Litteluse ProtectionRelays EL3100 Manual

3714 Kinnear Place
Saskatoon, SK
Canada
S7P 0A6
Ph: (306) 373-5505
Fx: (306) 374-2245 www.littelfuse.com/relayscontrols
EL3100 MANUAL
GROUND-FAULT & PHASE-VOLTAGE INDICATOR
REVISION 2-B-022216
Copyright © 2016 by Littelfuse Startco
All rights reserved.
Document Number: PM-1065-EN
Printed in Canada
EL3100 Ground-Fault & Phase-Voltage Indicator
This page intentionally left blank.
Page i
Rev. 2-B-022216
EL3100 Ground-Fault & Phase-Voltage Indicator
TABLE OF CONTENTS
SECTION
PAGE
Description ........................................................... 1
Features................................................................ 1
Remote Indication ............................................... 1
Output Contact.................................................... 1
Installation ........................................................... 1
Technical Specifications...................................... 5
6.1 EL3100 ....................................................................... 5
6.2 Remote LED’s (RK-310X-0X) ................................. 5
7
Ordering Information ......................................... 6
8
Warranty ............................................................. 6
Appendix A EL3100 Revision History .......................... 7
1
2
3
4
5
6
LIST OF FIGURES
FIGURE
1
2
3
4
PAGE
EL3100 Series Outline and Mounting Details ...... 2
Connection Diagram ............................................. 3
Remote 16-mm IP67 LED Lamp Outline and
Mounting Details................................................... 3
Remote LED Labels .............................................. 4
DISCLAIMER
Specifications are subject to change without notice.
Littelfuse Startco is not liable for contingent or
consequential damages, or for expenses sustained as a
result of a malfunction, incorrect application, or incorrect
adjustment.
Page ii
Rev. 2-B-022216
EL3100 Ground-Fault & Phase-Voltage Indicator
This page intentionally left blank.
Page iii
Rev. 2-B-022216
EL3100 Ground-Fault & Phase-Voltage Indicator
1. DESCRIPTION
The EL3100 is a self-powered ground-fault and phasevoltage indication system for three-phase systems. The
EL3100 meets the National Electrical Code requirements
for ground detectors for ungrounded alternating-current
systems as defined in NEC 250.21. It also meets the
Canadian Electrical Code requirements for ungrounded
alternating-current systems in accordance with
CEC 10-106(2).
Voltage connections are provided on the EL3100 for
208-, 240-, 480-, and 600-V systems. Three green LED’s
on the EL3100 indicate the presence of phase-to-ground
voltage and one red LED indicates a ground fault. The
phase LED intensity is a function of line-to-ground voltage
providing visual indication of phase balance.
There are cases when one of the three phase indicators
is off but no ground fault is indicated. This occurs on an
ungrounded system when there is a phase loss. Groundfault indication is still enabled and will be activated when
either of the energized phases develops a ground fault.
The EL3100 can operate stand-alone or with up to five
remote LED indicators. High-intensity 16-mm IP67 LED
lamps are available in red and green colors. LED indicators
and wiring operate in low-voltage mode.
A solid-state relay output provides indication of a
ground fault. The output relay is closed when the threephase neutral voltage shifts as the result of ground leakage.
2. FEATURES




Direct connection to EL3100 for voltages up to
600 Vac line-to-line
Provides faulted-phase indication for resistancegrounded and ungrounded systems
Provides phase-voltage indication for resistancegrounded and ungrounded systems
The EL3100 can be used stand-alone or with lowvoltage remote LED’s
o Solid-state (100 mA, 120 Vac/Vdc) output relay
o Three green phase-voltage LED’s
o One red ground-fault LED
o Up to five remote LED’s can be connected
3. REMOTE INDICATION
Terminals 10 through 15 are used for remote LED
indication. High-intensity LED’s with no internal resistors
are required. See Section 7 for ordering information. Fig.
2 illustrates a remote LED application where all LED’s are
used.
There are five remote LED outputs for phase-voltage
indication, no-ground-fault indication, and ground-fault
indication. Connect optional remote LED’s to terminals
DA, DB, and DC (12, 11, and 10) for phase-voltage
indication. The intensity of these LED’s is proportional to
phase-to-ground voltage. A ground fault or phase loss is
Page 1
Rev. 2-B-022216
indicated when one LED is off while the other two are on.
A remote LED connected to terminal DG (13) provides noground-fault indication. This LED is on when there is no
ground fault and is off when the three-phase-neutral
voltage shifts from ground potential as the result of a
ground fault (or if the system is de-energized). A remote
LED connected to terminal DR (14) is on when a ground
fault is present and off when no ground fault is present (or
the system is de-energized). Terminal DN (15) is the LED
common terminal.
NOTE: Unused LED outputs must be left unconnected.
4. OUTPUT CONTACT
A solid-state normally open ground-fault-indication
relay output is at terminals 16 and 17. The output relay is
closed when the three-phase neutral shifts more than
20 Vac with respect to ground for the “L” voltage inputs
and 40 Vac with respect to ground for the “H” voltage
inputs.
NOTE: The relay output has a rating of 100 mA at
120 Vac/Vdc and has a 35-Ω closed resistance.
5. INSTALLATION
Outline and mounting details of the EL3100 are shown
in Fig. 1. For 208- or 240-Vac systems use terminals
AL (7), BL (8), and CL (9). For systems above 240 Vac
and up to 600 Vac, use terminals AH (1), BH (3), and
CH (5). Connect bonding terminal (G) to ground. See Fig.
2. Terminals 2, 4, and 6 are not used.
NOTE: Bonding terminal (G) must be connected to ground
for correct fault indication and to ensure that fault potential
is not transferred to the display.
Outline and mounting details for the remote LED’s are
shown in Fig. 3. Cable length should be limited to
10 m (33 ft). The recommended cable is 22 - 18 AWG (0.33
to 0.82 mm2) wire. Use shielded cable for cable lengths
exceeding 2 m (6 ft). When shielded cable is used, connect
cable shield to terminal SH (18) at the EL3100 only.
Page 2
Rev. 2-B-022216
EL3100 Ground-Fault & Phase-Voltage Indicator
CABLE-TIE EYELET
4 PLACES
19
18
G
16
17
SH
15 14 13 12 11 10
DN DR DG DA DB DC
87.0
(3.43)
FAULT
DISPLAY
A
B
C
EL3100 SERIES
GROUND-FAULT & PHASE-VOLTAGE INDICATOR
AH
1
2
480/600
BH
3
4
CH
5
6
AL
7
208/240
BL
CL
8
9
52.5
112.5
(4.43)
(2.07)
56.0
TOP
SIDE
NOTE 3
(2.20)
NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).
2. MOUNTING SCREWS: M4 OR 8-32.
3. OVERALL HEIGHT WHEN MOUNTED
ON DIN EN50022 35-mm x 7.5-mm
TOP-HAT RAIL.
12.5
(0.50)
60.0
(2.36)
BOTTOM
(0.57)
14.5
M4 OR 8-32 TAP
2 LOCATIONS
NOTE 2
6.8
100.0
6.8
(0.27)
(3.94)
(0.27)
MOUNTING DETAIL
FIGURE 1. EL3100 Series Outline and Mounting Details.
Page 3
Rev. 2-B-022216
EL3100 Ground-Fault & Phase-Voltage Indicator
SERVICE
ENCLOSURE
A
B
C
NOTE 1
GROUND
1
NOTES:
AH
1. USE L TERMINALS FOR
SYSTEMS UP TO 240 VAC. USE
H TERMINALS FOR SYSTEMS
ABOVE 240 VAC UP TO
600 VAC.
19
7
AL
3
BH
8
BL
9
REMOTE INDICATION
CL
SH
18
DN
15
DR
14
DG
13
DA
12
DB
11
DC
10
NOTE 2
G
2. USE SHIELDED 22 AWG TO
18 AWG (0.33 TO 0.82 mm2)
CABLE FOR DISTANCES
LONGER THAN 2 M (6 FT).
USE BELDEN 3002A OR
EQUIVALENT.
G
A
G
B
G
3. NOTE LED POLARITY.
SEE FIG. 3.
5
CH
C
17
16
R
+
+
FAULT
NO FAULT
+
+
+
FAULT
PHASE A
PHASE B
PHASE C
NOTE 3
FIGURE 2. Connection Diagram.
Ø 16.0 ±0.1
(0.63 ±0.004)
(0.72)
18.3
+ GOLD TERMINAL
2.8 x 0.8 TYP
(0.11 x 0.03)
- SILVER TERMINAL
NOTES:
1. DIMENSIONS IN
MILLIMETRES (INCHES).
4.8
13.5
9.35
(0.19)
(0.53)
(0.37)
33.8
10.0
(1.33)
(0.39)
SIDE VIEW
PANEL CUTOUT
FIGURE 3. Remote 16-mm IP67 LED Lamp Outline and Mounting Details.
EL3100 Ground-Fault & Phase-Voltage Indicator
Page 4
Rev. 2-B-022216
30.0
NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).
2. DIMENSIONS ARE IDENTICAL FOR ALL LABELS.
50.0
(1.97)
20.0
Ø20.0 (0.79)
(0.79)
15.0
(0.59)
(1.18)
3. RK-311X-01 (PHASE B VOLTAGE) SHOWN.
NOTE 3
OUTLINE DETAIL
RK-310R-01
RK-310G-01
RK-311X-01
FIGURE 4. Remote LED Labels.
Page 5
Rev. 2-B-022216
EL3100 Ground-Fault & Phase-Voltage Indicator
6. TECHNICAL SPECIFICATIONS
6.1 EL3100
Phase Voltage:
Input L ................................ 240 Vac line-to-line
Input H ................................ 600 Vac line-to-line
Input L, maximums............. 240 Vac to ground,
0.8 mA input current
Input H, maximums ............ 600 Vac to ground,
2.0 mA input current
Internal Fuses (6) ................ 500 mA, 600 Vac,
not field serviceable
Environment:
Operating Temperature....... -40 to 60°C (-40 to 140°F)
Storage Temperature .......... -55 to 80°C (-67 to 176°F)
Humidity............................. 85% Non-Condensing
PWB Conformal Coating ......... MIL-1-46058 qualified
UL QMJU2 recognized
Certification ................................. CSA, Canada and USA
R
C
LR 53428
US
UL Listed
Frequency Response (3 dB) ..... 0 to 300 Hz
Trip Threshold:
Input L(1) ............................. 20 Vac
Input H(1) ............................. 40 Vac
Fault Current(2) .................... 350 µA
Solid-State Relay Output:
Configuration ...................... N.O. (Form A)
Operating Mode .................. Non-Fail-Safe
Rating ................................. 100 mA, 120 V,
12 W (ac or dc)
Protection ............................ 130 V MOV
Closed Resistance ............... 35 Ω maximum
Dielectric Strength .............. 1,500 Vac
Australia
CAN/CSA C22.2 No. 144-M91 – Ground Fault Circuit
Interrupters
ANSI/UL Std 1053, 6TH Ed. – Standard for Ground Fault
Sensing and Relaying Equipment
CAN/CSA C22.2 No. 14-10 – Industrial Control
Equipment
UL Std 508, 17TH Ed. – Industrial Control Equipment
Australia, Regulatory Compliance Mark (RCM)
6.2 REMOTE LED’S (RK-31XX-0X)
Terminal Block Wire Sizes:
Voltage Inputs(3).................. 20 to 12 AWG
(0.5 to 2.5 mm2)
(3)
Bonding ........................... 20 to 12 AWG
(0.5 to 2.5 mm2)
(3)
Relay ................................ 20 to 12 AWG
(0.5 to 2.5 mm2)
Display LED’s .................... 24 to 12 AWG
(0.2 to 2.5 mm2)
Dielectric Strength:
Input L(5) ............................. 1800 Vac, 1 s,
12 mA per phase
Input H(5) ............................. 2650 Vac, 1 s,
9 mA per phase
Shipping Weight ....................... 0.4 kg (0.9 lb)
EL3100 Dimensions:
Height ................................. 87 mm (3.4”)
Width .................................. 113 mm (4.4”)
Depth .................................. 56 mm (2.2”)
Mounting Configurations ......... DIN Rail and Surface
Current ..................................... 0.4 to 2.0 mA
Terminals(4) .............................. 2.8 mm (0.11”) x
0.8 mm (0.03”)
Configuration ........................... 16 mm (0.6”), panel
mount, IP67
Certification ................................. UL Recognized E317459
NOTES:
(1)
Three-phase neutral-to-ground shift between terminal
G (19) and source supply.
(2)
Current flowing in terminal G (19) (ground
connection).
(3)
Accepts No. 8 (M4) ring terminals.
(4)
Supplied with Faston terminals for 22 – 18 AWG
(0.33 to 0.82 mm2) wire.
(5)
With terminal G (19) connected to ground. Do not
remove ground connection to terminal G (19) during
dielectric testing to avoid test potential transfer to the
remote display.
EL3100 Ground-Fault & Phase-Voltage Indicator
7. ORDERING INFORMATION
EL3100-00
Remote LED Part Numbers
(see Fig. 4 for label details):
RK-31
-0
0= No Label
1= GF Status Label
(Single LED Kit Only),
Phase Labels
(Triple LED Kit Only)
R= Red
G= Green
0= Single LED Kit
1= Triple LED Kit
8. WARRANTY
The EL3100 Ground-Fault & Phase-Voltage Indicator is
warranted to be free from defects in material and
workmanship for a period of five years from the date of
purchase.
Littelfuse Startco will (at Littelfuse Startco’s option)
repair, replace, or refund the original purchase price of an
EL3100 that is determined by Littelfuse Startco to be
defective if it is returned to the factory, freight prepaid,
within the warranty period. This warranty does not apply
to repairs required as a result of misuse, negligence, an
accident, improper installation, tampering, or insufficient
care. Littelfuse Startco does not warrant products repaired
or modified by non-Littelfuse Startco personnel.
Page 6
Rev. 2-B-022216
Page 7
Rev. 2-B-022216
EL3100 Ground-Fault & Phase-Voltage Indicator
MANUAL
RELEASE DATE
APPENDIX A
EL3100 REVISION HISTORY
MANUAL
PRODUCT REVISION
REVISION
(REVISION NUMBER ON PRODUCT LABEL)
February 22, 2016
2-B-022216
January 27, 2014
2-A-012714
November 27, 2012
1
01
October 29, 2012
0
00
MANUAL REVISION HISTORY
REVISION 2-B-022216
SECTION 6
RCM certification added.
Frequency response specification added.
REVISION 2-A-012714
SECTION 5
Remote LED labels (Fig. 4) added.
SECTION 6
Dielectric strength specification added.
SECTION 7
Ordering information updated.
APPENDIX A
Revision history added.
REVISION 1
SECTION 6
Updated solid-state relay protection information.
REVISION 0
Initial release.
PRODUCT REVISION HISTORY
PRODUCT REVISION 02
Added filter capacitor.
PRODUCT REVISION 01
Solid-state relay protection changed to 130 V.
PRODUCT REVISION 00
Initial release.
02
EL3100 Ground-Fault & Phase-Voltage Indicator
This page intentionally left blank.
Page 8
Rev. 2-B-022216