PBAMR5 Series FEATURES • • • • • • • AC/DC Power Module Universal Input 90~264VAC High Efficiency up to 89% Short Circuit Protection Internal Input Filter Low Profile for Building Automation Class 2 Output (24LS Model) SPECIFICATIONS INPUT Input voltage range Line frequency Inrush current AC in 90-264VAC DC in 120-370VDC 47-63Hz From +61°C to +71°C, 2.5% per °C Cooling Free air Convection. Dimension L91 x W89.9 x D57 mm GENERAL Vi: 115VAC 20-25A Vi: 230VAC 40-50A OUTPUT Output voltage accuracy Derating +1% Efficiency 80% - 89% typical, model dependant Weight 380g STANDARDS UL/cUL Minimum load Not required. Line regulation +1% Load regulation +1% TUV Ripple and noise Hold up time BW = 20MHz, 50mV Vi = 115VAC, lo nom 5V & 12V 16ms Vi = 115VAC, lo nom 15V & 24V 10ms Vi = 230VAC, lo nom 60ms CE UL508 Listed UL1310 Class 2 power supply (15V & 24V models), UL60950-1 Recognised EN60950-1 AC/DC DIN RAIL MOUNTABLE 100 WATTS - AC/DC DIN RAIL MOUNTABLE - INDUSTRIAL CONTROL EN6100-3-2, EN61000-3-3, EN61000-6-2, EN55024, EN61000-4-2, EN61000-4-3, EN61000-4-4, EN61000-4-5, EN61000-4-6, EN61000-4-8, EN61000-4-11, EN61204-3 ENVIRONMENTAL C tick AS/NZ CISPR11 Group 1, Class A EMI standards EN61000-6-3, EN55022 Class B Storage temperature Non Operational -25 to +85° Relative humidity min 20% max 95% Input fuse T3.15A / 250VAC internal Rated over load protection For 5, 12, 15 & 24V, 110-150% of Vi nom. For 24LS, 102-108% of Vi nom. Isolation voltage Input / Output 3,000VAC PBAMR5-05 + 5 VDC 12000 mA 60 WATTS Isolation resistance Input / Output at 500VDC 100MΩ PBAMR5-12* + 12 VDC 6000 mA 72 WATTS Ambient temperature -25°C to +71°C PBAMR5-15 + 15 VDC 5000 mA 75 WATTS PBAMR5-24* + 24 VDC 4200 mA 100.8 WATTS PB AMR5-24LS + 24 VDC 3800 mA 91.2 WATTS SELECTION TABLE MODEL NUMBER OUTPUT POWER MECHANICAL & PIN CONFIGURATION *Non indent item Doc. No. PBC9 Rev.C 28-4-11 Powering Progress – www.powerbox.com.au 349