Security: KNX-Intrusion Alarm System L240 (.PDF)

KNX-Intrusion Alarm System L240
Product Overview
Contents
The highest levels of security, comfort and cost-effectiveness
2
Efficiency in the installation through bus technology
3
The SafeKey setting device
4
Intrusion detection system example project, increased risk
5
System overview and engineering instructions
6
Product overview
8
2CDC 541 158 D0201 1
The highest levels of security,
comfort and cost-effectiveness
The Intrusion Alarm Panel L240 is the result of many years
of experience in the security field and from three generations
od intrusion alarm systems. This professional alarm system is
designed for the integration into KNX installations for small to
medium sized objects. The flexibility of the bus-based system
and extendability of installation means that the same technology can be used for security applications in private residences
as well as non-residential buildings.
The alarm panel is operated using the Keypad L240/PT.
It is also required when the panel is extended or messages
are to be displayed in plain text.
Thus, the panel complies with the requirements to
VdS class C and to the European Standard EN 50131,
Grade 3.
The system can be extended to incorporate up to 80 detector circuits in different setting areas using external modules,
which are simply connected to the Alarm Panel bus. Consequently, the panel provides an application spectrum ranging
from private to commercial buildings and from the smallest to
the largest insurance risks.
Alarm Panel
KNX
Switch-Dim
Actuator
2 2CDC 541 158 D0201
Fan/Fan Coil Actuator
Blind Actuator
LCD Keypad
Efficiency in the installation
through bus technology
The Intrusion Alarm Panel L240 is simply extended by 4-wire
connection of modules to the security bus (XIB). In addition to
the Detector Circuit Modules L840/MG4 and L240/MG2, to
which conventional detectors are connected, you can also
connect BUS Motion Detectors with passive infrared and dual
technology.
The panel can be easily configured by PC via the serial
Interface Module L208/V.24 or the LAN IP Interface L240/IP.
Important events and access histories can also be read from
the central memory in this way.
The KNX interface from ABB offers a solution for the Intrusion
Alarm System L240, which integrates professional security
technology in KNX systems.
All 80 detectors or detector circuits of the Intrusion Alarm
System L240 are available as bi-directional communication
objects on the KNX and/or on the intrusion alarm system.
This allows security technology detectors to be used for other
functions.
So for example, opening a window will be detected by a
window contact and signalled to the KNX system, which
deactivates the room temperature controller. If however, no
one is at home and the alarm system is triggered, this
detector will trigger an alarm. Motion detectors can be used
both for intrusion detection as well as for automatically
switching on a light.
If a sensor is used for 2 applications, fewer sensors are
required, and if the heating is shut down, energy is also
saved.
But even more functions are possible: when opening a house
door using SafeKey and KNX, for example, the required level
of lighting and music can be switched on.
Thus, many day-to-day routines can be automated in this
way.
XIB
Sensors
Bus Motion Detector
SafeKey
2CDC 541 158 D0201 3
The SafeKey setting
device
…is simple and comfortable
to operate
Setting device and access control from
a single source!
Comfortable operation – optionally by
numeric code, chipkey or a combination
of both.
The system is disarmed with just
a single operation.
Up to 8 Evaluation Modules can be
connected via the XIB security bus to
the Intrusion Alarm Panel L240. This
facilitates the connection of the wall
reader and assures communication with
the panel.
The keys are learned-in using a module
in the panel and managed there via the
keypad or by using the programming
software WinPC. Every key can be
assigned with different levels of authorization for each of the 8 doors, so that
you can decide which key or person
is permitted to set the intrusion alarm
system. All locking actions together with
the key name and the time of the action
are registered in the event list memory
of the panel and can be accessed on
the keypad when required.
4 2CDC 541 158 D0201
…impresses with its elegant design
SafeKey setting devices combine
security and stylish ambiance.
Security that is convincing – elegant
design which impresses! Play it
safe and select a design and appearance
appropriate for your entrance or foyer.
SafeKey and wall reader are available
with a modern stainless-steel and matt
chrome-plated finish. In the classic
elegant design, they can be tastefully
combined with every existing style.
SafeKey chipkey
Electronic chipkey for key operation
and/or setting/unsetting. SafeKey
chipkeys can be authorized for any
number of different systems.
Every chipkey is a unique read
protected and copy protected device.
SafeKey wall readers with and
without keypad
Remote input device for setting/
unsetting.
The connection to the SafeKey
Evaluation Module is wired. A bolt lock
is required to ensure unavoidability
compliance.
…is absolutely flexible
The user management of the Intrusion
Alarm Panel manages the different
authorization levels for each person on
each door. New chipkeys and numeric
codes are created in seconds; misplaced
chipkeys can be quickly and easily
deactivated without the laborious,
cost-intensive task of replacing locking
cylinders.
Special highlight:
A chipkey can be authorized for
several SafeKey systems that are
independent of one another.
Intrusion detection system example project
increased risk
Motion detectors
Flash
Z
ÜE
Siren
Magnet reed contact set
Lock monitoring
Keypad
Z
ÜE
Panel
Dialling device
Setting device
House example project, increased risk
planning with L240 compliant to DIN VDE 0833.
Parts list with wired technology
Units
Device
Type
1
Intrusion Alarm Panel
L240
2
Battery
SAK7
If complete exterior surveillance is to be implemented, all windows must be
1
Keypad
L240/PT
monitored for opening with magnetic contacts to ensure lock monitoring
4
Motion Detectors
IR/XB
(either with VSUE or with blocking bolts).
2 (10)
Magnetic Reed Contact Set
MRS/W
2
Lock Bolt Switching Contact
WRK/W
(4)
Blocking Bolt
ADB
1 (5)
2 Zone Module
L240/MG2
1
Combination Signalling Device
SSF/GB
1
Siren
SSF/G
1
Setting Device
L240/BS in housing
1
Electric Bolt Lock
All doors (here terrace doors) are to be monitored for opening and locking.
with WEL or WELT
ESPE
2CDC 541 158 D0201 5
System overview and
engineering instructions
Exterior surveillance
What
How
With what
Doors/
Opening
Magnetic reed contacts
windows
Note
Drill hole or flush mounted
Connection to a distribution unit or zone
module
Breakage/
Passive or acoustic
rupture
glass break detectors
Locking
Strike plate contacts
Installation in the strike plate.
Lock monitoring
Installation in the surround.
for the windows
Connection to the distribution unit or
zone module.
Only in conjunction with monitoring of opening.
Interior monitoring
What
With what
Motion in rooms
Passive infrared detector
Note
Observe sources of interference!
Heat and cold sources.
Various effective ranges
through exchangeable lenses.
Dual detectors
Observe sources of interference!
Draughts, interfering transmitters.
Fire/smoke
Smoke alarm
Gas
Gas alarm
Not in kitchen/bathroom/sauna.
All combustible gasses
Observe installation location!
(light/heavy gasses)
Water
6 2CDC 541 158 D0201
Water alarm
Alarms
What
With what
Internal
Internal siren
External local
External siren with/without
Note
At least 3 m from the ground
strobe light
External silent
Dialling device with voice
A/B cable
output
Panel and accessories
What
Note
Panel
Installation location
Batteries
Consider the current consumption of the entire system
Keypads
At least one keypad
Enhanced operation and programming: At least one L840/PT is necessary
for all expansions and programming!
Connection module for
Also contains connections for MRS, WRK and ESPE;
SafeKey
situated beside the door.
Detection circuit expansions
L240/MG2: for connection of magnetic reed contact and glass break detectors
(windows). L840/MG4; for connection of contact-relevant detectors.
Remote programming via
Serial port on the PC or LAN interface on the PC or
Notebook
via the network.
Installation
What
Note
Main distribution board
For clearly arranged wiring to the panel.
Junction boxes
On windows, doors.
Cable ducts
From the door wing to frame. From door panel to frame (colour variants).
Cables
I-Y(ST) Y n x 0.6 or 0.8 mm
2CDC 541 158 D0201 7
Product range overview
Overview Intrusion Alarm System L240
6 detector circuits, 1 PA,
1 tamper, 1 lock,
1 external set
1 Strobe
Intrusion Alarm Panel L240
2 Sirens
SAK 7
1
2
3
4
5
6
7
8
9
x
0
Up to 7 Keypads L240/PT
SAK 7
XS/S 1.1
IR/X...
max. 40 devices
Intrusion Alarm Panel L240 with bus technology
is the universal solution for all applications. The following bus modules can be connected to the panel: 2 Zone Modules L240/MG2 for connection to the exterior perimeter detectors such as magnetic reed contacts and passive glass break sensors.
The module has 2 zones, to which 2 detectors can be connected via LSA terminals.
The module is an intelligent distributor by simple installation in a 60 mm installation
box in the vicinity of the window.
Zone Module L840/MG4 for expansion of the panel by up to 4 detector circuits.
A SAD enclosure is required.
L240/MG2
max. 24 devices
L840/MG4
max. 16 devices
L240/BS
max. 8 devices
SafeKey Evaluation Module L240/BS for connection of the SafeKey components
as well as all components required for a setting door (magnetic contacts, lock bolt
switching contact, bolt lock, internal siren). The management of the electronic keys
from the SafeKey range is undertaken completely on the LCD keypad of the panel.
In total, 80 detectors or detector circuits (zones) (10 groups to the panel and a further
70 on the bus).
Furthermore, up to 8 x L240/BS – a total of 8 doors – can be connected,
and 4 setting zones can be formed.
The interface to KNX facilitates complete integration of the security functions
into the KNX system, up to VdS class C.
Interface Module L240/IP for programming of the L240 via PC, incl. WinPC software.
Risk allocation, classification
Optional system accessories
•
•
•
•
•
•
•
•
•
•
•
VdS approved as an Intrusion Alarm Panel for VdS classes A, B, C
Corresponds to DIN VDE 0833 parts 1 & 3
Grade 3 according to European standard EN 50131-1 “medium to high risk”
Typical areas of application
Residential and commercial properties with more than one security zone,
commercial zones up to stage 6, and banks with an insurance company/police
requirement for a medium to high risk alarm system
Application limitations:
• The Intrusion Alarm Panel is suitable for all types of risk
• The limits of the application are only in the scale of the system (number of
detector zones)
• The Intrusion Alarm Panel is suitable for up to four setting zones
Max. 7 Keypads L240/PT
Max. 2 Batteries SAK7
8 SafeKey Evaluation Modules L240/BS
Zone Modules L240/MG2 and/or L840/MG4
1 Serial Interface L208/V.24
1 Ethernet Interface L240/IP
Supplementary Power Supply L240/N
KNX Interface XS/S 1.1
Suitable alarm equipment
•
•
•
Internal siren for occupancy alarm: 1 SSS
External siren/strobe: 1 SSF/G and 1 SSF/GB
Silent alarm: Local devices
Degree of expansion
Suitable setting devices
•
•
•
•
•
4 setting zones
80 programmable inputs
Motion detectors can be connected to the bus
Window contacts and glass break sensors can be connected to the bus via the
Bus Module L240/MG2
The panel can be extended with up to 8 SafeKey Evaluation Modules
L240/BS and Zone Modules L240/MG2 and/or L840/MG4.
Internal setting via Keypad L240/PT
External setting
•
•
Via Keypad L240/PT delayed in the security zone
With SafeKey components on L240/BS up to 8 doors
Suitable sensors
Obligatory system accessories
•
•
1 Battery SAK7
1 Keypad L240/PT per setting zone
8 2CDC 541 158 D0201
All detectors and contacts from the ABB intrusion alarm range.
The total current consumption must be observed.
Type
Detail
Order code
PG MB
Type
Detail
Order code
Intrusion Alarm Panel
Sealed Lead Acid Battery, 12 V DC, 7 Ah
For residential and commercial properties with more
For Intrusion Alarm Panel emergency power.
than one security zone, commercial zones up to
2 units can be installed. VdS class C.
PG MB
stage 6, and banks with an insurance company/
police requirement for a medium to high risk alarm
SAK7
GH V924 0001 V0011 50
-
system.
VdS approved as an Intrusion Alarm Panel for
BUS-IR Motion Detector
VdS classes A, B, C.
For direct connection to the bus of the Intrusion Alarm
Corresponds to DIN VDE 0833 parts 1 & 3, Stage
Panel L240, whereby a maximum of 40 detectors can
3 according to European standard EN 50131-1
be addressed by the panel.
“medium to high risk”.
The motion detectors with passive infrared technology
are registered for VdS classes B and C (anti-masking
L240/ENG
English
monitored). They facilitate monitoring of an area with
2CDG 230 017 R0011 50 -
an IR range of up to 15 m.
Interface for Intrusion Alarm Panel, MDRC
Integration into KNX systems is possible using the
IR/XB
VdS class B
2CDG 230 023 R0011 50
-
Interface XS/S1.1.
IR/XC
VdS class C
2CDG 230 024 R0011 50
-
Accordingly, there are numerous benefits:
MW
Mounting Bracket
GH V923 0039 V0020 50
-
For example, a door/window opening detector can
be used to switch off the heating and save energy in
BUS Dual Motion Detector
the unset state. When an alarm is triggered, the KNX
For direct connection to the bus of the Intrusion Alarm
devices can carry out actions such as switching on
Panel L240, whereby a maximum of 40 detectors
the light or operating the blinds.
can be addressed by the panel.
The interaction offers further benefits in terms of
The Dual-Motion Detector combines proven passive
system integration, which comply to the demands of
infrared technology with temperature-independent
the VdS up to class C.
microwave technology. The combination of both
functional principles results in a detector featuring
XS/S 1.1
high immunity to false alarms, even with unfavourable
2CDG 110 075 R0011 26 -
ambient conditions, and which still has high detection
LCD Keypad
security. The detectors are registered for VdS classes
For operation and programming of the panel.
B and C (anti-masking monitored). They facilitate
The messages are displayed on a two-line LCD
monitoring of an area with an IR range of up to 15 m.
display. Menu driven operation and programming of
the panel. Internal and external setting on the keypad
EIM/XB
VdS class B
2CDG 230 025 R0011 50
-
is possible. VdS class C.
EIM/XC
VdS class C
2CDG 230 026 R0011 50
-
MW
Mounting Bracket
GH V923 0039 V0020 50
-
L240/PT
2CDG 230 014 R0011 50 Zone Bus-Module, 2-fold
Serial Interface Module
For expansion of the panel by 2 detector circuits.
For programming of the L240 via PC with
Used for connection to the exterior perimeter
serial interface V24, incl. WinPC software.
detectors such as magnetic reed contacts and
passive glass break sensors. The module has
L208/V.24
2 zones, to which 2 detectors can be connected via
GH Q328 0220 R0001 50 -
LSA terminals. The module is an intelligent distributor
IP Interface Module
by simple installation in a 60 mm installation box
For programming of the L240 via PC with
in the vicinity of the window.
Ethernet interface, incl. WinPC software.
L240/MG2
L240/IP
2CDG 220 003 R0011 50
-
2CDG 230 013 R0011 50 Zone Bus-Module, 4-fold
For expansion of the panel by 4 detector circuits.
A SAD enclosure is required for installation.
L840/MG4
GH Q328 0011 R0001 50
-
2CDC 541 158 D0201 9
Type
Detail
Order code
PG MB
Type
Detail
Order code
SafeKey Wall Reader
Distribution Enclosure
For setting/unsetting with the Evaluation Module
For installation of the Bus Modules L840/MG4
L240/BS. The unit is actuated by inserting the
and L240/BS.
PG MB
electronic SafeKey chipkey. The SafeKey Wall
Reader WEL is equipped with the key reader and
SAD/GAP
Surface mounting
GH Q328 0015 R0001 50 -
SAD/GUP
Flush mounting
GH Q328 0013 R0001 50 -
SAD/ED
Wall box for
GH Q328 0014 R0001 50 -
an acknowledgement buzzer.
VdS class C.
WEL/A,ES
Stainless steel
GH Q305 0023 R0001 53 -
SAD/GUP
SafeKey Wall Reader with Keypad
For setting/unsetting with the Evaluation Module
Security Terminal, 4-fold, MDRC
L240/BS. The unit is actuated by inserting the
is used for the monitored connection of sensors from
electronic SafeKey chipkey and/or by a code keypad.
security technology (e.g. magnetic contacts or glass-
The SafeKey Wall Reader WELT is equipped with the
breakage sensors) to the ABB i-bus® KNX. The device
key reader, an acknowledgement buzzer and a code
has four inputs (“zones”) available and can be used
keypad.
as a stand-alone security system or in combination
VdS class C.
with the security module or control panel with KNX
interface. 12 V DC SELV power supply required, e.g.
WELT/A,ES
Stainless steel
GH Q305 0024 R0001 53 -
NTU/S 12.2000.1. Typical applications are door and
WELT/A,MC
Matt chrome-plated
GH Q305 0024 R0011 53 -
window surveillance, glas-breakage detection as well
as area surveillance.
SafeKey Chipkey
It is an electronic carrier medium for lock actuation
MT/S 4.12.2M
2CDG 110 109 R0011 26 -
and for setting/unsetting on a strike plate, door
cylinder or wall reader. A SafeKey Chipkey can be
Security Terminal, 8-fold, MDRC
authorized for any number of different SafeKey
is used for the monitored connection of sensors from
systems with different levels of authorization.
security technology (e.g. magnetic contacts or glassbreakage sensors) to the ABB i-bus® KNX. The device
SCS
has eight inputs (“zones”) available and can be used
GH Q305 0027 R0001 53 -
as a stand-alone security system or in combination
SafeKey Evaluation Module
with the security module or control panel with KNX
For connection of the SafeKey components as well
interface. 12 V DC SELV power supply required, e.g.
as all components required for a setting door
NTU/S 12.2000.1. Typical applications are door and
(magnetic contacts, lock bolt switching contact,
window surveillance, glas-breakage detection as well
bolt lock, internal siren). The management of the
as area surveillance.
electronic keys from the SafeKey range is undertaken
completely on the LCD keypad of the panel.
L240/BS
MT/S 8.12.2M
GH Q305 0031 R0001 53 -
2CDG 110 110 R0011 26 Security Terminal, 2-fold, FM
is used for the monitored connection of sensors from
Electromechanical Bolt Lock
security technology (e.g. magnetic contacts or glass-
Prevents access to the set zone of an Intrusion Alarm
breakage sensors) to the ABB i-bus® KNX. The device
Panel.
has two inputs (“zones”) available and can be used
The unit is mounted in the door frame. Only a single
as a stand-alone security system or in combination
bore or the counterpart for the locking bolt in the
with the security module or control panel with KNX
door panel is required. Suitable for use with WEL and
interface. 12 V DC SELV power supply required, e.g.
WELT. VdS class C.
NTU/S 12.2000.1. Typical applications are door and
window surveillance, glas-breakage detection as well
ESPE
EVSB
Replacement Locking
GH V925 0010 V0002 50 MT/U 2.12.2
Bolt
AMSP
Mounting kit, flat door
GH V925 0010 V0004 50 -
panel and frame
AMSE
as area surveillance.
GH V925 0010 V0001 50 -
Mounting kit, raised
door panel
10 2CDC 541 158 D0201
GH V925 0010 V0003 50 -
2CDG 110 111 R0011 26 -
Type
Detail
Order code
PG MB
Type
Detail
Order code
PG MB
Magnet Reed Contact Set
Lock Bolt Switching Contact
For opening surveillance of windows and doors,
For installation in the strike plate, for lock monitoring
complete for bolting or drilling
on doors.
Contents: 1 magnet, 1 reed contact with 4.0 m
Water-tight IP 67, with 2.5 m connection cable
connection cable LIYY 4 x 0.14 mm2, 2 housings,
LIYY 3 x 0.14 mm2. VdS class C.
3 spacer plates, 2 flanges and 4 anti-magnetic fixing
screws. VdS class B.
WRK/W
2CDG 250 003 R0011 50 -
MRS/W
White
GH Q320 1972 R0001 50 -
Window Opening Plunger
MRS/B
Brown
GH Q320 1972 R0002 50 -
Lock monitoring is carried out with a special
magnet and a reed contact.
Magnet Reed Contact Saver Set
The magnet is mounted on the push rod of the
For opening surveillance of windows and doors,
window sash, while the reed contact is mounted on
complete for bolting or drilling.
the frame.
Contents: 20 magnets, 20 reed contacts with 4.0 m
connection cable LIYY 4 x 0.14 mm2, 40 housings,
The connection cable LIYY 4 x 0.14 mm2 is 4 m
60 spacer plates, 40 flanges and 80 anti-magnetic
in length. VdS class C.
fixing screws. VdS class B.
VSUE
VMRS/W
White
GH Q320 1972 R0011 50 -
VMRS/B
Brown
GH Q320 1972 R0012 50 -
GH V921 0018 V0022 50 Blocking Bolt
Indirect lock monitoring by mechanical push opening
Rolling Door Magnet Reed Contact Set
of the window in conjunction with magnetic contacts
For monitoring opening or rolling doors or other large
that monitor opening.
doors in the industrial field.
Available in 2 spring strengths.
Contents: 1 magnet, 1 reed contact with 2 m
connection cable 4 x 0.14 mm2, 1 m protective tubing
ADB
150 N
GH V921 0018 V0020 50 -
and 1 set of mounting accessories.
ADB1
35 N
GH V921 0018 V0021 50 -
Dimensions: H x W x D =
Reed contact 159 x 50 x 19 mm;
Emergency Call Button
magnet 100 x 40 x 35 mm; degree of protection:
For manual alarm tripping. Complies with Police
IP 68; Environmental class to VdS 4; VdS class B.
regulations, since it features permanent trip
recognition, momentary-contact function, with cover
RTK
contact.
GH Q320 1973 R0021 50 -
Available in surface mount and flush mount versions.
Glass Break Sensor, passive
The cover plate is used primarily in the banking
For surveillance of glass surfaces of windows, display
sector or other institutions, where unintentional alarm
windows and doors with high interference immunity
triggering is possible due to public access.
and integrated memory display.
Colour: white. VdS class C.
For operation directly on detector circuits of Intrusion
Alarm Panels or Zone Terminals.
ND/W
Surface mounting
GH Q713 2443 R0011 50 -
Extremely compact dimensions.
NDU/W
Flush mounting
GH Q713 2443 R0021 50 -
Dimensions: H x W x D = 18 x 18 x 9 mm.
EP
Spare Papers (10 pcs.) GH Q713 2443 R0003 50 -
Mounted onto glass using Loctite Adhesive (LKS).
NDA/W
Cover plate
GH Q713 2443 R0004 50 -
With 5 m connection cable. VdS class B.
SPGS/W
White
GH V922 0004 V0009 50 -
SPGS/B
Brown
GH V922 0004 V0010 50 -
GP2
Mechanical Glass
GH V922 0004 V0004 50 -
Break Test Device
LKS
Loctite Adhesive
GH Q400 1906 R0001 50 -
2CDC 541 158 D0201 11
Type
Detail
Order code
PG MB
Type
Detail
Order code
PG MB
Gas Detector
Electronic Solid-State Siren
For measurement and evaluation of the concentra-
Electronic solid-state siren with intermittent tone for
tion of natural gas or liquefied gas in the air. The
alarm purposes in indoor installations.
detector requires a (10 – 30 V DC) voltage supply and
External dimensions: ø x H = 90 x 37 mm.
has a normally open floating relay output contact for
connection to the Intrusion Alarm Panels, features an
SSS
GH V927 0001 V0001 50 -
LED display and a Piezo buzzer. For ceiling and wall
Combination Signalling Device
mounting.
Siren in an aluminium protective housing with
SGL
GH Q305 0008 R0001 50 -
additional protective enamel coating. Protected
against sabotage by a case tamper contact. The
Water Detector
alarm inputs are wired onto a terminal strip.
A resin-encapsulated water detector with gold-
Dimensions: H x W x D = 200 x 205 x 88 mm
plated Termipoint pins, detects water ingress, e.g.,
pipe fractures, ingress of groundwater and sewage,
Strobe light mounted on top.
water damage caused by washing machines and
Dimensions: H x W x D = 258 x 205 x 88 mm
dishwashers etc., before the damage becomes too
Colour RAL 9002. VdS class C.
expensive. For operation directly on detector circuits
of Intrusion Alarm Panels or Zone Terminals.
SWM4
GH Q403 0001 R0004 50 Smoke Detector
For early detection of fire in buildings.
The VdS certified detector can be connected to 12 V
intruder zones with the detector base.
A floating two-way contact serves as an alarm output.
An optional reed relay in the last detector of the
zone monitors the supply voltage and the removal
of a smoke detector from the base. For testing the
detector, a testing aerosol or a remote test unit can
be used.
FC600/O
Optical Smoke
2CDG 430 047 R0011 52 -
Detector
FC600/TMAX
Optical/Thermal
2CDG 430 049 R0011 52 -
Detector
FC600/BREL
Detector Base, 12 V
2CDG 430 051 R0011 52 -
FPA03
Testing Aerosol, 250 ml
GH V902 0012 V0021 52 -
RL
Reed Relay, 12 V
GH V927 0013 V0100 50 -
12 2CDC 541 158 D0201
SSF/G
Without strobe light
GH Q305 0017 R0001 50 -
SSF/GB
With strobe light
GH Q305 0018 R0001 50 -
Your ABB partner
Note:
We reserve the right to make technical changes or
modify the contents of this document without prior
notice. With regard to purchase orders, the agreed
particulars shall prevail.
ABB AG does not accept any responsibility
whatsoever for potential errors or possible lack of
information in this document.
We reserve all rights in this document and in the
subject matter and illustrations contained therein.
Any reproduction, disclosure to third parties or
utilization of its contents - in whole or in parts - is
forbidden without prior written consent of ABB AG.
Copyright© 2010 ABB
All rights reserved
www.abb.com/knx
Order Number 2CDC 541 158 D0201 printed in Germany (06/10-0.2-ZVD)