TX6 PLUS UTP Keyed Jack Module Part Number: CJK688TG** INSTALLATION INSTRUCTIONS PN458A © Panduit Corp. 2008 Strain Relief Collar Wire Cap Jack CJK688TG** TERMINATION STEPS 2 1 3 0.5" 2.0" (50.8mm) (12.7mm) CWST Trim pair separator and/or ripcord if present. 4 6 5 Cable End 2 Cable End 1 " " " " R F 2 1 7 Cable End 1 Pr1 Pr4 8 Cable End 2 Pr3 Pr2 Pr3 Pr4 EGJT Pr2 Pr1 ** Denotes color. For Technical Support: www.panduit.com/resources/install_maintain.asp Page 1 of 2 INSTALLATION INSTRUCTIONS PN458A 9 10 CWST T568B T568A Cable End 1 Cable End 1 1 2 2 1 A Cable End 2 11 3 12 Cable End 2 2 1 B EGJT 2 A 1 B 3 A B 3 13 See note 4. REMOVAL STEPS 2 1 3 Notes: 1. For specified performance, follow TIA/EIA 568-B installation guidelines. 2. Jack Modules can terminate PVC or Plenum rated 22-26 AWG solid or stranded IWC cable with 0.048 inch (1.2 mm) maximum insulated conductor outside diameter. 3. Jack Modules may be re-terminated a minimum of 20 times. 4. On cable end 2 for A & B wiring and cable end 1 of A wiring, wrap the designated pairs around the proper center dividing post (A or B) and terminate in the proper location. 5. For technical and performance information, consult PANDUIT Technical Support. As with all Communication Components, the following statements apply: 1. Never install communications wiring during a lightning storm. 2. Never install communications wiring in wet locations unless the jack is specifically designed for use in wet locations. 3. Never touch uninsulated communications wiring or terminals unless the communication line has been disconnected at the network interface. 4. Use caution when installing or modifying communication wiring. E-mail: [email protected] For Instructions in Local Languages and Technical Support: http://www.panduit.com/resources/install_maintain.asp www.panduit.com Page 2 of 2 Fax: (708) 444-6993