TX6A 10Gig UTP Jack Modules Part Numbers: CJ6X88TG**, CJK6X88TG**, CJQ6X88TG**, CJH6X88TG** INSTALLATION INSTRUCTIONS © Panduit Corp. 2016 1 Strain relief collar Jack PN511F NOTE: Use setting 9 of CJAST tool. Turn 2 times to cut through the outer jacket and MaTriX tape only. 2 MaTriX tape CJAST Wire cap 3 4 5 CWST 6 7 8 9 0.5" (12.7mm) 2 10 11 EGJT Do not pre-arrange conductors. (OR) For Technical Support: www.panduit.com/resources/install_maintain.asp ** Denotes color. Page 1 of 2 INSTALLATION INSTRUCTIONS © Panduit Corp. 2016 2015 12 12 T568B Wiring PN511F T568A Wiring 1. R R F F (OR) 1. 2. 1. 2. (OR) 1. 2. R R F F 13 15 14 EGJT REMOVAL STEPS 2 1 3 Notes: 1. For specified performance, follow TIA/EIA 568-C installation guidelines. 2. Jack modules can terminate 22-26 AWG solid or stranded IWC data cable with 0.062" (1.57mm) maximum insulated conductor outside diameter. 3. Jack modules may be re-terminated a minimum of 20 times. 4. For technical and performance information, consult Panduit technical support. As with all Wiring Accessories, the following statements apply: 1. Never install communications wiring during a lightning storm. 2. Never install communications wiring in wet locations unless the jack is specifically designed for use in wet locations. 3. Never touch uninsulated communications wiring or terminals unless the communication line has been disconnected at the network interface. 4. Use caution when installing or modifying communication wiring. E-mail: [email protected] For Instructions in Local Languages and Technical Support: www.panduit.com/resources/install_maintain.asp www.panduit.com Page 2 of 2 Phone: 866-405-6654 Cable Prep for non-MaTriX Category 6A Cable 1 2 3 CWST 4 Continue with steps 8-15 on pages 1 and 2 to complete termination.