensation)
Storage humidity
25% to 85% (with no condensation)
Altitude
2,000 m max.
Terminal screw tightening torque
0.49 N·m
Terminal wiring method
Recommended wire
Solid wire:
2.5 mm2
Twisted wires: AWG16, AWG18
Note: 1. Ferrules with insulating sleeves must be used with twisted wires.
2. Two wires can be twisted together.
Recommended ferrules
Al 1,5-8BK (for AWG16) manufactured by Phoenix Contact
Al 1-8RD (for AWG18) manufactured by Phoenix Contact
Al 0,75-8GY (for AWG18) manufactured by Phoenix Contact
Case color
Munsell 5Y8/1
Case material
ABS resin (self-extinguishing resin) UL94-V0
Weight
Approx. 130 g
Mounting
Mounted to DIN Track or via M4 screws (tightening torque: 1.2 N·m)
Dimensions
22.5 (W) × 90 (H) × 100 (D) mm
3
K8AB-PW
■ Specifications
Input frequency range
45 to 65 Hz
Overload capacity
Continuous input: 115% of maximum input, 10 s max.: 125% of maximum input
Setting error
Operating value
Set value ±10% of rated input voltage
Operating time
Repeat error
Startup lock time
Set value ±0.5 s
Operating value
Operating value ±2%
Error calculation: Error = ((Maximum operating value − Minimum operating value (over 10 operations))/2)/
Average value × 100%
Reset value
Overvoltage:
Operating value x 95% ±2%
Undervoltage:
Operating value x 105% ±2%
Error calculation: Error = ((Maximum reset value − Minimum reset value (over 10 resets))/2)/
Average value × 100%
Operating time
Operating time repeat error: ±50 ms
Overvoltage:
Measured when input suddenly changes from 70% to 120% of setting.
Undervoltage:
Measured when input suddenly changes from 120% to 70% of setting.
The input voltage, however, must be between 70% and 125% of rating.
Startup lock time
Startup lock time repeat error: ±0.5 s
(The operating time when the operating time is set to the minimum value and the power supply suddenly
changes from 0% to 100%.)
Temperature influence
Operating value
Drift based on measured value at standard temperature:
−20°C to standard temperature: ±1,000 ppm/°C max.
Standard temperature to 60°C : ±1,000 ppm/°C max.
(Humidity: 25% to 80%)
Operating time
Fluctuation based on measured value at standard temperature:
−20°C to standard temperature: ±10% max.
Standard temperature to 60°C : ±10% max.
(Humidity: 25% to 80%)
Humidity influence
Operating value
Based on ambient humidity of 65%
25% to 80%: ±5% max.
Operating time
Based on ambient room humidity
25% to 80%: ±10% max.
Influence of input frequency
At 45 to 65 Hz
Operating value ±5%
Operating time ±10%
Note: The error in the operating value and operating time under standard conditions.
Applicable
standards
Conforming standards
EN60255-5 and EN60255-6
Installation environment (Pollution Degree 2, Overvoltage Category III)
EMC
EN61326
Safety standards
UL508
Insulation resistance
20 MΩ min.
Between external terminals and case
Between input terminals and output 1 terminals
Between input terminals and output 2 terminals
Between output 1 terminals and output 2 terminals
Dielectric strength
2,000 VAC for one minute
Between external terminals and case
Between input terminals and output 1 terminals
Between input terminals and output 2 terminals
Between output 1 terminals and output 2 terminals
Noise immunity
1,500 V power supply terminal common/normal mode
Square-wave noise of ±1 µs/100 ns pulse width with 1-ns rise time
Vibration resistance
Frequency 10 to 55 Hz, 0.35-mm single amplitude, acceleration 50 m/s2
10 sweeps of 5 min each in X, Y, and Z directions
Shock resistance
100 m/s2, 3 times each in 6 directions along three axes (up/down, left/right, forward/backward)
Degree of protection
Terminal section: Finger protection
Note: The reset value is valid only for automatic resets.
4
K8AB-PW
Connections
■ Wiring Diagram
Overvoltage and Undervoltage Operation Diagram
Overvoltage
setting value
N L1 L2 L3
Hysteresis: Fixed at 5%
L1
Input L2
L3
Hysteresis: Fixed at 5%
Voltage input
Undervoltage setting value
Flashing
Overvoltage alarm indicator
Flashing
Undervoltage alarm indicator
Lit
T
Lit
L2
T: Operating time (0.1 to 30 s)
L3
Overvoltage relay
14
Signal output
12
Undervoltage relay
T
L1
T: Operating time (0.1 to 30 s)
T1: Power ON lock (1 s or 5 s)
N
11
Overvoltage
alarm
T1
Note: 1. K8AB-PW output relay is normally operative.
2. The power ON lock function prevents unnecessary alarms from
being generated during the unstable period when the power is first
turned ON. There is no relay output during timer operation.
3. L1 and L2 use the same power supply and will not operate due to an
undervoltage if they drop below the rated input of 60%.
24
Signal output
22
21
Undervoltage
alarm
Load
5
K8AB-PW
Nomenclature
■ Front
Indicators
Item
Terminal block
(See notes 1 and 2.)
Overvoltage knob (OVER)
Power indicator
Relay status indicator
Alarm indicator
Undervoltage knob (UNDER)
Operating time knob (T)
Meaning
Power indicator
(PWR: Green)
Lit when power is being supplied (see note).
Relay status indicator
(RY: Yellow)
Lit when relay is operating (normally lit).
Alarm
indicator
(ALM:
Red)
Lit when there is an overvoltage.
The indicator flashes to indicate the error status
after the overvoltage has exceeded the threshold
value while the operating time is being clocked.
Overvoltage:
Red
Undervoltage: Lit when there is an undervoltage or phase loss.
Red
The indicator flashes to indicate the error status
after the undervoltage has exceeded the threshold
value while the operating time is being clocked.
Note: The input across L1 and L2 is used for the internal power
supply. Therefore, the power indicator will not be lit if there is no
input across L1 and L2.
Terminal block
(See notes 1 and 2.)
Setting Knobs
Item
Usage
Overvoltage knob (OVER) Can be set between −30% and 25% of the rated
input.
Undervoltage knob
(UNDER)
Can be set between −30% and 25% of the rated
input.
Operating time knob (T)
Used to set the operating time to 0.1 to 30 s.
Note: 1. Use either a solid wire of 2.5 mm2 maximum or a ferrule with
insulating sleeve for the terminal connection.
The length of the exposed current-carrying part inserted
into the terminal must be 8 mm or less to maintain dielectric
strength after connection.
For 2.5 mm2 or
smaller solid wires
8 mm max.
For ferrules with
insulating sleeves
8 mm max.
Recommended ferrules
Phoenix Contact
• Al 1,5-8BK (for AWG16)
• Al 1-8RD (for AWG18)
• Al 0,75-8GY (for AWG18)
2. Tightening torque
Recommended: 0.49 N·m
Maximum:
0.54 N·m
6
K8AB-PW
■ Operation and Setting Methods
Connections
1. Input
Connect to L1, L2, and L3 (for three-phase three-wire mode) or L1, L2, L3, and N (for three-phase fourwire mode), depending on the mode selected using pin 2 on the DIP switch.
The Unit will not operate correctly if the DIP switch setting and the wiring do not agree.
Make sure the phase sequence is wired correctly. The Unit will not operate normally if the phase
sequence is incorrect.
2. Outputs
Terminals 11, 12, and 14 are the output terminals for overvoltage (SPDT).
Terminals 21, 22, and 24 are the output terminals for undervoltage (SPDT).
N L1 L2 L3
Voltage input
L1
L2
N
L3
14
Signal output
12
24
Signal output
22
11
Overvoltage
alarm
21
Undervoltage
alarm
Load
DIP Switch Settings
The Startup lock time, number of wires, and rated voltage are set using the DIP switch located on the bottom of the Unit.
DIP Switch Functions
ON
K8AB-PW1
SWITCH
OFF
SW1
SW2
SW3
SW4
DIP switch
ON ● ↑
3
2
Power ON lock time 5 s
OFF ❍ ↓ OFF
---
---
---
●
1s
---
---
---
❍
Three-phase, four-wire
---
---
●
---
Three-phase, three-wire
---
---
❍
---
Number of wires
Rated voltage
4
1
ON
Three-phase, Three-phase,
three-wire
four-wire
240 V
138 V
●
●
---
---
230 V
133 V
●
❍
---
---
220 V
127 V
❍
●
---
---
200 V
115 V
❍
❍
---
---
3
2
1
Note: All pins are set to OFF at the factory.
K8AB-PW2
SWITCH
ON ● ↑
4
ON
Power ON lock time 5 s
OFF ❍ ↓ OFF
---
---
---
●
1s
---
---
---
❍
Three-phase, four-wire
---
---
●
---
Three-phase, three-wire
---
---
❍
---
Number of wires
Rated voltage
Three-phase, Three-phase,
three-wire
four-wire
480 V
277 V
●
●
---
---
415 V
240 V
●
❍
---
---
400 V
230 V
❍
●
---
---
380 V
220 V
❍
❍
---
---
Note: All pins are set to OFF at the factory.
7
K8AB-PW
Setting Method
1. Overvoltage
The overvoltage knob (OVER) is used to set the overvoltage.
The overvoltage can be set to between −30% and 25% of the rated input voltage.
Turn the knob while there is an input to the input terminals until the alarm indicator flashes (when the set value and the input have reached the
same level.)
Use this as a guide to set the voltage.
The rated input depends on the model and DIP switch setting.
Example: K8AB-PW1 with Pin 2 Turned OFF (Three-phase, Three-wire Mode) and Pins 3 and 4 Turned OFF (Rated Voltage of 200 V)
The rated input voltage is 200 VAC and the setting range is 140 to 250 V.
2. Undervoltage
Undervoltage is set using the undervoltage knob (UNDER).
The undervoltage can be set to between −30% and 25% of the rated input.
Turn the knob while there is an input to the input terminals until the alarm indicator flashes (when the set value and the input have reached the
same level.)
Use this as a guide to set the voltage.
The rated input depends on the model and DIP switch setting.
Example: K8AB-PW1 with Pin 2 Turned OFF (Three-phase, Three-wire Mode) and Pins 3 and 4 Turned OFF (Rated Voltage of 200 V)
The rated input voltage is 200 VAC and the setting range is 140 to 250 V.
3. Operating Time
The operating time is set using the operating time knob (T).
The operating time can be set to between 0.1 and 30 s.
Turn the knob while there is an input to the input terminals until the alarm indicator flashes (when the set value and the input have reached the
same level.)
Use this as a guide to set the current.
If the input exceeds (or drops lower than) the voltage setting, the alarm indicator will start flashing for the set period and then stay lit.
Dimensions
(Unit: mm)
Three-phase Voltage Relays
22.5
5
100
K8AB-PW1
K8AB-PW2
90
72
5
8
K8AB-PW
Questions and Answers
Q
Q
Checking Operation
How to Measure the Operating Time
Overvoltage
Change the input suddenly from 0% to 120% of the set
value and measure the time until the Unit operates.
Undervoltage
Change the input suddenly from 120% to 0% of the set
value and measure the time until the Unit operates.
Operating Time
Adjust the slide resistor so that the voltage applied to the
K8AB terminals is 120% of the overvoltage set value or
80% of the undervoltage set value when the auxiliary relay
operates in a test circuit. Close the switch and use the
cycle counter to measure the operating time.
Overvoltage
Gradually increase the input from 80% of the setting.
The input value will equal the operating value when the
input exceeds the setting and the alarm indicator starts
flashing. Operation can be checked by the relay output that
will start after the operating time has passed.
Undervoltage
Gradually decrease the input from 120% of the setting and
check the operation using the same method as for
overvoltage.
Example: For monitoring mode set to three-phase three-wire
monitoring, a rated voltage of 200 V, and an operating time
of 5 s.
Connection Diagram
Note: K8AB-PW@ output relays are normally operative.
L1
3φ,
200 VAC
Set value
Input voltage
V1
L2
L1
Flashing
R1
Lit
X/b
X
Alarm indicator
5s
X/a
V2 V3
L3
R2
L2
R1: Slide resistor
200 Ω 200 W
R2: 100 Ω 400 W
Relay output
L3
Connection Diagram
Overvoltage
L1
±
V1
3φ,
200 VAC
L2
C 200 V
Cycle counter
V2 V3
L1
L3
0 to 150 V
L2
Undervoltage
L3
Q
Operating Adjustment Knobs
Three-phase
variable autotransformer
Use a screwdriver to turn the knobs. There is a stopper to
prevent the knob from turning any further once it has been
turned completely to the left or right. Do not force the knob
past these limits.
Q
Overvoltage Detection When Only One Phase Exceeds
the Overvoltage Threshold
The K8AB monitors each of the three-phase voltages. This
means an overvoltage is detected if even only one phase
exceeds the threshold value. The same applies to
undervoltages.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
In the interest of product improvement, specifications are subject to change without notice.
9
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
safety equipment, and installations subject to separate industry or government regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
2009.11
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2009 All Right Reserved.